Professional Documents
Culture Documents
http://biz.lgservice.com
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Floor Standing Type Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions....................................................................................................................................3
Functions ...................................................................................................................................................7
Wiring Diagram........................................................................................................................................12
Test running.............................................................................................................................................29
Exploded View.........................................................................................................................................41
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
■ Installation
Do not use a defective or under- Always ground the product. Install the panel and the cover
rated circuit breaker. Use this of control box securely.
appliance on a dedicated circuit.
• There is risk of fire or electric • There is risk of fire or electric • There is risk of fire or electric
shock. shock. shock.
Always install a dedicated cir- Use the correctly rated break- Do not modify or extend the
cuit and breaker. er or fuse. power cable.
• Improper wiring or installation may • There is risk of fire or electric • There is risk of fire or electric
cause fire or electric shock shock. shock.
Do not install, remove, or re- Be cautious when unpacking For installation, always con-
install the unit by yourself and installing the product. tact the dealer or an Autho-
(customer). rized Service Center.
• There is risk of fire, electric shock, • Sharp edges could cause injury. • There is risk of fire, electric shock,
explosion, or injury. Be especially careful of the case explosion, or injury.
edges and the fins on the con-
denser and evaporator.
Do not install the product on a Be sure the installation area Do not let the air conditioner
defective installation stand. does not deteriorate with age. run for a long time when the
humidity is very high and a
door or a window is left open.
• It may cause injury, accident, or • If the base collapses, the air condi- • Moisture may condense and wet or
damage to the product. tioner could fall with it, causing damage furniture.
property damage, product failure,
and personal injury.
■ Operational
Do not touch(operate) the Do not place a heater or other Do not let electric parts of the
product with wet hands. appliances near the power product get wet.
cable.
• There is risk of fire or electrical • There is risk of fire or electric • There is risk of fire, failure of the
shock. shock. product, or electric shock.
Do not store or use flammable gas or com- If strange sounds, or small or smoke comes
bustibles near the product. from product. Turn the breaker off or discon-
nect the power supply cable.
• There is risk of fire or failure of product. • There is risk of electric shock or fire.
nilosaG
Do not open the inlet grill of the product during Be cautious that water could not enter the
operation. (Do not touch the electrostatic filter, product.
if the unit is so equipped.)
• There is risk of physical injury, electric shock, or prod- • There is risk of fire, electric shock, or product damage.
uct failure.
■ Installation
Always check for gas (refrigerant) leakage after Install the drain hose to ensure that water is
installation or repair of product. drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the product.
• To avoid vibration or water leakage. • Avoid personal injury.
90˚
■ Operational
Use a soft cloth to clean. Do not use harsh Do not touch the metal parts of the product
detergents, solvents, etc. when removing the air filter. They are very
sharp!
• There is risk of fire, electric shock, or damage to the • There is risk of personal injury.
plastic parts of the product.
x
Wa Thinner
Do not step on or put anyting on the product. Do not insert hands or other objects through
(outdoor units) the air inlet or outlet while the product is oper-
ated.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Functions
Indoor Unit
• High, Low
Fan Operation
AutoRestart
Remote Control
Operation ON/OFF
Fan Operation
Timer Control
Energy Saving
• Up: up to 30°C
• Down: down to 16°C
• High, Low
Outdoor Unit
Deice Control
• De-ice PCB
• One speed
Product Specifications
• HEAT PUMP MODELS
MODEL AP-Z286RC0
AP-Z286R20 AP-Z488TC0 AP-Z728FA1
ITEMS UNIT AP-Z286R30
Power Supply Ø, V, Hz 1 , 220-240~,50 3 , 380~415~ ,50 3 , 380~415~ ,50
Capacity Btu/hr 28,000 46,000 68,240
Cooling Power Input W 2,800 5,300 7,000
Current A 13 9.5 11.1
Capacity Btu/hr 27,800 48,000 72,000
Heating Power Input W 2,800 5,000 6,000
Current A 13 9 10
Model 5JS330DJSA008 AR061YAB ARA081YAC
Maker Matsushita Ele. LG Ele. LG Ele.
