AAMA 501.6-01
Recommended Dynamic Test
Method For Determining The
Seismic Drift Causing Glass
Fallout From A Wall System
M A N U F A C T U R E R S A S S O C I A T I O N
TABLE OF CONTENTS
501.4-00 (Revised 7/18/01) Recommended Static Test Method For
Evaluating Curtain Wall And Storefront Systems Subjected To Seismic
And Wind Induced Interstory Drifts
1.0 Scope ...............................................................................1
2.0 Introduction ......................................................................1
3.0 Definitions ........................................................................1
4.0 Historical Context...............................................................2
5.0 General Notes Regarding The Test Method ..............................3
6.0 Test Specimens ..................................................................4
7.0 Recommended Test Procedures .............................................4
8.0 Apparatus .........................................................................5
9.0 Safety Precautions..............................................................6
10.0 Test Agency .....................................................................6
11.0 Pass/Fail Criteria ..............................................................6
12.0 Test Report......................................................................7
13.0 Referenced Documents ......................................................7
© 2001
American Architectural Manufacturers Association
1827 Walden Office Square, Suite 550, Schaumburg, IL 60173
PHONE 847/303-5664 FAX 847/303-5774
EMAIL webmaster@aamanet.org WEBSITE www.aamanet.org
All AAMA documents may be ordered at our web site in the “Publications Store”.
Force – A push or pull action that tends to change the It is anticipated that new codes will provide more
shape of a deformable body or the state of motion of an guidance regarding the magnitude of seismic movements
object. appropriate for the seismic design of building wall
systems.
2) Immediate Occupancy Level, with moderate damage 5.4 Seismic performance requirements for operating
to non-structural elements and light damage to windows and doors installed within a curtain wall or
structural elements in the primary structural system storefront wall system might differ from those required
of the building; for “non-operating” components of the wall system.
3) Life Safety Level, with moderate damage to 5.5 The design displacements for project specific testing
structural and non-structural elements; and shall be specified in the contract documents. Unless
otherwise specified, horizontal displacements employed
4) Near Collapse Level (also known as the “Hazards in this test method shall be in the plane of the primary
Reduced Level” of performance in the FEMA 273 mock-up elevation. Design displacements shall be 0.010
Seismic Rehabilitation Guidelines.) x the greater adjacent story height, unless otherwise
specified.
Although these levels are still somewhat conceptual, they
provide at least some degree of guidance to designers. Specifier Note: The specifier should refer to the building
engineer of record considering the applicable building
code or NEHRP Table 5.2.8 or NEHRP Equation 6.1.4-1
5.7 The accredited independent testing agency shall be 7.2.1 Test chamber elements representing the primary
responsible for a chamber design and details of the building structure shall be displaced to produce the
movement system. specified movements. Each test shall consist of three (3)
full cycles. (Herein, a cycle is defined as a full
displacement in one direction, back to the originating
6.0 TEST SPECIMENS point, full displacement in the opposite direction, and
back to the originating point.) At the conclusion of the
6.1 The curtain wall or storefront test specimen shall be test, technicians and witnesses shall visually inspect the
of sufficient size and configuration to determine the mock-up for evidences of failure. The Test Agency shall
performance of all typical parts of the wall system. For record all areas of visual distress, such as disengagement,
curtain walls or other walls constructed with prefabricated metal distortion, sealant or glazing failure, or permanent
units, the specimen width shall be not less than two deformation. If glass breakage occurs during the
typical units plus the connections and supporting elements displacement test, the Test Agency personnel shall
at both sides, and shall be sufficient to provide full carefully examine the test specimen. If breakage was
loading on at least one typical vertical joint or framing caused by deformation or failure of the supporting frame
member, or both. The height shall not be less than the full of the glass, or by any interaction between the glass and
building story height or the height of the unit, whichever its supporting elements, record the findings and
is greater, and shall include at least one full horizontal discontinue the test. If the cause of the breakage cannot
joint, which accommodates vertical expansion. For be determined replace the glass with the original
multistory systems, the specimen height shall not be less components and repeat the test one additional time.
than two full building stories plus the height necessary to
include one full horizontal joint accommodating vertical 7.2.2 Elements representing the building structure shall
expansion. be displaced in a manner and method as determined by
the Testing Agency and may be subject to review by the
6.2 All parts of the curtain wall or storefront test design professional. (See Figure 1 for typical test
specimen shall be full size, using the same materials, type specimen configuration with moveable test chamber
of glass, details, methods of construction, and anchorage elements.)
as those used on the actual building.
