ADDISON ®

100% OUTSIDE AIR


SPLIT SYSTEM OUTDOOR CONDENSING UNITS
PAIRED WITH THIRD-PARTY AIR HANDLER

RCA-SERIES

DIMENSION AND SELECTION GUIDE

www.addison-hvac.com
Telephone: +1.407.292.4400

RATED IN ACCORDANCE TO AHRI STANDARD 365-2009


1
UNIT DATA - RCA051
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE

Total Capacity (Btu/h) 46,500


DATA

Electric Power (W) 3,550


NET COOLING
Energy Efficiency Ratio (EER) 13.1

Integrated Energy Efficiency Ratio (IEER) 14.4

Qty-Nominal Tons-Type 1 - 3.5 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 21.8 13.7 6.2 4.8
Locked Rotor Amps (LRA) 117 83 41 33
Qty - Horsepower (HP) 1 - 1/2
CONDENSER FAN
FLA (ea) 6.2 5.4 2.7 1.3
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 33.5 22.5 10.5 7.3
UNIT
Max. Time Delay Fuse or HACR Breaker 50 35 15 15
Airflow (CFM) 4,000
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 24 - 36
Quantity 2
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 3


/4 (Qty 1)
REFRIGERANT Liquid Line (in OD) 1
/2 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 3
/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3
/8 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 24
(lbs per circuit)
Unit Weight (lbs) 565
WEIGHTS
Shipping Weight (lbs) 615
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 39,000 37,400 36,000
35.0
Electric Power (W) 3,370 3,560 3,765
Total Capacity (Btu/h) 42,500 41,000 39,500
COOLING

40.0
Electric Power (W) 3,380 3,575 3,780
Total Capacity (Btu/h) 46,500 44,500 43,000
45.0
Electric Power (W) 3,400 3,590 3,800
Total Capacity (Btu/h) 50,500 48,500 47,000
50.0
Electric Power (W) 3,420 3,615 3,815
Total Capacity (Btu/h) 54,500 52,500 50,500
55.0
Electric Power (W) 3,440 3,635 3,840
2
UNIT DATA - RCA061
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE Total Capacity (Btu/h) 55,600
DATA
Electric Power (W) 4,244
NET COOLING
Energy Efficiency Ratio (EER) 13.1

Integrated Energy Efficiency Ratio (IEER) 14.2

Qty-Nominal Tons-Type 1 - 4.5 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 26.4 16.0 7.8 7.6
Locked Rotor Amps (LRA) 134 110 52 54
Qty - Horsepower (HP) 1 - 1/2
CONDENSER FAN
FLA (ea) 6.2 5.4 2.7 1.3
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 39.2 25.3 12.3 8.4
UNIT
Max. Time Delay Fuse or HACR Breaker 60 40 20 15
Airflow (CFM) 4,000
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 24 - 36
Quantity 2
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 7


/8 (Qty 1)
REFRIGERANT Liquid Line (in OD) 1
/2 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 3
/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3
/8 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 24
(lbs per circuit)
Unit Weight (lbs) 590
WEIGHTS
Shipping Weight (lbs) 640
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 45,000 43,000 42,000
35.0
Electric Power (W) 4,250 4,485 4,775
Total Capacity (Btu/h) 53,500 47,000 46,000
COOLING

40.0
Electric Power (W) 4,355 4,530 4,785
Total Capacity (Btu/h) 55,000 51,000 50,000
45.0
Electric Power (W) 4,380 4,615 4,865
Total Capacity (Btu/h) 57,000 56,000 54,000
50.0
Electric Power (W) 4,435 4,675 4,930
Total Capacity (Btu/h) 62,000 60,000 58,000
55.0
Electric Power (W) 4,530 4,770 5,035
3
UNIT DATA - RCA071
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE

