Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: The objective of this work is to investigate the yearly performance an absorption-compression cascade
Received 13 May 2017 refrigeration system driven by solar energy. Different operating scenarios are examined by testing differ-
Received in revised form 11 June 2017 ent combinations of refrigeration and condensation temperatures. Evacuated tube collectors coupled to a
Accepted 18 June 2017
storage tank are selected to be used for feeding the refrigeration system with the proper heat demand.
LiBr-H2O and R134a are selected as working pair in the absorption cycle and refrigerant in the compres-
sion cycle respectively. The analysis is performed in energetic, exergetic, economic and environmental
Keywords:
terms with a developed and validated model in EES (Engineering Equation Solver). According to the final
Solar refrigeration
Absorption-compression cascade system
results, the cascade system, in cases with low refrigeration temperatures is better economically while in
Absorption chiller higher refrigeration temperatures presents the greater percentage of electricity savings. On the other
Exergetic analysis hand, higher heat rejection temperature leads both to higher economic indexes and to higher electricity
VCC savings. For the case of heat rejection at 40 °C and refrigeration at 20 °C, the electricity savings are found
53.98%, the IRR 6.6% and the payback period close to 14 years.
Ó 2017 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.enconman.2017.06.063
0196-8904/Ó 2017 Elsevier Ltd. All rights reserved.
1056 E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069
Nomenclature
reflectors are complex and expensive technologies which need between these refrigerants and the general conclusion was the
accurate tracking mechanism and they usually utilized in applica- low performance of the examined system. Jain et al. [21] compared
tions for medium and high temperatures (usually over 150–200 °C) a similar system with a double stage VCC and they finally found
[16,17]. Thus, the use of evacuated tube collectors (ETCs) seems to 60% electricity savings.
be the most appropriate solution [18,19] for feeding sorption The majority of the studies are focused on systems with LiBr-
machines, as in the previously described cascade systems. H2O as the absorbent working pair, while various refrigerants have
In literature, there are numerous studies which have examined been tested. Cimsit and Ozturk [22] examined the performance of a
the cascade refrigeration system with absorption chiller and VCC. A cascade refrigeration system with LiBr-H2O with various refriger-
minor number of studies has been focused on systems with H2O- ants and they proved that R134a is a better solution than R410a
NH3 absorption chillers because of these machines are usually and NH3. Moreover, they showed that the electricity savings can
applied in applications which need extremely low evaporating reach up to 50%, compared to the conventional VCC. Moreover,
temperatures. Fernandez-Seara et al. [20] examined a cascade sys- Cimsit et al. [23] proved that the use of LiBr-H2O in cascade sys-
tem with H2O-NH3 as the absorbent working pair, while CO2 and tems is more efficient than the use of H2O-NH3. They indicated that
NH3 were tested as refrigerants. Similar results are obtained the use of CO2 as refrigerant leads to lower performance than
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1057
The temperature of the evaporator in the absorption chiller has 2.2. Mathematical formulation
selected to be 5 °C. This value has selected to have a low value in
order to reduce also the condenser temperature of the mechanical In this subsection, all the mathematical equations associated
compression system. This strategy targets to minimize the electric- with the modeling of the examined system (Fig. 1) are presented
ity consumption in the mechanical compression refrigeration sys- with details. All these equations are mainly energy and mass flow
tem. Moreover, the temperature level in the condenser of the rate balances, as well as definitions of various evaluation indexes.
absorption chiller is selected to be the same as the temperature
level in the absorber. This temperature is examined parametrically 2.2.1. Solar field modeling
in this study from 30 °C to 50 °C. The available solar irradiation in the collector level is calculated
In the mechanical compression system, the refrigeration load is as:
captured in its evaporator which operates with the temperature
Q s ¼ Ac GT ; ð1Þ
equal to Te. This temperature is examined parametrically from
40 °C to 0 °C. The refrigerant is selected to be R134a, an optimum The useful heat production of the collector field is calculated by
solution according to the literature review of Section 1. This refrig- the energy balance on the fluid volume:
erant leaves the evaporator, as saturated vapor (s.p. a), and it is Q u ¼ mc cp ðT col;out T col;in Þ; ð2Þ
delivered to the mechanical compressor. The isentropic efficiency
of this device is selected to be 90% and the mechanical efficiency The thermal efficiency of the collector is the ratio of the useful
70% [38]. The superheated vapor in the outlet of the compressor heat to the available solar irradiation on the collector level:
(s.p. b) enters to the condenser of the mechanical compression sys- Qu
tem which operates with saturation temperature equal to Tc,m. gth ¼ ; ð3Þ
Qs
Electrical energy is consumed in this device and the reduction of
this consumption is one of the main goals of the presented config- The efficiency curve of the ETC in this study is taken from Ref.
uration. This temperature level is selected to be 8 K greater than [39] and it is given as:
the evaporating temperature in the absorption chiller evaporator
T col;in T am
(Tc,m–Te,m = 8 K) [22]. This condenser rejects heat to the evaporator gth ¼ 0:6869 1:4709 ; ð4Þ
GT
of the absorption chiller and saturated liquid is created in its outlet
(s.p. c). This liquid is delivered to the adiabatic throttling valve The mass flow rate in the collector field is calculated according
(constant enthalpy process) and liquid/vapor mixture is created to the specific mass flow rate [36], as it is presented below:
in its outlet (s.p. d). This mixture is delivered to the evaporator
and the mechanical compression cycle closes.
