Contents Page
GENERAL 4
D1 CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL D1-1
FOR FULL OUTSIDE AIR PLANTS
D2 CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL D2-1
IN RECIRCULATION AIR VENTILATION SYSTEMS
D5 SEQUENCE CONTROL OF HOT WATER HEATING COIL AND CHILLED WATER D5-1
COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL
D7 SEQUENCE CONTROL OF MIXED AIR DAMPERS AND HOT WATER HEATING COIL D7-1
D8 SEQUENCE CONTROL OF MIXED AIR DAMPERS AND CHILLED WATER COOLING COIL D8-1
D11 SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL D11-1
D12 SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER D12-1
COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER CONTROL
D13 SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL D13-1
D14 SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND D14-1
CHILLED WATER COOLING COIL
D15 SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND D15-1
CHILLED WATER COOLING COIL
D16 SEQUENCE CONTROL OF MIXED AIR DAMPERS, ELECTRIC AIR HEATER AND D16-1
CHILLED WATER COOLING COIL
1 EN3C-0161 0698R0-MA
HONEYWELL MICRONIK 200 APPLICATION
R1 ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN R1-1
AIR DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF A HOT WATER HEATING COIL OR
CHILLED WATER COOLING COIL FOR FULL OUTSIDE AIR PLANTS
R2 ROOM/CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL IN R2-1
RECIRCULATION AIR VENTILATION SYSTEMS
R5 ROOM/DISCHARGE AIR CASCADE SEQUENCE CONTROL OF HOT WATER HEATING COIL AND R5-1
CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL
R7 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS R7-1
AND HOT WATER HEATING COIL
R8 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS R8-1
AND CHILLED WATER COOLING COIL
R9 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS, R9-1
HOT WATER AND CHILLED WATER VALVES
R10 ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN R10-1
AIR - DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF ELECTRIC AIR HEATER BATTERY
OR DIRECT EXPANSION COOLING SYSTEM (UP TO 6-STAGES/STEPS)
R11 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR R11-1
HEATER AND CHILLED WATER COOLING COIL
R12 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR R12-1
HEATER AND CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER
CONTROL
R13 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR R13-1
HEATER AND CHILLED WATER COOLING COIL
R14 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY R14-1
SYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL
R15 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY R15-1
SYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL
R16 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS, R16-1
ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL
EN3C-0161 0698R0-MA 2
HONEYWELL MICRONIK 200 APPLICATION
W1 OUTSIDE AIR TEMPERATURE COMPENSATED SUPPLY WATER FLOW TEMPERATURE CONTROL W1-1
W2 OUTSIDE AIR TEMPERATURE COMPENSATED HOT WATER FLOW TEMPERATURE CONTROL W2-1
WITH HIGH OR LOW LIMIT RETURN FLOW TEMPERATURE CONTROL
The R7426B,C controllers provide three outputs for sequence control of heating, mixed air dampers or energy recovery
systems and cooling and are suitable for the following applications:
• Space or return air temperature control
• Discharge air temperature control
• Cascade control of space or return air and discharge air temperature
3 EN3C-0161 0698R0-MA
HONEYWELL MICRONIK 200 APPLICATION
GENERAL
Day/Night Setpoint Operation. An external time clock connected to the controller occupancy input terminals 1&4 provides
day/night main temperature setpoint control determined by the programmed offset parameter value P.16 (SOFFS) for those
heating or ventilation systems operating 24 hour per day.
EN3C-0161 0698R0-MA 4
HONEYWELL MICRONIK 200 APPLICATION
R7426A
Step2 on Y1
Power
Step1 on o pen / 24V close /
O U T2 ~ O U T1
out2 20 21 22
on
out1
off 24Vac Relays
25 30 65 70 100 % Y1
Stage 2 1
R7426A
Step3 on Y1
Power
Step2 on o pen / 24V close /
O U T2 ~ O U T1
Step1 on
20 21 22
out2
on out1
24Vac Relays
off
20 25 45 50 70 75 100 % Y1
2 1
Stage
3
off A2 A1
30 50 70 80 100 sec Solid State Relay
Y1
RN1L40M25
L1 L2
100...440Vac
5 EN3C-0161 0698R0-MA
HONEYWELL MICRONIK 200 APPLICATION
R7426B
Step2 on Y3
Power
Step1 on o pen / 24V close /
O U T2 ~ O U T1
out2 26 27 28
on
out1
off 24Vac Relays
25 30 65 70 100 % Y3
Stage 2 1
R7426B
Step3 on Y3
Power
Step2 on o pen / 24V close /
O U T2 ~ O U T1
Step1 on
26 27 28
out2
on out1
24Vac Relays
off
20 25 45 50 70 75 100 % Y3
2 1
Stage
3
off A2 A1
30 50 70 80 100 sec Solid State Relay
Y3
RN1L40M25
L1 L2
100...440Vac
EN3C-0161 0698R0-MA 6
HONEYWELL MICRONIK 200 APPLICATION
R7426B
Step2 on Y2
Power
Step1 on o pen / 24V close /
O U T2 ~ O U T1
out2 23 24 25
on
out1
off 24Vac Relays
25 30 65 70 100 % Y3
Stage 2 1
7 EN3C-0161 0698R0-MA
HONEYWELL MICRONIK 200 APPLICATION
GRAPHICAL SYMBOLS
Immersion Temperature
5 16 Cooling Coil
T Sensor
Freeze Protection or
High Limit Thermostat in
6 17 Electric Heater
T Elektric Heating
Applications
EN3C-0161 0698R0-MA 8
HONEYWELL MICRONIK 200 APPLICATION
EA
6 M
∆p 11
9
0A
T M T T
3 6 ∆p 7 1
∆p
8 9 5
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor (1) measures the
actual value and the controller (4) compares this value with the desired
setpoint. If a deviation between the two values exists, the controller generates a Y1 (%) Cooling
100
3-position control signal to reposition the valve (5) to maintain the desired
discharge air temperature. In heating applications the controller output is
reverse acting and direct acting for cooling applications.
Freeze Protection. The freeze protection thermostat (7) switches the heating
coil pump ON - if OFF - at temperatures below its adjustable setpoint. In parallel
it provides a digital input signal to the controller (4) to switch the fan(s) OFF and Heating
close the dampers by an external installed relay logic and fully open the heating 0
0 Xw
valve (5) to prevent the heating coil from freezing.
CTRP1 Ystart T1
Time Control. Depending on the programmed time schedule of the internal Xp
controller real time clock the different operating control modes Comfort,
Standby, Night or OFF are selected. In the OFF operating mode the controller
automatically fully closes the heating valve (5), switches the fan(s) OFF and
thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426A
Y1
24V 24V op en/ 24V clo se/
O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Trans-
former
230Vac
1 24V
5 ML6420A Heating or 2 3 - Way Valve
Cooling
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
5 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
T
3
11
T
1
5
Y1
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor (1) measures
the actual value and the controller (4) compares this value with the actual
control point. The control point comprises the setpoint value which is Y1 (%) Cooling
100
continuously compensated by the outside air temperature sensor (3) value.
