Effective Control and Auxiliary Circuit Monitoring
Can Reduce Downtime and Increase Profitability
The governing standard of the Insulation All IMDs must be labelled to highlight system of
monitoring device (IMD) is BS EN 61557-8 as per use i.e AC, DC or AC/DC.
IEC 60364-4 and BS7671 557.3.4.3. and 538.1.1
BS EN 61577-8 prohibits use of passive devices
in an IT circuits which cannot detect symmetrical
faults. A symmetrical fault is particularly dangerous
to control circuit because it can lead to inadvertent
switching or false trippping without detection. The
diagram below shows a double high resistance
symmetrical insulation fault on DC PLC circuit. The
fault is not detectable by the passive device and
can therefore cause switch to be seen as closed.
Insulation monitoring technology combined
BS7671 clause 557.3.201 states: “A control circuit with earth fault location systems developed by
shall be designed, arranged and protected to limit Bender are employed in a wide range of critical
dangers resulting from a fault between the control control circuit applications within industry
circuit and other conductive parts liable to cause sectors that simply cannot afford unscheduled
malfunction (e.g. inadvertent operation) of the shutdowns or interruptions in production and
controlled equipment.” process operations.
BENDER UK
Low Mill Business Park, Ulverston, Cumbria, LA12 9EE
Tel: 44(0) 1229 480123 Tel ROI: +353 1 5060611
Effective Control and Auxiliary Circuit Monitoring
Can Reduce Downtime and Increase Profitability
The diagram below shows a typical structure of Bender technology can be permanently
a Control System incorporating IMD with fixed retrofitted and also has been extensively used
and portable earth fault location to precisely to locate long standing earth faults via portable
identity faults from distribution to control terminals.
circuit level.
BENDER UK
Low Mill Business Park, Ulverston, Cumbria, LA12 9EE
Tel: 44(0) 1229 480123 Tel ROI: +353 1 5060611
Effective Control and Auxiliary Circuit Monitoring
Can Reduce Downtime and Increase Profitability
An alternative way of monitoring for earth faults Earth fault alarm is an optional function on BA300
is by using a passive measurement principle, and shouldn’t be included with an external
although this method does not comply with earth fault monitoring system. Comparison of
the IEC61557-8 regulations for insulation earth fault detection features on an IT system is
monitoring devices. shown below.
Battery management system such as a BA 300 Knowledge is power
provides the following monitoring functions
compared with IMD: The benefits of using insulation monitoring
technology to enable early identification of earth
ff Over and under voltage conditions faults in mission critical AC or DC control and
auxiliary supplies cannot be underestimated.
ff High impedance alarm
Continuous monitoring equips maintenance
ff Earth fault alarm teams and plant operators with the vital
information to deliver effective predictive and
ff Battery ability to provide load current preventive maintenance that avoids shutdowns,
reduces downtime, increases productivity and
ff Battery in service monitoring improves profitability.
No
Detection of symmetrical faults Yes
(Passive, voltage imbalance principle)