_ col ¼ 0:02 Ac :
m ð5Þ
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1059
2.2.2. Storage tank modeling reason for making the mass flow energy balances on the absorber
The storage tank modeling is based on the thermal zones mod- because identical equations as (15) and (16) will be written.
eling [36]. According to this modeling, the storage tank is separated The next device that has to be described is the solution heat
into horizontal zones which include thermal oil of the same tem- exchanger. In this device, two are the demanded equations for
perature (uniform temperature in the entire zone). Heat and mass the proper modeling. Eq. (17) presents the energy balance in every
are exchanged between the zones and temperature stratification is stream and Eq. (18) is the effectiveness of the heat exchanger
created inside the tank. Hotter thermal oil is found in the upper [10,40]:
part and colder in the lower part of the storage tank. The present
mw ðh2 h12 Þ ¼ mstr ðh4 h45 Þ; ð17Þ
storage tank is separated into three mixing zones, a strategy that
has been followed also in other studies [10,40]. h4 h45
The energy balances in all the mixing zones are presented by gHEX ¼ ; ð18Þ
h4 h12
the following equations:
Furthermore, it is essential to state that the enthalpy is con-
qV dT s;1 served in the throttling vales and so the following equations have
cp ¼ mcol cp ðT col;out T s;1 Þ þ mh cp ðT s;2 T s;1 Þ
3 dt to be applied:
U T AT1 ðT s;1 T am Þ; ð6Þ
h45 ¼ h5 ; ð19Þ
The mass flow rate to the generator (mh) is taken equal to the T e;m ¼ T c;m 8; ð23Þ
mass flow rate of the collector field (mcol). This selection makes
The heat transfer in the generator is described with the follow-
the heat production to be equivalent to the heat supply and the
ing equations. Eq. (24) is the energy balance in the fluid volume of
system is more stable. The calculation of the outer surface of the
thermal oil in the hot circuit.
various mixing zones (AT) is described with details in Refs. [10,40].
_ h cp ðT h;in T h;out Þ;
Qg ¼ m ð24Þ
2.2.3. Absorption chiller modeling
Eq. (25) shows the heat transfer between the heat source (ther-
The modeling of the single stage absorption chiller operating
mal oil) and the generator solution:
with the LiBr-H2O working pair is presented below. The energy rate
balances and the mass flow rate balances are given below with T h;in T h;out
Q g ¼ ðUAÞg T T
; ð25Þ
details. Eqs. (11)–(14) are devoted to the energy balances on the lnðT h;in Tgg Þ
h;out
generator, evaporator, condenser and absorber of the absorption
chiller.
2.2.4. Mechanical compression refrigerator system modeling
Q g ¼ mr h3 þ mstr h4 mw h2 ; ð11Þ The basic equations which describe the mathematical modeling
of the mechanical compression refrigerator are given below. Eq.
Q e;m ¼ mr ðh8 h7 Þ; ð12Þ (26) shows the energy balance in the condenser and Eq. (27) shows
the energy balance in the evaporator.
Q c ¼ mr ðh3 h6 Þ; ð13Þ
Q c;m ¼ mref ðhc hb Þ; ð26Þ
Q a ¼ mr h8 þ mstr h5 mw h1 ; ð14Þ Q e ¼ mref ðha hd Þ; ð27Þ
The total mass flow rate balance in the generator is given The demanded electricity consumption in the compressor is
below: given as:
mr þ mstr ¼ mw ; ð15Þ ðhb ha Þ
Pel ¼ mref ; ð28Þ
The mass flow rate of the LiBr substance in the generator is gm
given below: The isentropic efficiency of the compressor is calculated accord-
X w mw ¼ X str mstr ; ð16Þ ing to Eq. (29):
It has been assumed that the steam in the state point 3 is pure hb;is ha
gis ¼ ; ð29Þ
H2O without LiBr. Moreover, it is important to state that there is no hb ha
1060 E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069
Moreover, it is important to present the enthalpy conservation the costs for operation and maintenance, according to Eq. (38). It is
in the throttling valve: important to state that the yearly refrigeration production (Ye) and
the yearly electrical consumption (Yel) are calculated with integra-
hd ¼ hc ; ð30Þ
tion during the entire year period.
Moreover, it is important to state that the yearly performance 2.2.7. Weather data
parameters are calculated with integration during the year period, The weather data in this paper regarding the climate conditions
using the monthly calculated parameters. of Athens, Greece (37°590 N, 23°440 E). The 21th day of every month
is selected as the most appropriate day for examination, according
2.2.6. Economic analysis to the ASHRAE standards. For these days, some useful parameters
The economic evaluation of the presented system is performed are calculated. The solar declination angle is given according to
with various indexes. In any case, the cascade system is compared Eq. (43) [36]. The parameter ‘‘Day” is the day number in the year
to the respective mechanical compression system which produces (for example Day = 1 for the 1st of January).
refrigeration at temperature levels equal to Te and rejects heat to
284 þ Day
the environment at temperature level equal to Tc. The Coefficient d ¼ 23:45 sin 2p ; ð43Þ
of performance for this equivalent case (COPeq) is calculated and
365
it is used in the following analysis
The day duration is calculated as [36]:
The first parameter is the net present value (NPV) which shows
the present value of the investment by taking into account the 2
ND ¼ arccosð tanð/0 Þ tanðdÞÞ; ð44Þ
future gains and the possible discount in the cash flows. 15
X
M The ambient temperature during the day is given according to
CF net
NPV ¼ C 0 þ j
; ð36Þ the Eq. (45) [44]. This equation shows that the maximum ambient
J¼1 ð1 þ rÞ temperature is observed at 14:00, a realistic assumption.