Type Rotary Scroll Scroll
Compressor
Capacity Btu/h 28,101 50,800 68,500
Input W 2,915 5,347 20,075
LRA A 68 63 71
Indoor 48 / 46 / 40 53 / 51 / 48 60
Noise Level dB(A)
Outdoor 58 58 63
Indoor 17 (600) 30 / 28 / 26 (1,060 /989 / 918) 57 / - / 48 (2,013 / - / 1,695)
Air Circulation CMM(CFM)
Outdoor 2,048 (58) 3,673 (104) 4,765.2 (135)
Indoor Sirroco Sirroco Sirroco
Fan Type
Outdoor Propeller Propeller Propeller
Refrigerant (R410A) oz(kg) 77.6 (2.2) 102 (2.9) 123.5 (3.5)
Room Temperature Control Micom (16~30) Micom (16~30) Micom (16~30)
With 22.4 (570) 23.2 (590) 41.3 (1,050)
Indoor Height 71.6 (1,820) 72.8 (1,850) 74.0 (1,880)
Depth 12.5 (317) 17.3 (440) 19.5 (495)
Dimension Inch(mm)
Width 34.3 (870) 34.4 (900) 37.4 (950)
Outdoor Height 25.8 (655) 48.2 (1,225) 54.3 (1,380)
Depth 12.6 (320) 14.6 (370) 13 (330)
Indoor 70.5 (32) 132.3 (60) 291.0 (132)
Net Weight lb(kg)
Outdoor 138.9 (63) 198.4 (90) 238.1 (113)
Liquid 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Connections Inch(mm)
Gas 5/8 (15.88) 3/4 (19.05) 3/4 (19.05)
Antibiotic Filter
Ground Terminal
Refrigerant Pipe Port
■ AP-Z488TC0
Indoor Unit Outdoor Unit
Piping
■ AP-Z728FA1
Indoor Unit Outdoor Unit
Wiring Diagram
(1) AP-Z286RC0, AP-Z286R20, AP-Z286R30
■ INDOOR
*AP-Z286RC0
GN/YL
1 2
GN/YL
DOOR DOOR
S/W1 S/W1 BK BL T/B2
HVB A/CL REVERSING BK
VALVE
ASM UNIT BL
1 2 3 4 5
BL
BL WH RD BK BL BK
MAIN (AC) PCB ASM
4
RD C TH
CN-
AIRC RY-COMP Deice PCB
CN- CN- BL RD
4WAY HEATER
CN- VARISTOR FUSE(250V,3.15A)
3 WH
TNS L4
HEATER BR
CN-FAN/M L1
RY-HEATER RY-LOW RD GN/YL
RY-MID BL YL 2 BR
L2 L3
RY-HIGH BK FMi CAPACITOR BK 1 0 YL
RY-HEATER CN- RY-S/H WH T/B1
BR
HEATER OR 1 WH
CN-AC/M CN/YL OR BK
BL 6 8
RY-OPEN YL SYNC DOOR BK
(250V,5A)
FAN
POWER RELAY WH BR
MOTOR
CN- CN- STEP LE/RI 2 R S
HEATER LE/RI
MAIN (DC) PCB ASM M MOTOR WH
O.L.P OR YL
CN- STEP UP/DOWN WH
UP/DOWN M MOTOR POWER SUPPLY 1
PTC2 T/S FUSE
C COMP
CN- CN- CN-TOP CN-ROOM CAPACITOR
CN-KEY BK
E-HEATER
3854A20144Z
PTC1
Cr CAPACITOR(COMP)
STEP
STEP
■ INDOOR
*AP-Z286R20, AP-Z286R30
■ OUTDOOR
*AP-Z286RC0, AP-Z286R20, AP-Z286R30
(2) AP-Z488TC0
GN/YL
INDOOR ELECTRIC CIRCUIT
TO OUTDOOR UNIT
5
BL
4
AC PCB ASM RD
BR BR OR
1(L) 2(N) 3
INDOOR BK BL
CAPACITOR BL
MOTOR RD CN-OUTUNIT BR
YL YL
TERMINAL
DOOR S/W CN-FAN
FUSE
GN/YL 250V
BLOCK
BK RY-COMP 3.15A
ASSY
RD RD
H.V
CN-AIRC
OR
WH RY-4WAY
RD
BK
DOOR S/W HEAT PCB ASM RY-HIGH
RY-MID
AIR CN-
CN-HEAT RY-LOW
CLEANER HEAT
RY-SYNC
(AIR CLEANER MODEL ONLY)
PIPE CN- SYN.
