Professional Documents
Culture Documents
Contents
1. Introduction ................................................................................................ 3
1.1 Features................................................................................................ 3
1.2 Short duration voltage variations .......................................................... 3
1.3 Application ............................................................................................ 4
1.4 Input description ................................................................................... 5
1.5 Output description................................................................................. 5
2. Description of operation............................................................................ 6
2.1 Configuration ........................................................................................ 6
2.1.1 Voltage measurement.................................................................. 6
2.1.2 Current measurement.................................................................. 6
2.1.3 Input/output configuration ............................................................ 6
2.2 Rated frequency ................................................................................... 7
2.3 Measuring mode ................................................................................... 7
2.4 Operation criteria .................................................................................. 7
2.5 Outputs of the function block ................................................................ 9
2.5.1 Swell ............................................................................................ 9
2.5.2 Sag ............................................................................................ 10
2.5.3 Interruption................................................................................. 11
2.5.4 Counters .................................................................................... 14
2.6 Indications and events ........................................................................ 15
2.7 Resetting............................................................................................. 15
2.8 Recorded Data.................................................................................... 16
2.9 Measurement accuracy....................................................................... 17
4. Technical Data...........................................................................................24
2
Distribution Automation PQVO3Sd
1. Introduction
1.1 Features
Voltage variations are the most typical power quality events that have the
largest impact on sensitive customers. Short-duration voltage variations are
almost always caused by a fault condition. Depending on where the fault is
located, the fault can cause either a temporary voltage rise (swell) or voltage
drop (sag). A special case of a voltage drop is complete loss of voltage
(interruption). The impact on the voltage during the actual fault condition is a
short duration variation. The typical duration of a short duration voltage
variation, as defined in most of the publications, is from 10 ms to 60 seconds.
Sag
A voltage sag is a sudden reduction of the supply voltage. In most
publications, a voltage sag is characterized as a voltage drop to a value
between 90 % and 1 % of the nominal voltage. Voltage sags are usually
caused by system faults but can also be caused by the switching of large
loads or the starting of motors. A typical voltage sag can also be associated
with a single line-to-ground fault. A fault on a parallel feeder will result in a
voltage drop at the substation bus. This fault affects all of the other feeders
until the fault is cleared.
Swell
A voltage swell is defined as an increase in supply voltage. Typical
magnitudes are between 110 % and 180 % of the nominal voltage. Swells are
also usually associated with system faults, but not as frequently as voltage
sags. A single line-to-ground fault in the system can result in a voltage swell
on the healthy phases. Switching off large loads or switching on large
capacitor banks can also cause voltage swells.
3
PQVO3Sd Distribution Automation
Interruption
A voltage interruption is defined as a decrease of the supply voltage to a value
less than 1 % of the nominal voltage. Interruptions can be the result of power
system faults, equipment failures, and control function failures. Utility
protective devices and the particular event causing the fault determine the
duration of an interruption.
1.3 Application
The PQVO3Sd function block is used for measuring short duration voltage
variations in distribution networks. Power quality is being evaluated in the
voltage waveform by measuring voltage swells, sags and interruptions.
For IEC symbols used in single line diagrams, refer to the manual “Technical
Descriptions of Functions, Introduction”, 1MRS750528-MUM
4
Distribution Automation PQVO3Sd
5
PQVO3Sd Distribution Automation
2. Description of operation
2.1 Configuration
• Measured currents are registered by the function block and can later
be used e.g. in calculation of power loss caused by a voltage sag or an
interruption.
The measuring devices and signal types for the analog channels are selected
and parameterized in a special dialog box of the graphic RECAP tool (IEC
configuration tool). The binary inputs are parameterized in the same
programming environment. The number of selectable analog inputs, binary
inputs and binary outputs depends on the hardware used.
When the analog channels and binary inputs have been selected and
parameterized in the dialog box, the inputs and outputs of the function block
can be configured in a graphic worksheet of the RECAP tool. The digital inputs
6
Distribution Automation PQVO3Sd
are connected to the Boolean inputs of the function block. In the same way,
the outputs of the function block are connected to the output signals.
Note 1. The function block setting Declared voltage is set to 100.0 % when
phase-to-phase voltages are connected, and to 57.7% in case that phase-to-
ground voltages are connected. This means that if a voltage different from
nominal voltage is connected to the terminal, the setting Declared voltage is
set to this voltage.
Note 2. If the LV side voltages (e.g. U12b) are connected to the function block,
then the LV side measurement of the phase currents must be used as well.
Otherwise it is not possible to use recorded data, provided by the function
block, for calculation of lost power.
Note 3. True RMS measurement must be selected for voltage and current
channels.
The rated frequency of the device is set via a dialog box in the configuration
tool. In addition, the global control parameter Rated frequency of the relay
can be used to read the rated frequency.
The function block measures true RMS voltage (includes harmonics etc.). The
results are compared to nominal voltage or declared voltage.
The PQVO3Sd function block measures short duration voltage variations, i.e.
voltage sags, swells and interruptions longer than 1 cycle (for interruptions1½
7
PQVO3Sd Distribution Automation
The maximum magnitude (in case of voltage swell) or depth (in case of
voltage sag or interruption) and the duration of the event can be obtained by
measuring the RMS value of the voltage for each phase. The maximum
magnitude and depth is defined as a percentage value calculated from the
difference between the nominal (or declared) and the measured voltage (e.g.
70 % depth means that the minimum magnitude of a sag event is 70 % of the
nominal amplitude). The duration of each phase corresponds to the period
during which the RMS values measured remain above or below the
corresponding limit. Figure 2 illustrates the duration and magnitude limits of
the function block.
