Professional Documents
Culture Documents
VRIOGS 012.7.1
Revision: A
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
ii VRIOGS 012.7.1 Revision A
APPROVAL STATUS
Document Developer
Metropolitan Train
(Metro Trains
Melbourne)
Intrastate Train
(V/Line)
Interstate Train
(ARTC)
Tram
(Yarra Trams)
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A iii
The Standard has been created through the collaboration of members of the
Victorian Rail Industry Operators’ Group (VRIOG) for the purpose of establishing
standards which, if implemented throughout the Victorian Rail Network, will facilitate
the interoperability of infrastructure.
The use of the Standard is not prescribed by law but, if adopted, conformity with the
provisions of the Standard is mandatory in order that the purpose of the Standard be
achieved.
DISCLAIMER
Each person is responsible for making his or her own assessment of all such
information and for verifying such information. The content of this publication is not a
substitute for professional advice.
The Director of Public Transport and VRIOG accept no liability for any loss or
damage to any person, howsoever caused, for information contained in this
publication, or any purported reliance thereon.
COPYRIGHT STATEMENT
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
iv VRIOGS 012.7.1 Revision A
TABLE OF CONTENTS
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 1
1) Words or phrases that appear capitalised out of context are defined within the
Definitions section of this VRIOG Standard.
2) The word “Shall” is to be understood as mandatory.
3) The word “Should” is to be understood as non-mandatory i.e. advisory or
recommended.
4) Uncontrolled Standards may not be referenced within the VRIOG Standards.
These include former PTC Standards, Franchisee Standards, Franchisee
Subcontractor Standards and Infrastructure Lessee Standards.
5) Controlled Standards, including Australian Standards and other VRIOG
Standards, may be referenced but only if:
The referenced item can not be adequately explained with an amount
of text that could not reasonably be inserted into the body of the
Standard.
The reader is not referenced to another Controlled Standard
necessary for the item to be adequately explained i.e. one document
link only.
The referenced document is a Figure or table and could not
reasonably be included in the appendices of the Standard.
6) The format employed in the VRIOG Standards is compatible with Australian
Standards, and will be used from this point on.
7) The numbering system for the VRIOG Standards is chronologically
sequential from the point of introduction, and is not based on any form of
interpretive system.
8) The VRIOG Standards contain engineering information necessary to operate
a safe Railway. VRIOG Standards will not contain any information that can be
construed as a work instruction, procedure, process or protocol. This
information forms the basis of each individual entity’s Safety Accreditation
Certification, and, as such, is outside the scope of VRIOG Standards.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
2 VRIOGS 012.7.1 Revision A
Terminology Definition
Accredited Rail A Rail Infrastructure Manager or Rolling Stock Operator who is
Operator (ARO) accredited under Part 5 of the Rail Safety Act 2006.
Application for An application to the Safety Director by an accredited rail operator
Variation of for variation of its accreditation due to the accredited rail operator
Accreditation proposing to make change to or to the manner of carrying out,
accredited rail operations that may reasonably be expected:-
• To change the nature, character and scope of the accredited
rail operator; or
To not be within the competence and capacity for which the
accredited rail operator is accredited.
Back Contacts: Normally Closed contacts (de-energized state).
Drop Away Voltage The maximum voltage (or current) by which all front contacts has
(or Current) opened.
Fragility Factor The ‘fragility factor’ (sometimes called the ‘G’ factor) of an article is
a measure of the maximum shock that can be applied to it without
damage being caused.
Front Contacts: Normally Open contacts (de-energized state).
Nominal Voltage The Voltage at which the Relay is designed to operate.
Non-Vital A term applied to equipment whose correct operation is not
essential to the integrity of the signalling system.
Pick Up Voltage (or The minimum voltage (or current) at which all front contacts of the
Current) relay has made.
Purchaser Person or organisation to which the vital relays is supplied or being
supplied.
Note: They may not be a direct representative of the ARO.
Service Operating The voltage range within which the relay should be operated when
Voltage in service.
Vital A term applied to equipment whose correct operation is essential to
the integrity of the signalling system.
VRIOG Victorian Rail Industry Operators Group – The list members group
consists of :-
• VicTrack
• V/Line Passenger
• Metro Trains Melbourne
• Yarra Trams
• Australian Rail Track Corporation
• Public Transport Division of the Department of Transport
VRIOGS Victorian Rail Industry Operators Group Standards.
Table 1 – Terminology
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 3
3.2 General
Vital Signalling relays have been purpose designed for application in fail safe
signalling circuits and can be divided into three categories:
This specification refers only to miniature plug-in relays in service within VRIOG.