The capital cost of the investment is the sum of the separate !
DR th N2D 2
costs. More specifically, the absorption chiller, the mechanical T am ¼ T am;m þ cos 2p ; ð45Þ
compression refrigerator, the solar collectors and the tank are the 2 24
main parts of the system that have to be taken into account in
the cost analysis. The other costs are assumed to be included in The solar irradiation for every moment is calculated according
these quantities. Eq. (37) describes the way that the capital cost to the following formula [43]. This formula assumes that the inci-
is calculated in every case: dent solar irradiation on the collector level is a sine function which
is a realistic assumption.
C 0 ¼ K mc Q e þ K ch Q e;m þ K ETC Ac þ K tan k V; ð37Þ
p HT 103 p ðth Þ
The yearly income is calculated as the income from the cooling GT ¼ sin ; ð46Þ
production minus the cost of the electrical consumption and minus 2 ND ND
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1061
It would be useful to state that the time parameter (th) takes 800 21 January
values from 0 to ND in Eqs. (45) and (46). Table 1 gives all the 700
21 February
important data about the solar potential and the ambient temper- 21 March
600
ature level for all the examined months [45,46]. Moreover, the 21 April
solar declination angle and the day duration are given for the 500 21 May
GT (W/m2)
21 June
twelve examined days. Figs. 2 and 3 depict the incident solar irra-
400 21 July
diation and the ambient temperature level during the twelves
300 21 August
examined days respectively. It is essential to note that these
21 September
weather data correspond to the literature data for Athens climate 200 21 October
and they represent typical days for all the months. Thus, it is pos- 21 November
100
sible to determine the monthly performance of the collector by 21 December
examining only one day every month. 0
0 3 6 9 12 15 18 21 24
Hours
2.3. Followed methodology
Fig. 2. Daily incident solar irradiation for all the examined months.
In this work, the cascade refrigeration system is examined in
dynamic basis during twelve characteristic days, one for every
21 January 21 February 21 March 21 April
month. The meteorological data of Figs. 2 and 3 are used in order 21 May 21 June 21 July 21 August
the yearly performance to be found. The presented mathematical 21 September 21 October 21 November 21 December
equations in Section 2.2 consist the developed mathematical mod- 35
Table 1
Weather data for the 21th day of each month [49–50].
Table 2 Table 4
Constant parameters of the present study. Parameters for the economic analysis.
Table 5
Validation results for the absorption chiller.
Table 6
Validation results for the cascade system.
500
COPsys
450
0.25
400
350 0.20
300
250 0.15
200
0.10
80 90 100 110 120 80 90 100 110 120
Tg (oC) Tg (oC)
Fig. 4. Daily refrigeration output for various generator (Tg) and evaporator (Te) Fig. 5. Daily system COP for various generator (Tg) and evaporator (Te) tempera-
temperatures, with condenser temperature (Tc) equal to 40 °C. tures, with condenser temperature (Tc) equal to 40 °C.
of 40 °C condenser temperature and 20 °C evaporator tempera- and in every case the optimum generator temperature, as it has
ture is examined. Fig. 9 show the daily variation of the solar irradi- been given in Fig. 6, is applied.
ation, of the ambient temperature and of the mean storage tank The daily refrigeration production is depicted in Fig. 11. The
temperature. The temperature inside the storage tank is ranged presented curves correspond to different condenser temperatures
from 94 °C to 118 °C during the day and it is maximized about and all the curves seem to be parallel. The refrigeration production
40 min after the solar noon (12:40). Fig. 10 illustrates the incident is getting higher when higher evaporator temperatures and lower
solar energy, the refrigeration production, as well as the electricity condenser temperatures are applied. Moreover, the curves are clo-
consumption during the day. It is important to state that the oper- ser to each other for lower temperature levels and their distance
ation of the refrigerator starts 50 min (6:50) after the sunrise and it increases with the increase in the evaporator temperature. This
presented maximum yield 40 min after the solar noon (12:40). The result shows that the condenser temperature effect on the results
system operation stops at the sunset (18:00). is greater when the system operates at higher evaporator temper-
The next step in this analysis is the presentation of the final atures. Similar results are taken from Fig. 12 about the system COP.
results about the system performance for all the examined opera- It would be useful to elaborate more the results by presenting
tion cases. More specifically, all the possible combinations of evap- some characteristic numerical results. The daily refrigeration pro-
orator temperatures and condenser temperatures are examined duction is varied from 527 kWh to 725 kWh when the evaporator
1064 E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069
GT (W/m2)
0.06 500
80
T (oC)
nex,sys
0.05 400
0.04 60
300
0.03 40
200
0.02
100 20
0.01
0.00
0 0
6 7 8 9 10 11 12 13 14 15 16 17 18
80 85 90 95 100 105 110 115 120
Tg (oC) Daily hours
Fig. 9. Daily variation of solar irradiation (GT), ambient temperature (Tam) and
Fig. 6. Daily system exergetic efficiency for various generator (Tg) and evaporator
storage tank temperature (Ts) for the case of [Te = 20 °C and Tc = 40 °C].
(Te) temperatures, with condenser temperature (Tc) equal to 40 °C.