SENSOR EVA TH CN- MOTOR
NOTE SYNC
CN-CABLE
RD : RED
BL : BLUE
BK : BLACK
BR : BROWN KEY PCB ASM
OR : ORANGE CN-CABLE
YL : YELLOW
CN- ROOM
GN/YL : GREEN/YELLOW ROOM TH SENSOR
DC PCB ASM
P/NO; 3854A20410A
TS TF
RY-1 PTC HEATER
RY-2 TS TF
PTC HEATER
BK
BK
BL
BL
1 2 3 4 5 6
POWER SUPPLY
(CONNECT CONTACT "R","N" OF OUTDOOR TERMINAL BLOCK "TM")
P/NO. : 3854A20411A
BK F1
BK D.P C TH
BK BK NO NC NO NC
TNS
WH
RD WH
WH F1 WH
OR
WH 52F1
BK BK
1 2
TM R S T N 1 3 5 21 OR
52C A1 OR 3 4
T/B1 WH 5 6
CRANK-CASE A2
POWER SUPPLY HEATER 2 4 6 22 7 8
3Ø,380-415V~,50Hz
T/B2
TERMINAL(4P)
BK
RD BL
RD
BK WH BK
BK
BK
Co Co
To the indoor unit
BK RD
1(L)
WH
WH 2(N)
RD
YL BK YL BK
(T1) 3
(T2)
OR OR (T3) V W BK BL 4
FMo FMo U 20SV 5
49FMo 49FMo BK BL
CM TMo
GN/YL
P/NO : 3854A20119V
(3) AP-Z728FA1
Operation Details
(1) The function of main control
1. Time Delay Safety Control
3min The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
3sec The indoor fan is ceased for 3 seconds to prevent relay noise.
(Protection of fan relay and micro chip)
30sec The 4-way valve is ceased for 30 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode.
A A
Setting Temp.
(Compressor ON)
Setting Temp. -1°C minimum minimum minimum
Hot 10sec. 10sec. 10sec.
Start minimum
10sec.
Selecting Selecting
Indoor Fan Speed OFF fan speed LOW OFF fan speed LOW OFF
• A point: The indoor pipe temperature to be less then 35°C & Discharge air Temperature to be less than 29°C.
The indoor fan operates for minimum 10sec. even if falls lower than 34°C.
During heating operation, the operating procedure of the indoor fan is as the following.
39˚C
34˚C
Heating Start
Stop(I) Low(II) Selecting Fan Speed(III)
(Hot-Start Operating)
A A
Setting Temp.
(Compressor ON)
Setting Temp. -1°C minimum minimum
Hot 10sec. 10sec.
Start minimum
1min
Selecting Selecting
Indoor Fan Speed OFF LOW fan speed LOW OFF fan speed LOW OFF
During heating operation, the operating procedure of the indoor fan is as the following.
Indoor Pipe Temp. D˚C D°C 28°C 30°C 32°C 26°C 28°C 30°C
B°C 27°C 29°C 31°C - - -
Heating Start
Stop(I) Low(II) Selecting Fan Speed(III)
(Hot-Start Operating)
6. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
• During heating operation, if piping temperatures fall below 26°C fan stops.
• The operation diagram is as following.
Maximum
INDOOR PIPE 1min
TEMP.
28°C
26°C
COMPRESSOR ON
7. Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than.
• Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises
over 12°C even if before 10 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes pass from
ending of the first defrost and more than.
-6°C
(Defrost ON)
HOT-
START
Selecting Selecting
Indoor Fan Speed fan speed LOW LOW LOW fan speed LOW LOW LOW
Compressor ON OFF ON OFF ON OFF ON OFF
27˚C
26˚C
25˚C
24˚C
23˚C
22˚C
21˚C
28min. 35min. 47min.
Setting energy Setting temp. Setting temp. Setting temp. maintains setting temp.
saving operation 23˚C 24˚C 25˚C 25˚C
100cm
• A place where noise prevention is taken into con-
sideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence, or other obstacles.
