Professional Documents
Culture Documents
Product description Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm). Sizes 16 and
18 AWG are preferred.
Compatible detectors: All Signature Series detectors
Compatible electrical boxes
AB4G-SB Surface Box for Audible Base
North American 2-1/8 in (54 mm) deep 4-inch square box
North American 4 by 4 inch octagonal ring (mud box)
Standard European 100 mm square box
Agency listings: Meets or exceeds requirements specified in
UL 268, UL 464, and ULC-S525
Base diameter: 6.8 in (173 mm)
Base height from box: 0.8 in (21 mm)
Maximum distance from ceiling (wall mount): 12 in (305 mm)
Storage temperature: -4 to 140 °F (-20 to 60 °C)
Cautions
To avoid accidental damage to the panel, disconnect all power
before wiring the unit.
Electrical supervision requires the wire run to be broken at
each terminal. Do not loop the signaling circuit field wires
around the terminals.
1. The unit default is for high dBA output. To set the output to
low dBA, cut the circuit board trace as marked on the back
of the PC board. (See Figure 3.)
2. The unit default is for temporal pattern output. To set the
output to steady tone, cut the circuit board trace as marked
on the back of the PC board. (See Figure 3.)
3. Select and install a compatible electrical box, and bring the
field wiring into the box.
4. Connect the field wiring to the terminals on the back of the
base plate. You must observe polarity for the unit to
function properly. (See Figure 3.)
5. Attach the base plate to the electrical box.
6. Align the trim ring so that the four tabs on the ring mate
with the four slots in the base plate, then press the trim ring Figure 1: Installing the Audible Detector Base
onto the base plate until the tabs lock.
7. Attach the desired Signature detector to the base. Align the
arrows on the detector and trim ring, press the detector into
the base, and rotate the detector until it locks into place.
8. Apply power and activate the unit to verify that it is
operating properly.
To configure output
volume or tone, cut
DATA- DATA- DATA+
the circuit board as
SIG+ SIG- OUT IN IN/OUT shown.
-
Data in - Data out
From Signature controller or To next Signature device
previous device + +
Application diagrams
Detector operates the base The Signature CR module is optional, and is used to silence
the bases on the line.
In this application the detector operates the base. That is, the
base follows the state of the detector, going into and out of
alarm with the detector.
AB4G AB4G
IN/OUT
IN/OUT
DATA+
DATA+
S IG+
S IG+
S IG-
S IG-
24 Vdc
From listed - Listed EOL
power supply + relay and
supervising
8 7 6 module
CR
4 3 2 1
Data in
From Signature +
controller
-
AB4G AB4G
IN/OUT
IN/OUT
DATA+
DATA+
S IG+
S IG+
S IG-
S IG-
24 Vdc
From listed - Listed EOL
power supply + relay and
supervising
8 7 6 8 7 6 5 module
CR CRR
4 3 2 1 4 3 2 1
Data in
From Signature +
controller
-
System turns on bases with synchronization If the Signature CRR module is not activated, then each
detector can still operate its base, but the bases will not be
In this application, all bases on the line are activated by system synchronized.
programming that triggers the Signature CRR module. The
bases are synchronized by the G1M-RM for temporal sound. The Signature CR module is optional, and is used to silence
the bases on the line.
AB4G AB4G
IN/OUT
IN/OUT
DATA+
DATA+
S IG+
S IG+
S IG-
S IG-
Listed EOL
relay and
supervising
module
8 7 6 5 8 7 6 8 7 6 5
G1M-RM CR CRR
4 3 2 1 4 3 2 1 4 3 2 1
24 Vdc
From listed -
power supply +
Data in
From Signature +
controller
-