Total Capacity (Btu/h) 74,500


DATA

Electric Power (W) 6,422


NET COOLING
Energy Efficiency Ratio (EER) 11.6

Integrated Energy Efficiency Ratio (IEER) 12.7

Qty-Nominal Tons-Type 1 - 6.3 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 23.2 11.2 7.7
Locked Rotor Amps (LRA) 164 75 54
Qty - Horsepower (HP) 1 - 1/2
CONDENSER FAN
FLA (ea) 5.4 2.7 1.3
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 34.4 16.7 11.2
UNIT
Max. Time Delay Fuse or HACR Breaker 50 25 15
Airflow (CFM) 4,000
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 24 - 36
Quantity 2
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 7


/8 (Qty 1)
REFRIGERANT Liquid Line (in OD) 1
/2 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 3
/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 1
/2 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 25
(lbs per circuit)
Unit Weight (lbs) 610
WEIGHTS
Shipping Weight (lbs) 660
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 60,200 58,000 56,000
35.0
Electric Power (W) 6,285 6,585 6,905
Total Capacity (Btu/h) 66,000 63,000 61,000
COOLING

40.0
Electric Power (W) 6,415 6,720 7,045
Total Capacity (Btu/h) 71,000 69,000 66,000
45.0
Electric Power (W) 6,600 6,860 7,245
Total Capacity (Btu/h) 77,000 74,000 71,000
50.0
Electric Power (W) 6,695 7,005 7,330
Total Capacity (Btu/h) 82,000 80,000 77,000
55.0
Electric Power (W) 6,840 7,150 7,480
4
UNIT DATA - RCA101
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 107,500
DATA
Electric Power (W) 9,430
NET COOLING
Energy Efficiency Ratio (EER) 11.4

Integrated Energy Efficiency Ratio (IEER) 12.8

Qty-Nominal Tons-Type 1 - 9.0 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 30.1 16.7 12.2
Locked Rotor Amps (LRA) 225 114 80
Qty - Horsepower (HP) 1-1
CONDENSER FAN
FLA (ea) 5.4 2.7 2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 41.6 23.1 19.3
UNIT
Max. Time Delay Fuse or HACR Breaker 70 35 30
Airflow (CFM) 6,200
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 26
Quantity 3
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 23.1
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


1

REFRIGERANT Liquid Line (in OD) 5


/8 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 1
/2 (Qty 1)
Optional Hot Gas Reheat (in OD) 5
/8 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 30
(lbs per circuit)
Unit Weight (lbs) 825
WEIGHTS
Shipping Weight (lbs) 900
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 89,000 86,000 83,000
35.0
Electric Power (W) 8,910 9,435 9,840
Total Capacity (Btu/h) 97,000 94,000 90,000
COOLING

40.0
Electric Power (W) 9,130 9,515 10,075
Total Capacity (Btu/h) 105,000 101,000 98,000
45.0
Electric Power (W) 9,300 9,750 10,225
Total Capacity (Btu/h) 113,000 109,000 106,000
50.0
Electric Power (W) 9,465 9,935 10,395
Total Capacity (Btu/h) 122,000 118,000 113,000
55.0
Electric Power (W) 9,660 10,110 10,680
5
UNIT DATA - RCA141
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE

Total Capacity (Btu/h) 137,100


DATA

Electric Power (W) 12,578


NET COOLING
Energy Efficiency Ratio (EER) 10.9

Integrated Energy Efficiency Ratio (IEER) 12.2

Qty-Nominal Tons-Type 1 - 12.0 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 48.1 18.6 15.1
Locked Rotor Amps (LRA) 245 125 100
Qty - Horsepower (HP) 1-1
CONDENSER FAN
FLA (ea) 5.4 2.7 2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 64.0 25.4 22.4
UNIT
Max. Time Delay Fuse or HACR Breaker 110 40 35
Airflow (CFM) 6,200
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 26
Quantity 3
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 23.1
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


