Professional Documents
Culture Documents
1. Start ARIavCAD, and the Project Settings screen opens. When opening the
first time, the default data and units appear. After that, every time ARIavCAD
is started, the last project saved opens.
2. Click on “Project”, and a dropdown menu will be released.
3. Click “New project”, and the Project settings screen opens with the default
values. Default units and data are the ones used in the last saved project.
1
4. Enter Data.
a.
b.
c.
2
f.
j.
3
actual cost increase due to the manifold structure (as percentage of the
cost of the valves themselves), or it could be a “fine” for using a
manifold, which would give preference of a chosen magnitude to
avoiding manifolds.
In this case, we enter a 5% surcharge, which is fairly low.
l.
By using the drop-down menu, the ARIavCAD user can determine the
maximum number of air valves to be allowed in a single manifold. The
possibilities offered are from 2 to 10. This is an actual boundary, and
not just a preference. ARIavCAD will not place any more air valves in
the manifold, than entered here. If the required flowrates ,as calculated
by ARIavCAD, are higher than the largest allowable manifold, of the
largest applicable (right type, right pressure rating) air valve, can
deliver, ARIavCAD will announce that no applicable air valve was
found. When this happens, a larger number should be chosen from the
drop-down menu, for the largest allowable manifold size.
It must be kept in mind that the larger the allowable manifold, the
longer it takes for ARIavCAD to complete the analysis, since more
iterations are required. It is wise to start with a smaller manifold and
enlarge it according to the needs of the particular project.
In this case, lets enter 2.
m.
4
of a given size is assumed, and required air intake capacities for
vacuum protection are determined by calculating the flow through this
drainage valve. In Virtual Drainage Analysis, the ARIavCAD user can
allow virtual drainage valves to represent pipe ruptures the size of
these drainage valves. The location and size of these virtual drain
valves can be determined and entered manually by the user, or can be
located by the software and sized in accordance with a predetermined
percentage of the pipe diameter at each location. This percentage
(ratio) is determined by the user and entered here.
Lets enter 50%.
o.
There are a number of ways to enter data in the Profile Data table.
5
Manual data entry
6
2. Click “Insert Station”.
…and press the Enter key until the table reaches the length you desire.
The table can be extended at any time in the same manner.
Data source:
Station ID Accumulated Length Elevation Diameter Flow Control Component Drainage Valve Diameter
0 0 75 300 5
1 100 90 300 0
2 150 80.8 300 0
3 150 95 300 0 Flow control components:
4 246 60 300 0 1 Drainage valve
5 351 95 300 0 2 Isolating valve
3 Drainage valve + Isolating valve
4 Reservoir
7 5 Pump station
6 500 55 300 0
7 550 103 300 0
8 680 92 300 0
9 791 97 300 0
10 800 100 300 0
11 824 65 300 0
12 855 90 300 0
13 914 77 300 0
14 950 85 300 0
15 1020 55 300 0
16 1080 75 300 0
17 1098 74.8 300 0
18 1120 76 300 0
19 1151 65 300 0
20 1180 44 300 3 250
21 1250 97 300 0
22 1287 106 300 0
23 1310 125 300 0
24 1384 180 300 0
25 1977 201 300 0
26 2251 158 300 0
27 2514 134 300 0
28 3125 122 300 0
29 3481 208 300 0
30 3597 158 300 0
31 3915 215 300 0
32 4200 143 300 0
33 4580 97 300 1 250
34 4891 110 300 0
35 5580 99 300 0
36 6810 55 300 0
37 7820 43 300 0
38 8036 20 300 1 250
39 9520 95 300 0
40 10020 110 300 0
41 10535 150 300 0
42 10865 145 300 0
43 12630 165 300 0
44 12965 97 300 0
45 13510 120 300 2
Station ID Accumulated Length Elevation Diameter Flow Control Component Drainage Valve Diameter
46 13925 155 300 0
47 14587 198 300 0
48 15832 92 300 0
49 16587 55 300 0
50 18979 175 300 0
51 20350 42 300 0
52 24235 42.2 300 0
53 24310 35 300 1 250
54 24825 57 300 0
8
55 25135 77 300 0
56 25698 125 300 0
57 26587 158 300 0
58 26854 195 300 0
59 28521 220 300 0
60 29025 76 300 0
61 29325 224 300 0
62 29821 95 300 0
63 29964 238 300 0
64 30155 157 300 2
65 30541 125 300 0
66 30947 103 300 0
67 31125 98 300 0
68 31598 130 300 0
69 31687 165 300 0
70 31987 199 300 0
71 32015 220 300 0
72 32165 210 300 0
73 32687 212 300 0
74 32897 221 300 0
75 32987 245 300 0
76 33261 204 300 0
77 33935 165 300 0
78 33997 169 300 0
79 34215 124 300 0
80 34567 95 300 1 250
81 34987 156 300 0
82 35104 148 300 0
83 35256 190 300 0
84 35897 224 300 0
85 35998 220 300 0
86 36158 201 300 0
87 36792 135 300 0
88 36952 124 300 0
89 37124 155 300 0
90 37358 120 300 0
91 37861 148 300 0
92 37998 168 300 0
93 38015 200 300 0
94 38298 157 300 0
Station ID Accumulated Length Elevation Diameter Flow Control Component Drainage Valve Diameter
95 38586 135 300 0
96 38768 172 300 0
97 39102 165 300 0
98 39354 185 300 0
99 39587 220 300 0
100 39867 216 300 0
101 40012 230 250 0
102 40215 225 250 0
103 40687 255 250 0
9
104 41562 155 250 0
105 42010 210 250 0
106 42802 230 250 0
107 42902 245 250 0
108 43085 240 250 0
109 43263 250 250 0
110 43687 256 250 0
111 43897 260 250 4
If a name followed by a number is entered in the first Id cell, in each new row,
the name and its Id number will progress automatically.