50cm
2) Outdoor unit
50cm
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat radi-
ation from the condenser is not restricted.
• There should not be any animals or plants which 0cm 50cm
could be affected by discharged hot air. 10
• Ensure the space indicated by arrows from the
wall, ceiling, fence, or other obstacles.
50c
m m
50c
0cm
10 50c
m
200mm
MODEL REFRIGERANT CHARGE
70mm
70mm AP-Z286RC0
90mm
INSIDE OUTSIDE
Wall
Plastic tube
(Bushing)
Tilt
Cut if necessary
Installation Method
1. Procedure
No. Installation works Descriptions
5 Tighten the flare nut (outdoor) Connecting the pipings of the outdoor unit.
9 Air purging of the piping and indoor unit The air which contains moisture and which
remains in the refrigeration cycle may cause a malfunction on the
compressor
12 Checking the drainage (indoor unit) To ensure if water flow drain hose of indoor unit.
14 Driver( , )
15 Pliers (150mm) Cutting the wires
16 Tapeline To measure the length
17 Core drill To make holes through the concrete wall and blocks
18 Voltmeter, Amperemeter, Clampmeter To measure the current and voltage
19 Insulation resistance tester To measure the insulation resistance
20 Glass thermometer To measure the intake and outlet air temperature of the indoor unit
21 Copper tubes To use the connecting pipings
22 Insulation material To cover the connecting pipings
23 Tape To finish the connecting pipings
24 Electrical Leakage Breaker To shut off the main power
25 Cable To connect the cable from outdoor unit to indoor unit
26 Drain hose sockets, elbows To remote the condensing water
1. Preparation of piping
Pipe cutter
Cut the pipes and the cable
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor and the Slanted Rough
90°
outdoor unit.
• Cut the pipes a little longer than measured
distance.
• Cut the cable 1.5m longer than the pipe length.
Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end down to avoid the metal powder
entering the pipe.
Pipe
Caution:
If burrs are not removed, they may cause a gas Reamer
leakage.
= Improper flaring =
1 2 3 4
2. Connection of piping
Move the indoor tubing and drain hose to the hole
• Remove tubing holder and pull the tubing out of the chassis.
Replace the tubing holder into original position
Route the tubing and the drain hose staight backwards.
Insert the connecting cable into the indoor unit through the hole.
• Do not connect the cable to the indoor unit
• Make a small loop with the cable for easy connection later.
Tape the tubing and the connecting cable.
Indoor unit installation.
Connecting the pipings to the indoor unit.
3. Precautions in bending
If it is necessary to bend or stretch the tubing,
use the spring which is attached to the tubing in
stead of pipe bender.
Spring
• Please make a careful notice to make a smooth line.
• Hold the tubing with your two hands closely and then
bend or stretch it slowly not to make any crack. R70mm
• Remember that the radius (R) should not exceed
70mm (Refer to Fig. 1)
Do not repeat the bending process to prevent the
tubing from cracking or crushing. (Fig. 1)
Keep in mind that the bending part should not be
cracked and make the radius (R) as long as possi-
ble (Refer to Fig. 2)`
R
(Fig. 2)
Test running
1. PRECAUTIONS IN TEST RUN
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
Carry out the test run more than 5 minutes without fail.
Caution
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the down room temperature checking button and ON/OFF button for 3 sec-
onds at the same time.
• To cancel the test run, press ON/OFF button.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring,
be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning,
temperature control, etc.).
3-way valve
1. Pump down
Gas side
Closed
3-Way
valve
Lo
CLOSE CLOSE
• Procedure
(1) Confirm that both liquid side and gas side (6) Operate the air conditioner in cooling mode
valves are set to the open position. and stop it when the gaug e indicates
– Remove the valve stem caps and confirm that 1kg/cm2g.
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate (7) Immediately set the 3-way valve to the closed
the valve stems. position.
– Do this quickly so that the gauge ends up indi-
(2) Operate the unit for 10 to 15 minutes. cating 3 to 5kg/cm2g.