3

REFRIGERANT Liquid Line (in OD) 5


/8 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 1
/2 (Qty 1)
Optional Hot Gas Reheat (in OD) 5
/8 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 35
(lbs per circuit)
Unit Weight (lbs) 900
WEIGHTS
Shipping Weight (lbs) 975
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 113,000 110,000 106,000
35.0
Electric Power (W) 12,000 12,470 13,085
Total Capacity (Btu/h) 124,000 119,000 115,000
COOLING

40.0
Electric Power (W) 12,150 12,845 13,340
Total Capacity (Btu/h) 133,000 129,000 124,000
45.0
Electric Power (W) 12,535 13,005 13,615
Total Capacity (Btu/h) 143,000 139,000 134,000
50.0
Electric Power (W) 12,710 13,295 13,905
Total Capacity (Btu/h) 153,000 148,000 144,000
55.0
Electric Power (W) 13,070 13,710 14,210
6
UNIT DATA - RCA171
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 165,900
DATA
Electric Power (W) 13,598
NET COOLING
Energy Efficiency Ratio (EER) 12.2

Integrated Energy Efficiency Ratio (IEER) 13.6

Qty-Nominal Tons-Type 1 - 13.5 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 51.3 23.1 19.9
Locked Rotor Amps (LRA) 300 150 109
Qty - Horsepower (HP) 2-1
CONDENSER FAN
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 74.8 33.4 28.9
UNIT
Max. Time Delay Fuse or HACR Breaker 125 50 45
Airflow (CFM) 12,400
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 32
Quantity 4
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


3

REFRIGERANT Liquid Line (in OD) 7


/8 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 5
/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 5
/8 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 50
(lbs per circuit)
Unit Weight (lbs) 1,250
WEIGHTS
Shipping Weight (lbs) 1,345
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 144,000 138,000 133,000
35.0
Electric Power (W) 12,265 12,865 13,540
Total Capacity (Btu/h) 157,000 151,000 146,000
COOLING

40.0
Electric Power (W) 12,400 13,015 13,670
Total Capacity (Btu/h) 170,000 164,000 158,000
45.0
Electric Power (W) 12,560 13,170 13,820
Total Capacity (Btu/h) 183,000 177,000 171,000
50.0
Electric Power (W) 12,775 13,390 14,015
Total Capacity (Btu/h) 198,000 191,000 185,000
55.0
Electric Power (W) 12,980 13,560 14,180
7
UNIT DATA - RCA201
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE

Total Capacity (Btu/h) 192,000


DATA

Electric Power (W) 16,271


NET COOLING
Energy Efficiency Ratio (EER) 11.8

Integrated Energy Efficiency Ratio (IEER) 13.2

Qty-Nominal Tons-Type 1 - 15.0 - Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 55.8 26.9 23.7
Locked Rotor Amps (LRA) 340 173 132
Qty - Horsepower (HP) 2-1
CONDENSER FAN
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 78.8 40.0 57.6
UNIT
Max. Time Delay Fuse or HACR Breaker 125 60 80
Airflow (CFM) 12,400
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 32
Quantity 4
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


3

REFRIGERANT Liquid Line (in OD) 7


/8 (Qty 1)
CONNECTION(S) Optional Hot Gas Bypass (in OD) 5
/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3
/4 (Qty 1)
Sheet Metal G90 Galvanized
Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 58
(lbs per circuit)
Unit Weight (lbs) 1,300
WEIGHTS
Shipping Weight (lbs) 1,400
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 167,000 161,000 155,000
35.0
Electric Power (W) 14,500 15,230 16,020
Total Capacity (Btu/h) 182,000 176,000 170,000
COOLING

40.0
Electric Power (W) 14,740 15,415 16,175
Total Capacity (Btu/h) 197,000 191,000 185,000
45.0
Electric Power (W) 14,955 15,665 16,355
Total Capacity (Btu/h) 213,000 207,000 199,000
50.0
Electric Power (W) 15,170 15,865 16,635
Total Capacity (Btu/h) 230,000 223,000 215,000
55.0
Electric Power (W) 15,390 16,100 16,850
8
UNIT DATA - RCA271
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 241,300
DATA
Electric Power (W) 22,343
NET COOLING
Energy Efficiency Ratio (EER) 10.8

