You are on page 1of 12

Energy & Buildings 228 (2020) 110405

Contents lists available at ScienceDirect

Energy & Buildings


journal homepage: www.elsevier.com/locate/enb

Performance of a cold storage air-cooled heat pump system with phase


change materials for space cooling
Xiaoming Chen a,⇑, Quan Zhang b, Zhiqiang (John) Zhai c, Jinyou Qiu a
a
Key Laboratory of New Energy and Energy-saving in Building, Fujian Province University, and College of Ecological Environment and Urban Construction, Fujian University
of Technology, Fuzhou 350108, China
b
College of Civil Engineering, Hunan University, Changsha 410082, China
c
Department of Civil, Environmental and Architectural Engineering, University of Colorado at Boulder, Boulder, CO 80309-0428, USA

a r t i c l e i n f o a b s t r a c t

Article history: This paper studies the performance of a cold storage heat pump system integrated with phase change
Received 28 April 2020 materials (PCMs) for space cooling. An air-cooled heat pump unit comprising of two constant rotation
Revised 2 August 2020 speed compressors is selected. The PCM is an organic material that is commercially available, and has
Accepted 18 August 2020
a phase change temperature of 10–12 °C. A coupled computational heat transfer model of the heat pump
Available online 14 September 2020
unit, fan coil units, and a cold storage tank filled with PCM slabs is developed. The simulations are per-
formed under the climatic condition of Fuzhou, China. The operational behaviors of the cold charging and
Keywords:
discharging processes of the system are analyzed. Furthermore, the overall electrical energy and electric-
Thermal energy storage
Phase change material (PCM)
ity charge consumptions at various indoor temperature set points are compared. The results indicate that,
Heat pump system the electrical energy consumption of the cold storage heat pump system increases as the indoor temper-
Cold charging temperature ature increases. However, there is very little difference in the electrical energy consumption of the con-
Performance ventional heat pump system and the cold storage system. While under the demand tariff, the electricity
charge saving ratio of the cold storage system over the conventional system is 9.07%-11.28%. In general,
as the indoor temperature set point reduces, the electricity charge saving ratio increases. Moreover, the
effect of cold charging temperature is also discussed. It is found that higher cold charging temperature
consumes less electrical energy, however, takes longer to store the same amount of cold, and the differ-
ences relies on the required amount of cold.
Ó 2020 Elsevier B.V. All rights reserved.

1. Introduction period to the off-peak period. Ice storage is one of the most widely
used thermal energy storage methods, mainly because water has
Thermal energy storage techniques play an important role in characteristics such as, high heat of fusion, affordability, wide
building energy conservation. They bridge the temporal gap availability, ecofriendly, etc. Fang et al. [7] conducted an experi-
between the supply and demand of energy. Thermal energy stor- mental study on the charging and discharging performances of
age exists in many forms, such as sensible heat, latent heat, etc. an ice storage air-conditioning system with spherical capsules
Over the recent years, there has been an increased emphasis on packed bed. Moreover, Sehar et al. [8] performed a numerical anal-
latent heat thermal energy storage technologies using phase ysis on the chiller energy consumptions of a conventional air-
change materials (PCMs). This interest is due to the obvious advan- conditioning system without cold storage and an ice storage air-
tages of high thermal energy storage capacity and narrow temper- conditioning system for office buildings. Furthermore, Jannesari
ature variation of the storage process [1–3]. and Abdollahi [9] compared the usages of thin rings and annual
PCMs can be integrated into the air-conditioning or heat pump fins around coil to improve the performance of ice-on-coil thermal
systems. They can be used to store the cold generated by chillers storage systems.
using the off-peak electricity tariff at night, which can be released However, when compared with a conventional air-conditioning
in the following day for space cooling [4–6]. Consequently, the system, the evaporating temperature of an ice storage air-
electrical energy demand for cooling can be shifted from the peak conditioning system is lower by 8–10 °C. Resultantly, the opera-
tional efficiency is reduced by 30%-40% [10]. Recently, PCMs with
a higher phase change temperature, that could be charged by stan-
⇑ Corresponding author. dard chillers have shown potential to improve the operational effi-
E-mail address: xmchen@fjut.edu.cn (X. Chen).

https://doi.org/10.1016/j.enbuild.2020.110405
0378-7788/Ó 2020 Elsevier B.V. All rights reserved.
X. Chen et al. Energy & Buildings 228 (2020) 110405

Nomenclature

a; b1 ; b2 Coefficients Greek symbols


A Cross sectional area (m2) g Efficiency
cp Specific heat (J/kg °C) k Thermal conductivity (W/m °C)
d Water gap (m) q Density (kg/m3)
de Equivalent diameter (m) Dp Pressure loss (Pa)
e Thickness (m) DT Temperature difference (°C)
hc Convective heat transfer coefficient (W/m2 °C) Nu Nusselt number
KP Additional coefficient of pressure
KV Additional coefficient of flow rate Subscripts
l Length (m) ai Inlet air
N Input power (kW) amb Ambient
P Wetted perimeter (m) char Cold charging
q Cooling capacity (kW) or heat transfer rate (kW) dischar Cold discharging
Q Accumulated thermal energy (kWh) FCU Fan coil unit
t Time (s) HP Heat pump unit
T Temperature (°C) in Inlet
u Velocity (m/s) init Initial state
V Volumetric flow rate (m3/h) pump Water pump
w Width (m) st Cold storage tank
x; y Space coordinates (m) w Water
wi Inlet water
Abbreviations wo Outlet water
COP Coefficient of performance
PCM Phase change material