TYPICAL
STORY
MOVABLE HEIGHT
FLOOR
ELEMENT
FIGURE 1
Typical Test Specimen Configuration
7.2.3 The time duration of each cycle is not prescribed, distress such as disengagement, metal distortion, sealant
but shall be recorded for information purposes only. tearing, glass fracture, glazing failure, or permanent
Changes in displacement direction(s) shall allow for deformation.
movement of equipment, stops, measuring devices, etc.
The Test Agency shall displace the chamber elements in a 7.5 Unless otherwise specified, the default test sequence
manner that does not induce sudden acceleration and shall be as follows:
deceleration. S Air Leakage (ASTM E283)
S Static Water Resistance (ASTM E331)
7.2.4 Additional cycles and/or displacement direction(s) S Dynamic Water Resistance (AAMA 501.1) (optional)
may be specified by the design professional. S Structural Performance @ Design Wind Pressure
(ASTM E330)
7.2.5 The design displacement shall be determined by the S Repeat Air Leakage (ASTM E283) (optional)
specifier according to the predicted interstory movements S Repeat Static Water Resistance (ASTM E331)
of the subject building. For multi-story mock-ups, the (optional)
displacement between levels may vary due to different S Seismic Movement @ Design Displacement (AAMA
story heights. Unless otherwise specified, the design 501.4)
displacement shall be 0.010 x the greater of the adjacent S Repeat Air Leakage (ASTM E283)
story heights. The displacement shall be measured at the S Repeat Static Water Resistance (ASTM E331)
movable floor element, not at the test specimen. S Structural Performance @ 1.5 x Design Wind
Pressure (ASTM E330)
7.3 Serviceability tests for air leakage (ASTM E283) and S Seismic Movement @ 1.5 x Design Displacement
water penetration (ASTM E331) may be conducted after (AAMA 501.4)
the static displacement tests. The air leakage and water
penetration tests should be conducted at the pressures Note: To determine the drift causing glass fallout
specified for the project. (i.e., ∆fallout), refer to AAMA 501.6-01.
“BOCA National Building Code Commentary” – 1999 “NEHRP Guidelines for the Seismic Rehabilitation of
Edition Buildings,” 1997, BSSC (Building Seismic Safety
Council) Washington, DC, Issued by Federal Emergency
“Standard Building Code” – 1997 Edition, Southern Management Agency as FEMA 273.
Building Code Congress International (SBCCI), 900
Montclair Road, Birmingham, AL 35213 Endnotes:
(1) “Seismic Code Questioned.” ENR/May 8, 1995 p. 3.
“International Building Code” – 2000 Edition,
International Code Council, 5203 Leesburg Pike, Suite (2) Reviewing the “Seismic Provisions of the 1988
708, Falls Church, VA 22041-3401 Uniform Building Code”, by Philip Terry, P.E. as
reported in Building Standards Magazine/March-April
“NEHRP Recommended Provisions for Seismic 1991 p. 11.
Regulations for New Buildings and Other Structures,”
20 0.8
Drift Amplitude (mm)
0 0.0
-10 -0.4
-20 -0.8
0 5 10 15 20 25 30
Time (sec)
200 7.9
Drift Amplitude (mm)
FIGURE 3
Schematic of Displacement Time History for Dynamic Crescendo Test
Controller
Load Y Function
Digital Disp. X Generator
Oscilloscope 458.2 4
5
8
4
5
8
458.91
. .
1 1
3 1
Displacement
Sliding Steel Tube Transducer
Links (LVDT)
Steel Plate Mounted
to Reaction Frame
FIGURE 4
Control and Data Acquisition System for Dynamic Racking Test Facility at the Building Envelope Research
Laboratory, Department of Architectural Engineering, The Pennsylvania State University, University Park, PA.