ELEVATOR MANUAL
《TABLE OF CONTENTS》
A. INSTALLATION METHOD & ADJUSTING
A-1. INSTALLATION METHOD
1. TEMPLATE…………………………………………………………………………1
1.1 LAYOUT DRAWING........................................................................................................1
1.2 Template...................................................................................................1
3. HOISWAY PARTS…………………………………………………………………9
3.1 BUFFER INSTALLATION………………………………………………………………………. 9
3.2 GUIDE RAIL INSTALLATION………………………………………………………………11
3.3 CORRECTION & ADJUSTMENT WORKS…………………………………………………14
3.4 GOVERNOR TENSION SHEAVE INSTALLATION………………………………………15
4. CAR PARTS…………………………………………………………………………17
4.1 SAFETY DEVICE…………………………………………………………………………… 17
4.2 CAR FRAME…………………………………………………………………………………18
4.3 COUNTER-WEIGHT FRAME…………………………………………………………………23
4.4 CAGE……………………………………………………………………………………………24
4.5 CAR DOOR ……………………………………………………………………………………25
5. ENTRANCE PARTS…………………………………………………………………30
5.1 HATCH SILL……………………………………………………………………………………30
5.2 JAMB…………………………………………………………………………………………30
5.3 HATCH DOOR……………..........................................................................................32
5.4 DOOR INTERLOCK…………………………………………………………………………….33
-i-
TABLE OF CONTENTS STVF5
1. SYSTEM INTRODUCTION………………………………………………………36
1.1 WARNING…………………………………………………………………………………….36
2. PREPARATION……………………………………………………………………38
2.1 PREPARATION………………………………………………………………………..… 38
2.2 CABLE INSTALLATION & WIRING………………………………………………..… 39
3. INSPECTION OPERATION………………………………………………………55
3.1 CHECK POINT BEFORE TURNING THE MAIN POWER ………………………..… 55
3.2 JUMPER THE NECESSARY PART………………………………………………..… 56
3.3 INSPECTION OPERATION…………………………………………………………..… 58
- ii -
TABLE OF CONTENTS STVF5
- iii -
TABLE OF CONTENTS STVF5
3. PARAMETER………………………………………………………………..…170
3.1 MONITOR……………………………………….………………………………………..…170
3.2 PROGRAM…………………………………………………………………………………172
4. DESCRIPTION OF PARAMETER…………………………………………177
4.1 MONITOR…………………….……………………………………………………………....177
4.2 PROGRAM………………………………………………………………………………......189
- iv -
INSTALLATION & ADJUSTING STVF5
Fig 1.1
a) Machine room Plan
b) Drilling of Holes (Building Work)
1.2 TEMPLATE
1) Installation of Template
Template shall be installed
correctly as it is basic work of
elevator installation.
Template are composed of Upper
template (Machine room) and
Lower template (Pit).
And they are connected by
piano wires.
Check the change of template
frequently.
-1-
INSTALLATION & ADJUSTING STVF5
Based on Layout Drawing, mark the location of upper template in machine room.
Entrance, Car and CWT Template are set same as location of upper template in
machine room. (See Fig 1.4)
In case of changing the position of entrance piano wire, check and adjust the location of
upper template.
Fig 1.4
a) Upper template plan
b) Side view of upper template
-2-
INSTALLATION & ADJUSTING STVF5
Fig 1.5
a) Lower Template Plan
b) Side view of Lower Template
-3-
INSTALLATION & ADJUSTING STVF5
-4-
INSTALLATION & ADJUSTING STVF5
TM500 TM600
X 257 253
X' 190 203
Fig 2.3 Machine beam installation
-5-
INSTALLATION & ADJUSTING STVF5
-6-
INSTALLATION & ADJUSTING STVF5
2.2 GOVERNOR
1) Governor Installation (See Fig 2.8)
Governor is properly located at machine room based on template and Layout Drawing.
-7-
INSTALLATION & ADJUSTING STVF5
-8-
INSTALLATION & ADJUSTING STVF5
3. HOISTWAY PARTS
3.1 BUFFER INSTALLATION
1) Car Buffer Installation
Buffer footing is correctly installed based on the piano wire of car template.
-9-
INSTALLATION & ADJUSTING STVF5
- 10 -
INSTALLATION & ADJUSTING STVF5
For exact dimension of car BG (between guide rail), insert shim liner.
- 11 -
INSTALLATION & ADJUSTING STVF5
- 12 -
INSTALLATION & ADJUSTING STVF5
- 13 -
INSTALLATION & ADJUSTING STVF5
- 14 -
INSTALLATION & ADJUSTING STVF5
- 15 -
INSTALLATION & ADJUSTING STVF5
- 16 -
INSTALLATION & ADJUSTING STVF5
4. CAR PARTS
4.1 SAFETY DEVICE
1) Safety Device Installation
Insert safety device into both side of guide rail. (See Fig 4.1)
Check the horizontal of upper / lower and left / right of safety device.
After install the safety device, remove the fix plate.
Before the operation of safety device, check 3.5mm clearance between the guide rail
and the gib of safety device. (See Fig 4.2)
Fig 4.1 Safety Device Installation Fig 4.2 Safety Device Installation (Side view)
(Top view)
- 17 -
INSTALLATION & ADJUSTING STVF5
- 18 -
INSTALLATION & ADJUSTING STVF5
- 19 -
INSTALLATION & ADJUSTING STVF5
- 20 -
INSTALLATION & ADJUSTING STVF5
Middle hole center of car header arm is exactly set 151mm to the end of car sill or
entrance piano wire.
- 21 -
INSTALLATION & ADJUSTING STVF5
- 22 -
INSTALLATION & ADJUSTING STVF5
2) Counter-Weight
Fill the sub weight into counter weight frame properly.
After fill the sub weight, fix weight fixing bracket to CWT frame. (See Fig 4.14)
- 23 -
INSTALLATION & ADJUSTING STVF5
4.4 CAGE
1) Cage Assembling (See Fig 4.15)
Assemble the car walls one by one.
(Check the alignment of each car wall)
Assemble the ceiling.
Assemble the handrail.
- 24 -
INSTALLATION & ADJUSTING STVF5
- 25 -
INSTALLATION & ADJUSTING STVF5
- 26 -
INSTALLATION & ADJUSTING STVF5
3) Clutch Assembling
Assemble the clutch to car door. (See Fig 4.20)
Check the gap between the fixed cam and moving cam.
- 27 -
INSTALLATION & ADJUSTING STVF5
- 28 -
INSTALLATION & ADJUSTING STVF5
- 29 -
INSTALLATION & ADJUSTING STVF5
5. ENTRANCE PARTS
- 30 -
INSTALLATION & ADJUSTING STVF5
After checking the vertical and horizon of jamb, fix the jamb to entrance wall.
(See Fig 5.4)
- 31 -
INSTALLATION & ADJUSTING STVF5
- 32 -
INSTALLATION & ADJUSTING STVF5
Check the gap between hatch door and hatch sill. (See Fig 5.7)
(If necessary, use shim liner)
- 33 -
INSTALLATION & ADJUSTING STVF5
Adjust the center of fixed roller and entrance with hatch door closed.
(See Fig 5.10)
Check and adjust the gap with release roller and clutch overlapped. (See Fig 5.11)
- 34 -
INSTALLATION & ADJUSTING STVF5
a)
b)
- 35 -
INSTALLATION & ADJUSTING STVF5
1. System Introduction
This system applied "CAN" communication method for both car and hall part.
And motor drive unit (Inverter) is in charge of the position control system,
So the elevator can stop direct without creeping speed and also multi pattern is available.
1.1 Warning
For your safety and prevention of abnormal function, please make sure following
information.
Panel.
TCB-3
It is requires minimum 1m
> 1m
safe work.
2) As this system uses serial communication, correct and thorough grounding is vitally
3) As all the connections are treated by the harness connectors and there are many
connectors in similar appearance, it's very important to confirm the right label or
- 36 -
INSTALLATION & ADJUSTING STVF5
4) As car top board (CCB-3 board) is installed in the Car Junction Box, be careful that the
CCB-3 board is not damaged by water leakage during installation.
5) As the Brake Resistor Module of the inverter is located on top of the control panel, the top
cover over the Brake Resistor Module is heated, so don't put the tools on top of the control
panel not to be burnt or shocked by the electricity.
- 37 -
INSTALLATION & ADJUSTING STVF5
2. Preparation
2.1 Preparation
1) Safety Training
* For safety, it is required to prevent any accident by wearing safeguard outfits, installing
2) Checking others
* The building power should be enough to work, and the capacity of NFB too.
1) Machine room
* Machine
* Brake
* Control panel
* Governor
2) Hoistway
* Counter Weight
- 38 -
INSTALLATION & ADJUSTING STVF5
- Put the proper sub-weight to prevent slip with unbalance between car and counter weight
part.
* Hoistway
- Check whether there is any obstacle in running car to prevent accident and danger of the
product.
- Install the safety guard at hatch opening at every floor.
3) Pit
* Buffer
- Check the correct position of buffer.
(If it is oil type, check the volume of oil inside buffer)
* Obstacle point
- Check the obstacle point inside of pit.
4) Control Panel
* Check the control panel is located at proper position for the work in the machine room.
* Take off the vinyl cover, and check all components are assembled and kept in order without
damages.
* Check the connectors are fixed between male and female
* Tighten up power terminal screws firmly.
* Make sure the specification of Reactor, NFB, Inverter and Braking Resistors.
Caution!
- 39 -
INSTALLATION & ADJUSTING STVF5
Caution!
If the connection of the power lines (PGM,PGP) are changed, the encoder will be
damaged.
If the connection of the phase signal PA and PB are changed, speed feedback
can not be performed. Reconfirm the wiring.
Shield cable should be grounded at "PGM" terminal or shied terminal of inverter
6) Grounding
The purpose of grounding is to protect the workers from the electric shock. When working
near the electric conducting equipments, be careful of accident by electric shock as it can be
fatal to workers.
- 40 -
INSTALLATION & ADJUSTING STVF5
Also, the grounding is one of the measure to minimize the interference of noise. The system
can be protected from the electronic noise by proper grounding and shielding.
* Items that shall be grounded
- Control Panel
- Motor
- Governor
- Reactor and Auto Transformer
- Operating Panel (OPB) - Hall Button Box
- Indicator Box and Hall Lantern Box
- Car Top Junction Box
- Switches (Limit Switch, Door Switch, Fire Switch, Parking Switch, etc.)
- Cable Duct at Machine Room and Hoist way
- Other Equipments
- 41 -
INSTALLATION & ADJUSTING STVF5
- 42 -
INSTALLATION & ADJUSTING STVF5
CAUTION!
As this system uses the cables with harness connectors at both ends forall field
contacting state is poor. So it requires special care in doing the connecting work.
<Notes>
Do the traveling cable connection work first and proceed the test run of the car using the
Then do the harness connection work while operating up and down the car loaded with the
harnessed cables.
1) Do not use the hatch junction box for connecting the traveling cable between the control
- 43 -
INSTALLATION & ADJUSTING STVF5
2) Pull out one end of the traveling cable to the machine room through the duct hole and
then to the inside of the control panel through the control panel duct hole. The end of the
cable, about 2M long, shall be available from the end of the control panel duct
for connection in the control panel.
3) Fix the traveling cable by using fixing pipe of minimum 30mm diameter tightly on the
machine room duct hole so that the traveling cable is not damaged or affected by the
weight of the cable itself.
4) Drop the other side of the traveling cable through the machine room duct hole down to the
hoistway and fix it by the cable hanger to be installed within 500mm from the top of the
hoistway.
5) Drop the traveling cable further down and fix it to the cable hanger installed at the point of
overhead(OH) +travel(TR)/2 +500mm from the top of the hoistway.
6) The other end of the traveling cable shall be fixed by the cable hanger at the bottom of the
car. At this time, the bottom curved part of the traveling cable shall be leveled 300±50mm
high from the bottom of the pit when the car stopped at the lowest floor level. And the
distance between the cables dropped down and the pulled up shall be maintained about
630mm in case of the flat type cable.
7) Pull up the traveling cable from the car bottom along the car wall to the car top and connect
it to T1 and T2 Connectors of CCB-3 Board in the car junction box. Any extra cables shall
be put aside not to cause any inconvenience to other works.