Integrated Energy Efficiency Ratio (IEER) 12.4

Qty-Nominal Tons-Type 1 - 21.0 - Tandem Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 33.3 17.9 12.8
Locked Rotor Amps (LRA) 239 125 80
Qty - Horsepower (HP) 2-1
CONDENSER FAN
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 85.7 45.7 32.8
UNIT
Max. Time Delay Fuse or HACR Breaker 110 60 45
Airflow (CFM) 12,400
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 32
Quantity 4
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


5

REFRIGERANT Liquid Line (in OD) /8 (Qty 1)


7

CONNECTION(S) Optional Hot Gas Bypass (in OD) /8 (Qty 1)


5

Optional Hot Gas Reheat (in OD) /8 (Qty 1)


7

Sheet Metal G90 Galvanized


Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 58
(lbs per circuit)
Unit Weight (lbs) 1,400
WEIGHTS
Shipping Weight (lbs) 1,500
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 213,000 205,000 197,000
35.0
Electric Power (W) 19,315 20,310 21,360
Total Capacity (Btu/h) 232,000 224,000 216,000
COOLING

40.0
Electric Power (W) 19,590 20,570 21,620
Total Capacity (Btu/h) 252,000 243,000 236,000
45.0
Electric Power (W) 20,020 21,000 21,895
Total Capacity (Btu/h) 273,000 264,000 254,000
50.0
Electric Power (W) 20,360 21,330 22,365
Total Capacity (Btu/h) 294,000 284,000 275,000
55.0
Electric Power (W) 20,720 21,700 22,730
9
UNIT DATA - RCA361
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE

Total Capacity (Btu/h) 288,600


DATA

Electric Power (W) 24,879


NET COOLING
Energy Efficiency Ratio (EER) 11.6

Integrated Energy Efficiency Ratio (IEER) 12.8

Qty-Nominal Tons-Type 1 - 24.0 - Tandem Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 48.1 18.6 15.1
Locked Rotor Amps (LRA) 245 125 100
Qty - Horsepower (HP) 4-1
CONDENSER FAN
FLA (ea) 3.4 / 3.4 / 5.4 / 5.4 1.7 / 1.7 / 2.7 / 2.7 2.0 / 2.0 / 2.0 / 2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 125.6 51.6 41.1
UNIT
Max. Time Delay Fuse or HACR Breaker 150 70 50.0
Airflow (CFM) 28,000
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 32
Quantity 4
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 70.0
Rows - Fins per Inch 2 - 14
MECHANICAL DATA

Suction Line (in OD) 1 /8 (Qty 1)


5

REFRIGERANT Liquid Line (in OD) 11/8 (Qty 1)


CONNECTION(S) Optional Hot Gas Bypass (in OD) /8 (Qty 1)
7

Optional Hot Gas Reheat (in OD) /8 (Qty 1)


7

Sheet Metal G90 Galvanized


Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 65
(lbs per circuit)
Unit Weight (lbs) 1,700
WEIGHTS
Shipping Weight (lbs) 1,820
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 240,000 231,000 221,000
35.0
Electric Power (W) 23,635 24,700 26,050
Total Capacity (Btu/h) 260,000 251,000 243,000
COOLING

40.0
Electric Power (W) 24,090 25,140 26,135
Total Capacity (Btu/h) 283,000 274,000 264,000
45.0
Electric Power (W) 24,410 25,485 26,620
Total Capacity (Btu/h) 306,000 296,000 285,000
50.0
Electric Power (W) 24,890 26,010 27,190
Total Capacity (Btu/h) 332,000 320,000 309,000
55.0
Electric Power (W) 25,085 26,360 27,570
10
UNIT DATA - RCA421
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 369,700
DATA
Electric Power (W) 33,609
NET COOLING
Energy Efficiency Ratio (EER) 11.0