Miniature plug-in relays (called miniature only because of their size in relation to the
large or standard plug-in relay) are manufactured to the British Rail 930 series of
specifications in 12V DC line, 24V DC line, 50V DC line, 110V AC line and various
track relay varieties together with electronic timers.
a) Where heavy duty contacts are necessary such as in contactor versions and;
b) Where the welding of a contact will not prejudice the safety features of the
relay.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
4 VRIOGS 012.7.1 Revision A
3.5 Application
General
DC
VRIOG Or Plugboard
Operating Remarks
Designation Manufacturer’s Coding
Voltage
Designation
MBA/12-4 QBA1/12-4 50 ACDFH BR Spec 932
MBA/12-4 QBA1/12-4 24 ABFGH BR Spec 932
MBLA/12-4 QBA1/12-4 12 ABDGS BR Spec 932
MBA/8-8 QBA1/8-8 50 ACDGH BR Spec 932
MBA/8-8 QBA1/8-8 24 ACDEH BR Spec 932
MBA/8-8 QBA1/8-8 12 ABDJS BR Spec 932
MBA/8-4 QBA1/8-4 50 ACDFH BR Spec 932
MSRA/8-4 QSRA1/8-4 50 ADEHJ BR Spec 934
MSRA/8-4 QSRA1/8-4 24 ADEFJ BR Spec 934
MSRA/6-6 QSRA1/6-6 50 ADFGJ BR Spec 934
MSPA/8-4 QSPA1/8-4 50 ABDGJ BR Spec 933
2MBA/4-4 QBBA1/4-4 50 ABCEH BR Spec 961
2MBA/4-4 QBBA1/4-4 24 ACEFK BR Spec 961
2MBLA/4-4 QBBA1/4-4 12 ABDKS BR Spec 961
2MBA/6-2 QBBA1/6-2 50 ABFHJ BR Spec 961
2MBA/6-2 QBBA1/6-2 24 ACEGK BR Spec 961
2MBLA/6-2 QBBA1/6-2 12 BEFGX BR Spec 961
Twin NV
TDU QTD1 50 ACGJX
Timer
Twin NV
TDU QTD1 24 ACHJX
Timer
Twin NV
TDU QTD1 12 ABEFS
Timer
MSX QTD4 12 BCEGX BR Spec 964
QTD5/5-2 or
MNR/5-2 50 BDFHX BR Spec 962
SELECT-2
MNR/4-3 QTD5/4-3 50 BEGHX BR Spec 962
MNR/5-2 QTD5/5-2 12 BDGHX BR Spec 962
MNR/4-3 QTD5/4-3 12 BEFJX BR Spec 962
MBCA/2H/4-4 QBCA/2H/4-4 50 BEGHJ BR Spec 966
MBCA/2H/4-4 QBCA/2H/4-4 24 BEFHJ BR Spec 966
MBLCA/2H/4-4 QBCA/2H/4-4 12 ABCKS BR Spec 966
MML/11-4 QL1/11-4 50 ABEFG BR Spec 935
MML/11-4 QL1/11-4 24 ABDEG BR Spec 935
MML/11-4 QL1/11-4 12 BDGJX BR Spec 935
M2T/2-2 QT2/2-2 4Ω ACFGK BR Spec 938
BR Specs 932
4MBT/2-2 QBT1/2-2 4Ω DFHJX
& 938
270MT/8-8 QN1/8-8 UM71 Output BDEGX BR Spec 930
270MT1/2-2 QT1/2-2 270Ω BCGJX BR Spec 938
MNS QTD3 50 AEGJX Refurbish only
MNM QTD3 50 AEGJX Refurbish only
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 5
General
DC
VRIOG Or Plugboard
Operating Remarks
Designation Manufacturer’s Coding
Voltage
Designation
MZSPA/7-4 QTR1/7-4 Output for AEHJX Refurbish only
QTD3
MZT/4-4 QPA2 40V AC track ADGHX Special
MS2/6-6 QS2/6-6 12 BCGHX BR930
QAJTC1 24 ADEJS JTC Amplifier
MNHX/8-4 QNHX1/8-4 110 AC ACEFH BR Spec 966
QNHXC1/2H/4-4 110 AC ADGKS SSI Interface
QNCM1/2HF/- 12 BCFHS
4MB
270MT/4-2 QT1/4-2 270Ω BDEJX AFO-M
Output
MSRA/6-2 QSRA4/6-2 50 BDEHK
MLSRA/6-2 QSRA4/6-2 12 ADFGS
2MBA/4-4 QBH1/4-4 50 ABCEM Non Vital
(Refurbish
only)
Table 2 – Relay Types
The matching of coding of relay to base is critical to the safety integrity of the
signalling system.
Under no circumstances is a base to be “re-coded”.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
6 VRIOGS 012.7.1 Revision A
Unless otherwise stated herein the relays shall comply in every respect with the
applicable BRB specifications.
