TRUONG THANH_49,984 PROJECT - YIELD ASSESMENT

SCENARIO TRUONG THANH.VC1


Inverters Units Pnom Ppeak Pnom Ppeak
Type "A" 32 1,562 kW 1,881 kW 50.0 MW 60.2 MW
Type "B" 0 0 kW 0 kW 0.0 MW 0.0 MW
ITEM % Loss kWh/m2 Pnom Project 50.0 MW
GHZ 1,801 Ppeak Project 60.2 MW
Orientation 1.65% 1,831 DC/AC 1.20x
Shading, linear -0.74% 1,817 System Fix --> 10º
IAM factor -3.20% 1,759 Free Dist. (m) 3.0 m
Soiling -2.50% 1,715 GCR 1.76x
Energy
ITEM % Loss
(MWh)
Array Nom Energy (STC) 103,285 93.7%
Irrad. Level -0.21% 103,071 93.6%
Temperature -8.17% 94,654 85.9%
Module Q 0.00% 94,654 85.9%
LID -1.00% 93,708 85.1%
Mismatch 0.00% 93,708 85.1%
Ohmic -0.95% 92,818 84.2%
Inverter efficiency -1.52% 91,404 83.0%
Others Inverter 0.00% 91,404 83.0%
Inverter nom power 0.00% 91,400 83.0%
Night & Auxiliary -0.01% 91,387 82.9%

Energy Eq H.
ITEM % Loss Plant factor PR
(MWh) (kWh/kWp)
Energy LV (Inverter) 91,387 1,519 17.3% 82.9%
AC Lines -0.26% 91,152 1,515 17.3% 82.7%
Transformation LV/MV -1.06% 90,187 1,499 17.1% 81.9%
Transmission Line -0.75% 89,511 1,487 17.0% 81.2%
Substation -0.25% 89,287 1,484 16.9% 81.0%
Self consumption -0.75% 88,618 1,473 16.8% 80.4%
Other 0.00% 88,618 1,473 16.8% 80.4%
Grid limit 0.00% 88,617 1,473 16.8% 80.4%

Availability -1.00% 87,731 1,458 16.6% 79.6%


1st year degradation -0.75% 87,073 1,447 16.5% 79.0%

Energy Eq H.
ITEM % Loss Plant factor PR
(MWh) (kWh/kWp)
P50 Avai.&Degr. 87,073 1,447 16.5% 79.0%
P90 Avai.&Degr. 79,287 1,317 15.0% 72.0%