If a deviation between the two values exists, the controller (4) generates a
3-position control signal to reposition the valve (5) to maintain the desired
discharge air temperature. In heating applications the controller output is
reverse acting and direct acting for cooling applications.
Time Control. Depending on the programmed time schedule of the internal Heating
controller real time clock the different operating control modes Comfort, 0
0 Xw
Standby, Night or OFF are selected. In the OFF operating mode the
CTRP1 Ystart T1
controller automatically fully closes the heating valve (5) and switches the fan
OFF. Xp
WIRING CONNECTIONS
3 T7416A 1 2
11 T7411B 4 6
1 T7411A/T7416A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426A
Y1
24V 24V op en/ 24V clo se/
O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Trans-
former
230Vac
1 24V
5 ML6420A Heating or 2 3 - Way Valve
Cooling
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
3 1 T7416A1006 Outside Air Temperature Sensor, Wall Mounting
4 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
5 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
OPTIONS
Item Quantity Part Number Description
11 1 T7411B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF AN ENERGY RECOVERY SYSTEM WITH A HOT WATER HEATING COIL D3
For use with ventilation systems comprising of an energy (heat) recovery system and a heating coil.
10
∆p
EA
M
6
5b ∆p 11
9
0A
T M T T
3 6 7 1
∆p ∆p
8 5a 9
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the Y (%)
two values exists, the controller generates a 3-position control 100
Energy
signal on output Y1or Y3 to reposition either the energy Recovery
recovery valve (5b) or the heating valve (5a) in sequence to Heating Y1
Y3 1/4 Xp
maintain the desired discharge air temperature.
In an air-glycol-air heat recovery system it is important, to avoid
icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch 0
indicates icing of the coil, the control valve (5b) will be closed 0 0 0 Xwh/Xw
by an additional field mounted relay. Return air and warm water CTRPH CTRP1
will be circulated through the exhaust air heat recovery coil to
XpH Xp T1
melt the ice deposits.
Freeze Protection. The freeze protection thermostat (7)
switches the heating coil pump ON, - if OFF - at temperatures below its adjustable setpoint. In parallel it provides a digital input
signal to the controller (4) to fully open the heating valve (5a), to switch OFF the fan(s) and close the dampers (6) by an
external installed relay logic to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Trans-
former
230Vac
24V
5b ML6420A Energy Recovery 1 2 3 - Way Valve
24V
2 1 2 - Way Valve 24V
5a ML6420A Heating Valve 1 2 3 - Way Valve
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9+10 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF AN ENERGY RECOVERY SYSTEM WITH A CHILLED WATER COOLING COIL D4
For use with ventilation systems comprising of an energy (heat/cool) recovery system and a cooling coil.
10
∆p
EA
M
6
5b ∆p 11
9
0A
T M T
6 1
3 ∆p ∆p
5a
8 9
Y2
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation Y (%)
between the two values exists, the controller generates a 100
3-position control signal on output Y1 or Y2 to reposition
either the energy recovery valve (5b) or the cooling valve (5a) Energy
in sequence to maintain the desired discharge air Recovery
temperature. Y1
Cooling
If the actual temperature is below the setpoint, the controller MINPOS Y2
modulates via output Y1 the heat recovery valve (5b) into the
0
open position. 0 0 0 Xwc/Xw
If the actual temperature exceeds the setpoint by more than CTRP1 CTRPC
25% of the throttling range (Xp1) - dead band between
Xp XpC T1
heating and cooling - the controller starts to open the energy
recovery valve (5b) to reclaim cooling energy. If the
temperature continues to increase and the energy recovery
valve is fully open, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5b) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Trans-
former
230Vac
24V
5b ML6420A Energy Recovery 2 - Way Valve 1 2
24V
3 - Way Valve 2 1
24V
5a ML6420A Cooling Valve 1 2 3 - Way Valve
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Temperature Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF HOT WATER HEATING COIL AND CHILLED WATER COOLING COIL
D5
AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL
For use with ventilation system comprising of heating and cooling coils with full outside air dampers.
EA
6
M
∆p 11
9
0A
T M T T
3 6
∆p ∆p 7 1
5b
8 9 5a
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation Y (%)
between the two values exists, the controller generates a 3- 100
position control signal to reposition the heating or cooling
valves to maintain the desired discharge air temperature.
If the temperature is below the heating setpoint the heating
valve (5a) modulates via output Y3 and if the temperature is Heating Cooling
above the cooling setpoint the cooling valve (5b) modulates Y3 Y2
via output Y2 to maintain the desired discharge air 0
temperature. 0 0 0 Xwh/Xwc
CTRPH CTRP1 CTRPC
Damper Control. If the controller switches from OFF to ON
mode (Comfort, Standby or Night) the controller drives the XpH Xp XpC T1
damper actuators to the open position via output Y1.
If the controller switches to the OFF mode, it drives the
dampers and valves automatically to their closed positions.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a) and close
the dampers (6) and cooling valve (5b) - if open - to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and dampers (6) and switches the fan(s) OFF.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
XWrh 24V 24V open/ 24V close/ open/ 24V close/ open/ 24V close/
OUT2 OUT1 OUT2 OUT1 OUT2 OUT1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6 ML6184E Damper open/closed Brown White Green
24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
24V
5a ML6420A Heating Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Temperature Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
10 ∆p
EA
6
M
5c ∆p
11
9
0A
T M T T
3 6 ∆p 7 ∆p 1
5b
8 5a 9
Y2
Y3
Y1
4
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412A 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
2 24V 1
5c ML6420A Energy Recovery
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b+5c 3 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9+10 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF MIXED AIR DAMPERS AND HOT WATER HEATING COIL D7
For use with ventilation systems comprising of mixed air dampers and a heating coil.
EA
M
6
∆p 11
M 9
6
0A
T M T T
3 ∆p 7 1
6 ∆p
8 5 9
Y3
Y1
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the 1/4 Xp
Y (%)
two values exists, the controller generates two 0(2)…10Vdc 100
control signals in sequence via outputs Y1 and Y3 Heating Damper
Y3 Y1
corresponding to the 0…100% correctional signal to reposition
the mixed air dampers or the heating valve to maintain the
desired discharge air temperature.