Integrated Energy Efficiency Ratio (IEER) 12.2

Qty-Nominal Tons-Type 1 - 31.5 - Tandem Scroll


Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
ELECTRICAL DATA

COMPRESSOR(S) Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60


Run Load Amps (RLA) 55.8 26.9 23.8
Locked Rotor Amps (LRA) 340 173 132
Qty - Horsepower (HP) 4-1
CONDENSER FAN
FLA (ea) 3.4 / 3.4 / 5.4 / 5.4 1.7 / 1.7 / 2.7 / 2.7 2.0 / 2.0 / 2.0 / 2.0
MOTOR(S)
Type PSC
Unit Minimum Circuit Ampacity 142.4 70.5 61.4
UNIT
Max. Time Delay Fuse or HACR Breaker 175 90 85
Airflow (CFM) 28,000
CONDENSER FAN(S)
Diameter (in)-Pitch (deg) 26 - 32
Quantity 4
Tube Material - Fin Material Copper - Aluminum
CONDENSER COIL(S)
Face Area (sq. ft) 70.0
Rows - Fins per Inch 2 - 14
MECHANICAL DATA

Suction Line (in OD) 2 /8 (Qty 1)


1

REFRIGERANT Liquid Line (in OD) 11/8 (Qty 1)


CONNECTION(S) Optional Hot Gas Bypass (in OD) /8 (Qty 1)
7

Optional Hot Gas Reheat (in OD) /8 (Qty 1)


7

Sheet Metal G90 Galvanized


Finish Polyester Coating
CABINET Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Charge based on 25' line set
REFRIGERANT - R410A 75
(lbs per circuit)
Unit Weight (lbs) 1,770
WEIGHTS
Shipping Weight (lbs) 1,900
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.

SATURATED SUCTION AMBIENT TEMPERATURE (°F)


TEMPERATURE (°F) 95.0 100.0 105.0
Total Capacity (Btu/h) 306,000 294,000 285,000
35.0
Electric Power (W) 31,685 33,335 34,495
Total Capacity (Btu/h) 334,000 322,000 309,000
COOLING

40.0
Electric Power (W) 32,350 33,705 35,465
Total Capacity (Btu/h) 359,000 350,000 338,000
45.0
Electric Power (W) 33,355 34,440 35,885
Total Capacity (Btu/h) 391,000 375,000 365,000
50.0
Electric Power (W) 33,900 35,550 36,695
Total Capacity (Btu/h) 421,000 407,000 391,000
55.0
Electric Power (W) 34,815 36,165 37,925
11
TYPICAL WIRING DIAGRAM

Condensing Unit
Condensing L1
Control Panel
Unit L2
Disconnect
R 24VAC, Switched
L3
Y Compressor
G Supply Fan
C 24VAC, Common, Unswitched

NOTES:
1. All electrical wiring and connections, including electrical grounding must comply with:
a. United States: Refer to NFPA 70- latest revision, National Electrical Code, and local ordinances.
b. Canada: Refer to CSA C22.1, Part 1- latest revision, Canadian Electrical Code and local ordinances.
2. Class 1 circuit
3. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or
provided by others.

TYPICAL SPLIT SYSTEM INSTALLATION

Disconnect

Interconnecting Control Wiring

Liquid Line Condensing Unit


Suction Line
Optional Hot Gas Reheat
Sleeve And Flashing Optional Hot Gas Bypass

Disconnect

Outside Air
or Return Air Supply Air
Air Handler

Trap And Drain Connection

NOTES:
1. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or
provided by others.
2. Air handler, air handler disconnect, interconnecting control wiring, all refrigerant line piping and sleeve/flashing materials are by others.
3. Suction, hot gas bypass, and hot gas reheat lines should be insulated with 5/8” minimum thickness closed cell foam insulation. Liquid line exposed
to high ambient temperatures should be insulated 5/8” minimum thickness closed cell foam insulation.