8) The traveling cable shall be bound closely on the car wall as shown at Fig 2.2 so that it does
not interfere with any devices in the hoistway while the car is running.
9) When connecting the cable in the car junction box, the cable shall be fixed by the cable
clamp available in the car junction box so that it's not disconnected from the car junction
box due to its load.
- 44 -
INSTALLATION & ADJUSTING STVF5
To perform easier connection to many other devices in the car as listed below, connectors
are provided at the end of cables. Be sure to confirm the marked labels on the connectors
and then connect each cable correctly to Car Top Board. Each cable shall be properly
- 45 -
INSTALLATION & ADJUSTING STVF5
Before install, confirm that the NFB of control panel turn off.
PC board (CCB-3 board, Emergency Power board), Fuse for spare part and Jumper Cable
for installation are included inside of Car Junction Box. The wiring between Car Junction
- 46 -
INSTALLATION & ADJUSTING STVF5
* Safety Switches
- 47 -
INSTALLATION & ADJUSTING STVF5
- 48 -
INSTALLATION & ADJUSTING STVF5
Fig 2.5 Wiring preparation diagram of OPB and Car Junction Box
- 49 -
INSTALLATION & ADJUSTING STVF5
1) Main OPB
OPB-3 board is located inside of Main OPB.
"Cable A1", "Cable B1", "Cable C1" and "Cable D1" are connected to OPB-3 board. The
other side of cables should be connected to CCB-3 board of Car Junction Box.
2) Disable OPB
"Cable E1", "Cable F1", and "Cable G1" are connected to Disable OPB.
"Cable F1" and "Cable G1" should be connected to OPB-3 board of Main OPB, and "Cable
E1" should be connected to CCB-3 board of Car Junction Box.
Indicator Cable "G1" is connected to connector “CU46“ of OPB-3 board or connector "CH2"
of Indicator board at Main OPB.
3) Sub - OPB
"Cable A2", and "Cable C2" are connected to Sub-OPB.
It should connected to CCB-3 board of Car Junction Box.
Name of Cable From To
CC54C
CAN CCB-3
(W/O VOICE)
Communication S.OPB-3 CC54A
Cable (C2) CN3
VOICE
(W/ VOICE)
Interphone Cable
Sub Interphone - CCB-3 CO1S
(A2)
- 50 -
INSTALLATION & ADJUSTING STVF5
Load Switch
Load Switch - M.OPB-3 CC26
Cable
7) Installation and connection of car Load Compensation board (LS board) Connect the
communication cable from LS board to connector "CC54B" on the OPB-3 board.
- 51 -
INSTALLATION & ADJUSTING STVF5
- 52 -
INSTALLATION & ADJUSTING STVF5
2.2.5 Others
* Install the Door Operator
(reference to the manual (Reference sheet) and connect the harness cable as above).
- 53 -
INSTALLATION & ADJUSTING STVF5
3) Set the position of LCD body to inner side of car to protect from touching at hoistway. And
connect the harness cable as above.
- 54 -
INSTALLATION & ADJUSTING STVF5
3. Inspection operation
After finish the wiring of car side and machine room part. take off the scaffolding to move the
Check whether the power inputs R,S,T of the control panel and the outputs U,V,W of the
motor are connected correctly. At this time, the phase of R,S,T have no relation with the
* Check the quantity of I/O Module in TCB-3 Bd, considering the specification.
- 55 -
INSTALLATION & ADJUSTING STVF5
1) Jumper the necessary points (at TCB-3 board and CCB-3 board)
* Refer to Figure 3.1 (at next page)
- Jumper 1 : Interlock switch
- Jumper 2 : Safety line of CCB-3 board
- Jumper 3 : Gate switch
- Jumper 4 : Safety line of TCB-3 board
- Jumper 5 : Safety device switch
- Jumper 7 : Safety-edge 2
- Jumper 7B : Safety-edge 1
- Jumper 8 : Safety-ray 2
- Jumper 8B : Safety-ray 1
- Jumper 10 : ULS switch
- Jumper 11 : Compensation switch
- Jumper 12 : DLS switch
If the some equipment is operate normal, don't use the jumper cable.
2) Make sure the connect of Traveling Cable between control panel and
CCB-3 board at Car Junction Box.
- Connection Wiring : T1 & T2
3) Make sure the connect of Harness Cable between OPB and Car Junction
Box.
- 56 -
INSTALLATION & ADJUSTING STVF5
- 57 -
INSTALLATION & ADJUSTING STVF5
<Preparation>
And if the voltage is normal, turn on the NFB at Main Distribution Box
3) Turn on the Switch CP2 (near the NFB) to input the power at Transformer
4) Check the voltage at Fuse "F1" and "F2". It should be 110V DC and 24V DC each between
grounding.
6) Turn on the remaining power switches and check all the In/Out conditions including P5
* Set the switch "SW1" of TCB-3 board to "Down" direction for inspection mode.
* Set the switch "SW3" of TCB-3 board to "Up" direction to connect the E-Stop signal.
* Set the AUTO/INSP switches of car junction box and internal of OPB to AUTO position.
- 58 -
INSTALLATION & ADJUSTING STVF5
4: DIG.
APPLIED DIGITAL TYPE LOAD SENSOR
TQ BIAS
17 : TQ BIAS LV 1F 23 % NO LOAD UP
18 : TQ BIAS LV 2F 83 % FULL LOAD UP
19 : TQ BIAS LV 1R -83 % NO LOAD DOWN
20 : TQ BIAS LV 2R -23 % FULL LOAD DOWN
22 : MIN LENGTH 35 MM 0:DIRECT LANDING, OVER 0 :DISTANCE OF CREEP
25 : MAX FLOOR 8 FL If Maximum Floor is 14, this data should be "14"
08 : Y1 SELECT RUN
INTER-
FACE 09 : Y2 SELECT ZERO SPEED
10 : Y3 SELECT TQ ANS
F : FORWARD 2 : PLDL
R : REVERSE 3 : PLUH
A : AUTO 4 : PLDH
02 S: Y1: RUN
FRASUDI1234 Y123M
I/O U : HOU Y2: ZERO SPEED
D : HOD Y3 : TQ ANS
I : INITIAL M : 30B
1 : PLUL
CURRENT POS CURRENT PULSE DATA
- 59 -
INSTALLATION & ADJUSTING STVF5
11) After checking the operation of the car direction, adjust the Brake, so that it works smoothly.
12) If the operation of car is normal on machine room, check the operation of car on car top and
inside the car.
- 60 -
INSTALLATION & ADJUSTING STVF5
* On car top, change the auto/insp switch to insp mode and use the up/down switches to
* In car, change the auto/ insp switch at car top to auto position and set the auto/insp switch
* For up direction, use the top floor call button. And for down direction, use the lowest floor
* Check whether there is any obstacle in running car to prevent accident and danger of the
product.
- 61 -
INSTALLATION & ADJUSTING STVF5
From C/P
(TCB-3,M33Bd.)
GND
Fig 4.1 Communication Cable
2) Interlock Harness
This harness is fastened together with communication cable harness.
Harness cable is designed for comfortable work at field.
- 62 -
INSTALLATION & ADJUSTING STVF5
6) In case of HPI
During installation, the harness cable from HPI is connected to Hall button in Hall Button
Box.
Preparation
* Check the material.
Project Name, Number of Elevator, Maximum floor.
* Prepare enough cable tie to fix the harness to each floor cable hanger.
* Prepare tools (Anchor or Hilti) to fix bracket at the wall of hoistway.
※ For narrow hoistway, the harness fixing bracket shall be prepared.
If necessary, wire the harness with them.
- 63 -
INSTALLATION & ADJUSTING STVF5
4.2.1 Wiring of Communication Cable, Interlock Cable, Pit Cable and Top Final Limit Switch
Cable.
3) The electrician in the machine room shall pull out the cable caring that the cable in the
hoistway is not bent and then fix it by using the fixing pipe in the machine room duct hole.
At this time, the end of the cable shall be available more than 2m from the end of the duct
hole for connection to the TCB-3 board in the control panel.
4) Straighten the cable coming from the machine room and fix the fixing bracket for cable
branch box at the marked point (1,000mm high point) with hilti tool.
After fixing the bracket, fix the harnessed cable firmly with plate and bolts.
(To fix the harness cables all at the top of hoistway)
- 64 -
INSTALLATION & ADJUSTING STVF5
5) When the work is finished at the top floor, move down the car with releasing the cable to the
top floor's hanger case.
6) Fastened the harness cables and the end plate of hanger case firmly with Cable Tie. Set
the distribution part of harness cable on upper side of hanger case. If the cable is enough
to fixing, fix the remaining cable on the hanger case.
- 65 -
INSTALLATION & ADJUSTING STVF5
- 66 -
INSTALLATION & ADJUSTING STVF5
10) Check the interference while the car is operating and door is opening and closing.
- 67 -
INSTALLATION & ADJUSTING STVF5
With below formula, you can get 50% Balance Load Setting.
Car Weight + Capacity X 50% = CWT Frame Weight + Counterweight
Load the car equivalent to 50% of the capacity with weights.
Move the car up and down and measure the currents at the motor. When the car is located at
same level with the counterweight in the hoistway, add or reduce the weight of counterweights
until the electrical amperes of measured currents become same.
- 68 -
INSTALLATION & ADJUSTING STVF5
* After installing LCD vane for all needed floors, check whether the sensor do not interfere
with vane when operating the car up and down at inspection speed. Repeat the checking 2
or 3 times to ensure that the touching point of vane and sensor.
4) If there are any safety circuits connected by the jumper cables, remove them and make sure
whether all the safety circuits are as per circuit diagram.
- 69 -
INSTALLATION & ADJUSTING STVF5
- 70 -
INSTALLATION & ADJUSTING STVF5
5.2.2 Initialization
- Set the car at bottom terminal floor and move down to lower than the level of bottom floor
- Write the data of address "0C80" to "01" with key on M33 Board, and push the enter key.
- When the car arrives at the top floor and operation for initialization is completed, turn the
AUTO/INS Switch of Control Panel to "Auto". If an "Error" happens during the initialization
operation, remove the cause of the error by referring to the Troubleshooting Manual or the
Control System Overview and carry out the initialization operation again. At this time,
(LED for Level → Upper Bar : ULA, Middle Bar : DZ, Lower Bar : DLA)
Then the Auto Door mode will be start, the door will not open with normal operation.
- For Auto mode, turn the Auto/Ins switch on TCB-3 board to Auto.
- 71 -
INSTALLATION & ADJUSTING STVF5
- Until the deceleration and landing become smooth and satisfactory, repeat the short run
- 72 -
INSTALLATION & ADJUSTING STVF5
- By riding in the car, check whether the car is operating normally by car call.
- Check the hall position indicators and hall buttons of all floors operate normally. Then
check the indicator in the car also operates normally.
- Adjust and set the landing vane, so that the landing error is within the limits of ±5mm.
- Check the overall operation status of the standard features.
- Check the optional features are operating exactly.
- Clean the car floor, car inside, machine room, door part and pit.
Reference 1. Layout of the M33 board Reference 2. Layout of the OPB-3 board
Reference 3. Layout of the CCB-3 board Reference 4. Layout of the TCB-3 board
- 73 -
INSTALLATION & ADJUSTING STVF5
1 2 3 4 1 2 3 4
Normal status Set the switches up
<->
Off ↔ On
- In case of pushing the "UP" button one more time, FNDs display as below.
So it indicate the status of 8 I/O signal which is in second module of TCB-3 board.
The signals are ULS, PLUL, PLUH, INIT, CE, PLDH, PLDL and DLS.
- 74 -
INSTALLATION & ADJUSTING STVF5
Position of Module ① ② ③ ④ ⑤ ⑥ ⑦ ⑧
Above FNDs show that ①, ②,③ signals are turned on and others are off.
The signals ULS, PLUL and PLUH are turned on and others are off status.