ciency. Therefore, both experimental and numerical researches mal energy storage using PCM. Reportedly, the suitable melting
have been conducted. With regards to experimental researches, temperature of PCM for the proposed system was about 19 °C. Fur-
Nagano et al. [11] designed and experimentally investigated a floor thermore, Chaiyat [16] designed an air conditioner with a pack bed
supply air-conditioning system integrated with granules contain- thermal energy storage unit filled with PCMs. Paraffin was utilized
ing PCMs. The phase change temperature of the PCM was approx- as the PCM, which has a melting point in the range of 19–22 °C.
imately 20 °C. It was concluded that in the simulated office space, When compared with an air conditioner without thermal storage
89% of the daily cooling load could be charged at night by a system unit, the proposed air conditioner using PCMs could save electrical
with a 30 mm thick packed bed of granules containing PCMs. Fur- energy consumption by 9% in the tropical conditions of Thailand. It
thermore, Nie et al. [12] designed and studied a thermal energy was reported that the payback period of the PCM balls was nearly
storage based air-conditioning unit for transport applications. 4.15 years. Moreover, Farah et al. [17] numerically investigated the
RT18HC was utilized as the PCM, having a phase change tempera- effect of adding a thermal energy storage unit using PCMs to an air
ture of 17–19 °C. It was concluded that, compared to the traditional source heat pump cooling system. A salt hydrate PCM with a melt-
air-conditioning system, the proposed system could reduce the ing temperature of 18 °C was utilized. The thermal energy storage
room temperature fluctuations by 40.6%, reduce the ON-OFF times unit was charged by the heat pump unit when the outdoor temper-
of the compressor by 27%, increase the overall COP of system by ature was relatively low, and discharged either whenever space
19.05%, and prolong the emergency cooling time by nearly 9 times. cooling was required during the day (mode M2) or during the peak
Moreover, Moreno et al. [13] studied a heat pump system inte- period only (mode M3). It was concluded that the heat pump unit
grated with thermal energy storage tanks. In summer conditions, consumed 11% and 6% of the electrical energy for thermal energy
tests were conducted on a water tank and a PCM tank filled with storage unit charging, and the thermal energy storage unit pro-
a salt hydrate PCM having a phase change temperature of 10 °C. vides 25% and 13% of the cooling energy in modes M2 and M3,
The results were compared, and following the comparison, it was respectively. Additionally, under the demand tariff, both modes
discovered that the PCM tank could provide 14.5% more cold for M2 and M3 resulted in reducing the total electricity cost by 14%
space cooling than the water tank. Additionally, it was also and 13%, respectively, when compared to the conventional heat
revealed that the indoor temperature could be maintained within pump unit without thermal energy storage unit (mode M1). More-
the thermal comfort range of 20.65% for a longer period. Having over, Wu et al. [18] carried out a numerical analysis on the thermal
said so, the PCM tank took 4.55 times longer to charge. Moreover, behavior of a cold storage system using spherical capsules packed
Chen et al. [14] proposed a refrigeration system using PCMs. The bed containing PCMs. N-tetradecane was utilized as the PCM, it has
study constructed and tested a prototype system, which used an a solidifying temperature of 2.73 °C and a melting temperature of
inorganic PCM with a phase change temperature of 17–21 °C. 7.79 °C. The heat transfer fluid (HTF) is a 40% ethylene glycol solu-
The analysis included the dynamic performances of the system tion. The study discussed the effects of inlet temperature, flow rate
under different modes of operation. It was reported that, under of HTF, porosity of the packed bed, and diameter of the capsules on
the national standard condition, the average COP for 60 min cold the solidification and melting time of the PCM, cold storage rate,
charging process is 2.2. A cooling capacity of over 0.5 kW could and cold released rate during the charging and discharging pro-
maintain the cold discharging process for about 93 min. cesses. It was found that, the inlet temperature and flow rate of
With regards to numerical studies, Yamaha and Misaki [15] car- HTF have a strong impact on the thermal performance of both
ried out an investigation on an air distribution system with ther- charging and discharging processes. However, the study did not

2
X. Chen et al. Energy & Buildings 228 (2020) 110405

analyze the consumption of electrical energy. Additionally, Zhu process, the water leaving the fan coil units passes through the
et al. [19] conducted an investigation on a ground source heat cold storage tank to be cooled by the PCMs, and then is directed
pump system comprising of PCMs for an office building in Wuhan, to the heat pump unit to be cooled further. The outlet water of
China. Hydrate sodium sulphate having a phase change tempera- the heat pump unit is directed to the fan coil units for space cool-
ture of 8.3 °C was utilized as the PCM. It was found that, compared ing. Lastly, during the conventional air-conditioning mode, the
to a common ground source heat pump without cold storage, the water from the heat pump unit is sent directly to the fan coil units
proposed ground source heat pump system with an optimal cool- for space cooling.
ing storage ratio of 40% has the potential to save up to 63.8% of A series of PCM slabs are parallelly arranged in the cold storage
the annual operational cost. Furthermore, Rahdar et al. [20] con- tank, which is illustrated in Fig. 2. Each slab comprises of PCMs
ducted an exergy, economic and environmental analysis, and a included in a container. The heat transfer process of such a slab
multi-objective optimization on the ice storage air-conditioning is supposed to be only conduction in an equivalent homogeneous
system and cold storage air-conditioning system using PCMs for material. The gap between the two adjacent PCM slabs serves as
an office building located in Ahwaz, Iran. The study utilized PCM the flow channel for water, which exchanges heat with PCMs to
(RT3HC) having a melting point of 3 °C. Reportedly, in comparison store and release thermal energy. The water flow direction follows
with the conventional air-conditioning system, the ice storage and the x-axis. This geometric configuration is chosen due to the sim-
the cold storage systems utilizing PCMs could save the annual elec- plicity in construction, high ratio of surface area to volume, and
trical energy consumption by 4.59% and 7.58%, respectively. Addi- less pressure drop in the heat transfer fluid. The heat transfer in
tionally, the payback periods was reported to be 3.16 and the PCM can be controlled by the choice of slab thickness [22,23].
5.56 years, respectively. Furthermore, Aljehani et al. [21] numeri- The PCM utilized is an organic material (RT11HC), which is
cally analyzed an air-conditioning system integrated with PCMs. commercially available [24]. It has a phase change temperature
Composite phase change material comprising of 78% Paraffin (n- of 10–12 °C. The cp-T curve of the PCM is shown in Fig. 3. The ther-
Tetradecane) and 22% Graphite was utilized, which has a melting mal conductivity is 0.2 W/(m °C), and the densities for solid and
range of 4–6 °C. The results indicated that when compared to an liquid states are 880 kg/m3 and 770 kg/m3, respectively.
air conditioner without thermal energy storage, the proposed cold
storage system has the capacity to downsize the compressor by 3. Mathematical model
50%, which results in reducing the electrical energy consumption
of the compressor by 30%. A computational heat transfer model is developed to predict the
In a thermal energy storage unit, a lower outlet HTF tempera- performance of the cold storage heat pump system. To simplify the
ture of a chiller results in a lower cold charging temperature, which analytical process, the following assumptions are made: (1) The
is equivalent to a higher heat transfer rate between HTF and PCMs. effect of natural convection of PCMs during the melting process
However, it also leads to decreasing the cooling capacity and the is neglected; (2) The flow of water is considered as a one-
coefficient of performance (COP) of a chiller. In addition, increasing dimensional problem in the x direction; (3) The heat transfer in
the indoor temperature set point results in improving the heat the PCM is treated as a two-dimensional problem in the (x, y)
exchange between the HTF and indoor air in the terminal unit. plane; (4) The thermal resistance of the walls in the PCM container
Consequently, the performance of a chiller is affected. Therefore, is ignored; (5) Heat gains from the surroundings are neglected.
in order to improve the energy efficiency of a cold storage system,
it is crucial to analyze the effects of cold charging temperature and
3.1. Model of thermal energy storage unit
indoor temperature set point on the system performance. How-
ever, to the best knowledge of the authors’, there has not been
The transient heat transfer equation for the PCM is
any research work reported in the literature on this topic.    
This paper develops a computational heat transfer model and @T @ @T @ @T
qcp ¼ k þ k ð1Þ
numerically studies the performance of a cold storage air-cooled @t @x @x @y @y
heat pump system using PCMs for space cooling. The simulations
In Equation (1) above, T denotes the temperature of PCM, oC; q
are conducted under the climatic condition of Fuzhou, China. The
denotes the density of PCM, kg/m3; cp denotes the specific heat of
operational behaviors of cold charging and discharging processes
PCM, J/(kgoC); k corresponds to the thermal conductivity of PCM,
of the system are analyzed. Moreover, the electrical energy and
W/(moC); x and y are space coordinates, m; and t is time, s.
electricity charge consumptions between the proposed cold stor-
The transient heat transfer equation for the water is:
age heat pump system and a conventional heat pump system are
compared at various indoor temperature set points. In addition, @T w @T w @ 2 T w hc P
the impact of cold charging temperatures is also investigated. qw cp;w ð þ uw Þ ¼ kw þ ðT wall  T w Þ ð2Þ
@t @x @x2 Aw
The outcomes of the study aid in the selection of suitable parame-
ters for designing PCM-based cold storage heat pump systems. In Equation (2) above, Tw corresponds to the temperature of
water, oC; qw denotes the density of water, kg/m3; cp,w denotes
the specific heat of water, J/(kgoC); uw corresponds to the water
2. System description velocity, m/s; kw denotes the thermal conductivity of water, W/
(moC); hc denotes the convective heat transfer coefficient between
As indicated in Fig. 1, the proposed cold storage heat pump sys- water and PCM slabs, W/(m2oC); P denotes the wetted perimeter,
tem comprises of an air-cooled heat pump unit, a cold storage tank m; Aw corresponds to the cross sectional area, m2; and Twall is the
filled with PCMs, fan coil units, three water pumps, seven electro- temperature of the PCM located at y = 0.
magnetic valves and water pipes, etc. The operational positions of The initial conditions are:
the electromagnetic valves depend on the modes of operation T ðx; y; t ¼ 0Þ ¼ T init ð3aÞ
The proposed system has three operating modes, namely, cold
charging, cold discharging, and conventional air-conditioning
T w ðx; t ¼ 0Þ ¼ T init ð3bÞ
modes. During the cold charging mode, the water is pumped to
the heat pump unit to be cooled, and then directed to the cold stor- where Tint corresponds to the initial temperature.
age tank to cool and solidify the PCMs. During the cold discharging The boundary conditions are as follows:
3
X. Chen et al. Energy & Buildings 228 (2020) 110405