MINPOS
The minimum outside air damper position adjustment
(MINPOS) on the controller determines the position to which 0
the outside air damper will be driven even though the 0 0 0 Xwh/Xw
CTRPH CTRP1 CTRPC
temperature input condition demands that it should drive to the
fully closed position. XpH Xp T1
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412A 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
Green Brown White
6 ML7284E Mixed Air Dampers
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5 2 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 17Nm
ML7174E2007 24Vac, 8Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Temperature Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF MIXED AIR DAMPERS AND CHILLED WATER COOLING COIL D8
Used with ventilation system comprising of mixed air dampers and a cooling coil.
EA
M
6
∆p 11
M 9
6
0A
T M T
3 ∆p 1
6 ∆p
8 5 9
Y2
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4) compares
this value with the desired setpoint. If a deviation between the 1/4 Xp
Y (%)
two values exists, the controller generates two 0(2)…10Vdc 100
control signals in sequence via outputs Y1 and Y2 Damper
Y1
corresponding to the 0…100% correctional signal to reposition
the mixed air dampers (6) or cooling valve (5) to maintain the
desired discharge air temperature. Cooling
Y2
If the actual temperature is below the setpoint, the controller MINPOS
modulates via output Y1 the mixed air dampers up to the
0
minimum position. 0 0 0 Xwc/Xw
If the actual temperature exceeds the setpoint by more than CTRP1 CTRPC
25% of the throttling range (Xp1) - dead band between heating Xp XpC T1
and cooling - the controller starts to close the outside and
exhaust air dampers and opens the return air damper. If the
temperature continues to increase and the mixed air dampers
reach the minimum position, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the cooling valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412A 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6 ML7284E Mixed Air Dampers Green Brown White
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 17Nm
ML7174E2007 24Vac, 8Nm
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Temperature Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF MIXED AIR DAMPERS, HOT WATER AND CHILLED WATER VALVES D9
Use with ventilation system comprising of mixed air dampers, heating and cooling coils.
EA
M
6 ∆p 11
M 9
6
0A
T M T T
3 6 ∆p 7 ∆p 1
5b
8 5a 9
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor Y (%)
1/4 Xp
(1) measures the actual value and the controller (4) compares 100
this value with the desired setpoint. If a deviation between the Damper
two values exists, the controller generates three 0(2)…10Vdc Y1
control signals in sequence via outputs Y1, Y2 and Y3
corresponding to the 0…100% correctional signal to reposition Heating Cooling
Y3 Y2
the mixed air dampers and heating and cooling valves to MINPOS
maintain the desired discharge air temperature.
If the actual temperature is below the setpoint, the controller 0
0 0 0 Xwh/Xwc/Xw
generates first a 0(2)...10Vdc control signal via output Y1 to CTRPH CTRP1 CTRPC
reposition the mixed air damper (6). If the temperature
XpH Xp XpC T1
continues to decrease and the mixed air dampers reached the
minimum position (MINPOS), the controller generates a
0(2)...10Vdc control signal via output Y3 to drive the heating valve (5a). If the temperature increases the sequence of operation
is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed air
dampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position
the cooling valve (5b).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to close
the outside and exhaust air dampers (6) and cooling valve - if open - and to switch OFF the fan(s) to prevent the heating coil
from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.
WIRING CONNECTIONS
7 T6046A NC C
3 T7411A/T7416A 1 2
11 T7412A 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
Green Brown White
6 ML7284E Mixed Air Dampers
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a+5b 2 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 17Nm
ML7174E2007 24Vac, 8Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Temperature Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
EA
M
6 ∆p
11
9
0A
T M T V T
3 6 ∆p ∆p 7 10 1
8 9 5
Y1/Y2/Y3
Temperature Control. The discharge air temperature sensor (1) measures the
actual value and the controller (4) compares this value with the desired setpoint.
If a deviation between the two values exists, the controller selects the number of
stages/steps required to maintain the desired discharge air temperature.
When configured for heating and cooling sequence operation, the controller will
first select the heating or cooling mode and than the number of stages/steps Heating
0
required. 0 Xw
CTRP1 Ystart T1
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort, Standby, Xp
Night or OFF are selected. In the OFF operating mode the controller
Step6 on
automatically switches OFF the selected number of stages/steps and the fan(s) Power
and thereby closes the dampers (6) by an external installed relay logic. Step5 on
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time Step2 on
delay by an external installed time delay relay. This allows the dampers time to Step1 on
open. As alternative to the time delay relay the end-position switches of the
damper actuators can be used to start the fan. on
6 signal sequence of
off Y3/Y2/Y1 out1/out2
10 15 25 30 70 75 85 90 100 %
Y3/Y2/Y1
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5 24Vac Relays
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5 1 or RY6 Auxiliary Relay Module with 6 relays or
6 24Vac coil
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF ELECTRIC AIR HEATER ANDCHILLED WATER COOLING COIL D11
Use with ventilation system comprising of an electric air heater and a cooling coil.
EA
M
6 ∆p
11
9
0A
T M T V T
3 7 10 5b 1
6 ∆p ∆p
8 9 5a
Y2
Y1/Y3
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor (1) Y (%)
measures the actual value and the controller (4) compares this 100
value with the desired setpoint. If a deviation between the two
values exists, the controller selects the corresponding number of
stages/steps (up to 4 stages linear or 15 stages binary) for
heating or generates a 3-position control signal to reposition the Heating Cooling
cooling valve to maintain the desired discharge air temperature. Y1/Y3 Y2
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5a 24Vac Relays
24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a 1 or RY4 Auxiliary Relay Module with 4 relays or
4 24Vac coil
5b 1 ML6420A3007 and Valve Actuator and
V5...A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL AND TWO
D12
POSITION (OPEN/CLOSE) DAMPER CONTROL
For use with ventilation system comprising of an electric air heater and a cooling coil with full outside air dampers.
EA
M
6 ∆p 11
9
0A
T M T V T
3 7 10 5b 1
6 ∆p ∆p
8 9 5a
Y3 Y2
Y1
4
If the temperature is below the heating setpoint the solid state XpH Xp XpC T1
relay(s) (5a) is modulated via output Y3 and if the temperature
is above the cooling setpoint the cooling valve (5b) is
out1/out2
modulated via output Y2. on
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
Brown White Green
6 ML6184E Damper open/closed
24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
A2 A1
100...440Vac
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a up to 3 RN1L40M25 Solid State Relay (Current Valve)
5b 1 ML6420A3007 and Valve Actuator and
V5...A.... Valve
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL D13
Used with ventilation system comprising of an electric air heater and a cooling coil.