- To check the status of I/O signals on the TCB-3 board and CCB-3 board, use the keypad
- 75 -
INSTALLATION & ADJUSTING STVF5
- 76 -
INSTALLATION & ADJUSTING STVF5
<The status of FEDs lights "(①~⑧)" when the Elevator stops at the first floor with automatic
condition and closed condition of door>
- 77 -
INSTALLATION & ADJUSTING STVF5
Reference 7. How to register Car and Hall Call in the Machine Room?
The way to register a call in machine room is not same as before.
To register a call, write the correct data of reference address.
Ex.) Register the 4th floor Car Call.
- Set the write mode with keypad on M33 board.
(move up the 1st and 2nd Dip switch)
- Write the data of the address "047C" to "08".
- Push the ENT key. Then 4th floor car call will be registered.
- 78 -
INSTALLATION & ADJUSTING STVF5
Table 3 Setting the Dip Switches of Indicator ("L" ; Off, "H" ; On)
* If one floor has two indicators, such as HIP and HPI applied at same floor, one
indicator set the dip switch as above table, and the other set the dip switches to "L"
all.
* If one indicator set the dip switches same as the others, the function of the
indicator will be abnormal.
- 79 -
INSTALLATION & ADJUSTING STVF5
How to operate STVF5 initialization : Set the car at bottom FLOOR and move down to lower
than the level of bottom FLOOR hatch sill (DLA, DZ ; Off, ULA ; On) and Write the DATA of
ADDRESS "0C80" to "01" with key on M33 Board. (In only Machine room inspection status)
ULA is must registered and DLA is must released at operation for initialization.
* Press the down switch on TCB Board while DLS is on and execute operation for
initialization.
* IF actual CAR SILL and HATCH SILL are not adjusted, adjust the vane position and do not
modify the others. (IF position of vane is moved, must be rerunning operation for
initialization. )
1) For DATA SETING, AUTO/INS switch in Control Panel is surely set "INS".
2) DIP SWITCH located on MAIN Bd(M33 Bd) set WRITE MODE. (DIP S/W No 1,2 is ON )
4) After complete DATA SETTING, press the "RESET" Button located on MAIN Bd. (M33 Bd)
5) After turn READ MODE, each DATA is must checked in comparison with Spec DATA.
- 80 -
INSTALLATION & ADJUSTING STVF5
- 81 -
INSTALLATION & ADJUSTING STVF5
10) HALL CALL, DOOR OPEN WAITING TIME SETTING. (ADD : A014H)
* DEFAULT(05) : DOOR OPEN WAITING TIME 5sec.
* DATA : 03 - 3sec, 05 - 5sec(1pont/1sec).
11) DISABLE CALL, DOOR OPEN WAITING TIME SETTING. (ADD. : A016H)
* DEFAULT(0A) : DOOR OPEN WAITING TIME 10sec.
* DATA : 03 - 3sec, 05 - 5sec(1pont/1sec).
- 82 -
INSTALLATION & ADJUSTING STVF5
18) When FIRE RETURN S/W is on, FIRST RETURN FLOOR SETTING.
(ADD. : A024H)
* DEFAULT(01) : BOTTOM FLOOR is FIRE RETURN 1'st FLOOR.
* DATA : 03 -- 3RD FLOOR from BOTTOM FLOOR is FIRE RETURN 1'st FLOOR.
19) When FIRE RETURN S/W is on, SECOND RETURN FLOOR SETTING.
(ADD. : A026H)
* DEFAULT(01) : BOTTOM FLOOR is FIRE RETURN 2'nd FLOOR.
* DATA : 03 -- 3RD FLOOR from BOTTOM FLOOR is FIRE RETURN 2'nd FLOOR.
- 83 -
INSTALLATION & ADJUSTING STVF5
29) CAR CALL TWO TOUCH FUNCTION ENABLE/DISABLE SETTING. (ADD. : A060H)
* DEFAULT(00) : TWO TOUCH CAR CALL CANCEL(no connection with ROM SPEC).
* DATA : 00 - CANCEL, Excepting 00 DATA - NOT CANCEL.
- 84 -
INSTALLATION & ADJUSTING STVF5
- 85 -
INSTALLATION & ADJUSTING STVF5
TABLE 1-2 : STVF3 INDICATOR LED DISPLAY CODE DATA (ADD. :A01EH)
* NOTE :
1. IF ADD. A01E DATA is existence, excepting table 1-2 DATA CODE,
ADDRESS A01E DATA is returned to 00H ( 00 : STANDARD DATA)
3. BULE LAMP is mostly used hospital. Because BULE LAMP is similar to IND,
BLUE LAMP is used same methods with MOVE.
- 86 -
INSTALLATION & ADJUSTING STVF5
TABLE 1-3 : STVF3 INDICATOR SPECIAL CHARACTER CODE DATA (ADD. :A020H)
CODE DISPLAY CODE DISPLAY CODE DISPLAY CODE DISPLAY
00 42 1A 5A ME 7C RG
01 1 39 2A 5B PB 7D P5
02 2 3A 3A 5C RC 7E P6
: : 3B M1 5D SB 7F BQ
0A 10 3C M2 5E UB 80 A
: : 3D M3 5F UG 81 B
0F 15 3E 1M 60 G 82 C
10 16 3F 2M 61 B1 83 D
11 17 40 3M 62 B2 84 E
: : 41 1P 63 B3 85 F
1A 26 42 2P 64 B4 86 G
: : 43 G1 65 B5 87 H
1E 30 44 G2 66 B6 88 I
1F 31 45 F1 67 B7 89 J
20 32 46 F2 68 B8 8A K
21 33 47 AA 69 B9 8B L
: : 48 AL 6A A1 8C M
27 39 49 AS 6B A2 8D N
28 40 4A BM 6C A3 8E O
29 E1 4B BF 6D M4 8F P
2A E2 4C BL 6E G3 90 Q
2B E3 4D CP 6F G4 91 R
2C E4 4E DS 70 F 92 S
2D P1 4F ES 71 -1 93 T
2E P2 50 GF 72 -2 94 U
2F P3 51 GP 73 -3 95 V
30 P4 52 KM 74 -4 96 W
31 L1 53 LB 75 -5 97 X
32 L2 54 LG 76 -6 98 Y
33 L3 55 LP 77 -7 99 Z
34 L4 56 LL 78 -8 9A PH
35 S1 57 LM 79 -9 9B PD
9C PS
36 S2 58 MB 7A 31A
9D SP
9E PM
37 S3 59 ML 7B 31B
9F S4
A0H 41 A6H 45 B0H 57 B6H 63
A1H 42 A7H 46 B1H 58 B7H 64
A2H 43 : : B2H 59 : :
A3H 44 ADH 54 B3H 60 D5H 94
A4H 45 AEH 555 B4H 61 D6H 95
A5H 46 AFH 56 B5H 62 D7H 96
Note 1. IF there is Special character which is not indicated on indicator on upper TABLE.
2. IF DATA SETTING ADDRESS A020 : 01, Special character is usable.
3. IF ADDRESS A020 DATA is not 01, Special character be not used.
4. After DATA SETTING ADDRESS A020 : 01, ALL FLOOR which is Selected from
TOP to BOTTOM have to put each FLOOR DATA ( MUST BE INPUT ALL FLOOR DATA ).
5. ADDRESS is assigned from A300(BOTTOM FLOOR), A302, A304, A306, A308,A30A,
A30C, A30E, A310, A312, A314, A316 - - -
- 87 -
INSTALLATION & ADJUSTING STVF5
6.2.1 INTRODUCTION
SYSTEM have RTC(REAL TIME CLOCK)and it provide variety SPEC. For example,
6) ADD. 0223 = XX(On working, SETTING HOUR TIME. = 13, one day is 24hour SETTING).
11) AFTER SETTING, RESET CP and CHECK SETTING DATA compare with below ADD.
9) ADD. A06E DATA = Checking ADD. A06E DATA. IF DATA is not 01, SETTING again.
- 88 -
INSTALLATION & ADJUSTING STVF5
6.3. NIGHT SILENT RUNNING & NIGHT VOLUME DOWN RUNNING USING RTC TIMER SPEC
6 3.1 NIGHT SILENT RUNNING INTRODUCTION : At Night, EL which gets run speed over 90M/min
(01= NIGHT VOLUME DOWN RUNNING, =03 BOTH, 00= NOT USE)
6.3.5 ETC : NIGHT VOLUME DOWN RUNNING is USING VIP PORT located VOICE
SYNTHESIZER
IF VIP RUNNING MODE is existed on E/L, NIGHT VOLUME DOWN RUNNING is not valid.
- 89 -
INSTALLATION & ADJUSTING STVF5
- 90 -
INSTALLATION & ADJUSTING STVF5
- 91 -
INSTALLATION & ADJUSTING STVF5
3) Load Setting.
(3.1) Setting condition
① It is only possible to condition of "machine room inspection state" and " Door Zone state"
and "Door Open state"
② It is possible to condition that CAN communication of LS board is ok.
(Check the address 0D83 : 0D83=x0 is OK, 0D83=x2 is not OK)
(3.2) Setting start
If you turn on 4PIN Dip switch No1 in M33 Board, it's READ MODE.
If you turn on 4PIN Dip switch No1, No2 in M33 Board, it's WRITE MODE.
You can read and write the Address of Load setting with push button
(SFT,UP,DN,ENT).
SFT button is shift button,
UP button is increase button,
DN button is decrease button,
ENT button is ENTER button.
① 01B0 Address = 01 ( ENT) in WRITE MODE
(3.3) No LOAD setting
① State of the cage equal to No Load.
② 01B1 Address = 01 ( ENT) in WRITE MODE
③ Wait for 10 sec
④ Confirm E1D8 Address Data in READ MODE, the data 30~40 is OK
(Correctly setting on the No LOAD)
(3.4) 50% Load setting
① State of the cage equal to 50% Load on the Cage.
② Wait for 10Min.
③ 01B2 Address = 01 ( ENT) in WRITE MODE
④ Wait for 10sec
⑤ Confirm E1D8 Address Data in READ MODE, the data 40~60 is OK
(Correctly setting on the 50% Load)
⑥ Confirm E1B2 Address Data in READ MODE, the data 52 is OK
(Correctly setting 50% Load)
(3.5) Confirmation of the setting
① A06C Address data = 01 (The Load setting END) in READ MODE
② E3B2 Address data = 90 (All OK) in READ MODE.
* If the A06C,E3B2 Address data not correct, One more try from (3.3).
- 92 -
INSTALLATION & ADJUSTING STVF5
4. INVERTER setting
(4.1) INVERTER Data setting (Using HHT)
① PROGRAM/CONTROL/17.TQ_BIAS_SELEC select "ANAL_TQ_BAIS".
② PROGRAM/CONTROL/23.TQ_BAIS_OFFSET confirm "38.450".
③ PROGRAM/CONTROL/35.DPRAM_TQ_USE select "1".
④ PROGRAM/CONTROL/22.TQ_BAIS_GAIN confirm "1.000".
(4.3) ROLL-BACK control with inverter data
① PROGRAM/CONTROL/22.TQ_BAIS_GAIN adjust, so there is not occurrence of
Elevator Roll-Back(normal data ±0.3~0.8)
5. Trouble shooting
① "F58" Error Massage indicates the LS Board-CAN communication Error or the Load setting
Error in the Elevator AUTO state.
② No Load setting Error : 01B5 = 01 in READ MODE
③ 50% Load setting Error : 01B7 = 01 in READ MODE
④ LS Board control Code in READ MODE
: E3B2 = 90 (After Load setting END, Normal state)
= D0 (Load setting state)
- 93 -
INSTALLATION & ADJUSTING STVF5
- 94 -
INSTALLATION & ADJUSTING STVF5
Ω
Ω
Ω
Ω
- 95 -
INSTALLATION & ADJUSTING STVF5
Ω
Ω
Ω
Ω
- 96 -
INSTALLATION & ADJUSTING STVF5
2.1 Features
* Efficient hall call assignment.
* Standing by dispersion .
* please refer to appendix of other functions.
2.2 Difference between card rack and ring group control system
- Card rack : composed by CPU Bd., SIO Bd., Output Bd., HHT Bd.