Heat pump unit Tst, wo 6 Tst, wi V6 1. Compressor


2. Air-cooled condenser
3. Condenser fan
1 4. Thermal expansion value
7 5. Water-cooled evaporator
V7 V5
3 6. Cold storage tank with PCMs
5 ... 7. Fan coil unit
V1 8 8. Water pump 1
9. Water pump 2
2
10. Water pump 3
V2 9
V1-V7. Electromagnetic valves
THP, wo Refrigeration
4 V3 10 V4 TFCU, wi Water

Mode On Off

Mode 1 (cold charging mode) Heat pump unit, 8, V1, V5 and V6 7, 9, 10, V2, V3, V4 and V7

Mode 2 (cold discharging mode) Heat pump unit, 7, 9, V2, V4 and V6 8, 10, V1, V3, V5 and V7

Mode 3 (conventional air-conditioning mode) Heat pump unit, 7, 10, V3, V4 and V7 8, 10, V1, V2, V5 and V6

Fig. 1. Schematic of the cold storage heat pump system.

@T ðx ¼ 0; y; t Þ
¼0 ð4aÞ
@x

Flow channel
T w ðx ¼ 0; t Þ ¼ T in ð4bÞ
PCM slab

y e @T ðx ¼ l; y; tÞ
¼0 ð4cÞ
Water x d Water @x

@T ðx; y ¼ 0; t Þ
k ¼ hc ðT wall  T w Þ ð4dÞ
@y
w
l
@T ðx; y ¼ e=2; tÞ
Fig. 2. Schematic of the thermal energy storage unit. ¼0 ð4eÞ
@y

where Tin corresponds to the inlet water temperature, oC; l denotes


100
the length of PCM slabs, m; and e corresponds to the thickness of
PCM slabs, m.
Heat
The convective heat transfer coefficient between the water and
80 Cool
the PCMs can be obtained by [25]:

kw Nu
hc ¼ ð5Þ
cp (kJ/kg C)

60 de
o

In Equation (5) above, Nu signifies the Nusselt number; and de


is the equivalent diameter, m.
40
The above energy equations are discretized by the finite volume
method (FVM), with a fully implicit scheme [26]. The finite differ-
ence equations are solved iteratively at each time step.
20
The heat transfer model which was developed is validated using
the experimental results from Vakilaltojjar [27,28]. The PCM in the
0
experiment is CaCl26H2O, which has a phase change temperature
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 of 28 °C. It was found that, the mean relative errors of air temper-
o ature in the outlet of thermal energy storage unit between the sim-
T ( C)
ulated and measured data for the melting and solidifying processes
Fig. 3. cp-T curve of the PCM [24]. were 1.7% and 3.1%, respectively, which is plotted in Fig. 4. The
good agreeance between the simulated and measured data indi-
4
X. Chen et al. Energy & Buildings 228 (2020) 110405

(a) Furthermore, a fan coil unit with an air flow rate of 595 m3/h
40 and an input power of 30 W is selected, and its cooling capacity
(qFCU, W) curve under the water flow rate of 6 l/min can be defined
as follows:
37
qFCU ¼ a þ b1 T FCU;wi þ b2 T FCU;ai ð8Þ
Temperature ( C)
o

In Equation (8) above, TFCU, wi and TFCU, ai denotes the inlet


34 Inlet temperature water and air temperatures of fan coil unit, respectively, oC. The
Experimental results fitted coefficients of a, b1 and b2 are listed in Table 1.
Present results
31 Halawa et al.'s results 3.3. Performance parameters
number of PCM slabs = 28
28 In order to evaluate the performance, the cold storage rate, cold
air gap = 5 mm
-1 released rate, stored cold, supplied cold, and COP of the cold stor-
air flow rate = 96 l s age heat pump system are calculated.
25 The cold storage rate (qchar, kW) of the cold storage tank during
0.00 0.25 0.50 0.75 1.00 1.25 the charging process can be obtained by:
Time (h) Vw   1
qchar ¼ qw cp;w T st;wo  T st;wi ð9Þ
3600 1000
(b) In Equation (9) above, Tst,wi and Tst,wo denotes the inlet and out-
35
Inlet temperature let water temperatures of the cold storage tank, respectively, °C;
Experimental results and Vw corresponds to the water flow rate, m3/h.
30 Present results The cold released rate (qdischar, kW) of the cold storage tank dur-
Halawa et al.'s results ing discharging process is:
Temperature ( C)