Wherever a relay does not comply with a particular BRB specification or equivalent,
its description shall be related to the closest relevant specification.
4.1 Plugboards
The coding of the plugboard shall be as indicated in Section 3.5 of this specification.
4.2 Connectors
The crimp type connectors shall be in accordance with BR Specification BR 831 and
suitable for wire size 24/.020 double insulated.
The nominal operating voltages of the relays within this specification are specified in
Section 3.5.
The operating performance parameters for other relays in this specification are
specified in the relevant appendix.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 7
Each relay shall be subjected to a series of tests to confirm that it conforms to the
requirements of the relevant BRB standard(s) and the requirements of this standard.
Each relay shall be supplied with a test sheet containing at least the following
information:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
8 VRIOGS 012.7.1 Revision A
All vital relays supplied by manufacturers and authorised relay servicing staff shall be
sealed. All relays installed in the field that are not presently sealed, shall be
considered as not fit for service.
This seal shall not be broken in the field except in exceptional circumstances when
directed by an authorized representative of an ARO Infrastructure Manager. In the
event of a defect being observed in a relay the seal shall be left intact until the relay
is examined by an appropriately competent railway safety worker. (See below.)
All new relays shall be supplied with BLACK seal plugs. This colour plug shall be
used exclusively for new relays only.
Any relay resealed shall be sealed with plugs of any colour other than black.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 9
The ARO Infrastructure Manager may assign another unique serial number to assist
maintenance of their asset register.
7.2 Labelling
Specifically, each relay shall have a self adhesive label (Type A see below) with its
assigned asset number, its VRIOG type (see Section 3.5) and its initial Pick up and
Drop away figures and the initials of the tester and the date of test. This label shall be
affixed to the front of the relay case immediately below the handle.
Following any subsequent overhaul or examination the relay shall be retested and
the results recorded on self adhesive label (Type B: see below), which shall be
affixed to the front of the relay case immediately above the handle.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
10 VRIOGS 012.7.1 Revision A
Each relay shall be supplied with a relay record card (See below) which is contained
within a “REPLACEMENT or SERVICEABLE RELAY” envelope which shall be
securely attached to the relay. The card shall be completed by the person installing
the relay. The card is to be then replaced with in the envelope and sent to the
relevant Infrastructure Asset Manager for updating of the Infrastructure Asset
Management System.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 11
The contact assemblies and other fittings within Q style railway signalling safety
relays are the quite fragile. The relays shall be packaged and handled in such a
manner that the transport and storage of these units does not materially influence
their subsequent in-service performance.
The relays shall be packaged such that the contact springs are in vertical alignment
with the contacts at the top and the plug-base is lowest. The cushioning of the
packaging must allow that the fragility factor of the relays is approximately 50: (Ref
Australian Standard “Packaging – Part 10: Protection against shock and vibration”
AS 2400.10 - 2006: Table 2).
The relays shall be packaged such that their performance including contact
resistance shall not deteriorate if stored in an environment equivalent to their
operating environment (Ref: VRIOG Standard “Environmental Conditions” VRIOGS
012.7.25) for 12 months before installation.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
12 VRIOGS 012.7.1 Revision A
Cases have occurred where newly installed miniature plug-in signalling relays have
failed to operate, and it was found that their contacts were out of adjustment due to
distortion of their stationary contact support brackets.
It has been demonstrated that this fault was a result of the relay having been
dropped or struck during transport or installation.
Extreme care shall be exercised in transporting and handling relays. Any relay which
is bumped should be closely examined and an operational check should be
performed, and if need be returned for overhaul and retest.
For relay which is dropped, they should be returned for overhaul and retest
immediately.
Because of the risk that relays may have been dropped or damaged without
knowledge, any relay which is to be placed in service shall be visually inspected
before being plugged into service.
If there is any sign of damage to the case or to the internal assembly of the relay it
shall not be put into service but sent for retest and if necessary, servicing.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 13
The removal and re-insertion of all miniature plug-in relays should be minimised to
avoid damage to and/or loss of tension in the contacts in the relay and base.
When inserting miniature plug-in relays into their bases, the relay must be held at 90
degrees to the base as it is plugged in. If the relay is offered up to the base at an
angle, there is a high risk that the contact fingers on the back of the relay will be bent
back leading to high resistance or open circuit between relay and base. This is
particularly important when inserting a relay of one make into a base made by a
different manufacturer.
Where miniature plug-in relays are removed from their bases for any reason, the
relays should be inserted back into the base from which they were removed and they
shall be replaced by a relay with a current test certificate.
Before Q Type (BRB930) miniature plug in relays which have been in service for
longer than 8 weeks are considered for reuse in new or altered works, the contacts
shall be retested and, if necessary, serviced and a current test report shall be
provided with the relay.