EA
M
6 ∆p
11
9
0A
T M T V T
3 7 10 5b 1
6 ∆p ∆p
8 9 5a
Y2
Y3
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
(1) measures the actual value and the controller (4)
compares this value with the desired setpoint. If a deviation Y (%)
between the two value exists, the controller generates two 100
0(2)...10Vdc control signals in sequence via outputs Y2 and
Y3 corresponding to the 0...100% correctional signal to drive
the electric current valve (5a) for proportional control of the
electric air heater or to reposition the cooling valve (5b) to Heating Cooling
maintain the desired discharge air temperature. Y3 Y2
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5b 1 ML7420A3006 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
10 ∆p
EA
6
M
5c ∆p 12
9
0A
T M T V T
3 6 ∆p 7 11 5b 1
∆p
8 9 5a
Y2
Y3
Y1
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
12 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
1 24V 2
5c ML6420A Energy Recovery Valve
24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
A2 A1
100...440Vac
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a up to 3 RN1L40M25 Solid State Relay (Current Valve)
5b + 5c 2 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
11 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
12 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
10
∆p
EA
6
M
5c ∆p
12
9
0A
T M T V T
3 6 ∆p 7 11 5b 1
∆p
8 9 5a
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
Y (%)
(1) measures the actual value and the controller (4) compares
100
this value with the desired setpoint. If a deviation between the Energy
two values exists, the controller generates in correspondence Heating Recovery
Cooling
to the 0...100% correctional signal 0(2)...10Vdc control signals Y3 Y1
1/4 Xp Y2
in sequence via outputs Y1, Y2 and Y3 to position the energy
recovery or cooling valves or to drive the electric current valve
to maintain the desired discharge air temperature.
0
If the actual temperature is below the setpoint, the controller 0 0 0 Xwh/Xwc/Xw
generates first a 0(2)...10Vdc control signal via output Y1 to CTRPH CTRP1 CTRPC
reposition the energy recovery valve (5c) to reclaim heating
XpH Xp XpC T1
energy. If the temperature continues to decrease and the
energy recovery value is fully open, the controller generates a
0(2)...10Vdc control signal via output Y3 to drive the electric current valve (5a) for proportional control of the electric air heater.
If the temperature increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues to
increase and the energy valve is fully open, the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position the
cooling valve (5b).
In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differential
pressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by an
additional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt the
ice deposits.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an external
installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
12 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5b + 5c 2 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
11 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
12 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
EA
M
6 ∆p
11
M 9
6
0A
T M T V T
3 6 ∆p ∆p 7 10 5b 1
8 9 5a
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The discharge air temperature sensor
1/4 Xp
(1) measures the actual value and the controller (4) compares Y (%)
this value with the desired setpoint. If a deviation between the 100
Damper
two values exists, the controller generates in correspondence to Y1
the 0...100% correctional signal 0(2)...10Vdc control signals in
sequence via outputs Y1, Y2 and Y3 to position the mixed air Heating Cooling
dampers or cooling valve or to drive the electric current valve to Y3 Y2
maintain the desired discharge air temperature. If the actual MINPOS
temperature is below the setpoint, the controller generates first 0
a 0(2)...10Vdc control signal via output Y1 to reposition the 0 0 0 Xwh/Xwc/Xw
mixed air damper (6). If the temperature continues to decrease CTRPH CTRP1 CTRPC
and the mixed air dampers reached the minimum position XpH Xp XpC T1
(MINPOS), the controller generates a 0(2)...10Vdc control
signal via output Y3 to drive the electric current valve (5a) for
proportional control of the electric air heater. If the temperature
increases the sequence of operation is reversed.
If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and
cooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed air
dampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position
the cooling valve (5b).
The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outside
air damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
0Vac (0%) control signals via output Y1, Y2 and Y3 to fully close the outside and exhaust air dampers (6) and the cooling valve
(5b), open the return air damper and to switch OFF the electric air heater via the current valve (5a). In addition the fans are
switched OFF by the Plant/System On/Off output.
If the controller switches from OFF to ON mode, the Plant/System On/Off output switches the fans ON and the controller
provides automatic control.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
11 T7412B 4 6
1 T7411A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V
Wrh 2..1 0V 2..1 0V 2..1 0V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6 ML7284E Mixed Air Dampers Brown White Green
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5b 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 0...10Vdc, 17Nm or
ML7174E1006 24Vac, 0...10Vdc, 8Nm
7 1 L4064K1006 High Limit Thermostat
8+9 3 DPS-Series Differential Air Pressure Switch
10 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN AIR
DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF A HOT WATER HEATING COIL OR R1
CHILLED WATER COOLING COIL FOR FULL OUTSIDE AIR PLANTS
A heating and ventilation system with room/return air temperature control and low limit discharge air or cascade control is used
where the base heating load is met by radiators and the ventilation system provides the supply of fresh outside air.
In cooling applications it is also used to supply fresh outside air using the same temperature control system as for heating
control.
EA
M T T 1b
6 1a
∆p 1c
9
T
0A
T M T T
3 6 ∆p 7 2
∆p
8 9 5
Y1
4
Temperature Control With Low Limit Control. The return or room air
temperature sensor (1a, b or c) and the discharge air temperature sensor (2)
measure the actual values and the controller (4) compares these values with the
desired setpoints (W1) and (Wlim). If a deviation between these values exists, the
lowest deviation signal of both is selected by the controller. Depending on this
deviation signal the controller generates a 3-position control signal to reposition Heating
the valve (5) to maintain the desired room or discharge air temperature. In 0
0 Xw
heating applications the controller output is reverse acting and direct acting for T2
CTRP2
cooling applications. Ystart
Xp
Cascade Temperature Control. The return or room air temperature sensor (1a, b
or c) measures the actual value and the controller (4) compares this value with the desired setpoint (W1) of the master loop.
Depending on the deviation an internal setpoint for the submaster loop, the discharge air temperature, is calculated. At zero
deviation the discharge air temperature is controlled at the programmed setpoint (Wcas) and if a deviation exists, the discharge
air setpoint is altered. The reset span of the discharge air setpoint is limited by the reset span adjustment (Rcas) and the limit
setting (Wlim).
The discharge air temperature sensor (2) measures the actual value and the controller compares this value with the desired
internal calculated setpoint. If a deviation exists, the controller generates a 3-position control signal to reposition the valve (5) to
maintain the desired discharge air temperature. In heating applications the controller output is reverse acting and direct acting
for cooling applications.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to switch the fan(s) OFF and close the
dampers by an external installed relay logic and fully open the heating valve (5) to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the heating valve (5), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2 NC C
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426A
Y1
24V 24V op en/ 24V clo se/
O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
1 24V 2 3 - Way Valve
5 ML6420A Heating or Cooling
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
5 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
T T 1b
1a
1c
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The return or room air temperature sensor (1a, b or c)
measures the actual value and the controller (4) compares this value with the
Y1 (%) Cooling
desired setpoint. If a deviation between the two values exists, the controller
100
(4) generates a 3-position control signal to reposition the valve (5) to maintain
the desired room or return air temperature. In heating applications the
controller output is reverse acting and direct acting for cooling applications.