Vw   1
o

25 number of PCM slabs = 28 qdischar ¼ qw cp;w T st;wi  T st;wo ð10Þ


3600 1000
air gap = 5 mm
-1 The amount of stored cold (Qchar, kWh) in the cold storage tank
air flow rate = 66 l s
20 during the charging process can be obtained by integrating Eq. (9)
with respect to the time, as follows:
Z
dt
15 Q char ¼ qchar ð11Þ
3600
The amount of supplied cold (Qdischar, kWh) by the cold storage
10 tank during discharging process is:
0.00 0.25 0.50 0.75 1.00 1.25
Z
dt
Time (h) Q dischar ¼ qdischar ð12Þ
3600
Fig. 4. Comparison of outlet air temperature of thermal energy storage unit during
the melting process (a) and solidifying process (b).
The COP of the system during the cold charging process
(COPchar) can be obtained by considering the ratio of cold storage
cate that the heat transfer model which was developed is accurate rate to the input power:
and reliable. qchar
COP char ¼ ð13Þ
N
3.2. Model of heat pump unit and fan coil unit In Equation (13) above, N denotes the total input power of the
system, kW.
In order to simplify the numerical solution, the characteristics The COP of the system during cold discharging process (COPdis-
of the heat pump unit and fan coil unit are modeled with the curve
char) is:
fitting method using the performance data from the
manufacturers. qdischar
COP dischar ¼ ð14Þ
An air-cooled heat pump unit with a nominal water flow rate of N
11.5 m3/h is chosen for this study. The heat pump unit comprises The total input power of the system during the cold charging
of two constant rotation speed compressors, and therefore has two process includes the input power of heat pump unit and water
series of energy regulation. The cooling capacity (qHP, kW) and pump, during the cold discharging process, the total power
input power (NHP, kW) curves of the heat pump unit with 100% includes the input power of heat pump unit, water pump, and
cooling (operating with two compressors) and 50% cooling (operat- fan coil units.
ing with one compressor) can be represented as follows: The input power of water pump (Npump, kW) can be determined
by [29]
qHP ¼ a þ b1 T HP;wi þ b2 T amb ð6Þ
K p K V Dppump V w 1
Npump ¼ ð15Þ
NHP ¼ a þ b1 T HP;wi þ b2 T amb ð7Þ 3600gpump 1000

In above relationships, THP, wi denotes the inlet water temper- where 4ppump denotes the pressure loss of water pump, Pa; gpump
ature of the heat pump unit, °C; Tamb denotes the ambient tem- denotes the efficiency of water pump; Kp corresponds to the addi-
perature, °C; and a, b1 and b2 are fitted coefficients, as listed in tional coefficient of pressure; and KV corresponds to the additional
Table 1. coefficient of flow rate. In the present study, the values of gpump, Kp
5
X. Chen et al. Energy & Buildings 228 (2020) 110405

Table 1
Coefficients for the performance curves of heat pump unit and fan coil unit.

Items Coefficient a Coefficient b1 Coefficient b2 R-square


qHP (100% cooling) 62.37 1.852 0.5662 0.9728
NHP (100% cooling) 9.363 0.1372 0.3088 0.9913
qHP (50% cooling) 36.43 1.067 0.3659 0.9939
NHP (50% cooling) 4.521 0.03096 0.1565 0.9880
QFCU 1505 190.1 201 0.9887

and KV are set at 60%, 1.15, and 1.1, respectively. Using the perfor- for the heat pump unit are both set at 3 min. The cold charging is
mance data from the manufacturers, the water pressure losses of completed when the outlet water temperature of the cold storage
the heat pump unit and fan coil unit are 67 kPa and 5.3 kPa, respec- tank (Tst, wo) is decreased to Tchar+4T. Fig. 6 illustrates the control
tively. During cold charging process, the overall water pressure loss flow of the cold storage heat pump system.
of the cold storage heat pump system is assumed to be 117 kPa, The cold discharging process is carried out from 8:00 am to
which includes the pressure losses of the heat pump unit, cold stor- 18:00 pm. During the discharging process, if the inlet water tem-
age tank, water pipes, water filters, and water values. In the mean- perature of the fan coil units (TFCU, wi) is increased to the set point
time, during the cold discharging process, the overall pressure is set Tdischar, the heat pump unit is switched on with one compressor.
to be 182.3 kPa, which comprises of the pressure losses of heat Else, the heat pump unit is not switched on, and only the cold stor-
pump unit, cold storage tank, fan coil units, water pipes, water fil- age tank provides cold for space cooling. Besides, the other com-
ters, and water values. pressor is switched on when TFCU, wi is again equal to Tdischar. In
The temperature rise of the water (4Tw, oC) when it passes the present study, Tdischar is set at 10 °C.
through the pump is considered, and it can be calculated by [30] For each case, the initial temperatures of the cold charging pro-
cess is 15 °C. In order to make the total water flow rates of the fan
K p K V Dppump
DT w ¼ ð16Þ coil units equal to the nominal water flow rate of the heat pump
qw cp;w gpump unit, a total of 32 fan coil units are in operation during the cold dis-
charging process. The geometric design of the PCM slabs has a
length of 1 m, width of 0.5 m, thickness of 20 mm, and a gap of
4. Results and discussions 10 mm between two adjacent PCM slabs. The number of PCM slabs
is assumed to be 300.
The simulations were conducted under the outdoor design
hourly meteorological data for summer air-conditioning of Fuzhou,
4.1. Operating behavior of the cold charging process
China. Fig. 5 presents the meteorological information [31].
The cold storage heat pump system starts to store cold at 1:00
Firstly, the operational behavior of the cold storage heat pump
am. Firstly, during the charging process, two compressors of the
system during the cold charging process under the charging tem-
heat pump unit are switched on. When the outlet water tempera-
perature of 7–9 °C is studied.
ture of the heat pump unit (THP, wo) reaches a set point (Tchar), one
As time elapses, the temperature of PCMs decreases. Addition-
of the compressors is switched off. Following this, the heat pump
ally, the thermal energy charged by PCMs initially is mainly in
unit operates with one compressor. Additionally, the heat pump
the form of sensible heat. So, it is initially observed that both the
unit is switched off when THP, wo reaches Tchar, and again it starts
inlet and outlet water temperatures of the cold storage tank decli-
with one compressor if THP, wo runs up to Tchar+4T. In other words,
nes rapidly, which is illustrated in Fig. 7. At 15 min, the outlet
the cold charging temperature is in the range from Tchar to Tchar+-
water temperature of the heat pump unit is decreased to its mini-
4T. However, the water pump is kept on running during the charg-
mum set point (7 °C), as a result, one compressor is switched off.
ing process. Moreover, the minimum running and shut-off periods
This lowers the cooling capacity of the heat pump unit. Resultantly,
a sudden rise of the inlet water temperature of the cold storage
38 tank is followed, with a range of 2.25 °C. Next, since thermal
energy charged by PCMs is primarily in the form of latent heat,
the inlet and outlet water temperatures of the cold storage tank
36
both decrease at a slower rate. At 1.8 h, the outlet water tempera-
ture of the heat pump unit reaches the minimum set point (7 °C)
34
again. So, the heat pump unit is switched off. At 1.85 h, the heat
Temperature ( C)

pump unit is switched on with one compressor because its outlet


o

32 water temperature rises to the maximum set point (9 °C), and its
shut-off period satisfies the minimum demand (3 min). This ON-
30 OFF operation of the heat pump unit is repeated until 4.14 h when
the outlet water temperature of the cold storage tank is decreased
28 to the set point for completing the cold charging (9 °C). The ON-
OFF operation causes oscillations in the inlet and outlet water tem-
26 peratures of the cold storage tank. In addition, during the shut-off
period, the inlet water temperature of the cold storage tank is
found to be higher than the outlet water temperature, as indicated
24
0 2 4 6 8 10 12 14 16 18 20 22 24 in Fig. 7. This is due to the heat gains from the pump which is kept
on running during the charging process [13,14].
Time (h)
Fig. 8 illustrates the cooling capacity provided by the heat pump
Fig. 5. Outdoor design hourly temperature for summer air-conditioning in Fuzhou, unit versus time during the cold charging process. It is evident
China [31]. from the figure that two compressors of the heat pump unit are
6
X. Chen et al. Energy & Buildings 228 (2020) 110405

(a) Cold charging mode (b) Cold discharging mode

Start Start

Turn on water pump


Turn on water pump
and fan coil units

Turn on heat pump unit with two No


TFUC, wi ≥ Tdischar ?
compressors
Yes
No Turn on heat pump unit with one
THP, wo ≤ Tchar ?
compressor
Yes
No
Turn off one compressor TFUC, wi ≥ Tdischar ?