PQVO3Sd measures RMS values for voltage. When this measured RMS
value drops below the sag limit, and in the same time remains above the
interruption limit, a sag is detected. If the voltage drops below the interruption
limit, an interruption is detected. When the measured RMS value rises above
the swell limit, a swell is detected.
Note 4. The function block setting Interrupt. limit must be set below the
setting Sag limit for correct and standardized operation of the function block.
Figure 2. Duration and voltage magnitude limits for swell, sag and interruption
measurement
If a voltage swell, sag or interruption is detected, the corresponding output
signal (SWELL, SAG or INT) is set to the Boolean value TRUE. The output
signal is TRUE during the swell, sag or interruption event. The outputs SWELL
8
Distribution Automation PQVO3Sd
and SAG can be active in the same time in case of e.g. a single-phase earth
fault (see Figure 7).
2.5.1 Swell
1. The SWELL output is set to TRUE when the voltage level of any phase
rises above the swell limit (IEC 61000-4-30).
2. The SWELL output is set to FALSE when the voltage levels of all phases
are equal to or below the swell limit (minus the hysteresis) or when the
swell is active longer than the maximum duration.
9
PQVO3Sd Distribution Automation
2.5.2 Sag
1. The SAG output is set to TRUE when the voltage level on any phase drops
below the sag limit (IEC 61000-4-30).
2. The SAG output is set to FALSE when the voltage levels of all phases are
equal to or above the sag limit (plus the hysteresis) or when the sag is
active longer than the maximum duration.
Figure 4. Three-phase sag. Phase U2 (green) starts and phase U3 (blue) ends the
event
10
Distribution Automation PQVO3Sd
2.5.3 Interruption
1. The INT output is set to TRUE when the voltage levels of all phases drop
below the interruption limit (IEC 61000-4-30).
2. The INT output is set to FALSE when the voltage level of any phase is
equal to or above the interruption limit (plus the hysteresis), or when the
interruption is active longer than the maximum duration.
11
PQVO3Sd Distribution Automation
12
Distribution Automation PQVO3Sd
13
PQVO3Sd Distribution Automation
Figure 8. One-phase sag which duration is longer than setting Duration max
2.5.4 Counters
The SAG_COUNTER output indicates the sum of the detected valid (the event
duration is between min and max duration) voltage sags since the last reset of
the function block. The same functionality correspondingly applies for the
SWELL_COUNTER and INT_COUNTER outputs.
14
Distribution Automation PQVO3Sd
When the voltage level of any phase is below or above the corresponding
limit, a start event (E1) is generated. An end event (E0) indicates ending of the
particular event in case. If the measured duration of the detected event is
between the minimum and maximum durations, it is considered as a valid
voltage variation event and then the measurement values are recorded. This
recording is indicated by the generation of the event E2, which is sent at the
same time as event E0 (see Figure 3). A voltage variation detection is also
indicated with a HMI text indication. Event sending can be seen in Figures 3-8.
For more information see section Recorded Data.
Note 6. The function block PQVO3Sd measures the duration of each voltage
channel separately, but the duration settings (Duration min and Duration
max) of the function block are compared to the total duration of the variation
event. The event duration can be seen in Figure 6. This event duration
determines whether the measurement values of the variation event are
recorded or not.
2.7 Resetting
The registers can be reset, either via the RESET input, over the serial bus or
via the local HMI.
The operation indicators, the counters and the recorded data can be reset as
follows:
15
PQVO3Sd Distribution Automation
General
The information required for later power quality analysis is recorded when the
function block has detected a valid voltage variation.
The data of the last three events are stored into the registers Recorded
data 1...3, beginning from Recorded data 1. These registers are updated in a
cyclical manner, where the values of the most recent event overwrite the
oldest recorded data. If recorded data has been reset or the relay has been
restarted, first event is again stored to Recorded data 1.
The time stamp for each of the 3 phases indicates the time instant at which
the voltage variation event was detected.
The time stamp for each of the 3 phases indicates the time instant at which
the measured voltage was at a minimum/maximum during the measured
power quality event.
Duration
Currents
16
Distribution Automation PQVO3Sd
Duration measurement
Measurement accuracy for duration measurement in normal operating
conditions is:
17
PQVO3Sd Distribution Automation
3.1 General
• The data direction of the parameters defines the use of each parameter as
follows:
• The different event mask parameters (see section “Control Settings”) affect
the visibility of events on the HMI or on the serial communication (LON or
SPA) as follows:
For example, if only the events E3, E4 and E5 are to be seen on the HMI of
the relay terminal, the event mask value 56 (8 + 16 + 32) is written to the
“Event mask 1” parameter (F514V101).
18
Distribution Automation PQVO3Sd
19
PQVO3Sd Distribution Automation
20
Distribution Automation PQVO3Sd
Min/max date U1 V208 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement
Min/max time U1 V209 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement
Min/max date U2 V210 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement
Min/max time U2 V211 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement
Min/max date U3 V212 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement
Min/max time U3 V213 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement
21
PQVO3Sd Distribution Automation
Min/max date U1 V308 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement
Min/max time U1 V309 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement
Min/max date U2 V310 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement
Min/max time U2 V311 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement
Min/max date U3 V312 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement
Min/max time U3 V313 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement
22
Distribution Automation PQVO3Sd
Min/max date U1 V408 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement
Min/max time U1 V409 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement
Min/max date U2 V410 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement
Min/max time U2 V411 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement
Min/max date U3 V412 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement
Min/max time U3 V413 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement
3.3.4 Events
23
PQVO3Sd Distribution Automation
4. Technical Data
Reset ratio Typ. 0.95
24