(3) Stop operation and wait for 3 minutes, then (8) Disconnect the charge set, and mount the 2-
connect the charge set to the service port of way and 3-way valve’s stem nuts and the ser-
the 3-way valve. vice port nut.
– Connect the charge hose to the service port. – Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
(4) Air purging of the charge hose. – Be sure to check for gas leakage.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
1) Re-airpurging
(Re-installation)
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R22 OPEN CLOSE
• Procedure
(1) Confirm that both the liquid side valve and the (6) Disconnect the charge set and the gas cylin-
gas side valve are set to the closed position. der, and set the 2-way and 3-way valves to the
open position.
(2) Connect the charge set and a gas cylinder to – Be sure to use a hexagonal wrench to operate
the service port of the 3-way valve. the valve stems.
– Leave the valve on the gas cylinder closed.
(7) Mount the valve stem nuts and the service
(3) Air purging. port nut.
– Open the valves on the gas cylinder and the – Use torque wrench to tighten the service port
charge set. Purge the air by loosening the flare nut to a torque of 1.8 kg.m.
nut on the liquid side valve approximately 45° – Be sure to check for gas leakage.
for 3 seconds then closing it for 1 minute;
repeat 3 times. * CAUTION:
– After purging the air, use a torque wrench to Do not leak the gas in the air during Air Purg-
tighten the flare nut on liquid side valve. ing.
Gas side
3-Way
valve Open
Lo
OPEN CLOSE
• Procedure
(1) Confirm that both the liquid side and gas side (3) Open the valve (Lo side) on the charge set
valves are set to the back seat. and discharge the refrigerant until the gauge
indicates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s – If there is no air in the refrigerant cycle (the
port. pressure when the air conditioner is not run-
– Leave the valve on the charge set closed. ning is higher than 1 kg/cm2G), discharge the
– Connect the charge hose to the service port. refrigerant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
2. Evacuation
(All amount of refrigerant leaked)
Gas side
3-Way
valve Open
Vacuum pump
Lo
OPEN CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose (3) Close the valve (Lo side) on the charge set,
of charge set center hose turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
(2) Evacuation for approximately one hour. tely 5 minutes after turning off the vacuum
– Confirm that the gauge needle has moved pump).
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dir ty or
depleted, replenish as needed.
3. Gas Charging
(After Evacuation)
Gas side
Open
3-Way
Check valve valve
Charging
cylinder
Lo
(1) OPEN CLOSE
• Procedure
\
(3) Open the valve (Lo side on the charge set and (5) Mount the valve stem nuts and the service
charge the system with liquid refrigerant. port nut.
– If the system can not be charged with the spec- – Use torque wrench to tighten the service port
ified amount of refrigerant, it can be charged nut to a torque of 1.8 kg.m.
with a little at a time (approximately 150g each – Be sure to check for gas leakage.
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
2) Heating Mode
(After Evacuation)
Charging
cylinder
Lo
(1) OPEN CLOSE
Check valve
Gas side
Open
3-Way
valve
• Procedure
(1) Connect the charge hose to the charge cylinder.
• Connect the charge hose which you disconnected This is different from previous procedures.
from the vacuum pump to the valve at the bottom of Because you are charging with liquid refrigerant from
the cylinder. the gas side, absolutely do not attempt to charge with
• If you are using a gas cylinder, use a scale and larger amounts of liquid refrigerant while operating
reverse the cylinder so that the system can be the air conditioner.
charged with liquid.
(2) Purge the air from the charge hose. (4) Immediately disconnect the charge hose from the
• Open the valve at the bottom of the cylinder and 3-way valve's service port.
press the check valve on the charge set to purge • Stopping partway will allow the gas to be dis-
the air. (Be careful of the liquid refrigerant). The charged.
procedure is the same if using a gas cylinder. • If the system has been charged with liquid refriger-
(3) Open the valve (Lo side) on the charge set and ant while operating the air conditioner turn off the
charge the system with liquid refrigerant. air conditioner before disconnecting the hose.
• If the system can not be charged with the specified
amount of refrigerant, it can be charged with a little (5) Mount the valve stem nuts and the service port
at a time (approximately 150g each time) while nut.
operating the air conditioner in the cooling cycle; - Use a torque wrench to tighten the service port nut.
however, one time is not sufficient, wait approxi-
mately 1 minute and then repeat the procedure - Be sure to check gas leakage.