Yes
Yes
Tst, wo ≤ Tchar ? Turn on the other compressor

No
No No
THP, wo ≤ Tchar ? 18:00 pm?

Yes Yes
No End
Running period ≥ 3 min?

Yes

Turn off heat pump unit

Yes
Tst, wo ≤ Tchar ?

No
No
THP, wo ≥ Tchar+ T?

Yes
No
Shut-off period ≥ 3 min?

Yes
Turn on heat pump unit with one
compressor

End

Fig. 6. Control flow of the cold storage heat pump system.

operating simultaneously in the region filled with sparse, while capacity gradually decreases from 39.65 kW to 37.2 kW. It fluctu-
only one compressor is operating in the other region. In addition, ates during the period of 1.8–4.14 h due to the ON-OFF operation of
the results from Fig. 8, indicate that the cooling capacity of the heat the heat pump unit.
pump unit reduces rapidly from 74.98 kW to 69.81 kW during the Fig. 9 illustrates the variations of cold storage rate and stored
period of 0–15 min. Since one compressor is switched off, a sudden cold in the cold storage tank versus time during the cold charging
drop of the cooling capacity is followed, with a variation of process. Since the cold storage rate of the cold storage tank is con-
30.17 kW. During the period from 15 min to 1.8 h, the cooling stricted to the cooling capacity of the heat pump unit, the change

7
X. Chen et al. Energy & Buildings 228 (2020) 110405

15 of the cooling capacity versus time is similar to that of the heat


Inlet water temperature of cold storage tank pump unit. It is observed that during the period of 0–15 min, the
Outlet water temperature of cold storage tank cold storage rate decreases rapidly from 74.09 kW to 68.83 kW.
13 An abrupt drop of the cold storage rate is followed, with a variation
of 30.16 kW. During the period from 15 min to 1.8 h, the cold stor-
age rate decreases gradually from 38.68 kW to 36.31 kW, and it
Temperature ( C)

11 presents an oscillation during the period of 1.8–4.14 h.


o

The amount of cold stored by the system increases to 17.87


kWh at 15 min, rises to 75.64 kWh at 1.8 h, and then to 118.88
9 kWh at 4.14 h. Accordingly, 63.6% of the cold is stored during the
first 1.8 h, while only 36.4% is stored during the remaining
2.34 h. More specifically, the system takes 43.5% of time to store
7 63.6% cold, and the remaining 56.5% of the time is used to store
the remaining 36.4% cold. Moreover, due to the ON-OFF operation
of the heat pump unit, a stepped shaped curve of the stored cold is
5 observed during the period of 1.8–4.14 h.
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 Fig. 10 illustrates the plots of the variations of input power and
Time (h) COP of the system versus time during the cold charging process. It
is observed that, during the period of 0–15 min, the input power
Fig. 7. Water temperatures versus time during cold charging process. decreases rapidly from 20.56 kW to 20.17 kW, a sudden drop with
a change of 10.22 kW is followed. During the period from 15 min to
1.8 h, there is a slow variation of the input power from 9.95 kW to
9.81 kW, with an oscillation within the range of 0.86–9.82 kW dur-
ing the period of 1.8–4.14 h.
75 The COP of system ranges from 3.60 to 3.41 during the period of
0–15 min. An abrupt rise of the COP of system is followed, with a
variation of 0.47. This can be attributed to the fact that one com-
60 one compressor operating pressor is switched off, and the COP of the heat pump unit is higher
Cooling capacity (kW)

with one compressor operating than when there are two compres-
sors operating. During the period from 15 min to 1.8 h, the COP of
45 the system gradually reduces from 3.89 to 3.7, and it fluctuates
during the period of 1.8–4.14 h due to the ON-OFF operation of
the heat pump unit.
30 Based on the analysis above, there are three distinct stages dur-
ing the cold charging process for the cold storage heat pump sys-
Two compressors tem. The first stage starts from the beginning to the time when
15 one of the two compressors is switched off (the period of 0–
operating
15 min). Simultaneously, the second stage begins, and it ends
when the heat pump unit is switched off for the first time (period
0 from 15 min to 1.8 h). Finally, during the third stage of the cold
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
charging process, the heat pump unit repeats ON-OFF operation
Time (h) (period of 1.8–4.14 h).
Fig. 8. Cooling capacity of heat pump unit versus time during cold charging process.

75 125 25 5
Cold storage rate Input power
Stored cold COP
60 100 20 4
Cold storage rate (kW)

Input power (kW)


Stored cold (kWh)

45 75 15 3
COP

30 50 10 2

15 25 5 1

0 0 0 0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Time (h) Time (h)

Fig. 9. Cold storage rate and stored cold versus time during cold charging process. Fig. 10. Input power and COP versus time during cold charging process.

8
X. Chen et al. Energy & Buildings 228 (2020) 110405

4.2. Operational behavior of cold discharging process

Cold released rate / cooling capacity (kW)


100 1000
Cold storage tank
Heat pump unit
This section analyzes the operational behavior of the cold stor- Cooling capacity
80 Fan coil units 800
age heat pump system during the cold discharging process with a
charging temperature of 7–9 °C.

Supplied cold (kWh)