12
TYPICAL INSTALLATION WITH CONDENSING UNIT ON BOTTOM

Optional Hot
Gas Reheat

Condensate Trap And Pipe


Loop To Top Of Coil
Suction
Liquid
Optional Hot
Gas Bypass

Slope Down Towards


Condensing Unit

NOTES:
1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler.
2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler.
3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the
air handler. The trap is inverted at the top of the vertical rise.

TYPICAL INSTALLATION WITH CONDENSING UNIT ON TOP

Optional Hot Gas


Bypass

Suction

Liquid
Optional Hot Gas
Reheat

Condensate Trap And Pipe

Slope Down From Air Handler

NOTES:
1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler.
2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler.
3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the
air handler. The trap is inverted at the top of the vertical rise.

13
DIMENSIONS - RCA 051/061/071

TOP VIEW MULTI-DIMENSIONAL VIEW


A

COIL

ELECTRICAL
COIL

B
CONTROLS

LIQUID
C Ø E OPTIONAL HOT GAS REHEAT
D
SUCTION OPTIONAL HOT GAS BYPASS
COMPRESSOR

F Q

P
N
M
L

H A K R

SIDE VIEW BACK VIEW

A B C D E F G H K L M N P Q R
(in) 3.00 47.38 42.25 52.25 0.75 40.38 39.13 2.00 3.50 5.00 9.00 13.00 20.00 3.25 53.38

14
DIMENSIONS - RCA 101/141

A
TOP VIEW MULTI-DIMENSIONAL VIEW

COIL
COIL

COIL
B
ELECTRICAL

OPTIONAL HOT
GAS BYPASS
LIQUID
C
D ØE SUCTION OPTIONAL HOT GAS REHEAT

COMPRESSOR

P
F
N
G
M

A
L
K
J
A H Q

SIDE VIEW FRONT VIEW

A B C D E F G H J K L M N P Q
(in) 3.00 68.00 45.50 55.50 0.88 41.38 40.13 49.50 4.00 5.56 8.56 8.38 11.38 14.13 74.00

15
DIMENSIONS - RCA 171/201/271

TOP VIEW MULTI-DIMENSIONAL VIEW

COIL

LIQUID

SUCTION OPTIONAL HOT


COMPRESSOR ELECTRICAL GAS BYPASS
OPTIONAL HOT GAS REHEAT

J
B H

G
F
E

D A

SIDE VIEW BACK VIEW

A B C D E F G H J
(in) 64.25 52.88 51.38 79.00 22.00 25.50 29.00 16.00 21.00

16
DIMENSIONS - RCA 361/421

TOP VIEW MULTI-DIMENSIONAL VIEW

COIL

OPTIONAL HOT
GAS BYPASS
SUCTION LIQUID

ELECTRICAL OPTIONAL HOT GAS REHEAT


COMPRESSOR

B H
C
G
F
E

D A

SIDE VIEW BACK VIEW

A B C D E F G H J
(in) 101.25 53.63 52.13 84.00 22.00 25.50 29.00 16.00 21.00

17
REFERENCE INFORMATION
AMBIENT TEMPERATURE CORRECTION FACTORS
AMBIENT TEMPERATURE (°F) 85 90 95 100 105 110 115
TOTAL CAPACITY (Btu/h) 1.05 1.03 1.00 0.98 0.95 0.91 0.87
SENSIBLE CAPACITY (Btu/h) 1.03 1.02 1.00 0.99 0.97 0.97 0.93
ELECTRIC POWER (W) 0.95 0.98 1.00 1.03 1.05 1.08 1.11

RECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER BELOW CONDENSING UNIT (IN OD)
0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 5/8, 5/8 3/8 1/2 3/8 3/4, 3/4 1/2 1/2 3/8
48,000 3/4, 3/4 3/8 5/8 3/8 3/4, 3/4 1/2 5/8 3/8
60,000 3/4, 3/4 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/2
72,000 7/8, 7/8 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/2
84,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/2
96,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/2
120,000 1-1/8, 7/8 1/2 3/4 5/8 1-3/8, 1-1/8 5/8 3/4 5/8
150,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-1/8 5/8 7/8 5/8
180,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-3/8 5/8 7/8 5/8
220,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4
250,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4
300,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-5/8, 1-3/8 3/4 1-1/8 3/4
360,000 1-3/8, 1-5/8 3/4 1-1/8 7/8 1-5/8, 1-5/8 7/8 1-1/8 7/8
420,000 1-5/8, 1-5/8 3/4 1-3/8 7/8 1-5/8, 1-5/8 7/8 1-3/8 7/8

51-75 FT. EQUIVALENT LENGTH 76-100 FT. EQUIVALENT LENGTH


NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 7/8, 5/8 1/2 5/8 1/2 7/8, 3/4 1/2 5/8 N/A
48,000 7/8, 3/4 1/2 3/4 1/2 7/8, 7/8 1/2 5/8 N/A
60,000 1-1/8, 3/4 1/2 3/4 1/2 7/8, 7/8 1/2 3/4 N/A
72,000 1-1/8, 7/8 1/2 3/4 5/8 1-1/8, 7/8 5/8 3/4 N/A
84,000 1-1/8, 7/8 5/8 7/8 5/8 1-1/8, 7/8 5/8 3/4 N/A
96,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-1/8, 1-1/8 5/8 3/4 N/A
120,000 1-1/8, 1-1/8 5/8 7/8 3/4 1-1/8, 1-1/8 5/8 7/8 N/A
150,000 1-3/8, 1-1/8 5/8 1-1/8 3/4 1-3/8, 1-1/8 3/4 7/8 N/A
180,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 N/A
220,000 1-3/8, 1-3/8 3/4 1-1/8 7/8 1-5/8, 1-3/8 3/4 1-3/8 N/A
250,000 1-3/8, 1-3/8 3/4 1-3/8 7/8 1-5/8, 1-3/8 7/8 1-3/8 N/A
300,000 1-5/8, 1-3/8 7/8 1-3/8 1-1/8 2-1/8, 1-5/8 7/8 1-3/8 N/A
360,000 2-1/8, 1-5/8 7/8 1-3/8 1-1/8 2-1/8, 1-5/8 1-1/8 1-3/8 N/A
420,000 2-1/8, 1-5/8 1-1/8 1-3/8 1-1/8 2-1/8, 1-5/8 1-1/8 1-5/8 N/A
NOTES:
1. Line sizes are calculated assuming single scroll compressors in Models 051-201 and tandem scroll compressors in Models 271-421. Contact the factory for
any other compressor configuration.
2. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) Handbook-Refrigeration.
3. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to
high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation.
4. First suction line diameter size is for horizontal runs. Second suction line diameter size is for vertical risers.
5. Maximum suction line vertical lift is 60’. Riser-sized traps are required for every 20’ of vertical riser starting at the lowest point.
6. If ordered, hot gas reheat and hot gas bypass require only one line.
7. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an
alternative.
8. Contact factory for applications with digital scroll compressors.
9. Contact factory for layouts requiring more than 75’ of actual line length.