120 250
Solar Refrigeraon load Electricity
110 200
100
Q (kWh)
150
Tg,opt (oC)
90
100
80
50
70
0
60 6 7 8 9 10 11 12 13 14 15 16 17 18
30 35 40 45 50 Daily hours
Tc (oC)
Fig. 10. Solar energy, refrigeration load and electricity consumption during the day
Fig. 7. Optimum generator temperature levels for various condenser temperatures for the case of [Te = 20 °C and Tc = 40 °C].
(Tc).
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
700 850
680 V = 5 m³ 800
660 750
V = 10 m³
700
Ee (kWh)
640 V = 15 m³
650
Ee (kWh)
620 V = 20 m³ 600
600
550
580 500
560 450
540 400
0 -10 -20 -30 -40
520
Te (oC)
500
0 -10 -20 -30 -40 Fig. 11. Daily refrigeration output for various evaporator (Te) and condenser (Tc)
Te ( C) temperatures, with optimum generator temperature in every case (Tg).
Fig. 8. Daily refrigeration output for different storage tank volumes and evaporat-
ing temperatures, with condenser temperature (Tc) equal to 40 °C. the influence of evaporator temperature (dCOPsys/dTe = 0.0023
kWh/K), a result which is consistent with the respective for the
daily refrigeration production.
temperature is equal to 20 °C. For condenser temperature equal The next examined parameter is the system exergetic efficiency.
to 40 °C, it is ranged from 544 kWh to 679 kWh. It is obvious that The parameter is given in Fig. 13 for all the examined operating
the refrigeration production is less influenced by the evaporator conditions. Lower values of evaporator temperatures lead to
temperature (dEe/dTe = 4.95 kWh/K) than the condenser tempera- greater exergetic efficiency, as Eq. (34) indicates. Moreover, higher
ture (dEe/dTc = 6.75 kWh/K). The system COP is varied from condenser temperature leads to lower exergetic efficiency because
0.2732 to 0.3670 for evaporator temperature equal to 20 °C, of the consequent decrease in the system COP (see Fig. 10). It is
while when the condenser temperature is kept constant to 40 °C clearly presented in Fig. 13 that the evaporator temperature plays
it takes values from 0.2656 up to 0.3657. The impact of the con- a significant role on the exergetic output of the system. For con-
denser temperature (dCOPsys/dTc = 0.0050 kWh/K) is greater than denser temperature equal to 40 °C, the exergetic efficiency varies
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1065
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
0.45 90%
80%
0.40 70%
Electricity Savings
60%
0.35
COPsys
50%
0.30 40%
30%
0.25 20%
10%
0.20 0%
0 -5 -10 -15 -20 -25 -30 -35 -40
0 -10 -20 -30 -40
Te (oC)
Te (oC)
Fig. 12. Daily system COP for various evaporator (Te) and condenser (Tc) temper-
Fig. 14. Daily electricity savings for various evaporator (Te) and condenser (Tc)
atures, with optimum generator temperature in every case (Tg).
temperatures, with optimum generator temperature in every case (Tg).
from 0.03774 to 0.08043 (dgex,sys/dTe = 0.1067%). For evaporator representative case. It is important to note that similar monthly
temperature equal to 20 °C, the system exergetic performance variation is observed among all the operation cases (Te and Tc)
takes values from 0.05352 up to 0.07153 (dgex,sys/dTc = 0.0905%). and thus only one is adequate in order to present and to comment.
Fig. 14 exhibits the electricity savings that are taken from the The following figures will present the final results for all the
examined system compared to the conventional single stage examined operation cases.
mechanical compression system. This equivalent system is sup- Fig. 15 depicts the solar energy potential for the total collector
posed to operate between (Te) and (Tc) in every case. The results field, the refrigeration production and the electricity consumption
of this figure indicate a significant reduction in the electricity con- for the twelve months of the year. August is the month with the
sumption for all the examined cases. More specifically, the electric- greater solar potential and the greater refrigeration production,
ity savings are higher for greater condenser temperatures and for while December is the one with the lowest. Generally, the period
lower evaporator temperatures. It can be said, that the electricity fro June to September is the period with the greater yield, while
savings are higher when the absorption chiller operation covers a the period from November to February is the one with the lowest.
greater fraction of the demanded temperature difference between Similar results are obtained by the Fig. 16 which gives the system
Te and Tc. For condenser temperature equal to 40 °C, the electricity monthly COP and the exergetic efficiency.
savings are ranged from 46.18% to 76.14%. For the lower examined In August, the solar energy potential is about 51,090 kWh, the
condenser temperature (Tc = 30 °C), the electricity savings are ran- refrigeration production 17,346 kWh, the electricity consumption
ged from 32.76% to 60.31%, while for the higher condenser temper- 4134 kWh, the mean system COP 0.3141 and the mean system
ature (Tc = 50 °C) they are ranged from 57.13% to 79.41%. exergetic efficiency 0.0635. In December, the solar energy potential
is about 25,227 kWh, the refrigeration production 6528 kWh, the
3.2. Yearly evaluation electricity consumption 1556 kWh, the mean system COP 0.2437
and the mean system exergetic efficiency 0.0325.
