You are on page 1of 5

Shristi Enterprises

We work for Your safety

CERTIFICATE OF TEST & CALIBRATION


It is hereby confirmed that the unit has been inspected & tested for correct operation as per OME manual. This
Calibration report refers only to the instrument calibrated by us. Readings mentioned in this report are
Valid & Noted at the time of Calibration.
All Calibration gases are traceable to a known national / international standard.

Certificate No. AB151/2021-22 dated 07.08.2021

Customer Name : HPCL Vishkha Refinery


Type of Instrument : Fixed Gas Detector
Make : Oldhum
Model : OLCT-20
Sensor : SO2 Sensor
Range : 0 – 100ppm
Instrument Sr. No. : 18080AS-008
Acceptable Accuracy : +/-2%
Date of Calibrations : 07.08.2021
Sr. Sensor Type Zero Calibration Span Calibration Alarm -1 Alarm -2 Status
No. (Rising) (Rising)
SO2
1 Pass Pass 2 ppm 5 ppm Ok
(Electrochemical)
Date of Next Calibrations. 06.02.2022

Calibration Gas Details:


Calibration Gas Concentration Canister No. Valid Up to
SO2 50ppm SO2 Bal. Air 1545554 21.07.2022

Manufacturer: Effectech Gases Pvt. Limited


Traceable to: NPL, New Delhi

Calibration Result: Detector is calibrated Successfully

THANKING YOU
YOURS FAITHFULLY,
FOR SHRISTI ENTERPRISES

Guru Pandey
Service Engineer

Note: It is recommended that the Instrument (Sensor) should be Calibrated at least every Six
Months.

A/003, Sakharam Apt., Bldg. No.1, Tuliji Road, Nallasopara (E), Palghar - 401 209.
Mob.: +91 80972 37494 Email : sales@shrisenterprise.com GSTIN : 27BCPP1044G1Z9
Shristi Enterprises
We work for Your safety

CERTIFICATE OF TEST & CALIBRATION


It is hereby confirmed that the unit has been inspected & tested for correct operation as per OME manual. This
Calibration report refers only to the instrument calibrated by us. Readings mentioned in this report are
Valid & Noted at the time of Calibration.
All Calibration gases are traceable to a known national / international standard.

Certificate No. AB152/2021-22 dated 07.08.2021

Customer Name : HPCL Vishkha Refinery


Type of Instrument : Fixed Gas Detector
Make : Oldhum
Model : OLCT-20
Sensor : NO2 Sensor
Range : 0 – 100ppm
Instrument Sr. No. : 1709170-006
Acceptable Accuracy : +/-2%
Date of Calibrations : 07.08.2021
Sr. Sensor Type Zero Calibration Span Calibration Alarm -1 Alarm -2 Status
No. (Rising) (Rising)
NO2
1 Pass Pass 1 ppm 5 ppm Ok
(Electrochemical)
Date of Next Calibrations. 06.02.2022

Calibration Gas Details:


Calibration Gas Concentration Canister No. Valid Up to
NO2 50ppm NO2 Bal. Air 050285 25.12.2021

Manufacturer: Effectech Gases Pvt. Limited


Traceable to: NPL, New Delhi

Calibration Result: Detector is calibrated Successfully

THANKING YOU
YOURS FAITHFULLY,
FOR SHRISTI ENTERPRISES

Guru Pandey
Service Engineer

Note: It is recommended that the Instrument (Sensor) should be Calibrated at least every Six
Months.

A/003, Sakharam Apt., Bldg. No.1, Tuliji Road, Nallasopara (E), Palghar - 401 209.
Mob.: +91 80972 37494 Email : sales@shrisenterprise.com GSTIN : 27BCPP1044G1Z9
Shristi Enterprises
We work for Your safety

CERTIFICATE OF TEST & CALIBRATION


It is hereby confirmed that the unit has been inspected & tested for correct operation as per OME manual. This
Calibration report refers only to the instrument calibrated by us. Readings mentioned in this report are
Valid & Noted at the time of Calibration.
All Calibration gases are traceable to a known national / international standard.

