You are on page 1of 10

Doc Ref.

KPJB-
PT.KOMIPO PEMBANGKITAN JAWA BALI
PLTU TANJUNG JATI B UNIT #3&4 Form
KPJB-
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

No. Doc ITRN-61401-03-2014-03 Date 26 March 2014 System Dewatering System

Inspecte
Subject Reviewed
SR No. 1008434, 100827 Approved
and 1008169 Reclaim water tank pump A & B
d by by by

Trouble Reclaim water tank A & B noise and vibration high (00DS-P978A/B)
Equipment

Occurrence 24 March 2014, 13 March 2014, 4 March 2014


Date

Operation Operation Status


Status Reclaim Pump
Operation Status
Unit A Unit B
Noise √ √
Vibration √ √
Temperature √ √

Bearing ( SKF6310 / C3 )
Equipment Unit A Unit B
ND NDE ND NDE
Bearing
Damage Damage Damage Damage

Oil Seal (Ø=50 72.12)


Equipment Unit A Unit B
ND NDE ND NDE
Oil Seal
Damage Damage Damage Damage

Mechanical seal (Ø=50 72.12)


Equipment Unit A Unit B
Mechanical Seal Ok Damage

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

Trouble Status 1. There are 2 pumps that the refer the above table
2. The shaft bearing bushings of pump are worn out
Unit A Unit B
Equipment
Commissioning Existing Commissioning Existing

Bearing ND NDE ND NDE ND NDE ND NDE


Bushing Ø50 Ø50 Ø50 Ø50 Ø50 Ø50 Ø50 Ø50
+0.02 +0.02 -0.03 -0.05 +0.02 +0.02 -0.06 -0.05

3. The shaft mechanical seal of pump are worn out


Unit A Unit B
Equipment
Commissioning Existing Commissioning Existing
Mechanical
Seal Ø50 -0.05 Ø49.40 Ø50 -0.05 Ø48.90

4. The shaft oil seal of pump are worn out


Unit A Unit B
Equipment
Commissioning Existing Commissioning Existing
ND NDE ND NDE ND NDE ND NDE
Oil Seal Ø50 Ø50 Ø50 Ø50 Ø50 Ø50 Ø50 Ø50
+0.02 +0.02 -0.03 -0.05 +0.02 +0.02 -0.06 -0.05

5. The shaft run out of pump are worn out


Equipme Unit A Unit B
nt Bearing Bearing Bearing Bearing
Impeller NDE DE Coupling Impeller NDE DE Coupling
0.40 0.00 0.00 0.05 0.42 0.00 0.00 0.05
Run Out
micron micron micron micron micron micron micron micron

Action to be 1. Dismantling the pumps and measuring the gap clearance from shaft, check
taken balancing impeller and volute casing.

Cause of 1. The long term operation caused internal part of component wear out especially
bushing bearing and impeller unbalance and than volute casing wear out.
Trouble
2. Wear out of the bearing bushing and than oil seal damage due to long term
operation to oil contamination by water.

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

Countermeasure 1. Making shaft, balancing impeller and volute casing at third party.
2. Restoring all the pump components by proper measures

Future Plan 1. Purchasing the new pumps for block maintenance.


2. Making shaft, balancing impeller and volute casing at third party..
Remark Predective maintenece monitoring (statistical based and conditional based)

Attachment 1. P&ID
2. Inspection Results of Lube oil pump existing condition
3. Trouble report of reclaim water pump A/B, based of Service Request Record
2013/20014

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

1. P & ID

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

2. Inspection Results of Lube oil pump existing condition

Part View

bearing bushings DE #A

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

shaft bearing bushings

bearing bushings NDE #A

bearing bushings DE #B

bearing bushings NDE #B

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

shaft mechanical seal #A


shaft mechanical seal

shaft mechanical seal #B

shaft oil seal

Oil seal DE #A

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

Oil seal NDE #A

Oil seal DE #B

Oil seal NDE #A

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601
PT.KOMIPO PEMBANGKITAN JAWA Doc Ref. KPJB-0953-04
BALI Form
PLTU TANJUNG JATI B UNIT #3&4 KPJB-0953-04-ZZ-FM-01
No.
Design
Trouble Inspection Report Division
Mechanical Division
Revision
Laporan Inspeksi Gangguan 00
Number

Tanjung Jati B #3&4 Coal Fired Power Plant


Desa Tubanan, Kecamatan Kembang, Kabupaten Jepara
Jawa Tengah, Indonesia Tel. 0291 4270493 Fax. 0291 4270601