3.2.1. Energetic and exergetic evaluation The next step is to present the yearly results for all the exam-
This subsection is devoted to the energetic and exergetic evalu- ined cases. These results are illustrated in Figs. 17–21. The analysis
ation of the system during the year. The meteoroidal data for of these results is similar to the analysis of the presented results in
Athens climate, as they have presented in Section 2.2.7, are used Figs. 11–14. Thus, the analysis of Figs. 17–21 will be more briefly.
in order to take the results of this subsection. First of all, the Fig. 17 shows the yearly refrigeration production and Fig. 18 the
monthly variation of the most important parameters is given in yearly system COP. These quantities are getting higher when
Figs. 15 and 16. These figures regard the case with 40 °C condenser greater evaporator temperature and lower condenser temperature
temperature and 20 °C evaporator temperature, which is one are selected.
0.06 July
June
0.05 May
0.04 April
March
0.03 February
0.02 January
0 -10 -20 -30 -40 0 10000 20000 30000 40000 50000
Te (oC) Monthly energy (kWh)
Fig. 13. Daily system exergetic efficiency for various evaporator (Te) and condenser Fig. 15. Solar energy potential, refrigeration production and electrical consumption
(Tc) temperatures, with optimum generator temperature in every case (Tg). in monthly basis for the case of [Te = 20 °C and Tc = 40 °C].
1066 E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069
Yearly COPsys
September
0.35
August
July 0.30
June
May 0.25
April
March 0.20
February 0 -10 -20 -30 -40
January Te (oC)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Fig. 18. Yearly system COP for all the examined operation scenarios.
Performace Index
Fig. 16. System exergetic efficiency and COP in monthly basis for the case of
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
[Te = 20 °C and Tc = 40 °C].
0.09
0.08
Fig. 19 proves that the yearly exergetic efficiency is greater for
lower evaporator temperatures and for lower condenser tempera- 0.07
tures. Fig. 20 shows that the electricity consumption is higher
ex,sys
0.06
when a lower temperature in the evaporator and in the condenser Yearly
is applied. The electricity consumption has similar behavior such 0.05
as the exergetic efficiency of the system. Fig. 21 shows that the
0.04
electricity savings have reverse behavior compared to the electric-
ity consumption; lower evaporator and condenser temperatures 0.03
leads also to lower electricity savings.
0.02
0 -10 -20 -30 -40
3.2.2. Economic and environmental evaluation Te (oC)
This subsection evaluates the obtained results by an economic
point of view. All the usual indexes as the net present value, the Fig. 19. Yearly system exergetic efficiency for all the examined operation scenarios.
internal rate of return and the payback period are given for all
the examined operating scenarios. Moreover, the savings of carbon
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
dioxide due to the reduction in the electricity consumption are
80000
Yearly electricity - Eel (kWh)
given.
Fig. 22 illustrates the net present value (NPV) for all the exam- 70000
ined combinations of evaporator and condenser temperatures. The 60000
NPV is positive for the majority of the examined cases and it takes 50000
values up to 163 k€. It is negative only for cases with condenser
40000
temperature equal to 30 °C and relatively high evaporator temper-
atures (0 °C and 10 °C). In these cases, the installation of the pre- 30000
sent system is not recommended. This result is explained by the 20000
smaller electricity savings in these cases, as well as by the small 10000
electrical requirements. These cases correspond to smallest tem-
0
perature differences between condenser and evaporator (Tc–Te), a 0 -10 -20 -30 -40
negative fact for installing the suggested cascade system. More- Te (oC)
over, it is essential to state that the NPV is higher in the cases that
Fig. 20. Yearly electricity consumption for all the examined operation scenarios.
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
220000 the electricity savings are higher and generally the difference
Yearly refrigeraon - Ee (kWh)
(Tc–Te) is greater.
200000
Fig. 23 exhibits the internal rate of return (IRR) for the exam-
180000 ined cases. This parameter shows the investment yearly efficiency
in economic terms. It reaches up to 13.4%, which is an attractive
160000
value for a technology with solar energy utilization. The cases with
140000 IRR lower than 3% (discount factor of this study) are not profitable
solutions. For a typical application with (Te = 20 °C and
120000 Tc = 40 °C), the IRR is about 6.6%, an encouraging value for the sus-
tainability of this investment. It is also essential to state that the
100000
0 -10 -20 -30 -40 curves of the IRR have similar trends with the NPV curves of
Te (oC) Fig. 22.
Figs. 24 and 25 show the payback and the simple payback per-
Fig. 17. Yearly refrigeration production for all the examined operation scenarios. iod respectively. Payback period takes into account the selected
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1067
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
35
80%
75% 30
70% 25
65%
60% 20
55% 15
50%
10
45%
40% 5
35%
0
30% 0 -10 -20 -30 -40
0 -10 -20 -30 -40
Te (oC)
Te (oC)
Fig. 24. Payback period for all the examined operation scenarios.
Fig. 21. Yearly electricity savings for all the examined operation scenarios.
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
180000 25
15
100000
80000
10
60000
40000
5
20000
0
0
0 -10 -20 -30 -40
0 -10 -20 -30 -40
Te (oC)
Te (oC)
Fig. 22. Net present value for all the examined operation scenarios.
