See Richarson Cost Estimating Manuals, 1988 / Section 100 - 240 / for Details, p4&5
Capacity Factor = f(X&Y) = CF = 4.13 Limited from 1 to 6
Cooling factor , K = f(CF & TWB) 73.20 Limited from 0 to 160
B Factor=K*USGPM*1E-06= 7.69 Out Of Range Limited from 0.5 to 4.0
If "Out Of Range, Select Mult 10 No. of Units
B Factor per Unit = 0.77 In Range Limited from 0.5 to 4.0
Installed Cost of Tower = $2,920,376 1987 $U.S. in the USA (No Basin Cost)
Total Fan HP = 1,838 HP/Unit = 184
Basin Area in sf = 27,049 Area/unit = 2,705
Installed Pumps+Elec Motors = $1,974,194 1987, $U.S. Installed = 3.2 x PC
Basin Installed Cost = $665,148 1987, $U.S. FEI = 344.1
Total Installed Cooling Tower $5,559,718 1987, $U.S. FEI = 344.1