10
Back to the data source:
11
Importing Data From Excel
12
2. Click Browse
and find the Excel file you wish to import. Make sure that the first row in the
Excel sheet consists of the column headings, and that the data is directly
below that (without empty rows).
13
5. Click the dropdown for distance
And choose the type of distance data provided by data source (Sec. Distance =
sectional distance; Acc. Distance = accumulated distance). In this case Acc.
Distance.
14
7. Click OK
And watch the counting of the number of stations recorded (Records
imported).
The profile data is imported from the Excel file to the ARIavCAD Profile Data table.
From this point on, all procedures are the same, no matter how data was entered up
to this point.
15
Since Id cannot be 0, change the first Id from 0 to A.
The information included in the basic profile table, up to now, includes only the basic
data of distances and elevations. It does not include any information on the pipes used in
the project, on pumps and/or reservoirs, on accessories along the pipeline, on flow rates
and pressure, etc.
Since pipe characteristics and properties can change along the project alignment, data
entry is done in sections.
This project was originally analyzed using the A.R.I. Plan software, and this is its basic
data:
16
1. Right click the mouse while pointing in the row where the Section begins
2. Click Section 1
17
a. The name of the section can be changed by entering a new name.
18
d. Leave “New” for Pipe age.
19
f. The pipeline in this section can be buried or above ground: checked =
buried, unchecked = above ground. We will leave it checked for buried.
3. Click OK
20
In Station 101, pipe diameter changes from 300 mm to 250 mm, so we have to
enter a new section.
In ARIavCAD all flow components and accessories are objects that include icons,
pictures, and data. In order to enter a component or accessory in the profile data table, it
must first be dragged from the library, and then, some additional data must be entered for
it.
21
1. Drag a pump to the Accessories column of the first station.
At the beginning of the pipeline, the flow rate and the pressure of the pump
are the initial flow rates and pressure of the system, from which the starting
point of the hydraulic gradeline is determined.
3. Input data
a. According to the data source, the initial operating flow rate is 350 m3/h.
Enter 350 for Flow Rate.
b. We assume an initial pressure of 12 bar. Enter 12 for Pressure.
c. In this case, there is only one pump in the pump station, so it is “Inline”. If
there are more than one pump in the station, they could be installed in
22
series (one after the other) or in parallel. A pump installed in series is
inline, and a pump installed in parallel is not inline.
Leave the check mark on Yes for inline.
4. Click OK
In most cases, it is a common and good practice to install a check valve after a pump.
7. Click the check valve icon in the Flow control accessories dialog box
8. Enter Data
a. The diameter of a check valve is usually the same as the pipeline on which
it is installed. Since the pipeline diameter is 300 mm, enter 300 for
Diameter.
b. Since we do not know the head loss coefficient for this particular check
valve, we will use the default check valve head loss coefficient of 0.2.
Enter 0.2 for Head loss coefficient.
23
At Station 20, there are isolating valves and a drainage valve, in order to allow the
draining of either or both sides of the drainage valve.
9. Drag two Isolating valves and a drainage valve to the Accessories cell of
station 20
24
The order in which accessories are installed is very important. Here, one isolating valve
should be upstream from the drainage valve, and one downstream from it. This is so the
upstream and downstream sections could be drained separately. The order in which the
Accessories appear in the Flow control accessories dialog box is the order they are in the
field. In the case above the order is wrong, but it can be changed.
10. Mark the drainage valve in the Flow control accessories dialog box
a. The diameter of the isolating valve is the same as the pipe, 300 mm. Enter
300.