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort,
Standby, Night or OFF are selected. In the OFF operating mode the Heating
controller automatically fully closes the heating valve (5) and switches the fan 0
0 Xw
OFF.
CTRP1 Ystart T1
If the controller switches from OFF to ON mode the Plant/System On/off Xp
output switches the fan ON and the controller provides automatic control.
WIRING CONNECTIONS
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426A
Y1
24V 24V op en/ 24V clo se/
O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
24V
5 ML6420A Heating or Cooling 1 2 3 - Way Valve
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1a 1 T7411A1001 Duct Temperature Sensor 135mm length
T7411A1019 300mm length
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
4 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
5 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
11
∆p
EA
M T T 1b
6 1a
5b ∆p 1c
9
T
0A
T M T T
3 6 ∆p 7 2
∆p
8 9 5a
Y3
Y1
4
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2 NC C
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac 1 24V
5b ML6420A Energy 2 3 - Way Valve
Recovery
24V 2 - Way
2 1 1 24V 3 - Way Valve
5a ML6420A Heating Valve Valve 2
24V 2 - Way Valve
2 1
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9+10 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
11
∆p
EA
M T T 1b
6 1a
5b ∆p 1c
9
T
0A
T M T
3 6 ∆p 2
∆p
8 9 5a
Y1 Y2
4
FUNCTIONAL DESCRIPTION
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint Y (%)
(W1) of the master loop. Depending on the deviation an 100
internal setpoint for the submaster loop, the discharge air
temperature, is calculated. At zero deviation the discharge air Energy
temperature is controlled at the programmed setpoint (Wcas) Recovery
and if a deviation exists, the discharge air setpoint is altered. Y1
Cooling
The reset span of the discharge air setpoint is limited by the MINPOS Y2
reset span adjustment (Rcas) and the limit setting (Wlim).
0
The discharge air temperature sensor (2) measures the 0 0 0 Xwc/Xw
actual value and the controller (4) compares this value with CTRP2 CTRPC
the desired internal calculated setpoint. If a deviation Xp XpC T2
between the two values exists, the controller generates a 3-
position control signal on output Y1or Y2 to reposition either
the energy recovery valve (5b) or the cooling valve (5a) in sequence to maintain the desired discharge air temperature.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
3 - Way 24V
5b ML6420A Energy 230Vac
Valve 1 2
Recovery 2 - Way
2 24V 1
Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
ROOM/DISCHARGE AIR CASCADE SEQUENCE CONTROL OF HOT WATER HEATING COIL AND
R5
CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL
For use with ventilation system comprising of heating and cooling coils with full outside air dampers.
EA
M T T 1b
6 1a
∆p 1c
9
T
0A
T M T 5b T
3 6 ∆p 7 ∆p 2
8 5a 9
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Y (%)
Temperature Control. The return or room air temperature 100
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air Heating Cooling
temperature, is calculated. At zero deviation the discharge air Y3 Y2
temperature is controlled at the programmed setpoint (Wcas) 0
and if a deviation exists, the discharge air setpoint is altered. 0 0 0 Xwh/Xwc
The reset span of the discharge air setpoint is limited by the CTRPH CTRP2 CTRPC
reset span adjustment (Rcas) and the limit setting (Wlim).
XpH Xp XpC T2
The discharge air temperature sensor (2) measures the
actual value and the controller (4) compares this value with
the desired internal calculated setpoint. If a deviation
between the two values exists, the controller generates a 3-position control signal to reposition the heating or cooling valve to
maintain the desired discharge air temperature.
If the temperature is below the heating setpoint the heating valve (5a) is modulated via output Y3 and if the temperature is
above the cooling setpoint the cooling valve (5b) is modulated via output Y2 to maintain the desired discharge air temperature.
Damper Control. If the controller switches from OFF to ON mode (Comfort, Standby or Night) the controller drives the damper
actuators to the open position via output Y1.
If the controller switches to the OFF mode it drives the dampers and valves automatically to their closed positions.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a) and close
the dampers (6) and cooling valve (5b) – if open - to prevent the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and dampers (6) and switches the fan(s) OFF.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time to
open. As alternative the end-position switches of the damper actuators can be used to start the fan.
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2
2 T7411A 1 2 NC C
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X
24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
6 ML6184E Damper Open-Closed Brown White Green
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b 2 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
10
∆p
EA
M T T 1b
6 5c 1a
∆p 1c
9
T
0A
T M T 5b T
3 6 ∆p 7 ∆p 2
8 5a 9
Y2
Y3
Y1
4
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2
2 T7411A 1 2 NC C
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X
24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
24V
5c ML6420A Energy Recovery 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
24V
5a ML6420A Heating Valve 3 - Way Valve 1 2
2 24V 1
2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a+5b+5c 3 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm or
ML6184E1008 230Vac, 17Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9+10 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
EA
M T T 1b
6 1a
∆p 1c
M 9
6 T
0A
T M T T
3 ∆p 7 2
6 ∆p
8 5 9
Y3
Y1
FUNCTIONAL DESCRIPTION
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint 1/4 Xp
Y (%)
(W1) of the master loop. Depending on the deviation an 100
Heating Damper
internal setpoint for the submaster loop, the discharge air Y3 Y1
temperature, is calculated. At zero deviation the discharge air
temperature is controlled at the programmed setpoint (Wcas)
and if a deviation exists, the discharge air setpoint is altered.
The reset span of the discharge air setpoint is limited by the MINPOS
reset span adjustment (Rcas) and the limit setting (Wlim). 0
0 0 0 Xwh/Xw
The discharge air temperature sensor (2) measures the actual CTRPH CTRP2 CTRPC
value and the controller (4) compares this value with the
XpH Xp T2
desired internal calculated setpoint. If a deviation between the
two values exists, the controller generates two 0(2)…10Vdc
control signals in sequence via outputs Y1 and Y3
corresponding to the 0…100% correctional signal to reposition the mixed air dampers or the heating valve to maintain the
desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5), to close
the outside and exhaust air dampers (6) and to switch OFF the fan(s) to protect the heating coil from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the heating valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2
2 T7411A 1 2 NC C
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X
24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..10V 24V 24V
Wrh 2..1 0V 2..1 0V 2..10V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
Y 24V 24V
6 ML7284E Mixed Air Dampers
3 1 2
5 ML7420A Heating Valve Y 24V 24V
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5.....A..... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 17Nm or
ML7174E2007 24Vac , 8Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
EA
M T T 1b
6 1a
∆p 1c
M 9
6 T
0A
T M T
3 ∆p 2
6 ∆p
8 5 9
Y2
Y1
FUNCTIONAL DESCRIPTION
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the controller
(4) compares this value with the desired setpoint (W1) of the 1/4 Xp
Y (%)
master loop. Depending on the deviation an internal setpoint for 100
the submaster loop, the discharge air temperature, is Damper
Y1
calculated. At zero deviation the discharge air temperature is
controlled at the programmed setpoint (Wcas) and if a
deviation exists, the discharge air setpoint is altered. The reset Cooling
Y2
span of the discharge air setpoint is limited by the reset span MINPOS
adjustment (Rcas) and the limit setting (Wlim).