Fig. 25. Simple payback period for all the examined operation scenarios.
discount factor while the simple payback period assumes this All the previous results about the economic evaluation of the
parameter equal to zero. Generally, the payback period is greater examined systems show that the cascade system is a sustainable
than the respective simple payback period. When these parameters solution. In the majority of the cases, the financial indexes are
are greater than the project life, then the investment is considered encouraging. Only for applications with the lowest examined con-
as non-profitable. This result is taken only for the cases [Te = 0 °C, denser temperatures and relatively high evaporator temperatures,
Tc = 30 °C] and [Te = 10 °C, Tc = 30 °C], which are the cases with the investment seems not to be viable.
negative net present value. Generally, payback periods close to In the end of this subsection, the carbon dioxide savings are
15 years are observed. This result is encouraging for the invest- given in Fig. 26 for all the examined cases. It is essential to state
ment in the suggested cascade system. For example, for the typical that the energy mixture of Greece has been used in order to obtain
case [Te = 20 °C, Tc = 40 °C] the payback period is 13.95 years and these results. More specifically, it is assumed that 1 MWhel leads to
the simple payback period is 12.07 years. The minimum payback 0.989 tn of CO2 production [56]. The obtained results show signif-
period is 7.76 years for the case [Te = 40 °C, Tc = 50 °C] and the icant saving in CO2 at yearly basis. These results are associated
simple payback period, in this case, is 7.13 years. with the electricity consumption and the electricity savings which
are presented in Figs. 20 and 21.
Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C Tc = 30 C Tc = 35 C Tc = 40 C Tc = 45 C Tc = 50 C
70
14%
Yearly CO2 Savings (tn)
12% 60
10%
50
8%
IRR
6% 40
4%
30
2%
0% 20
0 -10 -20 -30 -40 0 -10 -20 -30 -40
Te (oC) Te (oC)
Fig. 23. Internal rate of return for all the examined operation scenarios. Fig. 26. Yearly carbon dioxide savings for all the examined operation scenarios.
1068 E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069
Table 7
Summary of the results for yearly operation with the condenser temperature (Tc) equal to 40 °C.
3.2.3. Final evaluation and discussion a system which exploits a renewable source such as solar energy
This subsection is devoted to present the obtained results and achieves electricity savings over 50%.
briefly. Table 7 includes the main results for the typical condenser Moreover, it can be concluded that the system is found to be
temperature of 40 °C and for all the examined evaporator temper- suitable in cases with greater temperature difference (Tc–Te). In
atures. These results regard the energetic, exergetic, economic and these cases, there is a greater margin for improvement and the
environmental evaluation of the examined system. reduction in the electricity consumption can cover easier the extra
The net present value is ranged from 27,713 € to 97,387 €, pre- capital cost for the solar field and the absorption chiller.
senting a significant variation. On the other hand, the IRR is ranged
from 4.36% to 9.33%, leading a relatively lower variation. Moreover,
the payback and the simple payback periods are varied from 10.72 References
to 18.10 years and from 9.57 to 15.06 years respectively. These [1] Loni R, Kasaeian AB, Mahian O, Sahin AZ. Thermodynamic analysis of an
results prove that the investment in this technology is generally organic rankine cycle using a tubular solar cavity receiver. Energy Convers
vital when the system is designed to operate at a usual condenser Manage 2016;127:494–503.
[2] Krajačić G, Duić N, Vujanović M, Kılkısß S
ß , Rosen MA, Al-Nimr MA. Sustainable
temperature.
development of energy, water and environment systems for future energy
In the energetic analysis, it is noticeable that higher electricity technologies and concepts. Energy Convers Manage 2016;125:1–14.
savings are observed at higher evaporator temperatures. On the [3] Bellos E, Tzivanidis C, Antonopoulos KA. Parametric analysis and optimization
of a solar assisted gas turbine. Energy Convers Manage 2017;139:151–65.
other hand, the carbon dioxide savings are lower in these cases
[4] Qiu Y, He Y-L, Li P, Du B-C. A comprehensive model for analysis of real-time
because of the impact of the real electrical consumption (see optical performance of a solar power tower with a multi-tube cavity receiver.
Figs. 20 and 21). The system COP varies from 0.2645 to 36.41 Appl Energy 2017;185(1):589–603.
and it increases for higher evaporator temperatures. On the other [5] Bellos E, Tzivanidis C, Moschos K, Antonopoulos KA. Energetic and financial
evaluation of solar assisted heat pump space heating systems. Energy Convers
hand, the exergetic efficiency decreases for higher evaporator tem- Manage 2016;120:306–19.
peratures and it takes values from 0.0690 (for Te = 40 °C) to [6] Bataineh K, Taamneh Yazan. Review and recent improvements of solar
0.0277 (for Te = 0 °C). sorption cooling systems. Energy Build 2016;128:22–37.
[7] Kerme ED, Chafidz A, Agboola OP, Orfi J, Fakeeha AH, Al-Fatesh AS. Energetic
and exergetic analysis of solar-powered lithium bromide-water absorption
4. Conclusions cooling system. J Clean Prod 2017;151:60–73.
[8] Mohan G, Kumar U, Pokhrel MK, Martin A. A novel solar thermal
polygeneration system for sustainable production of cooling, clean water
This work examines an absorption-compression cascade refrig- and domestic hot water in United Arab Emirates: dynamic simulation and
eration system which is assisted by solar collectors. Evacuated tube economic evaluation. Appl Energy 2016;167:173–88.
[9] Chen Y, Han W, Jin H. Proposal and analysis of a novel heat-driven absorption–
collectors (300 m2), coupled to a storage tank (5 m3), supply the compression refrigeration system at low temperatures. Appl Energy 2017;185
demanded heat input to an absorption chiller operating with (2):2106–16.