- 97 -
INSTALLATION & ADJUSTING STVF5
- Difference between card rack and ring group control system Bd.
version details
FI-1 : GC1***
Card rack FI-2 : GC2*** for FI-1,2,3 system
FI-3 : GC3**
Ring V1.0 iGC0* (ex:iGC05) for T&S, FI-4, STVF-5 system
Ring V2.0 iGC2* (ex:iGC23) V1.0 + expansion of function
- The lantern of service car is flickered from speed decreased to door closed.
- If you press a hall button, both button lamp and lantern are on.
- Passengers don't have to object the other car, because of lantern displayed.
- The lantern of service car is flickered from speed decreased to door closed.
method
merit demerit details
card rack ring
- simple predict
arrival operation - impossibility of
standard standard standard
prediction - application of total predict
indicator
- 98 -
INSTALLATION & ADJUSTING STVF5
SW 2 A SW 1 0
- If removing the fiber optic cable, please grip the connection part.
- Connect the fiber optic cable from group SIO Bd. "LCD1" to #1 main SIO Bd. and
- 99 -
INSTALLATION & ADJUSTING STVF5
NO 1) Is ROM connected to Bd
2)Is the SW1 value of group control 2) Is ROM version right? when EPROM in
YES
YES
YES
NO
Are LED25~28 4 bit of "A0" output CPU shall be
CPU in trouble
board flickering? replaced.
YES
When connecting fiber optic cable, is NO Is fiber optical module LED NO Fiber optic
LED in front of fiber optical module of of SIO Bd for each car
SIO Bd lighting green? lighting green? cable faulty.
YES
SIO Bd faulty.
- 100 -
INSTALLATION & ADJUSTING STVF5
- If you disconnect DSP CPU Bd. or etc, please turn off the power (DC24V) first.
b) Please refer to detail setting method which is shown at chapter 3 "Group Control HHT".
- 101 -
INSTALLATION & ADJUSTING STVF5
➃ Connect the Fiber Optic Cable between "LCD2" of lift #2 and "LCD1" of lift #3.
➄ Connect the Fiber Optic Cable between "LCD2" of last lift and "LCD1" of Master
- 102 -
INSTALLATION & ADJUSTING STVF5
- Home indicator control board transfers the floor information to the home automation
device by connecting “CAN-PI" of ring group control board V2.0 .
- Set SW1 value according to the floor.
- 103 -
INSTALLATION & ADJUSTING STVF5
1 2 3 4 5 6 7
1 Floor 1 0 0 0 0 0 0
2 Floor 0 1 0 0 0 0 0
10 Floor 0 1 0 1 0 0 0
11 Floor 1 1 0 1 0 0 0
- It must be connected the end resistor to "CH4" connector at the control board
of bottom floor.
3.3 Setting for SIO Bd.
※Attention
A. For simplex, optical module is not inserted on SIO Board.
For group, 2 optical modules are inserted on SIO Board.
B. In case of removing the SIO Board from Main Board, turn off the power.
- 104 -
INSTALLATION & ADJUSTING STVF5
- 105 -
INSTALLATION & ADJUSTING STVF5
- 106 -
INSTALLATION & ADJUSTING STVF5
4. HHT SETTING
※ This HHT manual is based in Ring group control system.
Please refer to FI-1,2,3 HHT manual in case of card rack group control system.
※ After connecting HHT, press "ESC" and "ENTER" key simultaneously to display
any mode.
- 107 -
INSTALLATION & ADJUSTING STVF5
S03 Normal 0
The handicapped operation in group
HANDICAP Handicapped 1
S05
The main(lobby) floor in group operation.
BASIC FLOOR
S06
The rated speed of elevators
E/L SPEED
Immedate 0
S07
Method of forecasting function (lantern)
IMMEDI. ASGN
Arrival 1
S08 USE 1
Hall Call Two Touch Cancel Function
HALL CANCEL
NO USE 0
S09
#1 MAX PERSN ~ the maximum number of persons can be ridden in
S14 each car of the group.
#6 MAX PERSN
S15
#1 UNDER FLR ~
♠the lowest floor of unbalance in the group.
S20
#6 UNDER FLR
S21
#1 MID UBFLR ~
♠the middle unbalanced floor
S26
#6 MID UBFLR
S27
#1 MID 2UBFL ~
♠the 2nd middle unbalanced floor
S32
#6 MID 2UBFL
♠ S15~S20 mode : Setting of unbalance floor in group operation (UNDER FLOOR).
Ex) If a car #2 car stops from B5 floor to 10 floor and a car #1 car stops from B3 floor to 10
floor, a car #1 serves 2 less floors than a car #2 from the lowest floor.
So set '2' in "S15 #1 UNDER FLR" mode and set '0' in "S16 #2 UNDER FLR".
- 108 -
INSTALLATION & ADJUSTING STVF5
♠ S21~S26 mode : LCD vane is not installed for one car but installed for other car (1st).
EX) Set '13', if the group cars stop at 15 floors and one car stops at 14 floors except 13th
floor (no LCD vane).
♠ S27~S32 mode : LCD Vane is not installed for a car #1 but installed for other car (2nd).
EX) Set '5' in S21 Mode and set '13' in S27 Mode, if the group stops at 15 floors and a car
#1 stops at 13 floors except 5th floor and 13th floor.
2) S33~S46 mode
#1 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
#2 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
#3 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
#4 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
#5 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
#6 ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
- 109 -
INSTALLATION & ADJUSTING STVF5
TOP 0000 0000 0011 1111 1111 1111 1111 1111 BOTTOM
S33 TOTAL STOP1 0 0 3 F F F F F
TOP 0000 0000 0111 1111 1111 1111 1111 1111 BOTTOM
S35 #1 STOP FL1 0 0 7 F F F F F
TOP 0000 0000 0111 1111 1111 1111 1111 1000 BOTTOM
S36 #2 STOP FL1 0 0 7 F F F F 8
TOP 0000 0000 0111 1111 1111 1111 1011 1000 BOTTOM
S37 #3 STOP FL1 0 0 7 F F F B 8
TOP 0000 0000 0111 1111 1111 1110 1011 1000 BOTTOM
S38 #4 STOP FL1 0 0 7 F F E B 8
TOP 0000 0000 0111 1111 1111 1111 1011 1111 BOTTOM
S39 #5 STOP FL1 0 0 7 F F F B F
TOP 0000 0000 0111 1111 1111 1110 1011 1111 BOTTOM
S40 #6 STOP FL1 0 0 7 F F E B F
※If stop floors are under 32 floor, "S34,41~46" mode is set all "0" automatically.
3) S47 SAVE INITIAL
- Set '1' for saving data, after checking data of 'S01'~'S46'.
- After setting '1', data of S01~S46 is saved in I/O Board of Group MICOM.
4) M48~M53 mode
- 110 -
INSTALLATION & ADJUSTING STVF5
M53 GROUP M/MAP Check all variable data used in group program.
♠ M49 YEAR/MONTH/DAY
Ex) ‘2004 / 03 / 30’ -> ‘00040330‘
♠ M50 HOUR : MINUTE : SECOND
Ex) '16 : 20 : 45' -> ‘00162045’
- 111 -
INSTALLATION & ADJUSTING STVF5
♠ Ex) '4;008084' means the number of group cars is 4 and each car is at the status :
#1 [4] : Group communication is normal and status is Attendant or Independent.
#2 [8] ; Group communication is normal and status is group operation.
#3 [0] ; Group communication is abnormal.
#4 [8] ; Group communication is normal and status is group operation.
5. Troubleshooting
(1) Is CPU of group control system normal?
- Refer to the table of card rack or ring group control board.
- If CPU led is abnormal after reset, the board should be replaced.
- 112 -
INSTALLATION & ADJUSTING STVF5
Ex)
4 : 0 0 8 4 0 8
be replaced.
- 113 -
INSTALLATION & ADJUSTING STVF5
- 114 -
INSTALLATION & ADJUSTING STVF5
- 115 -
INSTALLATION & ADJUSTING STVF5
UP PEAK * At the time to attend the office, all lifts are waiting for passengers
○
CONTROL in a lobby.
SEPARATE * When many hall calls are registered specified floors, lifts will
○
WAIT CONTROL move to those floors and waiting separately.
AUTOMATIC * When a lift is 80% loaded, it will automatically bypass and other
○
BYPASS lifts are assigned hall calls.
AUTOMATIC
CUT SERVICE * In case of a lift problem or disorder, group cut off the lift
○
IN automatically.
OUT OF ORDER
ENERGY * When building condition is dull, the lifts are restricted to move.
○
SAVING So total electric power of building will be saved.
NONSTOP
* When operator commands nonstop floor service mode, lifts can
FLOOR ☆
be serviced at specified floors.
SERVICE
* When the cut signal is inputted, the lift is cut off from the group
CUT SERVICE ☆
and switched to independent mode.
○ : STANDARD ☆ : OPTION
- 116 -
INSTALLATION & ADJUSTING STVF5
C. TROUBLESHOOT
ERROR CODE :
SAFETY LINE FAULT FLAG : 043CH Ref. Drawing : COL3
F11
<Trouble>
1. If the relay "29" is off because that one of referenced safety switches is cut, the lift
will stop
and cannot operate. (Safety switches can be checked with COL3 of elementary
wiring diagram.)
2. If the DC24V power signal is off, the lift cannot operate. And "F11" will be displayed
also .
- 117 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
Fault of Magnetic Contactor(MC) FLAG : 043BH Ref. Drawing : COL2
F11
<Trouble>
1. If the contactor "MC" is not operate properly, Error "F11" will be displayed.
When the NFB of Control Panel(C/P) is on, contactor "MC" will be on also and
the power supply to inverter with contactor "MC". But the contactor "MC" is not
on or sub-contact of "MC" is not operate properly over 5 sec, the error "F11" will
be displayed and cannot operate the lift.
2. If the contactor "MC2" is not operate properly, the error "F11" will be displayed
and cannot operate the lift.
When the lift stop, contactor "MC2" will be de-energized within 1 sec. But the
contact of "MC2" is not released normally, signal "MC2i "(address : 0130) is
sensed the situation and system will be shut down for safety. ( when the lift
stop, the data of address 0130 should be "00".)
<Ref. Drawing>
1.COL1,COL2,COL4 (MCi : 011F )
2.COL1,COL2,COL4 (MC2i : 0130 )
<Solution>
1. - Check the operation of relay "MCA" on PWR Bd and contactor "MC"
- Check the operation of relay "MCA" with data of address " 01A0".
1) If the relay "MCA" is energized, the data is "01".
2) If the relay "MCA" is de-energized, the data is "00".
3) If the data is not same as above, check the TCB-3 Bd.
2. - Check the operation of relay "MC2A" on PWR Bd, and contactor "MC2".
- Check the contact of contactor "MC2", contact should be operate normal.
-. Check the input signal of "MC2i" with data of address "0130", it should be on
and off according to operation of “MC2".
- 118 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
ANTI-STALL ERROR FLAG :0410H Ref. Drawing : ****
F21
<Trouble>
If the lift run without stop continuously over setting time, it will be emergency stop.
The error "F21" will be displayed, and display of indicator will be flickering.
(Setting time of ANTI-STALL : AUTO ->45sec, INSP -> 15min.)
<Ref. Drawing>
<Solution>
1. Check the operation of brake. The brake should be open and close properly.
2. Check the wearing of rope and sheave of machine.( to check the slip of rope)
3. Check the setting time for ANTI-STALL with data of address "A00E".
If the setting of time is too short, the lift will detecting the ANTI-STALL error with
normal operation.
(When the data is "02", it show 45sec, and "03 show 60sec.)
4. Check the balance weight according to the capacity of load.
If the 50% balance weight is not correct, the rope can slip.
- 119 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
DPRAM ERROR FLAG : 0491H Ref. Drawing : ****
F31
<Trouble>
The connection between M33 Bd and INVERTER DPRAM is not connected properly ,
the lift cannot operate and the error "F31" will be displayed .
<Ref. Drawing>
COL.1
<Solution>
1.Check the connection between CN12 of INVERTER and H6 of M33 Bd.
2.Check the condition of this cable.
3.Check the earth cable of this cable.
- 120 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
Fault of FWD/REV signal FLAG : 0262H Ref. Drawing : ****
F41
<Trouble>
If the lift move without any signals of running and open brake from main controller
(M33Bd).
The lift cannot operate and contactor "MC" will be off
The error "F41" will be displayed.