As illustrated in Fig. 11, the inlet and outlet water temperatures 60 600
of the cold storage tank as well as the inlet water temperature of
the fan coil units increase sharply at first. When the heat pump Cold released rate
unit is switched off, the inlet water temperature of the fan coil 40 400
units is found to be approximately equal to the outlet water tem-
perature of the cold storage tank. At 10 min, the heat pump unit is
20 Supplied cold 200
switched on with one compressor because the inlet water temper-
ature of the fan coil units rises up to its set point (10 °C). Therefore,
sudden drops of the inlet water temperatures of the cold storage 0 0
tank and fan coil units is observed, with the changes of 1.45 °C 0 2 4 6 8 10
and 2.66 °C, respectively. Then, the inlet and outlet temperatures Time (h)
of the cold storage tank as well as the inlet temperature of the
Fig. 12. Cold released rate, cooling capacity and supplied cold during cold
fan coil units gradually increase until 2.72 h, where the inlet water
discharging process.
temperature of the fan coil units meets its set point (10 °C) again,
with the variations of 12.88–14.33 °C, 9.92–12.71 °C, and 7.34–
10 °C, respectively. Due to the switching on of the other compres- cooling capacity of the heat pump unit by 29.17 kW are seen, this
sor, sudden declines of the inlet water temperatures of the cold can be attributed to the switching on of the other compressor. In
storage tank and fan coil units are observed again, with the ranges general, during the period of 2.72–10 h, the cold released rate of
of 1.19 °C and 2.18 °C, respectively. Finally, the inlet and outlet the cold storage tank initially increases before gradually decreas-
water temperatures of the cold storage tank and the inlet temper- ing, with the change of 0.46–8.43 kWh. In the meantime, the cool-
ature of the fan coil units gradually rise until the end, with the ing capacity of the heat pump unit declines at first and then it
ranges of 13.14–13.49 °C, 12.71–13.45 °C, and 7.82–8.45 °C, gradually increases, with the range of 65.16–68.26 kW.
respectively. The inlet and outlet water temperatures of the cold The amount of cold supplied by the cold storage tank for space
storage tank are found to be equal in the end, in other words, the cooling reaches 10.47 kWh at 10 min, before increasing to 79.2
cold discharging process is completed. kWh at 2.72 h, and again increasing to 119.72 kWh at 10 h. The
Fig. 12 illustrates the variations of the cooling capacities of the output provided by the heat pump unit increases to 95.38 kWh
heat pump unit and fan coil units, the cold released rate of the cold at 2.72 h, and ultimately reaches 577.42 kWh. The results suggest
storage tank, and the amount of cold supplied for space cooling that 17.2% of the cold for space cooling during the 10 h cold dis-
versus time during the cold discharging process. The present study charging process is provided by the cold storage tank, while
found that, during the period of 0–10 min, the cold released rate of 82.8% is provided by the heat pump unit.
the cold storage tank decreases rapidly from 64.91 kW to Fig. 13 shows the plots of the variations of input power and COP
59.14 kW. Since the heat pump unit is switched on with one com- of the system versus time during the cold discharging process. Dur-
pressor, a sudden drop of the cold released rate is followed, with ing the period of 0–10 min, only the water pump and fan coil units
the range of 19.63 kW. During the period from 10 min to 2.72 h, are operating, as a result, the input power is maintained at 2.3 kW.
the cold released rate of the cold storage tank reduces gradually The COP is high, with the range of 27.88–25.36. Since the heat
from 39.51 kW to 21.67 kW, simultaneously, the cooling capacity pump unit is switched on with only one compressor, a sudden rise
of the heat pump unit slowly increases from 35.66 kW to of the input power by 9.68 kW and an abrupt drop of the COP of
37.66 kW. Next, an abrupt drop of the cold released rate by system by 19.15 is observed. During the period from 10 min to
15.97 kW in the cold storage tank and a sudden increase of the 2.72 h, the input power gradually increases from 11.98 kW to
12.49 kW, while the COP of the system slowly decreases from

15
30 30

13
25 25
Temperature ( C)

Input power (kW)


o

11 20 20

Input power
COP

15 15
9 COP

10 10

7 Inlet water temperature of cold storage tank


Outlet water temperature of cold storage tank 5
5
Inlet water temperature of fan coil units
5 0
0 2 4 6 8 10 0 2 4 6 8 10
Time (h) Time (h)

Fig. 11. Water temperatures versus time during cold discharging process. Fig. 13. Input power and COP versus time during cold discharging process.

9
X. Chen et al. Energy & Buildings 228 (2020) 110405

6.21 to 4.66. Since the other compressor is switched on, and also pump system has the capability to save the overall electrical
because the COP of the heat pump unit with two compressors energy consumption by 1.17%-2.47%. More specifically, this means
operating is lower than the one with one compressor operating, that there is very little difference in the overall electrical energy
an abrupt rise of the input power by 11.33 kW and a sudden drop consumption of the two systems.
of the COP of system by 1.66 are observed once more. In general, The electricity profile for commercial buildings in Fuzhou, China
during the period from 2.72 to 10 h, the input power reduces ini- is as follows: The electricity tariff during the mid-peak hours (7:00
tially before gradually increasing in the range of 23.78–24.51 kW, am–8:30 am, 11:30 am–14:30 pm, 17:30 pm–19:00 pm, 21:00 p
on the other hand, the COP of system increases initially before m–23:00 pm) is 0.5959 CNY/kWh [32]. In comparison with the
decreasing gradually in the range of 3.06–2.83. electricity tariff during the mid-peak hours, the value during the
The above analyzes indicate that three distinct stages also exist peak hours (8:30 am–11:30 am, 14:30 pm–17:30 pm, 19:00 pm–
during the cold discharging process. The first stage starts at the 21:00 pm) is 50% higher, during the off-peak hours (23:00 pm–
beginning and ends at the time when the heat pump unit is 7:00 am) it is decreased by 50% [33]. As presented in Fig. 14, it is
switched on with one compressor (period of 0–10 min). Simultane- observed that during the comparison of the conventional heat
ously, the second stage commences, and it concludes when the pump system and the cold storage heat pump system, the latter
other compressor is switched on (period from 10 min to 2.72 h). can save the electricity charge by 9.07%-11.28%. In general, a lower
Finally, the cold discharging process enters the third stage. During the indoor temperature set point results in a higher electricity
the third stage, the heat pump unit keeps operating with two charge saving ratio.
compressors.
4.4. Effect of cold charging temperature
4.3. Electrical energy and electricity charge consumptions
The cold storage heat pump system under the charging temper-
The overall electrical energy consumption of the cold storage atures of 5–7 °C, 6–8 °C, and 7–9 °C are simulated and compared to
heat pump system during the period of cold charge and discharge study the impact of cold charging temperature on its charging
at various indoor temperature set points is determined, the results performance.
are presented in Fig. 14. It is found that when the indoor temper- Fig. 15 illustrates the variation of the average COP versus the
ature set point is increased from 24 °C to 30 °C, the overall electri- stored cold during the cold charging process for the cold storage
cal energy consumption of the system increases from 197.8 kWh to system under various charging temperatures. As the stored cold
264.8 kWh, which is an increase of 33.87%. This can be attributed increases, the average COP of all systems decreases initially. How-
to the fact that increasing indoor temperature, the temperature dif- ever, this is followed by an increase, before decreasing again. This
ference between the chilled water and indoor air in the fan coil behavior could be explained as follows: as time elapses, the tem-
units increases, which in turn increases the cooling capacity of perature of PCMs decreases, and therefore the inlet water temper-
the fan coil units. Resultantly, additional cold should be supplied ature of the heat pump unit reduces, which in turn lowers the COP
by the heat pump unit. In particularly, the cold supplied by the of the heat pump unit. Resultantly, the average COP initially
heat pump unit increases from 461.86 kWh to 684.37 kWh when decreases as the cold stored increases. When the cold charging pro-
the indoor temperature set points is increased from 24 °C to cess enters the second stage, only one compressor is operating.
30 °C. Hence, the electrical energy consumption of the system Since the COP of the heat pump unit with one compressor operat-
increases as the indoor temperature increases. ing is higher than that with two compressors operating, a rise of
Furthermore, the overall electrical energy consumption and the average COP with the increase of the stored cold is followed.
electricity charge to supply the same amount of cold for space As the cold charging process enters the third stage, the water pump
cooling during the daytime from 8:00 am to 18:00 pm is compared keeps operating. So, even if the heat pump unit is switched off, the
for a conventional heat pump system and the cold storage heat electrical energy consumed by the water pump continually
pump system. For the conventional heat pump system, the water increases, however, the increase of the stored cold is very small
from the heat pump unit is sent directly to the fan coil units for or 0. More specifically, the cold storage system is operating with
space cooling. The results in Fig. 14 indicate that, when compared low energy-efficiency when the heat pump is switched off during
with the conventional heat pump system, the cold storage heat