25
b. We do not know the exact Head loss coefficient of the isolating valve, so
we will leave the 0.7 default value.
14. Mark and enter data for the second isolating valve the same as step 12
above
15. Click OK
16. Drag a drainage valve to the Accessories cell of Station 33 and follow
steps 10, 13, and 15 for this station.
26
18. Drag an isolating valve to the Accessories cell of Station 45 and follow
steps 10, 12, and 15
a. For components that are not at the start of the pipeline being analyzed,
“Flow Rate” actually means the change in flow rate between the upstream
side of the component and the downstream side. Here, there is no
downstream to the reservoir, since this is the last station in the project, so
we leave 0 for flow rate.
27
b. We assume free flow into the reservoir, so the water level is taken to be
the same as the pipe elevation. Enter 260.
23. Click OK
This was not in the original project, but for this exercise, lets assume there is a pipe
connection at Station 101, where water flows out of the main at a flow rate of 20 m3/h. A
connection at which water enters or leaves the pipeline being analyzed is considered by
ARIavCAD to be a “Side orifice”.
The direction of flow through a side orifice is very important. When the flow
direction is out of the pipeline analyzed, the flow rate is negative because the
28
downstream flow is lower than the upstream flow. If the flow is into the pipeline
analyzed, the flow rate is positive because the downstream flow is higher than the
upstream flow. Again, the flow rate here refers to the change in flow rate in the
pipeline being analyzed.
a. Since the direction of the 20 m3/h flow at this side orifice is out of the
pipeline, enter –20.
b. The pressure (or head) in the pipeline, downstream from a pipe connection
(side orifice) depends on the pressure in the pipe connecting to the
pipeline.
If the pressure in the connecting pipe is higher than the pressure in the
main pipeline, its pressure determines the downstream pressure. If the
pressure in the connecting pipe is lower than the pressure in the main
pipeline, the main pipeline continues to determine the pressure
downstream.
If the pressure in the connecting pipe is lower than the pressure in the
main pipeline, which means that the flow is out of the main pipeline, than
this pressure has no effect on the ARIavCAD analysis, since it does not
directly effect the downstream pressure significantly.
If the pressure in the connecting pipe is higher than the pressure in the
main pipeline, which means that the flow is into the main pipeline, than
this pressure effects the ARIavCAD analysis, and it directly effects the
downstream pressure significantly (actually, determines it).
In our example the flow through the side orifice is from the main pipeline
out, so the pressure in the connection to the side orifice is not significant
to the ARIavCAD analysis. Therefore, since we do not know what the
actual pressure is, we will leave 0 for the side orifice pressure.
c. Since we do not know what is the actual head loss coefficient of the side
orifice, we will leave the default value of 0.1.
29
1. Click Analyze
The Analysis dialog box offers a number of alternative criteria for analysis.
The ARIavCAD user can choose to perform only Fill rate analysis, or any combination
of analysis types and/or criteria offered.
30
1. Fill rate analysis is the basic analysis that ARIavCAD always performs. In
this analysis ARIavCAD uses the fill rate velocity entered in the Project
Settings to determine the air discharge flow rate required to enable this
velocity. The air discharge flow rate required is equal to the pipe filling flow
rate.
2. Drainage analysis determines the air intake capacity required to prevent
damages caused by vacuum and down-surge, during pipe drainage through
drainage valves. It is possible to simulate pipe rupture by the use of virtual
drainage valves that represent ruptures of given sizes. A virtual drainage
analysis is actually a simulated pipe rupture analysis for ruptures of up to the
size of the virtual drainage valves. Virtual drainage valves, like real drainage
valves, can be entered manually by dragging from the components library to
the profile data table and entering its data, or:
3. By marking the Automatic virtual check box, ARIavCAD will automatically
place virtual drainage valves, sizing them according to the ratio entered in the
Project settings.
4. Burst analysis determines the air intake capacity required to prevent damages
caused by vacuum and down-surge, during free-flow pipe drainage through a
full diameter pipe burst. Since the results of this analysis can sometimes be
extreme, the user can determine a partial air intake capacity expressed as
percentage of the actual burst analysis calculated requirement (see Burst
Ratio, page 4).
5. When Water column separation is chosen, ARIavCAD locates sites of
probable water column separation occurrences due to sudden flow stoppages
(power failure, rapid valve closure, etc.), and places air valves, in these
locations. These air valves are sized to admit air into the pipeline at a rate
equal to the operational flow rate of the pipeline, in order to prevent damages
caused by vacuum and down-surge, as well as limiting the possible
consequent upsurge, resulting from column separation and, at times, column
return.
