You are on page 1of 2

Data sheet 3EH4450-1CC14

Surge arrester 3EH4 Internal taper according to EN50181 Connector size 2


Arrester standard: IEC60099-4 Ur: 45.0 kV, Uc: 36.0 kV Arrester class: DH
In: 10 kA Qrs: 0.4C. Qth: 1.1C. Rated short circuit current Is: 16 kA
Individual cardboard packaging

Electrical data
standard IEC 60099-4
Designation / of arrester class DH
Discharge current / according to IEC 60099-4 / rated value 10.0 kA
Discharge capacity of electrical charge 0.4 C
Thermal discharge capacity of electrical charge / nominal 1.1 C
value
voltage / rated value 45.0 kV
Arrester continuous voltage 36.0 kV
High current impulse / of arrester 100.0 kA
Discharge short-circuit current / nominal value 16.0 kA
Line frequency / rated value / minimum 48.0 Hz
Line frequency / rated value / maximum 62.0 Hz
Residual voltage
● at 1 kA / at (8/20) µs 97.8 kV
● at 3 kA / at (8/20) µs 106.1 kV
● at 5 kA / at (8/20) µs 110.9 kV
● at 10 kA / at (8/20) µs 119.3 kV
● at 20 kA / at (8/20) µs 137.1 kV
● at 125 A / at (30/60) µs 87.1 kV
● at 250 A / at (30/60) µs 89.4 kV
● at 500 A / at (30/60) µs 91.8 kV
● at 1 kA / at (30/60) µs 95.4 kV
● at 2 kA / at (30/60) µs 100.2 kV
TOV withstand
● limited to 1 s 48.4 kV
● limited to 10 s 45.0 kV
Rest lightning impulse voltage / of enclosure / at (1,2/50) 200.0 kV
µs
Mechanical data
height 466.0 mm
net weight 6.5 kg
color / of the insulating body grey
Accessories
type of installation 3 drilled holes for M8 screws. Hole circle diameter: 102 mm
pack type Single
General data
ambient temperature / minimum -30.0 °C

3EH44501CC14 Subject to change without notice


12.22.2020
Page 1/2 © Copyright Siemens
ambient temperature / maximum 55.0 °C
installation altitude 1 000.0 m
AL Code N
ECCN code N
Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3EH4450-1CC14

3EH44501CC14 Subject to change without notice


12.22.2020
Page 2/2 © Copyright Siemens