4.2
o
400 16 Tchar = 5~7 C
Electrical energy consumption by cold storage system
o
Electrical energy consumption by conventional system Tchar = 6~8 C
Electrical energy consumption (kWh)

350 14 4.0
Electrical energy saving ratio by cold storage system o
Electricity charge saving ratio by cold storage system Tchar = 7~9 C
300 12

3.8
Saving ratio (%)

250 10
COP

200 8
3.6
150 6

100 4
3.4
50 2

0 0 3.2
24 25 26 27 28 30 0 30 60 90 120 150
o
Indoor temeprature set point C Stored cold (kWh)

Fig. 14. Overall electrical energy and electricity charge consumptions under various Fig. 15. Average COP versus stored cold during charging process under various cold
indoor temperature set points. charging temperatures.

10
X. Chen et al. Energy & Buildings 228 (2020) 110405

the ON-OFF operation period. Therefore, as a result of the continu- 5. Conclusions


ously increasing stored cold, the average COP decreases once more.
The results suggest that heat pump units with a digital scroll com- The performance of a cold storage heat pump system with PCMs
pressor or ones with an inverter compressor could be ideal for cold under various cold charging temperatures and indoor temperature
storage systems, mainly because they can decrease or eliminate set points was investigated using the computational heat transfer
the ON-OFF operation period of heat pump units. model developed in this paper. The heat pump unit is air-cooled
Furthermore, it is found that the cold storage heat pump system with two constant rotation speed compressors. The main conclu-
with a higher cold charging temperature has a higher average COP sions of the study can be listed as follows:
to store the same amount of cold than the system with a lower cold
charging temperature. Increasing the stored cold is initially benefi- (1) Three distinct stages can be observed during the cold charg-
cial before becoming less beneficial. According to the results, a ing process. The first stage starts from the beginning and
higher cold charging temperature has a positive impact on the sys- ends when one of the two compressors is switched off.
tem performance, in particularly in the partial cold storage. Most Simultaneously, the second stage commences, and it con-
notably, the greatest difference between the systems with cold cludes when the heat pump unit is switched off for the first
charging temperatures of 5–7 °C and 7–9 °C is observed at a stored time. Finally, the cold charging process enters the third
cold of 58.46 kWh. The overall electrical energy consumption for stage. During the third stage, the heat pump unit repeats
the case of 5–7 °C is 17.27 kWh, with an average COP of 3.39. ON-OFF operation with one compressor.
The overall electrical energy consumption for the case of 7–9 °C (2) Three distinct stages exist during the cold discharging pro-
is 15.76 kWh, with an average COP of 3.71. The result suggest that cess. The first stage starts at the beginning and concludes
the system with a charging temperature of 5–7 °C to store 58.46 when the heat pump unit is switched on with one compres-
kWh cold consumes 9.58% more electrical energy than with 7– sor. Simultaneously, the second stage begins, and it ends
9 °C. However, a higher cold charging temperature requires longer when the other compressor is switched on. Finally, the cold
to store the same amount of cold, which is presented in Fig. 16. In discharging process enters the third stage and continues in
particularly, the time required for the cases of 5–7 °C and 7–9 °C to this stage till the end. During the third stage, the heat pump
store 58.46 kWh cold is 0.86 h and 1.33 h, respectively, this pro- unit keeps operating with two compressors.
vides evidence that, the former charges 35.34% faster than the (3) The overall electrical energy consumption of the cold storage
latter. heat pump system increases as the indoor temperature
The results from Fig. 16 show that, the cold storage heat pump increases. In the studied conditions, when the indoor tem-
system with a lower cold charging temperature ultimately has a perature set point is increased from 24 °C to 30 °C, the over-
higher amount of cold stored, with the values of 142.09 kWh, all electrical energy consumption of the system increases
132.99 kWh, and 118.88 kWh for the cases of 5–7 °C, 6–8 °C and from 197.8 kWh to 264.8 kWh, which is an increase of
7–9 °C, respectively. This means that when compared with the case 33.87%.
of 7–9 °C, the cases of 5–7 °C and 6–8 °C is capable of increasing the (4) There is very little difference in the overall electrical energy
overall stored cold by 19.5% and 11.9%, respectively. Moreover, consumption of the conventional heat pump system and the
during the charging process, decreasing the cold charging temper- cold storage system. While under the demand tariff, the
ature can reduce the ON-OFF times of the heat pump unit. In par- electricity charge saving ratio of the cold storage system
ticularly, the ON-OFF times of the heat pump unit during the third over the conventional system is 9.07%-11.28%. In general,
stage for the systems with charging temperatures of 7–9 °C, 6–8 °C as the indoor temperature set point reduces, the electricity
and 5–7 °C are observed to be 22, 14, and 9, respectively. The result charge saving ratio increases.
suggest that when compared with the case of 7–9 °C, the cases of (5) A higher charging temperature has a positive effect on the
6–8 °C and 5–7 °C can effectively reduce the ON-OFF times of the energy-efficiency of cold charging process, and the benefit
heat pump unit by 36.4% and 59.1%, respectively. This can be is dependent on the cold required (the cooling demand on
attributed to the fact that, lowering the cold charging temperature the following day), however, it takes longer. In particularly,
can delay the time taken for the outlet water temperature of the a system with a charging temperature of 5–7 °C consumes
heat pump unit to reach its minimum set point, thereby reducing 9.58% more electrical energy to store 58.46 kWh cold when
the ON-OFF times of the heat pump unit. compared to the case with a charging temperature of 7–9 °C,
however, it charges 35.34% faster.
80 160 (6) In comparison with a system using a charging temperature
o
Tchar = 5~7 C of 7–9 °C, the cases of 5–7 °C and 6–8 °C increase the overall
70 o 140
Tchar = 6~8 C amount of cold which can be stored by 19.5% and 11.9%,
o respectively, and reduces the ON-OFF times of the heat
Cold storgae rate (kW)

60 Tchar = 7~9 C 120


pump unit by 59.1% and 36.4%, respectively.
Cold storage rate
Stored cold (kWh)

50 100
Heat pump units with a digital scroll compressor or ones with
40 80 an inverter compressor could be ideal for cold storage systems
integrated with PCMs, mainly because they can reduce or eliminate
30 60
the ON-OFF times of heat pump units, which will be taken into
20 40 account in future studies.