0
The discharge air temperature sensor (2) measures the actual 0 0 0 Xwc/Xw
CTRP2 CTRPC
value and the controller (4) compares this value with the
desired internal calculated setpoint. If a deviation between the Xp XpC T2
two values exists, the controller generates two 0(2)…10Vdc
control signals in sequence via outputs Y1 and Y2
corresponding to the 0…100% correctional signal to reposition the mixed air dampers (6) or cooling valve (5) to maintain the
desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the cooling valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..10V 24V 24V
Wrh 2..1 0V 2..1 0V 2..10V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
3 1 2
5 ML7420A Cooling Valve Y 24V 24V
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5.....A..... Valve
6 3 ML7284E1006 or Damper Actuator 24Vac, 17Nm or
ML7174E2007 24Vac , 8Nm
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
EA
M T T 1b
6 1a
∆p 1c
M 9
6 T
0A
T M T 5b T
3 ∆p 7 2
6 ∆p
8 5a 9
Y2
Y3
Y1
4
FUNCTIONAL DESCRIPTION
Temperature Control. The return or room air temperature
sensor (1a, b or c) measures the actual value and the controller 1/4 Xp
Y (%)
(4) compares this value with the desired setpoint (W1) of the
100
master loop. Depending on the deviation an internal setpoint for Heating Damper
the submaster loop, the discharge air temperature, is Y3 Y1
calculated. At zero deviation the discharge air temperature is
controlled at the programmed setpoint (Wcas) and if a deviation Cooling
exists, the discharge air setpoint is altered. The reset span of Y2
MINPOS
the discharge air setpoint is limited by the reset span
adjustment (Rcas) and the limit setting (Wlim). 0
The discharge air temperature sensor (2) measures the actual 0 0 0 Xwh/Xwc/Xw
CTRPH CTRP2 CTRPC
value and the controller (4) compares this value with the
desired internal calculated setpoint. If a deviation between the XpH Xp XpC T2
two values exists, the controller generates three 0(2)…10Vdc
control signals in sequence via outputs Y1, Y2 and Y3
corresponding to the 0…100% correctional signal to reposition the mixed air dampers or heating or cooling valve to maintain
the desired discharge air temperature. The minimum outside air damper position adjustment (MINPOS) on the controller
determines the position to which the outside air damper will be driven even though the temperature input condition demands
that it should drive to the fully closed position.
Freeze Protection. The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below its
adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to close
the outside and exhaust air dampers (6) and cooling valve - if open - and to switch OFF the fan(s) to prevent the heating coil
from freezing.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closes
the valves (5a and 5b) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)
OFF.
If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controller
provides automatic control.
WIRING CONNECTIONS
7 T6046A
3 T7411A/T7416A 1 2
2 T7411A 1 2 NC C
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..10V 24V 24V
Wrh 2..1 0V 2..1 0V 2..10V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac green brown white
24V 24V
6 ML7284E Mixed Air Dampers Y
3 1 2
5b ML7420A Cooling Valve Y 24V 24V
3 1 2
5a ML7420A Heating Valve Y 24V 24V
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a+5b 2 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5.....A..... Valve
6 3 ML7284E1006 Damper Actuator 24Vac, 17Nm or
ML7174E2007 24Vac, 8Nm
7 1 T6046A1006 or Freeze Protection Thermostat
FT015 or FTB015
8+9 3 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN AIR -
DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF ELECTRIC AIR HEATER BATTERY OR R10
DIRECT EXPANSION COOLING SYSTEM (UP TO 6-STAGES/STEPS)
Used with ventilation system using electric air heating, where the base heating load is met by a radiator heating system and the
ventilation system is used to ensure the supply of outside air.
Instead of electric heating, the controller can be used to control up to 6-stages of direct expansion cooling.
- Heating mode: 4 stages, sequentially switched steps to operate external relays or
4 binary coded switching outputs to provide up to 15 load steps.
- Cooling mode: 2 stages, sequentially switched steps to operate external relays.
EA
T T 1b
M 1a
6 ∆p 1c
9
T
0A
T M T V T
3 ∆p 7 2
6 ∆p 10
8 9 5
Y1/Y2/Y3
Temperature Control With Low Limit Control. The return or room air
temperature sensor (1a, b or c) and the discharge air temperature sensor (2)
measure the actual values and the controller (4) compares these values with the
desired setpoints (W1) and (Wlim). If a deviation between these values exists, the
lowest deviation signal of both is selected by the controller. Depending on this
deviation signal the controller selects the number of stages/steps required to Heating
0
maintain the desired room or return air or low limit discharge air temperature. 0 Xw
CTRP1/2 T1/2
Cascade Temperature Control. The return or room air temperature sensor (1a, Ystart
Xp
b or c) measures the actual value and the controller (4) compares this value with
Step6 on
the desired setpoint (W1) of the master loop. Depending on the deviation an Power
Step5 on
internal setpoint for the submaster loop, the discharge air temperature, is
calculated.
Step2 on
The discharge air temperature sensor (2) measures the actual value and the
Step1 on
controller compares this value with the desired internal calculated setpoint. If a
deviation exists, the controller selects the number of stages/steps required to
on
maintain the desired discharge air temperature. 6 signal sequence of
For both applications the controller output is reverse acting for heating mode and off Y3/Y2/Y1 out1/out2
direct acting for cooling mode. 10 15 25 30 70 75 85 90 100 %
When configured for heating and cooling sequence operation, the controller will Y3/Y2/Y1
first select the heating or cooling mode and than the number of stages/steps
required.
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically switches
OFF the selected number of stages/steps and the fan(s) and thereby closes the dampers (6) by an external installed relay
logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5 24Vac Relays
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5 1 or RY6 Auxiliary Relay Module with 6 relays
6 24Vac coil relays
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
EA
T T 1b
M 1a
6 ∆p 1c
9
T
0A
T M T V T
3 ∆p 7 10 2
6 ∆p
8 9 5b
5a
Y2
Y1/Y3
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
5a 24Vac Relays
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a 1 or RY4 Auxiliary Relay Module with 4 relays
4 24Vac coil relays
5b 1 ML6420A3007 and Valve Actuator and
V5...A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND
R12
CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER CONTROL
For use with ventilation system comprising of an electric air heater and a cooling coil with full outside air dampers.