6. Choosing Remove excessive air valves will filter out some of the less critical
air valves otherwise assigned by ARIavCAD.
7. Though ARIavCAD provides basic protection against down-surge and even
for upsurge, the software does not perform actual surge analysis. Since most
surge analysis softwares do not design hydraulic systems, but only analyze
existing or planned systems, ARIavCAD is a great tool for pre-surge-analysis
design and can fit perfectly with existing surge software, such as KY Pipe’s
Surge2000 in finding efficient surge solutions.
31
For our first analysis we will run a combined analysis, which includes Fill rate
analysis, Automatic virtual plus actual Drainage analysis, and water column
separation. We will deactivate the filtering mechanism for the first run.
2. Click Start
The different stages of the analysis can be followed by watching the green progress bar.
32
Pay attention to the comments appearing in Information section. In this particular project,
no critical or important information appears, but quite often, there are important
comments that should be reviewed.
Clicking on Close will open the Profile data screen, showing the profile table with the
components (air valves and virtual drain valves) entered by ARIavCAD.
At the head of the report, below the legend, appears the full profile plot of the pipeline,
including the hydraulic gradeline and system flow components (accessories). At the
default x-y scale (1x10), it may be difficult to distinguish the smaller elevation changes
or other details. The scale can be changed separately for the x and/or the y axis.
33
4. Change the y-scale from 10 to 20
It can be very difficult to see details when viewing the full pipeline. It is possible to add
profile views, and in each view to emphasize a different part of the pipeline.
5. Click Add graph, and scroll down to the new profile view
34
6. Click the arrow next to Zoom to open the drop-down zoom menu, and click
Zoom window
8. Click Pan or press mouse wheel, and drag the enlarged area to the
desired position within the graph (Pressing wheel or middle button on mouse and
dragging replaces clicking Pan)
35
9 Click Zoom, choose Zoom real time, and drag and pan to the desired size and
position (drag left mouse for size, drag mouse wheel for position) (Zoom all
returns the full profile - double click on the mouse wheel or middle button =
Zoom all)
10. Add graphs, as needed, and enlarge critical sections of the pipeline, by
following steps 5 to 9
11. Clicking Select, and then clicking on an air valve icon, will display data
and picture of the particular air valve and station
36
12. Scroll down in the report. Below the graphs, appears a station by station
table with data and accessory icons for each station
13. At the end of the table, appears a summery, listing the different types of
valves and their number in this project
37
14. Clicking Expand will enlarge the accessory icons and will add more detail
in the Accessories column (Clicking Collapse will return the original style)
15. Removing the check mark from Long version will eliminate all stations in
the report that do not have any accessories This function is very important
in projects with many stations.
38
16. Clicking Close will return us to the Profile data screen where all the
accessories designated by ARIavCAD now appear.
17. Right click in the table area, and a dialog box will appear
39
19. Click Project settings to enter the window, and then click View report to
return to the report WITHOUT RUNNING ANALYSIS AGAIN
Virtual drain valves were removed from the report, leaving only real drain valves.
Virtual drain valves were removed from the report table, as well.
40
20. Return to the Profile and click in the Accessories column at Station 20
The Flow control accessories dialog box opens.
In the Flow control accessories dialog box we can edit some of the properties
and characteristics of the accessories, including their position in the station. In
this particular example, for instance, the drain valve should be between the
two isolating valves.
21. Light up Drainage valve, and click Move down twice
41
Since the pipeline rises from Station 20, 136 ft to the next air valve, there is a
very slim chance, if any, that there will be a significant water column
separation down-stream from the isolating valve. Therefore, the air valve
down-stream from (after) the isolating valve can be removed
22. Light up the last K-012 air valve, click Remove, and click OK
All changes were verified (by clicking OK) and, in the profile data table, the
drain valve of Station 20 was moved to between the two isolating valves and
the last air valve was removed.
42
23. Return to Project settings and click View report to return to the report
25. Click Print and choose Microsoft Office Document Image Writer (or
Adobe pdf) instead of a printer and save with other ARIavCAD reports
43
25. Click print, this time choosing a printer, and print a report.
Now, you have a saved digital copy and a printed paper-copy of this particular analysis
report of this project. You can go back and try a different analysis of the same project, for
comparison. You can also send a copy of the ARIavCAD project file to someone else
who has the ARIavCAD software by following the following steps:
The person receiving the project file can save it to his hard disk or other dada disk, and
open it with his ARIavCAD. After opening ARIavCAD the person receiving the project
file can:
44
4. Click View report to see the analysis performed by the sender (only the main graph
will be seen – without the zoomed-in graphs).
You can accept the report and analysis or you can make changes and analyze the
project any way you wish, by following instructions above.
45