10 Stored cold 20
CRediT authorship contribution statement
0 0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Xiaoming Chen: Conceptualization, Software, Formal analysis,
Time (h)
Writing - original draft. Quan Zhang: Methodology, Writing -
Fig. 16. Cold storage rate and stored cold versus time during charging process review & editing. Zhiqiang (John) Zhai: Writing - review & editing,
under various cold charging temperatures. Supervision. Jinyou Qiu: Software, Data curation, Visualization.
11
X. Chen et al. Energy & Buildings 228 (2020) 110405

Declaration of Competing Interest [13] P. Moreno, A. Castell, C. Solé, G. Zsembinszki, L.F. Cabeza, PCM thermal energy
storage tanks in heat pump system for space cooling, Energy Build. 82 (2014)
399–405.
The authors declare that they have no known competing finan- [14] X. Chen, Q. Zhang, Z. Zhai, D. Wu, S. Liao, Experimental study on operation
cial interests or personal relationships that could have appeared characteristics of a novel refrigeration system using phase change material,
Energy Build. 150 (2017) 516–526.
to influence the work reported in this paper.
[15] M. Yamaha, S. Misaki, The evaluation of peak shaving by a thermal Storage
system using phase-change materials in air distribution systems, HVAC&R
Acknowledgments Research 12 (3c) (2006) 861–869.
[16] N. Chaiyat, Energy and economic analysis of a building air-conditioner with a
phase change material (PCM), Energy Convers. Manage. 94 (2015) 150–158.
The research work of this paper was supported by the Interna- [17] S. Farah, M. Liu, W. Saman, Numerical investigation of phase change material
tional Science and Technology Cooperation Program of China thermal storage for space cooling, Appl. Energy 239 (2019) 526–535.
(2017YFE0105800), National Natural Science Foundation of China [18] S. Wu, G. Fang, X. Liu, Thermal performance simulations of a packed bed cool
thermal energy storage system using n-tetradecane as phase change material,
(No. 51878254), Natural Science Foundation of Fujian Province, Int. J. Therm. Sci. 49 (9) (2010) 1752–1762.
China (No. 2019J01776), and Research Foundation of Education [19] N. Zhu, P. Hu, Y. Lei, Z. Jiang, F. Lei, Numerical study on ground source heat
Bureau of Fujian Province, China (JT180319). pump integrated with phase change material cooling storage system in office
building, Appl. Therm. Eng. 87 (2015) 615–623.
[20] M.H. Rahdar, A. Emamzadeh, A. Ataei, A comparative study on PCM and ice
References thermal energy storage tank for air-conditioning systems in office buildings,
Appl. Therm. Eng. 96 (2016) 391–399.
[1] C. Veerakumar, A. Sreekumar, Phase change material based cold thermal [21] Ahmed Aljehani, Siddique Ali K. Razack, Ludwig Nitsche, Said Al-Hallaja,
energy storage: materials, techniques and applications – a review, Int. J. Refrig. Design and optimization of a hybrid air conditioning system with thermal
67 (2016) 271–289. energy storage using phase change composite. Energy Conversion and
[2] H. Weinläder, F. Klinker, M. Yasin, PCM cooling ceilings in the Energy Management 169 (2018) 404-418.
Effificiency Center—passive cooling potential of two different system designs, [22] B. Zalba, J.M. Marı́n, L.F. Cabeza, H. Mehling, Free-cooling of buildings with
Energy Build. 119 (2016) 93–100. phase change materials, International Journal of Refrigeration 27(8) (2004)
[3] M.A. Said, H. Hassan, A study on the thermal energy storage of different phase 839-849.
change materials incorporated with the condenser of air-conditioning unit and [23] J.M. Marín, B. Zalba, L.F. Cabeza, H. Mehling, Improvement of a thermal energy
their effect on the unit performance. Energy and Buildings 202 (2019) 109353. storage using plates with paraffin–graphite composite, Int. J. Heat Mass Transf.
[4] E. Oró, A. de Gracia, A. Castell, M.M. Farid, L.F. Cabeza, Review on phase change 48 (12) (2005) 2561–2570.
materials (PCMs) for cold thermal energy storage applications, Appl. Energy 99 [24] Rubitherm GmbH <http://www.rubitherm.eu/en//index.html> (accessed
(2012) 513–533. 19.07.20).
[5] S. Li, Z. Liu, Xue-Jiao, A comprehensive review on positive cold energy storage [25] John H. Lienhard IV and John H. Lienhard V, A Heat Transfer Textbook, fourth
technologies and applications in air conditioning with phase change materials, ed., Phlogiston Press, Cambridge, Massachusetts, USA, 2012.
Appl. Energy 255 (2019) 113667. [26] W. Tao, Numerical Heat Transfer, second ed., Xi’an Jiaotong University Press,
[6] K. Faraj, M. Khaled, J. Faraj, F. Hachem, C. Castelain, Phase change material Xi’an, 2001 (In Chinese).
thermal energy storage systems for cooling applications in buildings: A review, [27] S.M. Vakilaltojjar, Phase change thermal storage system for space heating and
Renew. Sustain. Energy Rev. 119 (2020) 109579. cooling, PhD Thesis, School of Advanced Manufacturing and Mechanical
[7] G. Fang, S. Wu, X. Li, Experimental study on cool storage air-conditioning Engineering, University of South Australia, Adelaide, 2000.
system with spherical capsules packed bed, Energy Build. 42 (2010) 1056– [28] E. Halawa, W. Saman, F. Bruno, A phase change processor method for solving a
1062. one-dimensional phase change problem with convection boundary,
[8] F. Sehar, S. Rahman, M. Pipattanasomporn, Impacts of ice storage on electrical Renewable Energy 35 (8) (2010) 1688–1695.
energy consumptions in office buildings, Energy Build. 51 (2012) 255–262. [29] Z. Cai, T. Long, Fluid Mechanics, Pump and Fan, fifth ed., China Architecture &
[9] H. Jannesari, N. Abdollahi, Experimental and numerical study of thin ring and Building Press, Beijing, 2009 (in Chinese).
annular fin effects on improving the ice formation in ice-on-coil thermal [30] China electronics engineering design institute, Air-conditioning system design
storage systems, Appl. Energy 189 (2017) 369–384. manual, third ed., Beijing: China Architecture & Building Press, 2017. (In
[10] X.Q. Zhai, X.L. Wang, T. Wang, R.Z. Wang, A review on phase change cold Chinese)
storage in air-conditioning system: materials and applications, Renew. [31] China Meteorological Bureau. Climate information Center, Climate Data office
Sustain. Energy Rev. 22 (2013) 108–120. and Tsinghua University, Department of Building Science and Technology,
[11] K. Nagano, S. Takeda, T. Mochida, K. Shimakura, T. Nakamura, Study of a floor China standard weather data for analyzing building thermal conditions, China
supply air conditioning system using granular phase change material to Architecture & Building Press, Beijing, 2005 (In Chinese).
augment building mass thermal storage-heat response in small scale [32] < http://fgw.fuzhou.gov.cn/zz/fzgggz/jgysf/jfgs/201506/t20150615_76039.
experiments, Energy Build. 38 (5) (2006) 436–446. htm> (accessed 10.07.20).
[12] B. Nie, X. She, Z. Du, C. Xie, Y. Li, Z. He, Y. Ding, System performance and [33] Notice of the Fujian Provincial Price Bureau on the reasonable adjustment of
economic assessment of a thermal energy storage based air-conditioning unit electricity price . < http://xxgk.longyan.gov.cn/fgj/gkml/0600/201809/
for transport applications, Appl. Energy 251 (2019) 113254. t20180913_1368443.htm > (accessed 10.07.20).

12

You might also like