<Ref. Drawing>
COL1and COL2
<Solution>
1. Check the output signals of M8 module on TCB-3 Bd. (5th and 6th signals)
2. Check the I/O signals (FWD/REV) of inverter with HHT.
When the lift is stop, these signals should be off.
3. Check the operation of relay FWD and REV of TCB-3 Bd.
4. If the relays are normal, check the signal "XZSP" and "XRUN".
- When the lift don't move, the signal “XZSP" & "XRUN" (XZSP: 0115H= 01H,
XRUN: 0114H= 00H)
- When then lift move, the signal "XZSP" & "XRUN" (XZSP : 0115H = 00H, XRUN :
0114H = 01H)
- 121 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
MT_TERMAL/CCS SW ERROR FLAG : 049AH Ref. Drawing : ****
F12
<Trouble>
1. If the motor thermal is operate during running, the lift will be stop at the nearest
floor.
And it cannot start again until the motor is cooled fully. (incase of
AC-GEARLESS motor)
But inspection operation is possible.
2. If the compensation chain is extend down, the switch will be detected and the
lift will
stop at the nearest floor. And the error "F12" will be displayed. (incase of
120m/min only)
But inspection operation is possible.
<Ref. Drawing>
COL.4 (CCS/MT : 0120H)
<Solution>
1. Check the temperature of motor whether the motor is heated fully.
1) Check the line of THI and THC signal.
2) Check the operation of relay "MT". (the data of address "0120" should be "00"
in normal.)
3) Check the current of motor.
4) Check the temperature of machine room.(check the ventilator)
- 122 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
FLOOR ERROR FLAG : 0417H Ref. Drawing : ****
F22
<Trouble>
When the display of floor is "0", and the error "F22" will be displayed.
The lift cannot operate with automatic.
<Ref. Drawing>
COL1,COL7 (H6 DPRAM CABLE)
<Solution>
1. Check the data of MAX FLOOR in inverter and the data of TOP FLOOR (04B1) in
M33 Bd.
These two data should be same.
2. Check the operation of LCD signals.
3. Check the quantity of vane. It should be same as the quantity of floors
4. Check the DPRAM cable between inverter and M33 Bd.
If this cable is near the power cables (R,S,T, U,V,W. or AC220V lines), signals will
be disturbed. And the length of this cable should be less than 2mr.
5. Check the data of address "0145". If the initial operation is finished normal, the
data should be "01". (XHIGH = 0145)
6. Make sure the data of "DPRAM INPUT1" in inverter with HHT is "0001000".
- 123 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE : F42 INITIAL OPERATION ERROR FLAG : 0421H Ref. Drawing : ****
<Trouble>
After initial operation, the error " F42 “ is displayed.
The lift cannot operate with automatic.
<Solution>
1. Check the signals of LCD sensor.
2. Check the data of " TOP FLOOR" of inverter.
3. Check the location of switch DLS/ULS. When the lift is stop at terminal floor level,
switch DLS or ULS is not operated with cam.
- 124 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE : F52 PULSE ERROR FLAG : 0346H Ref Drawing : ****
<Trouble>
When the lift stop at the nearest floor, and the door will be open. After then, the lift
will close the door and move down to bottom terminal floor with 60m/min speed.
The error "F52" will be displayed.
And the lift will operate normal again. Fault "F52" will be cleared by itself.
<Ref. Drawing>
COL1
<Solution>
1. If this error is appeared just after the initial operation.
1) Check the connection of shield cable for encoder.(ground point)
2) Check the damaged part of cable or case for encoder
- 125 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
SERIAL CPU ERROR FLAG : 0436H Ref. Drawing : ****
F33
<Trouble>
The lift cannot operate and error "F33" is displayed.
<Ref. Drawing>
<Solution>
1. Check the data of address "E1C0" .
If the system is normal, the data will increase continuously.
If not, change the M33 Bd.
2. Check the version number of CAN SERIAL program.
- Untill 2006,January, E1D0 = 15, E1D6H = 07 (CAN SERIAL program Ver. = 1.57)
- 126 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
CAN COMMUNICATION ERROR FLAG : 043AH Ref. Drawing : ****
F63
<Trouble>
The lift can operate with inspection only. And the error "F63" is displayed.
<Ref. Drawing>
<Solution>
1. Check the connection between "CM10" of M33 Bd and CT7-3,4 of TCB-3 Bd.
2. Check the connection of T-CABLE (T1) between TCB-3 Bd and OPB-3 Bd.
- 127 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
CHECK SUM ERROR FLAG : 0439H Ref. Drawing : ****
F73
<Trouble>
The lift stop suddenly and the error "F73" displayed.
Also 2nd floor car call lamp will be flickering.
<Ref. Drawing>
<Solution>
1. Check the ground between Car Junction Box and CCB-3 Bd.
Check the fixing nut of CCB-3 Bd.
2. Check the ground of OPB-3 Bd and OPB panel.
3. The spare cables of T-CABLE should be connected to ground point on control
panel.
4 The spare cables of T-CABLE should be connected to ground point on CCB-3 Bd
and CAGE.
5. Check the connector CM10 of M33 Bd and CT7-3,4 of TCB-3 Bd.
6. Check the earth line on distribution box of machine room and control panel.
7. Check the connection between two buss bars on control panel together.
- 128 -
INSTALLATION & ADJUSTING STVF5
<Trouble>
The lift stop suddenly with door open signals.
The error "F14" is displayed. If the door open signal is disappear, the lift will
operated normal.
<Ref. Drawing>
COL4
X41 : 0101H
X40 : 0102H
<Solution>
1. Check the interlock switches at ever floor.( check the gap adjustment between
clutch and release roller.)
2. Check the contactor of gate switch and operation of gate switch .
3. Check the operation of relay "40" and "41".
- 129 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
DOOR JUMPER ERROR FLAG : 041A/BH Ref. Drawing : ****
F24
<Trouble>
The lift cannot operate auto mode, and the error "F24" is displayed.
(If there is some jumper point of interlock or gate switch, the lift will detect it and
stop operation with auto.)
<Ref. Drawing>
COL.4
<Solution>
1. Check the jumper point of interlock switches for all floor.
2. Check the jumper point of gate switch.
3. Check the door open and close limit switch signals.(DOL/DCL)
4. Check the door power signal.
5. Check the relay or contactor "40" and "41".
- 130 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
DCL ERROR FLAG : 042FH Ref. Drawing : ****
F34
<Trouble>
The door of lift will be closed, but it cannot close fully and open again.
And the lift do it 3 times and it will stop with open the door .
The error "F34" is displayed and the lift can operate inspection mode only.
<Ref. Drawing>
COL.6
<Solution>
1. Check the door sill of stop floor.
2. Check the signal of "DCL".
The data of address "0169" should be changed "01" and "00" according to door
open and close.
- 131 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
DOL ERROR FLAG : 0427H Ref. Drawing : ****
F44
<Trouble>
1. The lift cannot open fully and try to open the door 2 times more.
If the lift still cannot open fully, it will move to next floor automatically.
And it will try open the door again.
2. If the door still cannot open fully 2 times more at next floor, the lift will move again
to next floor same as before.
3. If the lift cannot open fully 3 times more, the lift will move to basic floor
automatically and the door open. And error "F44" will displayed and cannot move
auto mode.
<Ref. Drawing>
COL.6
<Solution>
If the door open limit signal does not input to controller until 15 seconds, the lift will
check it at the next floor same as above by itself. So we check the followings.
1. Check the some materials to prevent door opening at the sill of door.
- 132 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
CLOSE_FAULT 1 ERROR FLAG : 042CH Ref. Drawing : ****
F54
<Trouble>
The lift cannot start and error "F54" displayed and registered calls are cancelled.
And the door will open and close several times.
<Ref. Drawing>
<Solution>
If the door close limit signal is on but close signals (gate switch and interlock
switches) are not on, then the car cannot start and this error will be happen.
1. Check the door signals "X40" ,"X41" and " DCL" when the door closed fully.
2. Check the status of relay "40" and "41" on TCB-3 Bd.
3. Check the data of address "0101" and "0102" when the door closed fully.
The data should be "01" all.
4. Check the "DCL" signal with data of address " 0169".
closed fully : "00" others : "01".
- 133 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
CLOSE_FAULT 2 ERROR FLAG : 042DH Ref. Drawing : ****
F64
<Trouble>
The lift cannot start and error "F64" displayed and registered calls are cancelled.
And the door will open and close several times.
<Ref. Drawing>
COL.6
<Solution>
If the door close signals (gate switch and interlock switches) are on all but the door
close limit signal is not on, then the car cannot start and this error will be happen.
- 134 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
CAR BRAKE ERROR FLAG : 03FEH Ref. Drawing : ****
F74
<Trouble> : If the system is applied rope brake or car brake, this error is available.
1. If the lift move with door open and pass the door zone, car brake or rope brake will
operate .
And the lift will be stop and error "F74" will be displayed.
2. If the car brake or rope brake is open for normal operation, but the signal "RBKIN"
is not on.
Then error "F74" will be displayed, and the lift cannot operate.
<Ref. Drawing>
COL.4
<Solution>
1. Check the adjustment of brake and wearing the liner of brake.
2. Check the touching point between release roller and clutch on the way to running.
3. Set the data of address "A400" to "00". to clear the error.
- 135 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
X30B ERROR FLAG : 0404H Ref. Drawing : ****
F15
<Trouble>
The lift cannot move and the error "F15" is displayed.
The MC contactor is de-energized also.
<Ref. Drawing>
COL.1
<Solution>
1. Check the inverter with "HHT" and clear the main reason of error.
If the inverter error is still existed, change the inverter.
2. Check the connection cable between TCB-3 Bd. and inverter
3. Check the connection of main power cables. (such as "U","V","W" and "R","S","T")
And check the building power on normal operation of lift.
- 136 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INVERTER OUTPUT ERROR FLAG : 0419H Ref. Drawing : ****
F25
<Trouble>
The lift move and stop repeat with short distance until it pass the terminal floor.
And the error "F25" is displayed.
<Ref. Drawing>
COL.1
<Solution>
When the lift move without running signal from main controller, this error will be
happen.
And if the speed of lift is higher than zero speed, inverter control the speed of motor
to make zero speed with dynamic breaking.
- 137 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INVERTER SETTING ERROR FLAG : 041EH Ref. Drawing : ****
F35
<Trouble>
The lift cannot start and the error "F35" is displayed.
If the M33 Bd. does received "RUN"(0104 = 01) or "BKS"(0106=01) signals from
inverter for the lift stop, this error will be happen.
<Ref. Drawing>
COL.1
<Solution>
1. Check the connection of connector "CN8" between inverter and TCB-3 Bd.
2. Check the connection of connector "H9" between inverter and TCB-3 Bd.
- 138 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INV. RUN ERROR FLAG : 041FH Ref. Drawing : ****
F45
<Trouble>
The lift cannot start and the error "F45" is displayed.
If the M33 Bd does not received "RUN"(0104 = 00) or "BKS"(0106 =00) signals from
inverter for start, this error will be happen
<Ref. Drawing>
COL.1
<Solution>
1. Check the connection of connector "CN8" between inverter and TCB-3 Bd.
2. Check the connection of connector "H9" between inverter and TCB-3 Bd.1.
3. Check the start signal (FWD/REV) on inverter with "HHT". (signals from M33Bd)
4. Check the start signal "RUN"(0104 = 00) or "BKS"(0106 =00) on M33 Bd.(signals
from inverter)
5. Check the error of inverter with HHT.
6. Check the connection of power cables and check the building power.
- 139 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INV.RUN ERROR1 FLAG : 0420H Ref. Drawing : ****
F55
<Trouble>
The lift stop suddenly on the way to moving. The error "F55" is displayed .
After then the lift can start again with normal. But the main reason is not cleared,
the lift will stop again .
<Ref. Drawing>
<Solution>
If the M33 Bd received signals “SA” (Speed Agree, 0159H=00) or “ZSP(Zero Speed,
0105H =01) from inverter during running.
- 140 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INV. INITIAL ERROR FLAG : 0498H Ref. Drawing : ****
F65
<Trouble>
This is only for SSVF5(MRL) and STVF5-GL(Gearless).