LiBr/H2O. This absorption chiller is the cycle of a cascade system, [10] Bellos E, Tzivanidis C, Antonopoulos KA. Exergetic and energetic comparison of
LiCl-H2O and LiBr-H2O working pairs in a solar absorption cooling system.
while the down cycle is a VCC with R134a. The objective of this
Energy Convers Manage 2016;123:453–61.
study is to evaluate the sustainability of this system in energetic, [11] Jain V, Sachdeva G, Kachhwaha SS. Energy, exergy, economic and
exergetic, economic and environmental terms. In order to perform environmental (4E) analyses based comparative performance study and
a suitable work, the system is examined under dynamic conditions optimization of vapor compression-absorption integrated refrigeration
system. Energy 2015;91:816–32.
for twelve days during the year (one for every month). It is impor- [12] Jain V, Kachhwaha SS, Sachdeva G. Thermodynamic performance analysis of a
tant to state that before the yearly analysis, the system is opti- vapor compression–absorption cascaded refrigeration system. Energy Convers
mized for a typical day in order to determine the optimum Manage 2013;75:685–700.
[13] Li Z, Jing Y, Liu J. Thermodynamic study of a novel solar LiBr/H2O absorption
generator temperature and storage tank volume. The analysis is chiller. Energy Build 2016;133:565–76.
performed with the EES (Engineering Equation Solver) and the [14] Allouhi A, Kousksou T, Jamil A, Bruel P, Mourad Y, Zeraouli Y. Solar driven
developed model has been validated with literature results. cooling systems: an updated review. Renew Sustain Energy Rev
2015;44:159–81.
According to the final results, the system is able to produce [15] Labed A, Moummi N, Aoues K, Benchabane A. Solar drying of henna (Lawsonia
great amounts of refrigeration with significant electricity savings. inermis) using different models of solar flat plate collectors: an experimental
Moreover, the financial indexes indicate that the installing of this investigation in the region of Biskra (Algeria). J Clean Prod 2016;112
(4):2545–52.
system is a viable choice. Below, the most important results for [16] Sharan P, Bandyopadhyay S. Solar assisted multiple-effect evaporator. J Clean
the typical case with evaporator temperature equal to 20 °C Prod 2017;142(4):2340–51.
and condenser temperature equal to 40 °C are presented. The [17] Bellos E, Mathioulakis E, Tzivanidis C, Belessiotis V, Antonopoulos KA.
Experimental and numerical investigation of a linear Fresnel solar collector
yearly refrigeration production is found to be about 155 MWh,
with flat plate receiver. Energy Convers Manage 2016;130:44–59.
the electricity consumption about 37 MWh, the yearly system [18] Angrisani G, Entchev E, Roselli C, Sasso M, Tariello F, Yaïci W. Dynamic
COP 0.314 and the exergetic efficiency 0.051. In the financial anal- simulation of a solar heating and cooling system for an office building located
ysis, the NPV is found to be about 58 k€, the IRR 6.6%, the payback in Southern Italy. Appl Therm Eng 2016;103:377–90.
[19] Buonomano A, Calise FO, d’Accadia MD, Ferruzzi G, Frascogna S, Palombo A,
period 14 years and the simple payback period about 12 years. The et al. Experimental analysis and dynamic simulation of a novel high-
payback period of 14 years is not a low value but it is acceptable for temperature solar cooling system. Energy Convers Manage 2016;109:19–39.
E. Bellos et al. / Energy Conversion and Management 148 (2017) 1055–1069 1069
[20] Fernandez-Seara J, Sieres J, Vazquez M. Compression–absorption cascade [38] Tzivanidis C, Bellos E, Antonopoulos KA. Energetic and financial investigation
refrigeration system. Appl Therm Eng 2006;26:502–12. of a stand-alone solar-thermal Organic Rankine Cycle power plant. Energy
[21] Jain V, Sachdeva G, Kachhwaha SS. Thermodynamic modelling and parametric Convers Manage 2016;126:421–33.
study of a low temperature vapour compression-absorption system based on [39] Zambolin E, Del Col D. An improved procedure for the experimental
modified Gouy-Stodola equation. Energy 2015;79:407–18. characterization of optical efficiency in evacuated tube solar collectors.
[22] Cimsit C, Ozturk IT. Analysis of compression–absorption cascade refrigeration Renew Energy 2012;43:37–46.
cycles. Appl Therm Eng 2012;40:311–7. [40] Bellos E, Tzivanidis C, Antonopoulos KA. Exergetic, energetic and financial
[23] Cimsit C, Ozturk IT, Hozol M. Second law based thermodynamic analysis of evaluation of a solar driven absorption cooling system with various collector
compression-absorption cascade refrigeration cycles, Analysis of types. Appl Therm Eng 2016;102:749–59.
compression–absorption cascade refrigeration cycles. J Therm Sci Technol [41] Petela R. Exergy analysis of solar radiation. In: Enteria N, Akbarzadeh A,
2014;34(2):9–18. editors. Solar thermal sciences and engineering applications. CRC Press, Taylor
[24] Colorado D, Velazquez VM. Exergy analysis of a compression–absorption & Francis Group; 2013 [chapter 2].
cascade system for refrigeration. Int J Energy Res 2013;37:1851–65. [42] Mróz TM. Thermodynamic and economic performance of the LiBr–H2O single
[25] Colorado D, Rivera W. Performance comparison between a conventional vapor stage absorption water chiller. Appl Therm Eng 2006;26(17–18):2103–9.
compression and compression-absorption single-stage and double-stage [43] Belessiotis V, Mathioulakis E, Papanicolaou E. Theoretical formulation and
systems used for refrigeration. Appl Therm Eng 2015;87:273–85. experimental validation of the input–output modeling approach for large solar
[26] Xu Y, Jiang N, Pan F, Wang Q, Gao Z, Chen G. Comparative study on two low- thermal systems. Sol Energy 2010;84:245–55.
grade heat driven absorption-compression refrigeration cycles based on [44] Bellos E, Tzivanidis C, Symeou C, Antonopoulos KA. Energetic, exergetic and
energy, exergy, economic and environmental (4E) analyses. Energy Convers financial evaluation of a solar driven absorption chiller – a dynamic approach.