Certificate No. AB153/2021-22 dated 07.08.2021

Customer Name : HPCL Vishkha Refinery


Type of Instrument : Fixed Gas Detector
Make : Oldhum
Model : OLCT-20
Sensor : Nh3 Sensor
Range : 0 – 100ppm
Instrument Sr. No. : 18011AB-023
Acceptable Accuracy : +/-2%
Date of Calibrations : 07.08.2021
Sr. Sensor Type Zero Calibration Span Calibration Alarm -1 Alarm -2 Status
No. (Rising) (Rising)
Nh3
1 Pass Pass 20 ppm 30 ppm Ok
(Electrochemical)
Date of Next Calibrations. 06.02.2022

Calibration Gas Details:


Calibration Gas Concentration Canister No. Valid Up to
Nh3 50ppm Nh3 Bal. Air 228771 01.01.2022

Manufacturer: Effectech Gases Pvt. Limited


Traceable to: NPL, New Delhi

Calibration Result: Detector is calibrated Successfully

THANKING YOU
YOURS FAITHFULLY,
FOR SHRISTI ENTERPRISES

Guru Pandey
Service Engineer

Note: It is recommended that the Instrument (Sensor) should be Calibrated at least every Six
Months.

A/003, Sakharam Apt., Bldg. No.1, Tuliji Road, Nallasopara (E), Palghar - 401 209.
Mob.: +91 80972 37494 Email : sales@shrisenterprise.com GSTIN : 27BCPP1044G1Z9
Shristi Enterprises
We work for Your safety

CERTIFICATE OF TEST & CALIBRATION


It is hereby confirmed that the unit has been inspected & tested for correct operation as per OME manual. This
Calibration report refers only to the instrument calibrated by us. Readings mentioned in this report are
Valid & Noted at the time of Calibration.
All Calibration gases are traceable to a known national / international standard.

Certificate No. AB154/2021-22 dated 07.08.2021

Customer Name : HPCL Vishkha Refinery


Type of Instrument : Fixed Gas Detector
Make : Oldhum
Model : OLCT-20
Sensor : H2S Sensor
Range : 0 – 100ppm
Instrument Sr. No. : 1807112-001
Acceptable Accuracy : +/-2%
Date of Calibrations : 07.08.2021
Sr. Sensor Type Zero Calibration Span Calibration Alarm -1 Alarm -2 Status
No. (Rising) (Rising)
H2S
1 Pass Pass 10 ppm 15 ppm Ok
(Electrochemical)
Date of Next Calibrations. 06.02.2022

Calibration Gas Details:


Calibration Gas Concentration Canister No. Valid Up to
H2S 25ppm H2S Bal. Air M1908006008 09.07.2022

Manufacturer: Effectech Gases Pvt. Limited


Traceable to: NPL, New Delhi

Calibration Result: Detector is calibrated Successfully

THANKING YOU
YOURS FAITHFULLY,
FOR SHRISTI ENTERPRISES

Guru Pandey
Service Engineer

Note: It is recommended that the Instrument (Sensor) should be Calibrated at least every Six
Months.

A/003, Sakharam Apt., Bldg. No.1, Tuliji Road, Nallasopara (E), Palghar - 401 209.
Mob.: +91 80972 37494 Email : sales@shrisenterprise.com GSTIN : 27BCPP1044G1Z9
Shristi Enterprises
We work for Your safety

CERTIFICATE OF TEST & CALIBRATION


It is hereby confirmed that the unit has been inspected & tested for correct operation as per OME manual. This
Calibration report refers only to the instrument calibrated by us. Readings mentioned in this report are
Valid & Noted at the time of Calibration.
All Calibration gases are traceable to a known national / international standard.

Certificate No. AB155/2021-22 dated 07.08.2021

Customer Name : HPCL Vishkha Refinery


Type of Instrument : Fixed Gas Detector
Make : Oldhum
Model : OLCT-20
Sensor : CO Sensor
Range : 0 – 100ppm
Instrument Sr. No. : 190109P-041
Acceptable Accuracy : +/-2%
Date of Calibrations : 07.08.2021
Sr. Sensor Type Zero Calibration Span Calibration Alarm -1 Alarm -2 Status
No. (Rising) (Rising)
CO
1 Pass Pass 20 ppm 35 ppm Ok
(Electrochemical)
Date of Next Calibrations. 06.02.2022

Calibration Gas Details:


Calibration Gas Concentration Canister No. Valid Up to
CO 100ppm CO Bal. Air M1908006008 09.07.2022

Manufacturer: Effectech Gases Pvt. Limited


Traceable to: NPL, New Delhi

Calibration Result: Detector is calibrated Successfully

THANKING YOU
YOURS FAITHFULLY,
FOR SHRISTI ENTERPRISES

Guru Pandey
Service Engineer

Note: It is recommended that the Instrument (Sensor) should be Calibrated at least every Six
Months.

A/003, Sakharam Apt., Bldg. No.1, Tuliji Road, Nallasopara (E), Palghar - 401 209.
Mob.: +91 80972 37494 Email : sales@shrisenterprise.com GSTIN : 27BCPP1044G1Z9

You might also like