After finished initial operation, the lift will stop at top floor and the error "F65" is
displayed.
The lift cannot operate with auto mode.
( The floor data of Inverter is higher than the data from initial operation .)
<Ref. Drawing>
<Solution>
If the data of "MAX FLOOR" on inverter is not same as the data from initial
operation, this error will be happen.
1. Check the actual floor information.
2. Check the floor information of M33 Bd with data of address "04B1".
3. Check the floor information of inverter with HHT .("MAX FLOOR")
4. Confirm the above two data should be same.
5. Check the vane of LCD in hoistway.
- 141 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
INV. ERROR FLAG : 0499H Ref. Drawing : ****
F75
<Trouble>
This is only for SSVF5(MRL) and STVF5-GL(Gearless).
After finished initial operation, the lift will stop at top floor and the error "F75" is
displayed.
The lift cannot operate with auto mode.
( The floor data of Inverter is lower than the data from initial operation .)
<Ref. Drawing>
<Solution>
If the data of "MAX FLOOR" on inverter is not same as the data from initial
operation, this error will be happen.
1. Check the actual floor information.
2. Check the floor information of M33 Bd with data of address "04B1".
3. Check the floor information of inverter with HHT .("MAX FLOOR")
4. Confirm the above two data should be same.
5. Check the vane of LCD in hoistway.
- 142 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
BRAKE ON ERROR (1) FLAG:0412H Ref. Drawing : ****
F16
<Trouble>
The lift cannot start and the error "F16" is displayed.
And the lift cannot operate until reset the system.
<Ref. Drawing>
COL.3
<Solution>
If the brake open signal (BKOP) is not input to controller when the lift start, the
error "F26" will displayed. And the lift start again. If the lift get same error one more
time continuously,
the lift stop again and the error "F16" is displayed . Also it cannot operate again.
1. Check the brake open switch. The signal should be on and off according to the
operation of brake . (the data of address BKOP = 0103)
2. Check the connection of brake open switch. (COM and NC)
3. Check the operation of brake, and check the adjustment of brake open switch.
4. If the lift has the sub_brake system that is car_brake or rope gripper,
Check the operation sub_brake system, and check the adjustment of
"RBKI"(0118=01/00) input signal
- 143 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
BRAKE ON ERROR (2) FLAG : 042BH Ref. Drawing :
F26
<Trouble>
The lift cannot start and the error "F26" is displayed.
And the lift can start again. If the signal of brake open (BKOP) is become normal, it
will operate. But the signal is not normal again, the lift cannot operate and the error
"F16" will be displayed.
<Ref. Drawing>
COL.3
<Solution>
1. Check the brake open switch. The signal should be on and off according to the
operation of brake . (the data of address BKOP = 0103)
2. Check the connection of brake open switch. (COM and NC)
3. Check the operation of brake, and check the adjustment of brake open switch.
- 144 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
BRAKE OFF ERROR FLAG : 0429H Ref. Drawing : ****
F36
<Trouble>
After the lift stop at level, all registered call is canceled and the error "F36" is
displayed.
This error should be happen with auto mode and inspection mode.
<Ref. Drawing>
COL2,4
<Solution>
1. When the lift stop at some floor, the signal "BKOP" should be off (0103 =01) within
2 seconds.
If not, this error will be happen
1). Check the brake open switch. The signal should be on and off according to
the operation
of brake . (the data of address BKOP = 0103)
2). Check the connection of brake open switch. (COM and NC)
3). Check the operation of brake, and check the adjustment of brake open switch.
2. In EN_CODE, If the contactor "BK" is not operate properly, the error "F36" will be
displayed and
operate the lift.
1). Check the "BK" contactor.
2). Check the connection of contactor.
- 145 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
ULS/DLS ERROR FLAG : 0445H Ref. Drawing : ****
F17
<Trouble>
The lift stop suddenly and the error "F17" is displayed.
The lift cannot start and the error "F17" is displayed. And the lift cannot operate
again.
<Ref. Drawing>
COL.3
<Solution>
If the signal ULS(UP LIMIT S/W :0108H=00) and DLS(DOWN LIMIT S/W :010FH=00) is
all off,
the lift cannot operate or cannot start.
1. Check the contact of switch ULS and DLS.
2. Check the adjustment of switch ULS and DLS.
3. Check the data of address ULS and DLS reference to above data.
4. Check the disturbing part of switch ULS and DLS with some material like as
T-CABLE.
- 146 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
PLU/PLD ERROR FLAG : 0446H Ref. Drawing : ****
F27
<Trouble>
1. The lift stop suddenly at nearest floor, and the error "F27" is displayed.
2. The lift stop at every floor.
This error is happen at auto mode and initial operation mode only.
<Ref. Drawing>
COL.3
<Solution>
If the signal PLUL(PRELIMINARY UP LIMIT S/W :0109H=00) and PLDL(PRELIMINARY
DOWN LIMIT S/W :010EH=00) are on all, the lift cannot operate and this error will be
happen.
- 147 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
LCD ERROR FLAG : 043EH Ref. Drawing : ****
F37
<Trouble>
The lift decelerate very long time and cannot stop at the level. After then the error
"F37" is displayed.
This error is available for auto mode only.
<Ref. Drawing>
COL.4
<Solution>
If the lift decelerate over than 15 seconds to approach the floor level, it will be stop
and the error "F37" is displayed.
1. Check the operation of LCD and vane
2. Check the signals of LCD sensor with data.
( ULA = 0110), (ILU = 0111), (ILD = 0112), (DLA = 0113)
3. Check the operation of encoder.
4. Check the slip of rope.
5. Do the initial operation again to reset the data of floor height.
- 148 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
RE-LEVEL ERROR FLAG : 03C6H Ref. Drawing : ****
F47
<Trouble>
If the lift is not level with door open, the lift will move again to make level.
(re-levelling : optional feature)
But the running time is over than 5 seconds, it will stop and error "F47" is displayed.
<Ref. Drawing>
COL.4
<Solution>
1. Check the LCD sensor of ULA(0110H) and DLA(0113H).
2. Check the location of vane.
3. Confirm the speed of re-level. If the speed is too high , it will move up and down
continuously to stop at the level.
4. Check the operation of brake.
- 149 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
DECEL ERROR FLAG : 0426H Ref. Drawing : ****
F57
<Trouble>
The lift stop at terminal floor, and the error "F57" is displayed.
The registered call will be cancelled all and it will return to auto mode with normal.
<Ref. Drawing>
COL.3,COL10
<Solution>
If the lift decelerate at terminal floor with limit switches such as PLUL,PLUH,PLDL,
and PLDH, the error "F57" is displayed.
- 150 -
INSTALLATION & ADJUSTING STVF5
<Trouble>
1. The lift cannot operate with group control, the error "F18" is displayed.
But the single car operation is normal.
<Ref. Drawing>
COL11
<Solution>
1. Check the parameter of group control.
(The data of address 05C0 is "01" and A002 is "00".
2. Check the RM Bd.
- D6(COM-GREEN) LED should be on. (If it is on, optical cable is normal)
- D7(ERR-RED) LED should be off.( If it is on, optical cable is abnormal.)
3. Check the optical cable. (bended or damaged part)
4. Check the connection of optical cables according to the reference drawing.
5. Confirm the data of address "05C1" is "01". (Group communication is normal.)
6. Data setting
- A002 = "00" : GROUP and RMS(Remote Monitoring System) is available.
- A002 = "01" : GROUP is available.
- A002 = "02" : RMS(Remote Monitoring System) is available.
- A002 = "03" : GROUP and RMS(Remote Monitoring System) is not available.
- 151 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
RMS COMMUNICATION ERROR FLAG : 03D1H Ref. Drawing : ****
F28
<Trouble>
1. The lift cannot operae with CRT(Computer Monitoring System), the error "F28"
is displayed.
But the single car operation is normal.
<Ref. Drawing>
<Solution>
1. Check the parameter of CRT system.
(The data of address 04D1 is "01" and A002 is "00".
2. Check the 24V power of CRT Bd.
3. Check the connection of H1 cable(HIROSE 40PIN) according to the reference
drawing.
4. Data setting
- A002 = "00" : GROUP and RMS(Remote Monitoring System) is available.
- A002 = "01" : GROUP is available.
- A002 = "02" : RMS(Remote Monitoring System) is available.
- A002 = "03" : GROUP and RMS(Remote Monitoring System) is not available.
- 152 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
RUN BY ERROR FLAG : 043DH Ref. Drawing : ****
F38
<Trouble>
<Ref. Drawing>
COL.4
<Solution>
- 153 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
WATER OVER ERROR FLAG : 0497H Ref. Drawing : ****
F48
<Trouble>
1. The lift stop at nearest floor, and cancel the registered call.
And then the lift move up to top floor and open the door.
The error "F48" is displayed.
<Ref. Drawing>
COL.4
<Solution>
If the water level sensor is detect the water in pit, signal WLS is on.
- 154 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
LOAD SETTING ERROR FLAG : 01B4H Ref. Drawing : ****
F58
<Trouble>
This error is available for SSVF5(MRL) and ST5GL(gearless).
The lift have start shock and the error "F58" is displayed on auto mode .
Also the lift can operate on auto/inspection mode with normal.
<Ref. Drawing>
COL7
<Solution>
If the lift is not yet adjust the load setting (LVDP) or CAN communication error is
happen, the error "F58" is displayed.
1. Check the adjustment of LVDP. The data of address "01B4" should be "01".
2. Check the condition of CAN communication between LVDP and M33 Bd, the data
of address "0D83" should be "02".
- 155 -
INSTALLATION & ADJUSTING STVF5
ERROR CODE :
HALL DEVICE ERROR FLAG : 05B4H Ref. Drawing : ****
F68
<Trouble>
The hall call cannot registered at some floor or all floor.
And display of hall indicator disappear. The error "F68" is displayed.
But the lift can operate with car call normally.
<Ref. Drawing>
<Solution>
If there is some error on hall indicator, this error will be happen.
1. Check the condition of indicator.
Check the abnormal indicator with data of address "0DA8" - ODAB" according to
reference manual.
0DA8 : checked indicator form 1st floor to 8th floor.
0DA9 : checked indicator form 9th floor to 16th floor.
0DAA : checked indicator form 17th floor to 24th floor.
0DAB : checked indicator form 25th floor to 32th floor.
ex) 0DA8 ------- 8th 7th 6th 5th 4th 3rd 2nd 1st floor
data" A4 " ----- 1 0 1 0 0 1 0 0
(8 4 2 1) (8 4 2 1)
8+2 = “A” “4“
So, 8th and 6rd, 3rd floor indicators are some error.
- 156 -
INSTALLATION & ADJUSTING STVF5
#SAFETY
LINE ERROR
# X40,X41
#MAG.ON # BRAKE # DUPLEX
*MT_TERMAL ERROR # X30B ERROR
F1 ERROR ON error ULS/DLS COMM.
ERROR (on the ( 5sec.)
#DC24V ( 2times ) ERROR ERROR
operation)
POWER
ERROR
#M33&
* LCD
INV.DPRAM * SERIAL CPU # BRAKE
* DCL_ERROR # INV.SET ERROR ERROR c/p door open
F3 CABLE ERROR BKS◎,RUN◎,30B◎ OFF error
(auto mode only) (auto error
ERROR (89c52) (BRAKING )
mode)
E
R *initial
#FWD/REV *
R ERROR # INV. RUN ERROR water over
F4 SIGNAL * DOL_ERROR RELEVEL
O BKS,RUN,30B◎ error
ERROR ERROR
R
R
A
*
N * PULSE * FLOOR ERROR # INV.RUN ERROR1 run by
F5 CLOSE_FAULT1
K ERROR (MAIN <-> CTB) (speed disagree) error
DCL ◎, 40
#initial
* HALL
ERROR * CTB CPU #INV. init. ERROR
F6 CLOSE_FAULT2 DEVICE
LCD sensor ERROR MAX > init. data
DCL (, 40◎ ERROR
error
# move with
* CHECK SUM #INV. init. ERROR
F7 opening
ERROR MAX < init. data
ROPE BRAKE
F8
NOTE :
# -> CANNOT OPERATION * SERIAL COMMUNICATION ERROR
* -> INSPECTION MDDE IS AVAILABLE ( CCB CPU 1st floor CAGE B/T ON/OFF) => F63 DISPLAY
( OFF
◎ -> ON * CHECK SUM ERROR ( " 2nd floor CAGE B/T ON/OFF) =>
F73 DISPLAY
- 157 -
INSTALLATION & ADJUSTING STVF5
I A 98 A 003 H
FACTORY
EX)H:HYUNDAI
W:WOOJIN
SERIAL NO.