Manage 2017;133:535–47. Energy Convers Manage 2017;137:34–48.
[27] Marimón MA, Arias J, Lundqvist P, Bruno JC, Coronas A. Integration of [45] Kouremenos DA, Antonopoulos KA, Domazakis ES. Solar radiation correlations
trigeneration in an indirect cascade refrigeration system in supermarkets. for the Athens, Greece, area. Sol Energy 1985;35:259–69.
Energy Build 2011;43:1427–34. [46] Kouremenos DA, Antonopoulos KA, Doulgerakis S. Direct and diffuse solar
[28] Wu W, Shi W, Wang B, Li X. Annual performance investigation and economic radiation correlations for tilted surfaces in Athens, Greece. Sol Energy 1987;38
analysis of heating systems with a compression-assisted air source absorption (3):203–17.
heat pump. Energy Convers Manage 2015;98:290–302. [47] F-Chart Software, Engineering Equation Solver (EES); 2015. Available at:
[29] Sun ZG. Experimental investigation of integrated refrigeration system (IRS) http://www.fchart.com/ees.
with gas engine, compression chiller and absorption chiller. Energy 2008;33 [48] Tillner-Roth R, Baehr HD. An international standard formulation for the
(3):431–6. thermodynamic properties of 1,1,1,2-tetrafluoroethane (HFC-134a) for
[30] Hojjat Mohammadi SM, Ameri M. Energy and exergy comparison of a cascade temperatures from 170 K to 455 K and pressures up to 70 MPa. J Phys
air conditioning system using different cooling strategies. Int J Refrig Chem, Ref Data 1994;23(5).
2014;41:14–26. [49] Electrical Research Association. 1967 Steam Tables, Thermodynamic
[31] Garimella S, Brown AM, Nagavarapu AK. Waste heat driven absorption/vapor- Properties of Water and Steam; Viscosity of Water and Steam, Thermal
compression cascade refrigeration system for megawatt scale, high-flux, low- Conductivity of Water and Steam. London: Edward Arnold Publishers; 1967.
temperature cooling. Int J Refrig 2011;8:1776–85. [50] Pátek J, Klomfar J. A computationally effective formulation of the
[32] Kairouani L, Nehdi E. Cooling performance and energy saving of a thermodynamic properties of LiBr–H2O solutions from 273 to 500 K over full
compression–absorption refrigeration system assisted by geothermal energy. composition range. Int J Refrig 2006;29(4):566–78.
Appl Therm Eng 2006;26(2–3):288–94. [51] Shirazi A, Taylor RA, Morrison GL, White SD. A comprehensive, multi-objective
[33] Chinnappa JC, Crees MR, Murthy SS, Srinivasan K. Solar assisted vapor optimization of solar-powered absorption chiller systems for air-conditioning
compression/absorption cascaded air-conditioning systems. Sol Energy applications. Energy Convers Manage 2017;132:281–306.
1993;50:453–8. [52] Canada NR. RETScreen international. 4.1 ed.
[34] Munfath Khan MS, Orfi J. Cooling performance and energy saving analysis of [53] Al-Ugla AA, El-Shaarawi MAI, Said SAM, Al-Qutub AM. Techno-economic
cascade refrigeration system powered by solar energy for Riyadh region (Saudi analysis of solar-assisted air-conditioning systems for commercial buildings in
Arabia). Int J Sustain Build Technol Urban Dev 2014;5(1):44–52. Saudi Arabia. Renew Sustain Energy Rev 2016;54:1301–10.
[35] Boyaghchi FA, Mahmoodnezhad M, Sabeti V. Exergoeconomic analysis and [54] Yang S, Liang J, Yang S, Qian Y. A novel cascade refrigeration process using
optimization of a solar driven dual-evaporator vapor compression-absorption waste heat and its application to coal-to-SNG. Energy 2016;115(1):486–97.
cascade refrigeration system using water/CuO nanofluid. J Clean Prod [55] Gogoi TK, Konwar D. Exergy analysis of a H2O–LiCl absorption refrigeration
2016;139:970–85. system with operating temperatures estimated through inverse analysis.
[36] Duffie JA, Beckman WA. Solar engineering of thermal processes. 3rd Energy Convers Manage 2016;110:436–47.
ed. Hoboken, NJ, USA: Wiley; 2006. [56] Balaras CA, Dascalaki EG, Droutsa KG, Kontoyiannidis S. Empirical assessment
[37] Solutia technical bulletin 7239115C-TherminolVP. Available online at (https:// of calculated and actual heating energy use in Hellenic residential buildings.
www.therminol.com/products/Therminol-VP1). Appl Energy 2016;164:115–32.