18
REFERENCE INFORMATION
RECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER LEVEL WITH OR ABOVE CONDENSING UNIT (IN OD)
0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 5/8 3/8 1/2 3/8 3/4 3/8 1/2 3/8
48,000 3/4 3/8 5/8 3/8 7/8 1/2 5/8 3/8
60,000 3/4 1/2 5/8 1/2 7/8 1/2 5/8 1/2
72,000 7/8 1/2 5/8 1/2 1-1/8 1/2 5/8 1/2
84,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/2
96,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/2
120,000 1-1/8 5/8 3/4 5/8 1-1/8 5/8 3/4 5/8
150,000 1-1/8 5/8 7/8 5/8 1-3/8 3/4 7/8 5/8
180,000 1-1/8 3/4 7/8 5/8 1-3/8 3/4 7/8 5/8
220,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4
250,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4
300,000 1-3/8 7/8 1-1/8 3/4 1-5/8 7/8 1-1/8 3/4
360,000 1-3/8 7/8 1-1/8 7/8 1-5/8 7/8 1-1/8 7/8
420,000 1-5/8 1-1/8 1-3/8 7/8 1-5/8 1-1/8 1-3/8 7/8

51-75 FT. EQUIVALENT LENGTH 76-100 FT. EQUIVALENT LENGTH


NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 3/4 3/8 5/8 1/2 3/4 1/2 5/8 N/A
48,000 7/8 1/2 3/4 1/2 7/8 1/2 5/8 N/A
60,000 7/8 1/2 3/4 1/2 7/8 1/2 3/4 N/A
72,000 7/8 1/2 3/4 5/8 7/8 1/2 3/4 N/A
84,000 1-1/8 5/8 7/8 5/8 1-1/8 5/8 3/4 N/A
96,000 1-1/8 5/8 7/8 5/8 1-1/8 5/8 3/4 N/A
120,000 1-1/8 3/4 7/8 3/4 1-3/8 5/8 7/8 N/A
150,000 1-3/8 3/4 1-1/8 3/4 1-3/8 3/4 7/8 N/A
180,000 1-5/8 3/4 1-1/8 3/4 1-3/8 3/4 1-1/8 N/A
220,000 1-5/8 7/8 1-1/8 7/8 1-5/8 3/4 1-3/8 N/A
250,000 1-5/8 7/8 1-3/8 7/8 1-5/8 7/8 1-3/8 N/A
300,000 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 N/A
360,000 2-1/8 1-1/8 1-3/8 1-1/8 2-1/8 1-1/8 1-3/8 N/A
420,000 2-1/8 1-1/8 1-3/8 1-1/8 2-1/8 1-1/8 1-5/8 N/A

NOTES:
1. Line sizes are calculated assuming single scroll compressors in Models 051-201 and tandem scroll compressors in Models 271-421. Contact the factory for
any other compressor configuration.
2. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) Handbook-Refrigeration.
3. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to
high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation.
4. Maximum suction line vertical lift is 60’. Loop piping to the top of the coil.
5. Maximum liquid line vertical lift is 60’.
6. If ordered, hot gas reheat and hot gas bypass require only one line.
7. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an
alternative.
8. Contact factory for applications with digital scroll compressors.
9. Contact factory for layouts requiring more than 75’ of actual line length.

19
THANK YOU FOR YOUR BUSINESS

7050 Overland Road


Orlando, FL 32810 U.S.A.
Telephone: +1.407.292.4400
Fax: +1.407.290.1329
www.addison-hvac.com

Installation Code and Quarterly Inspections: All installation and service of ADDISON® equipment must be performed by a contractor qualified in the
installation and service of equipment sold and supplied by Addison and conform to all requirements set forth in the ADDISON® manuals and all applicable
governmental authorities pertaining to the installation, service, operation and labeling of the equipment. To help facilitate optimum performance and safety,
Addison recommends that a qualified contractor conduct, at a minimum, quarterly inspections of your ADDISON® equipment and perform service where
necessary, using only replacement parts sold and supplied by Addison.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through
ADDISON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
These products (with the exception of the CGTH and UHA[X][S] 30 - 75) are not for residential use.
This document is intended to assist licensed professionals in the exercise of their professional judgment.
Specifications are subject to change without notice.

© 2014 Addison All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic,
electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission
of Addison.

Printed in the USA ADRCA2DSGNA 0114 Rev A