000 ~ 999
PRODUCED MONTH
JAN.~SEP.
A(OCT), B(NOV), C(DEC)
PRODUCED YEAR
EX) 1998 -> 98
2000 -> 00
PRODUCT TYPE
ITEM
EX) INVERTER : I
GATE Bd : G
MAIN Bd : M
- 158 -
INSTALLATION & ADJUSTING STVF5
- 159 -
INSTALLATION & ADJUSTING STVF5
DESCRIPTION
ITEM LABEL NAME REMARK
STVF 1&2 STVF 3&5, FI 4
Multi-purpose control
MU(X2) Selective input 2 Door zone sensor input
input selection
- Multi-speed
HU(X3) Selective input 3 selection, PLUH sensor input
- DI Torque input,
HD(X4) Selective input 4 - Torque Bias switch PLDH sensor input
-Pre-Excitement
signal,
MD(X5) Selective input 5 - Speed limit switch Spare1 input
THI
Thermistor Motor Thermistor
Input Input Terminal
Terminals for motor thermistor TB1
THC
- 160 -
INSTALLATION & ADJUSTING STVF5
VP Encoder V Phase
WP Encoder W Phase
LD1 Load Sensor Input Input terminal of sensor signal to compensate load
Load
Detection
TB1
Load Sensor
LD2
Common
- 161 -
INSTALLATION & ADJUSTING STVF5
- 162 -
INSTALLATION & ADJUSTING STVF5
Control
30B INV. Error Output Contact
Output
30B-30C OPEN : Fault Capacity
Contact
30B-30C CLOSE : Normal : 220Vac
30C INV. Error Common 500mA
- 163 -
INSTALLATION & ADJUSTING STVF5
LCD DISPLAY
2 x 16 (TOTAL : 32CHARACTERS) - Press to enter sub directory
- Press to save data changed
by UP and DOWN keys.
HIVD900 HHT Menu shown in Figure 2.2 is tree structure based. Root directory has monitor
and program modes. Monitor mode has basic, I/O, error and floor data modes. Program
mode has control, interface, motor, and factory modes. Each mode in monitor and program
has its own menu according to the character.
- 164 -
INSTALLATION & ADJUSTING STVF5
- 165 -
INSTALLATION & ADJUSTING STVF5
0 1 M O N IT O R
0 2 P R O G R A M
CURSOR ENTER
0 1 B A S IC
0 2 I/O
Figure 2.4 Moving to a selected sub menu
When you come out to a previously selected menu, press ESC key as shown in Figure 2.5.
0 1 B A S IC
0 2 I/0
CURSOR ESC
0 1 M O N IT O R
0 2 P R O G R A M
Figure 2.5 Moving to a previously selected menu
- 166 -
INSTALLATION & ADJUSTING STVF5
- 167 -
INSTALLATION & ADJUSTING STVF5
→ AUTO-LOAD2
All the data in PROGRAM/02.MOTOR and EL SPEED, MAX RPM, LONGRUN RPM,
INSPECT RPM, CREEP RPM, RELEVEL RPM, DECEL POINT2 in PRPGRAM/01 .
CONTROL are set as standard value automatically by selecting motor in PROGRAM
/03_MOTOR/02_MOTOR_SELECT.
Also the O.S LEVEL in PROGRAM/FACTORY is set as default value automatically by
selecting motor in PROGRAM/03.MOTOR/02.MOTOR SELECT.
※ When you try to change the value of the ‘Control’ and ‘Interface’, you must change t
hat of the ‘02_MOTOR_SELECT’ in advance and then the others are to be changed.※
- 168 -
INSTALLATION & ADJUSTING STVF5
08*ACC
0 .7 2 M /S E C 2
- 169 -
INSTALLATION & ADJUSTING STVF5
3. PARAMETER
3.1 MONITOR
3.1.1 BASIC
DETAILS
ITEM FUNCTION NAME DATA RANGE UNIT
(Chap. 4)
01 HYUNDAI ELEVATOR Program version 4.1.1.1
- 170 -
INSTALLATION & ADJUSTING STVF5
3.1.2 I/O
ST 1&2 ST 3&5
ITEM REMARK
BIT NAME INPUT BIT NAME INPUT
F UP F UP
R DOWN R DOWN
E AUTO(EXT) A AUTO
S RESET U HOU
X Z DZ
1 X1 D HOD
2 X2 I INIC
3 X3 1 PLUL Switch
02 I/O
4 X4 2 PLDL Switch
5 X5 3 PLUH Switch
6 X6 4 PLDH Switch
Y Y -
M 30B M 30B
※ If the bit signal is input, it is set up ‘1’ below the bit name.
3.1.3 ERROR
※ When the fault occurs in the inverter, the fault is displayed orderly. (cf. Section 4.1.3)
- 171 -
INSTALLATION & ADJUSTING STVF5
3.2 PROGRAM
3.2.1 CONTROL
3.2.1.1 STVF 1 & 2
INIT. DETAILS
ITEM FUNCTION NAME DATA RANGE UNIT
VALUE (Chap. 4)
01 EL SPEED 30 ~ 300 90 MPM 4.2.1.1
※ The initial value of the control data is a standard data of the 15KW induction motor.
- 172 -
INSTALLATION & ADJUSTING STVF5
18 MODE 0 ~ 99 0 4.2.1.15
- 173 -
INSTALLATION & ADJUSTING STVF5
3.2.2 INTERFACE
3.2.2.1 STVF 1 & 2
INIT. VALUE DETAILS
ITEM FUNCTION NAME DATA RANGE UNIT
IM SynM (Chap. 4)
01 SPEED LIMIT 0.0 ~ 2400 1500 250 RPM
02 ZERO SPD LVL 0.0 ~ 100.0 5 3 RPM 4.2.2.1
03 SPD AGREE WID 0.0 ~ 100.0 30 30 % 4.2.2.2
04 AO1 SELECT 0~AOSELECTNUM-1 SPEED REF 4.2.2.4
05 AO2 SELECT 0~AOSELECTNUM-1 SPEED FBK 4.2.2.4
06 AO3 SELECT 0~AOSELECTNUM-1 TORQUE REF 4.2.2.4
07 AO4 SELECT 0~AOSELECTNUM-1 TORQUE FBK 4.2.2.4
02_INTERFACE 08 AO1 CENTER -2,500 ~ 2,500 0 0 4.2.2.5
09 AO1 RANGE -2,500 ~ 2,500 2000 200 4.2.2.5
10 AO2 CENTER -2,500 ~ 2,500 0 0 4.2.2.5
11 AO2 RANGE -2,500 ~ 2,500 2000 200 4.2.2.5
12 AO3 CENTER -2,500 ~ 2,500 0 0 4.2.2.5
13 AO3 RANGE -2,500 ~ 2,500 50 100 4.2.2.5
14 AO4 CENTER -2,500 ~ 2,500 0 0 4.2.2.5
15 AO4 RANGE -2,500 ~ 2,500 50 100 4.2.2.5
- 174 -
INSTALLATION & ADJUSTING STVF5
04 AUTO TUNE 0 ~ 99 0 -
04
FACTORY DATA are protected by password to prevent main data from being changed.
FACTORY
※ All motor data are set automatically by selecting motor in PROGRAM /03_MOTOR
/02_MOTOR_SELECT.
※ The table is a standard data of the 15KW induction motor.
- 175 -
INSTALLATION & ADJUSTING STVF5
04 FACTORY FACTORY DATA are protected by password to prevent main data from being changed.
※ All motor data are set automatically by selecting motor in the PROGRAM /03_MOTOR
/02_MOTOR_SELECT.
※ The table is a standard data of the GL3.5TA/GM5TA motor.
- 176 -
INSTALLATION & ADJUSTING STVF5
4. DESCRIPTION OF PARAMETER
4.1 MONITOR
4.1.1 BASIC
4.1.1.1 HYUNDAI ELEVATOR
- Displays program information, version number.
Induction STVF 1&2 HIVD900G Mx.x Synchronous STVF 1&2 HIVD900SS Mx.x
Motor Motor
(Geared) STVF 3&5, FI 4 HIVD900G Dx.x (Gearless) STVF 3&5, FI 4 HIVD900SS Dx.x
4.1.1.4 CURRENT
- The actual electric current which flows into the motor is indicated.
4.1.1.5 VOLTAGE
- The terminal voltage of the motor is indicated.
- 177 -
INSTALLATION & ADJUSTING STVF5
4.1.1.8 FLOOR
- The current floor of the CAR is indicated.
4.1.1.9 CALL
- The current CALL which is register is indicated.
4.1.1.10 MODE
- The current operation mode of the elevator is indicated.
0 : Automatic operation, 1 : Initial operation, 2 : Inspect operation, 3 : PLO operation,
4 : RELEVEL operation, 5 : Fire operation(60m/m), 6 : Operation below 60[m/m], 99 : STOP
4.1.1.11 INITIAL
- It is indicated with ‘1’ if the initialization of the elevator was completed in the normality.
4.1.1.16 DPRAM
- The basic data or important signals for driving an elevator share information with DPRAM.
BIT
7 6 5 4 3 2 1 0
HHT display
angle
DPRAM OUTPUT 1 × × afterinit decelon2 decelon1 ptnout ×
detect
maxfloor maxfloor
DPRAM OUTPUT 2 × × × plodir × watchcp
dn up
※ x : unused bit.
- 178 -
INSTALLATION & ADJUSTING STVF5
※ DPRAM INPUT ※
OPERATION
DATA NAME FUNCTION REMARK
RUN STOP
※ DPRAM OUTPUT ※
OPERATION REMARK
DATA NAME FUNCTION
RUN STOP
afterinit initial operation confirmation 1 0
decelon2 Deceleration2 1 0
decelon1 Deceleration1 1 0
ptnout Speed pattern presence confirmation 1 0
angledetect Motor U-angle measurement operation 1 0 Syn. Motor
plodir PLO operation direction 1(up) 0(down)
watchcp watchdog count of CP 1 0
maxfloordn max floor up confirmation 1 0
maxfloorup max floor down confirmation 1 0
4.1.2 I/O
- The explanation about each bit refers 3.1.2 paragraphs.
- 179 -
INSTALLATION & ADJUSTING STVF5
4.1.3 ERROR
4.1.3.1 ERROR LIST
KEYPAD
ERROR CONTENTS
DISPLAY
Inverter output current is over limited FACTORY /
OVER CURRENT OC FAULT
OC LEVEL
Feedback speed is over limited speed level.
OVER SPEED OVER SPEED
Check PROGRAM/FACTORY/OS LEVEL.
DC link voltage is over the over voltage level.
OVER VOLTAGE OV FAULT
Over voltage level : 780 Vdc
DC link voltage is below the under voltage level.
UNDER VOLTAGE UV FAULT
Under voltage level : 410 Vdc
INVERTER OVER Inverter is overloaded.
INV OV LOAD
LOAD (10 second at torque 250%)
Input of encoder A phase or another phase does
ENCODER BREAK PG BREAK
not come in.
IPM FAULT IGBT FAULT Over current at U+, U-, V+, V-, W+, W-, BR IPM
MEMORY FAULT EEPROM ERR The data is not stored properly in the NV-ROM.
DOUBLE DIRECTION
DOUBLE DIR FWD and REV are inputted at the same time.
ERROR
MOTOR OV
MOTOR OVER HEAT Motor is overheated
HEAT
MOTOR THERMAL The motor thermal sensor was breakdown or not
MTR TH BK
BREAK connected
- 180 -
INSTALLATION & ADJUSTING STVF5
- 181 -
INSTALLATION & ADJUSTING STVF5
- 182 -
INSTALLATION & ADJUSTING STVF5
UNDER VOLT
yes
yes
yes
no
- 183 -
INSTALLATION & ADJUSTING STVF5
- 184 -
INSTALLATION & ADJUSTING STVF5
PG BREAK
yes
- 185 -
INSTALLATION & ADJUSTING STVF5
VERSION ERR
yes
PROGRAM/FACTORY/23.IN
IT EEPROM has to ON.