EA
T T 1b
M 1a
6 ∆p 1c
9
T
0A
T M T V T
3 ∆p 7 10 2
6 ∆p
8 9 5b
5a
Y2
Y3
Y1
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V op en/ 24V clo se/ op en/ 24V clo se/ op en/ 24V clo se/
Wrh O U T2 O U T1 O U T2 O U T1 O U T2 O U T1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
Open-Closed 24V
5b ML6420A Cooling Valve 3 - Way Valve 1 2
24V
2 - Way Valve 2 1
A2 A1
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a up to 3 RN1L40M25 Solid State Relay (Current Valve)
5b 1 ML6420A3007 and Valve Actuator and
V5...A.... Valve
6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
EA
T T 1b
M 1a
6 ∆p 1c
9
T
0A
T M T V T
3 ∆p 7 10 2
6 ∆p
8 9 5b
5a
Y2
Y3
4
FUNCTIONAL DESCRIPTION
Y (%)
Temperature Control. The return or room air temperature 100
sensor (1a, b or c) measures the actual value and the
controller (4) compares this value with the desired setpoint
(W1) of the master loop. Depending on the deviation an
internal setpoint for the submaster loop, the discharge air Heating Cooling
temperature, is calculated. At zero deviation the discharge air Y3 Y2
temperature is controlled at the programmed setpoint (Wcas) 0
and if a deviation exists, the discharge air setpoint is altered. 0 0 0 Xwh/Xwc
The reset span of the discharge air setpoint is limited by the CTRPH CTRP2 CTRPC
reset span adjustment (Rcas) and the limit setting (Wlim).
XpH Xp XpC T2
The discharge air temperature sensor (2) measures the
actual value and the controller (4) compares this value with
the desired internal calculated setpoint. If a deviation between the two values exists, the controller generates two 0(2)...10Vdc
control signals in sequence via outputs Y2 and Y3 corresponding to the 0...100% correctional signal to drive the electric current
valve (5a) for proportional control of the electric air heater or to reposition the cooling valve (5b) to maintain the desired
discharge air temperature.
If the temperature is below the heating setpoint the controller generates a control signal on output Y3 to control the electric
current valve (5a) and if the temperature is above the cooling setpoint, the controller generates a control signal on output Y2 to
position the cooling valve (5b).
Time Control. Depending on the programmed time schedule of the internal controller real time clock the different operating
control modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates
0% output signals on Y2 and Y3 to switch OFF the electric heater , to close the cooling valve (5b) and to switch OFF the fan(s)
by the Plant/System On/Off output and thereby close the dampers (6) by an external installed relay logic.
If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delay
relay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper
actuators can be used to start the fan.
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X 24V 24V 0..1 0V 24V 24V 0..1 0V 24V 24V 0..10V 24V 24V
Wrh 2..1 0V 2..1 0V 2..10V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
3 1 2
Y 24V 24V
5b ML7420A Cooling Valve
8 10
5a R7425A/B Y
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5b 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
10
∆p
EA
T T 1b
M 1a
6
5c ∆p 1c
9
T
0A
T M T V T
3 6 ∆p ∆p 7 11 2
8 9 5b
5a
Y2
Y3
Y1
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/
SPA T1 T2 T3 OFF
4 R7426B
Y1 Y2 Y3
X 24V 24V o pe n / 24V c lo s e/ o pe n / 24V c lo s e/ o pe n / 24V c lo s e/
Wrh OUT2 OUT1 OUT2 OUT1 OUT2 OUT1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac 24V
5c ML6420A Energy 1 2
Recovery Valve
3 - Way Valve 1 24V 2
5b ML6420A Cooling Valve
100...440Vac
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426B1014 or Temperature Controller with clock or
R7426B1006 without clock
5a 1 RN1L40M25 Solid State Relay, up to 3 possible for higher loads
5b + 5c 2 ML6420A3007 and Valve Actuator and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
11 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
10
∆p
EA
T T 1b
M 1a
6
5c ∆p 1c
9
T
0A
T M T V T
3 6 ∆p ∆p 7 11 2
8 9 5b
5a
Y2
Y3
Y1
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X
Wrh
24V 24V 0 ..1 0 V 24V 24V 0 ..1 0 V 24V 24V 0 ..1 0 V 24V 24V
2 ..1 0 V 2 ..1 0 V 2 ..1 0 V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
3 1 2
Y 24V 24V
5c ML7420A Energy
Recovery Valve
3 1 2
5b ML7420A Cooling Valve Y 24V 24V
8 10
5a R7425A/B Y
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5b + 5c 2 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 2 ML6184E1009 or Damper Actuator 24Vac, 17Nm or
ML6684E1008 230Vac, 17Nm
7 1 L4064K1006 High Limit Thermostat
8+9+10 4 DPS-Series Differential Air Pressure Switch
11 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
ROOM/ DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS,
R16
ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL
For use with ventilation system comprising of mixed air dampers, an electric air heater and a cooling coil.
EA
M T T 1b
1a
6 ∆p 1c
M 9
6 T
0A
T M T V 5b T
3 6 ∆p ∆p 7 10 2
8 9
5a
Y2
Y3
Y1
4
WIRING CONNECTIONS
3 T7411A/T7416A 1 2
2 T7411A 1 2
1c T7412C 5 4 3 6
1c T7412B 4 3 6
1b T7412A 1 2
1a T7411A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426C
Y1 Y2 Y3
X Wrh 24V 24V 0 ..1 0V 24V 24V 0 ..1 0V 24V 24V 0..10V 24V 24V
2 ..1 0V 2 ..1 0V 2..10V
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac green brown white
24V 24V
6 ML7284E Mixed Air Dampers Y
3 1 2
5b ML7420A Cooling Valve Y 24V 24V
8 10
5a R7425A/B Y
EQUIPMENT LIST
Item Quantity Part Number Description
1a or 1 T7411A1001 or Duct Temperature Sensor 135mm length or
1b or T7412A1018 or Room Temperature Sensor or
1c T7412B1057 Room Temperature Sensor with CPA
T7412C1030 Room Temperature Sensor with CPA and Occupancy Switch
2 1 T7411A1001 or Duct Temperature Sensor 135mm length or
T7411A1019 Duct Temperature Sensor 300mm length
4 1 R7426C1012 or Temperature Controller with clock or
R7426C1004 without clock
5a 1 R7425A/B Electric Current Valve
5 1 ML7420A3006 and Valve Actuator 0(2)...10Vdc and
V5....A.... Valve
6 2 ML7284E1006 or Damper Actuator 24Vac, 0...10Vdc, 17Nm or
ML7174E1006 24Vac, 0...10Vdc, 8Nm
7 1 L4064K1006 High Limit Thermostat
8+9 3 DPS-Series Differential Air Pressure Switch
10 1 DPS-Series Differential Air Pressure Switch
OPTIONS
Item Quantity Part Number Description
3 1 T7411A1027 or Outside Air Sensor, Duct Mounting or
T7416A1006 Wall Mounting
B
A
AB
4 T
1
T
2 Y1 5
FUNCTIONAL DESCRIPTION
Temperature Control. The supply water flow temperature sensor (1) measures
the actual value and the controller (4) compares this value with the actual control
point. The control point comprises the basic setpoint value which is continuously Y1 (%) Cooling
compensated by the outside air temperature sensor (2) value. If a deviation 100
between the two values exists, the controller (3) generates a 3-position control
signal to reposition the valve (4) to maintain the desired supply water temperature.