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
14 VRIOGS 012.7.1 Revision A
This specification refers to the following BRB Specifications which form attachments
to this Specification:-
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 15
These relays shall conform to the requirements of BRB Specification 932A (attached
to this specification) with the exception of Clauses 19, 22.1 and 22.2.
The operating voltages for 12V relays (MBLA/12-4) when tested in accordance with
Clause 18 shall be in accordance with Section 4.3 of this specification.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
16 VRIOGS 012.7.1 Revision A
APPENDIX B MSPA/8-4
These relays shall conform to the requirements of BRB Specification 933 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact Arrangement:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 17
These relays shall conform to the requirements of BRB Specification 934 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
Note: Clause 13.1 is modified to include a 50V QSRA/6-6 relay. The contact
configuration of this relay is shown below:
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact Arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
18 VRIOGS 012.7.1 Revision A
These relays shall conform to the requirements of BRB Specification 961A (attached
to this specification) with the exception of Clauses 19, 22.1 and 22.2.
The operating voltages for 12V relays (2MBLA/4-4 and 2MBLA/6-2) when tested in
accordance with Clause 18 shall be in accordance with Section 4.3 of this
specification.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact Arrangement:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 19
APPENDIX E MSX
Safety critical slow release timer (3 to 300 seconds).
These units shall conform where applicable to the general requirements of BRB
Specification 930 (attached to this specification) with the exception of Clauses: 19,
22.1 and 22.2.
The registration code for the timer unit is shown in Section 3 of this specification.
The timer shall be identified and labelled in accordance with Section 7 of this
specification. The time setting and associated strappings shall be noted on the relay
test label (Label Type B in Section 7.2 of this Standard.)
If a relay cannot be coarse adjusted to suit the adjustment range, then the relay
should be rejected.
Input voltage 12V DC ± 20%.
Output voltage, DC: Adjustable by strapping:
• 12V: D2 to D1 strapped
• 24V: D2 to D7 strapped
• 50V: D2 to D8 strapped
Delay Adjustment:
• Coarse adjustment - by wire straps on plugboard
3 to 10 seconds No straps
11 to 30 seconds A1 to A7 strapped
31 to 100 seconds A1 to A2 to A7 strapped
101 to 300 seconds A1 to A2 to A3 to A7 strapped
Terminal arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
20 VRIOGS 012.7.1 Revision A
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 21
APPENDIX F (continued)
MNR/5-2, MNR/4-3
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
22 VRIOGS 012.7.1 Revision A
These relays shall conform to the requirements of BRB Specification 966 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
The operating voltages for 12V relays (MBCLA/2H/4-4) when tested in accordance
with Clause 18 shall be in accordance with Section 4.3 of this specification.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 23
APPENDIX H MML/11-4
These relays shall conform to the requirements of BRB Specification 935 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 6 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
24 VRIOGS 012.7.1 Revision A
APPENDIX I M2T/2-2
These relays shall conform to the requirements of BRB Specification 938 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2 and Appendix C.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 25
APPENDIX J 4MBT/2-2
These relays shall conform to the requirements of BRB Specifications 932 and 938
(attached to this specification) with the exception of Clauses 19, 22.1 and 22.2.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
26 VRIOGS 012.7.1 Revision A
APPENDIX K 270MT/8-8
These relays shall conform to the requirements of BRB Specification 930 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
This relay is specifically configured to act as an output relay for CSEE UM71 track
circuit receivers.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 27
APPENDIX L MNHX/8-4
These relays shall conform to the requirements of BRB Specification 966 including
Appendix F7 (attached to this specification) with the exception of Clause 19.1.
Used to interface the output of SSI equipment with other signalling apparatus.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
28 VRIOGS 012.7.1 Revision A
APPENDIX M MNHXC/2H/4-4
These relays shall conform to the requirements of BRB Specification 966 including
Appendix F7 (attached to this specification) with the exception of Clause 19.1.
Used to interface the output of SSI equipment with other signalling apparatus.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
VRIOGS 012.7.1 Revision A 29
APPENDIX N 270MT/4-2
These relays shall conform to the requirements of BRB Specification 930 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2 and Appendix C.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.
30 VRIOGS 012.7.1 Revision A
APPENDIX O MS2/6-6
These relays shall conform to the requirements of BRB Specification 930 (attached to
this specification) with the exception of Clauses 19, 22.1 and 22.2.
The registration codes for the above relays are shown in Section 3 of this
specification.
The relays shall be identified and labelled in accordance with Section 7 of this
specification.
Contact arrangements:
NOTE: This document is controlled only when viewed on the DOT Engineering Standards website.
Any other copy of this document is uncontrolled, and the content may be inaccurate.