- 186 -
INSTALLATION & ADJUSTING STVF5
- 187 -
INSTALLATION & ADJUSTING STVF5
- 188 -
INSTALLATION & ADJUSTING STVF5
4.2 PROGRAM
4.2.1 CONTROL
4.2.1.1 EL SPEED
- Elevator rated speed is input.[MPM]
- 189 -
INSTALLATION & ADJUSTING STVF5
- 190 -
INSTALLATION & ADJUSTING STVF5
3. Setting method
① In the no load
- Adjust in 15% load.
- Enter the reasonable value in 20. TQ BAIS LV 1R for the elevator going down.
- Enter the reasonable value in 18. TQ BIAS LV 1F for the elevator going up.
② In the balance
- The torque bias value does not apply.
- 191 -
INSTALLATION & ADJUSTING STVF5
3. Setting method
① In the no load
- Adjust in 15% load.
- Enter the reasonable value in 20. TQ BAIS LV 1R for the elevator going down.
- Enter the reasonable value in 18. TQ BIAS LV 1F for the elevator going up.
② In the balance
- The torque bias value does not apply.
- 192 -
INSTALLATION & ADJUSTING STVF5
② In order to start the setting the DIP1 in the M33 board must be placed on the data writing
mode, and enter 01 in the address 01B0 .
③ In order to set the no load the CAR has to be no-load, and enter 01 in the address 01B1.
After 10 seconds, the DIP1 in the M33 board is placed on the data reading mode and
examine the data of the address E1B2. It is the normality if 20.
④ In order to set the 50% load the CAR and CWT has to be the balance, enter 01 in the
address 01B2 and then wait 5 minutes. Also examine the data of the address E1B2 after
above 10 seconds it waits. It is the normality if 52(±1).
⑤ Read the MONITOR /TORQUE BIAS value in HHT of the inverter. Enter this value in
CONTROL/16. TQBIAS OFFSET as it is.
⑥ Check if the MONITOR /TORQUE BIAS is 0. If not 0, add it to the CONTROL/16. TQBIAS
OFFSET. If not yet 0, add it to the CONTROL/16. TQBIAS OFFSET repeatedly until the
MONITOR /TORQUE BIAS is 0.
⑦ Wait the 5 minutes until the rubber is demobilized if 16.TQBIAS OFFSET setting is
completed,.
- 193 -
INSTALLATION & ADJUSTING STVF5
4.2.1.15 MODE
- The currently mode of the elevator operation is indicated.
0 : Automatic operation, 1 : Initial operation, 2 : Inspect operation, 3 : PLO operation,
4 : RELEVEL operation, 5 : Fire operation(60m/m), 6 : Operation below 60[m/m], 99 : STOP
- 194 -
INSTALLATION & ADJUSTING STVF5
4.2.2 INTERFACE
4.2.2.1 ZERO SPEED LEVEL
- The output (zero speed) is switched off when the elevator speed is under setting
speed(ZERO SPEED LEVEL), Otherwise the output is switched on.
4.2.3 MOTOR
4.2.3.1 INVETER SELECTION
- This data in MOTOR\01.INVERTER SEL selects the current inverter capacity.
The SCALE IS and O.C LEVEL in PROGRAM/04.FACTORY are set automatically by
selecting the inverter capacity in PROGRAM/03.MOTOR/01.INVERTER SEL mode during
this period.
- 195 -
INSTALLATION & ADJUSTING STVF5
② DATA SETTING
- Run the motor the above 1 rotating with FWD direction.
- Enter 1 in MOTOR/14.KNOW ANGLE and check if MOTOR/15.U ANGLE is or not.
(Examine if the inner value of the motor terminal matches this MOTOR/15.U ANGLE.)
- Check the normal operation running to up or down at Inspection speed, and record
MOTOR/15. U ANGLE to be used for the later user.
- 196 -
INSTALLATION & ADJUSTING STVF5
5. DESCRIPTION OF FUNCTION
5.1 STVF 1 & 2
Long run, short run, creep, and inspection speeds are needed in a standard elevator
application. Those speeds can be selected by combination of Speed①,②, and ④.
z Data range : 0 2400 rpm
z Each speed can be programmed in PROGRAM/CONTROL mode.
○ ○ ○ Stop - -
○ ○ ● Zero speed - -
Initial operation
○ ● ○ (= Inspection Yes None
speed)
○ ● ● Creep operation Yes Yes
● ○ ○ Inspection
Yes None
operation
●: On(Close), ○: Off(Open)
The basic velocity pattern for the elevator operation can be divided into eleven modes and
differently applied to velocity pattern according to the drive variety
- 197 -
INSTALLATION & ADJUSTING STVF5
R ead y (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
※ Eighth mode(creep pattern) can’t be used unless the user purposely tunes a specific value of
the inverter.
The velocity patterns according to the drive variety are listed in following Table
Pattern
HHT READY 1 2 3 4 5 6 7 8 9 10
Operation mode
AUTO 0 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
INITIAL 1 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
INSPECT 2 ○ ○ ○ ○ ○ ○ ○
PLO 3 ○ ○ ○ ○ ○ ○ ○ ○ ○
RELEVEL 4 ○ ○ ○ ○ ○
FIRE 5 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
LOWSPD 6 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ELD 7 ○ ○ ○ ○ ○ ○ ○ ○ ○
- 198 -
INSTALLATION & ADJUSTING STVF5
- 199 -
INSTALLATION & ADJUSTING STVF5
range remark
15 JM[kgm] 0.1-2.0
2) If the value of motor parameter after auto tuning is beyond the range on the above list . please
redo “AUTO TUNING”.
3) If the value of motor parameter is beyond the range, the inverter should show “TUNING ERR”.
- 200 -
INSTALLATION & ADJUSTING STVF5
- 201 -
INSTALLATION & ADJUSTING STVF5
- 202 -
INSTALLATION & ADJUSTING STVF5
03 THERM SELECT ON ON ON ON ON ON ON
AUTO
04 0 0 0 0 0 0 0
TUNE
MOTOR
05 5.5 7.5 11 15 18.5 22 30
CAPACIT [kW]
RATING A
07 14.5 18.5 25.6 35 43 51 64
[Arms]
MOTOR
08 4 4 4 4 4 4 4
POLES [P]
PG PULSE
09 1024 1024 1024 1024 1024 1024 1024
[PPR]
WRPM
10 1500 1500 1500 1500 1500 1500 1500
BASE [RPM]
WRPM MAX
11 2000 2000 2000 2000 2000 2000 2000
[RPM]
FLUXDRE
12 0.88 0.87 0.7 0.7 0.75 0.77 0.75
RATE [A]
13 IQSE RATE [A] 16.2 22.7 32.8 43.0 56.9 63.22 77.0
14 IDSE RATE [A] 12.6 12.89 15.6 20.6 21.19 22.19 38.56
- 203 -
INSTALLATION & ADJUSTING STVF5
GL/M2.5TA 4.5 235 12.8 24 10000 95.5 18.1 20 0 3000 46.650 2.033 1.44
GF17A 3.7 227 10.8 32 10000 95.5 15.3 20 0 3000 40.3 1.055 1.39
GL2.5TA5 3.7 235.9 10 24 10000 95.5 14.1 20 0 3000 42.8 2.072 1.38
GS20A 4.6 295 12.8 24 10000 95.5 18.1 20 0 3000 36.2 1.818 1.38
GS25A 6.2 275 18.5 24 10000 95.5 26.2 20 0 3000 25.4 1.184 1.41
GF25A 6.2 221 16.5 32 10000 95.5 23.3 20 0 3000 23.3 0.494 1.41
GT25A 6.2 320 16 32 10000 95.5 22.6 20 0 3000 29.9 0.859 1.55
GF35A 7.1 242 19.5 32 10000 95.5 25 30 0 3000 25.3 0.271 1.31
GS35A 7.1 253 18.5 24 10000 95.5 26.2 30 0 3000 27.2 1.271 1.41
GT35A 7.1 318 16 32 10000 95.5 22.6 30 0 3000 27.1 0.728 1.61
GL3.5TA/GM5TA 7.5 312 17.8 24 10000 95.5 25.2 45 0 3000 32.5 1.15 1.72
GL3.5TA5 7.5 250.6 17.8 24 10000 95.5 24.7 30 0 3000 25.8 0.985 1.53
GF17B 6.5 193.5 21.5 32 10000 167 25 30 0 3000 10.1 0.264 0.7
GL2.5TB5 6.5 250.6 21.2 24 10000 167 25 30 0 3000 18.0 0.959 0.9
GL/M2.5TB 8 271 22.3 24 10000 167 31.5 30 0 3000 15.53 0.667 0.83
GF25B 10.8 232 26.6 32 10000 167 37.6 40 0 3000 8.72 0.187 0.87
GT25B 10.8 317 24 32 10000 167 33.9 40 0 3000 10.9 0.301 0.94
GS180L 11 248.2 27.5 24 8192 209 38.9 40 0 3000 8.12 0.524 1.1
GS35B 12.4 315 31 24 10000 167 43.8 40 0 3000 10.4 0.475 0.86
GT35B 14.1 305 32 32 10000 191 45.24 50 0 3000 6.7 0.182 0.8
GF35B 15 235 35.8 32 10000 191 50.6 50 0 3000 5.88 0.12 0.77
GL3.5TB/GM5TB 15 295 35.5 24 10000 191 50.2 50 0 3000 8.11 0.288 0.86
GL3.5TB5 15 238.4 35.8 24 10000 191 50.6 50 0 3000 6.55 0.242 1.06
- 204 -
INSTALLATION & ADJUSTING STVF5
z PROGRAM/MOTOR
1. INVERTER SEL, 2. MOTOR SELECT
10. WRPM BASE, 15. JM
z PROGRAM/CONTROL
1. EL SPEED, 2. MAX RPM
INDUCTION 3. LONGRUN RPM, 10. TQ BIAS SELEC
MOTOR 11. TQ BIAS LV 1F, 12. TQ BIAS LV 2F
13. TQ BIAS LV 1R, 14. TQ BIAS LV 2R
17. MIN LENGTH, 20. MAX FLOOR
22. FWD DIRECTION, 23.DPRAM TQ USE
z PROGRAM/FACTORY
2. SCALE VDC
z PROGRAM/MOTOR
3. INVERTER SEL, 2. MOTOR SELECT
11. KNOW ANGLE, 12. U ANGLE
15. JM
z PROGRAM/CONTROL
SYNCHRONOUS 1. EL SPEED, 2. MAX RPM
MOTOR 3. LONGRUN RPM, 10. TQ BIAS SELEC
15. TQ BIAS GAIN, 16. TQ BIAS OFFSET
17. MIN LENGTH, 20. MAX FLOOR
22. FWD DIRECTION, 23.DPRAM TQ USE
z PROGRAM/FACTORY
4. SCALE VDC
- 205 -
INSTALLATION & ADJUSTING STVF5
5.5/30 Kw 30 Ω
900SS/GT
(Synchronous 7.5 Kw 15 Ω
Motor)
11/15 Kw 24 Ω
2. SMPS Board
HIVD900 SMPS board is classed as the induction motor type and the synchronous motor
type, and 900G 30kw type is equal to 700G 30kw type.
900SS/GT
(Synchronous 5.5/7.5/11/15 Kw H9G15SF SCN1 (6Pin)
Motor)
- 206 -
INSTALLATION & ADJUSTING STVF5
3. SENSING Board
HIVD900 SENSING board is classed as 5.5/7.5kw type and 11/15kw type, and it is not used in
900G 30kw type.
5.5/7.5 Kw 50A(CT1,2,3)
11/15 Kw 100A(CT1,2,3)
4. Gate Board
HIVD900 Gate board is classed as the induction motor type and the synchronous motor type,
and classified according to the inverter capacity.
① ⑪
② ⑫
③ *
* *
*
- 207 -
STVF5 SERIES ELEVATOR MANUAL
December. 2007
Revision 3