(pumping down-pin).
1. Check temperature difference between intake and discharge air and operating current.
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem-
perature difference is larger.
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
YES
YES
YES
YES
YES
Exchange MICOM
YES
NO
Is the AC220V
(AC 240 V) between connector YES
(CN-outunit) and of Main
P.C.B
Is the input power AC220V NO
(AC240V) at COMP magnetic coil
NO contactor?
NO
Is the unit operating? YES
Check the COMP magnetic Check the wiring
YES contactor of outdoor unit. connection
Reset the power NO
ON/OFF S/W ON Is it heating mode?
NO
Room temp <Set temp?
Replacement MICOM
YES
Is the DC5V NO
at 18 pin of terminal MICOM Replacement MICOM
YES
Is the DC12V
at each terminal? NO Replacement IC02M
(RY-4WAY COIL)
YES
Is the
AC220V (AC 240 V) between connec- NO
tor(4WAY) and CN-outunit of Main Replacement RY-4WAY
P.C.B
YES
Is the DC12V at NO
each terminal? (RY-COMP Replacement IC02M
COIL)
YES
Is the AC220V
(AC 240 V) between connector(CN-outunit) NO
Replacement RY-COMP
and of Main
P.C.B
YES
YES
YES
YES
YES
YES
Is the DC 12V NO
at eack terminal? (RY-HEATER Replacement IC02M
COIL)
YES
Is the
AC220V (AC 240 V) between NO
connector(HEATER) and CN-outunit of Replacement RY-HEATER
Main P.C.B
YES
Exploded View
■ AP-Z286RC0, AP-Z286R20, AP-Z286R30
1. Indoor Unit
137211
147582A 147582B
147581A
147581B
146811B 146811A
146811A
146811C 132111
146811B
235512 146811C
267110
437210A
W0CZZA 249941
268711B 135313B
249951 135303B
237201
135313A
135303A
W4810A
354210
W4811B
263230
135515
W4810B
35211A
159830A
35211C
266000
336600
266000
352150
130911
W4811A 159830B
266090
336610
349480
346810
140570
359012
2. Outdoor Unit
137213B
552203A
552203B
435511
437212
649950
552116
W6920
268711F
137213A
554160
W0CZZB
554031
C S
W0CZZC
R
349600
546810
430411
559010
447910
437210B
435512
349480
435301
■ AP-Z488TC0
1. Indoor Unit
135310
753000
267110
146812 753010
137211
268714
W4811
668713
W4810
354210
237202
354210
W4810
263230-1
330870
152302
135313
135515
249951
249941
268715
W0CZZ
W50400
359012
336610
346810
349480 W4810
135317
150170 349600
130400
435512
549610
2. Outdoor Unit
447910
556001 437212
W0CZZ
135301
268711
- 46 -
437210
552202
137213
554160 552201
W49800
552203
435511
150400
W52120
147780
430410 552203
■ AP-Z728FA1
1. Indoor Unit
437210
135080A
W49300A
135310
235450
268711A 135080A
149400C
149400E
149400D
W49300B
237900 147582
149410
149400A
149400B
237202
330720
359012 135316
336610A
359012 147911B
330720
W4810A
W0CZZA
749740A
159830
336610B
135303 349610
346810
135313
749740B
147911A
W4810B
268711B
249951
753010A
135515
753010B
137213G
137213C
137213F
W4811C
150170
137213A
354210
352118
137213B
354212
137213E
437212
352115
W4811A
137213D
W4811B
130400
330871
267110
263230
730700
552115
237205
Model
APUZ728FA1
2. Outdoor Unit
435512
Heating
546810
Classification
135500
349480 546810 W6640C
566001
- 49 -
Description
Compressor
Harness,Multi
W6640D 552200
649950
435301
W6640B
W6640A 552117
W6631 W52240
552116
566000
552202 554160
561410 55211G
Part Number
559010
TBZ30617501
EAD41895702
447910
148000
137213
661400
349480
W6631
554160
552203A
Location Number
552203B
437211
435301
-
430410 435513
Remark
152503
Exploded View