In heating applications the controller output is reverse acting and a positive winter
compensation authority is used, with decreased outside air temperature the
control point is increased. Heating
0
In cooling applications the controller output is direct acting and a negative summer 0 Xw
compensation authority is used, with increased outside air temperature the control CTRP1 Ystart T1
point is decreased. Xp
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort, Standby,
Night or OFF are selected. In the Standby or Night mode the main temperature setpoint is decreased by the programmed offset
values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to H2, automatically the pump switches OFF at outside air temperatures
above 8°C, if the valve is closed for more than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (4) and switches the pump OFF.
WIRING CONNECTIONS
2 T7416A 1 2
5 T7412B 4 6
1 T7413A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
3 R7426A
Y1
24V 24V open/ 24V close/
OUT2 OUT1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
24V
4 ML6420A 1 2 3 - Way Valve
Heating or Cooling Valve
2 24V 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1 1 T7413A1009 or Immersion Temperature Sensor with Brass Well, 135mm length or
T7413A1066 Immersion Temperature Sensor for chilled water applications
plus 1 43193884-001 Brass Well, 135mm length
2 1 T7416A1006 Outside Air Temperature Sensor, Wall Mounting
3 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
4 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
OPTIONS
Item Quantity Part Number Description
5 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
T
2
B
A
AB
5 T
1
T
3 Y1 6
FUNCTIONAL DESCRIPTION
Temperature Control. The supply water flow temperature sensor (1) and return
water flow temperature sensor (2) measures the actual values and the controller Y1 (%) Cooling
(4) compares these values with the actual control point and the desired limit 100
setpoint (Wlim). The control point comprises the basic setpoint value which is
continuously compensated by the outside air temperature sensor (3) value. If a
deviation between these values exists, the controller selects the highest or lowest
deviation signal in correspondence with the selected limit function.
Depending on this deviation signal the controller generates a 3-position control
signal to reposition the valve (5) to maintain the desired supply or return water Heating
0
flow temperature. 0 Xw
The controller output has to be configured reverse acting for heating applications CTRP1 Ystart T1
and the desired positive winter compensation authority determines the reset effect Xp
on the main setpoint (W1).
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. In the Standby or
Night mode the main temperature setpoint is decreased by the programmed offset values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to H2, automatically the pump switches OFF at outside air temperatures
above 8°C, if the valve is closed for more than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (5) and switches the pump OFF.
WIRING CONNECTIONS
3 T7416A 1 2
2 T7413A 1 2
6 T7412B 4 6
1 T7413A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
4 R7426A
Y1
24V 24V open/ 24V close/
OUT2 OUT1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
24V
5 ML6420A Heating Valve 1 2 3 - Way Valve
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1+2 2 T7413A1009 Immersion Temperature Sensor with Brass Well, 135mm length
3 1 T7416A1006 Outside Air Temperature Sensor, Wall Mounting
4 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
5 1 ML6420A3007 and Valve Actuator and
V5.....A..... Valve
OPTIONS
Item Quantity Part Number Description
6 1 T7412B1057 or Remote Setpoint Adjustment Potentiometer, Wall Mounting or
43182690-001 Front Panel Mounting
T 1a
1b
B T
A
AB
4 T
2
Y1
FUNCTIONAL DESCRIPTION
Temperature Control. The room air temperature sensor (1a or 1b) measures the
actual value and the controller (4) compares this value with the desired setpoint
Y1 (%) Cooling
(W1) of the master loop. Depending on the deviation an internal setpoint for the
submaster loop, the supply water flow temperature, is calculated. At zero
deviation the supply water flow temperature is controlled at the programmed
setpoint (Wcas) and if a deviation exists, the supply water setpoint is altered. The
reset span of the supply water setpoint is limited by the reset span adjustment
(Rcas) and the limit setting (Wlim).
The supply water flow temperature sensor (2) measures the actual value and the Heating
controller (4) compares this value with the desired internal calculated setpoint. 0
0 Xw
If a deviation between the two values exists, the controller generates a 3-position CTRP2 T2
Ystart
control signal to reposition the valve (5) to maintain the desired supply water flow Xp
temperature.
Time Control. Depending on the programmed time schedule of the internal
controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. In the Standby or
Night mode the main temperature setpoint is decreased by the programmed offset values SOFFS (Standby) or NOFFS (Night).
If the configuration parameter C.04 (Ctrltyp) is set to H2, automatically the pump switches OFF, if the valve is closed for more
than 5 minutes during Comfort, Standby or Night mode.
In the OFF operating mode the controller automatically closes the valve (5) and switches the pump OFF. The night cycle
program compares the actual room temperature to the low cycle limits and either turns the heat and pump on or off or does
nothing. If the temperature is below the limit setpoint (NightLow) the controller opens fully the heating valve and switches the
pump ON. When the temperature reaches the other limit (1K differential), the valve closes and the pump switches OFF.
WIRING CONNECTIONS
2 T7413A 1 2
1b T7412C 5 4 3 6
1b T7412B 4 3 6
1a T7412A 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CPA/ ON/ 24V
SPA T1 T2 T3 OFF
3 R7426A
Y1
24V 24V open/ 24V close/
OUT2 OUT1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
24Vac
Transformer
230Vac
24V
4 ML6420A Heating Valve 1 2 3 - Way Valve
24V
2 1 2 - Way Valve
EQUIPMENT LIST
Item Quantity Part Number Description
1a+1b 1 T7412A1018 or Room Temperature Sensor or
T7412B1057 Room Temperature Sensor with CPA
2 1 T7413A1009 Immersion Temperature Sensor with Brass Well, 135mm length
3 1 R7426A1016 or Temperature Controller with clock or
R7426A1008 without clock
4 1 ML6420A3007 and Valve Actuator and
V5....A.... Valve
EN3C-0161 0698R0-MA
Honeywell Regelsysteme GmbH
Honeywellstr. 2-6
D-63477 Maintal
Tel. (0 61 81) 401-1
Fax (0 61 81) 401-400
DIN
Subject to change without notice. Printed in Germany. Manufacturing location is certified according to
EN ISO 9001
EN3C-0161 0698R0-MA