Professional Documents
Culture Documents
Micom P631, P632, P633, P634: Transformer Differential Protection
Micom P631, P632, P633, P634: Transformer Differential Protection
Technical Manual
Regional English
The P63x menu texts (“data model”) referred to throughout this manual are regional texts which have been
customized for the UK/US and similar markets. Diagrams contained in this manual use this terminology. It is
commonly referred to as the “English (English)” data model and is denoted by -800 in the model number and
product documentation.
Refer to the Getting Started (GS) section for information on device and software setup to allow viewing of either
the Reference (English) or Regional (English) menu texts.
The original documentation for this product is still applicable and may be consulted for further reference; however
this manual is intended to provide the required information for setting, commissioning and maintaining the product
using this customized data model.
Note: The technical manual for this device gives instructions for its installation, commissioning, and
operation. However, the manual cannot cover all conceivable circumstances or include detailed
information on all topics. In the event of questions or specific problems, do not take any action
without proper authorization. Contact the appropriate AREVA technical sales office and request
the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of AREVA
including settlements of warranties, result solely from the applicable purchase contract, which is
not affected by the contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission of
AREVA, it will invalidate the warranty, and may render the product unsafe.
The AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered
or not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
SS
SAFETY SECTION
P63x/EN SS/D11 Safety Section
SS
Safety Section P63x/EN SS/D11
(SS) - 1
CONTENTS
1. INTRODUCTION 3 SS
2. HEALTH AND SAFETY 3
3.2 Labels 4
6.4 Environment 7
P63x/EN SS/D11 Safety Section
(SS) - 2
SS
Safety Section P63x/EN SS/D11
(SS) - 3
1. INTRODUCTION
This Safety Section and the relevant equipment documentation provide full information on SS
safe handling, commissioning and testing of this equipment also includes reference to typical
equipment label markings.
The technical data in this Safety Section is typical only, see the technical data section of the
relevant equipment documentation for data specific to a particular equipment.
Before carrying out any work on the equipment the user should be familiar with
the contents of this Safety Section and the ratings on the equipment’s rating
label.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.
• Are familiar with the installation, commissioning, and operation of the equipment and of
the system to which it is being connected;
• Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
• Are trained in the care and use of safety apparatus in accordance with safety
engineering practices;
(SS) - 4
Note: This symbol may also be used for a Protective Conductor (Earth) terminal if that
terminal is part of a terminal block or sub-assembly e.g. power supply.
3.2 Labels
See Safety Guide (SFTY/4L M) for typical equipment labeling information.
(SS) - 5
To ensure that wires are correctly terminated the correct crimp terminal and tool
for the wire size should be used.
The equipment must be connected in accordance with the appropriate connection
diagram.
Protection Class I Equipment SS
- Before energizing the equipment it must be earthed using the protective
conductor terminal, if provided, or the appropriate termination of the
supply plug in the case of plug connected equipment.
- The protective conductor (earth) connection must not be removed since
the protection against electric shock provided by the equipment would be
lost.
- When the protective (earth) conductor terminal (PCT) is also used to
terminate cable screens, etc., it is essential that the integrity of the
protective (earth) conductor is checked after the addition or removal of
such functional earth connections. For M4 stud PCTs the integrity of the
protective (earth) connections should be ensured by use of a locknut or
similar.
The recommended minimum protective conductor (earth) wire size is 2.5 mm²
(3.3 mm² for North America) unless otherwise stated in the technical data section
of the equipment documentation, or otherwise required by local or country wiring
regulations.
The protective conductor (earth) connection must be low-inductance and as short
as possible.
All connections to the equipment must have a defined potential. Connections that
are pre-wired, but not used, should preferably be grounded when binary inputs
and output relays are isolated. When binary inputs and output relays are
connected to common potential, the pre-wired but unused connections should be
connected to the common potential of the grouped connections.
Before energizing the equipment, the following should be checked:
- Voltage rating/polarity (rating label/equipment documentation);
- CT circuit rating (rating label) and integrity of connections;
- Protective fuse rating;
- Integrity of the protective conductor (earth) connection (where
applicable);
- Voltage and current rating of external wiring, applicable to the application.
Accidental touching of exposed terminals
If working in an area of restricted space, such as a cubicle, where there is a risk of
electric shock due to accidental touching of terminals which do not comply with
IP20 rating, then a suitable protective barrier should be provided.
Equipment use
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Removal of the equipment front panel/cover
Removal of the equipment front panel/cover may expose hazardous live parts,
which must not be touched until the electrical power is removed.
UL and CSA listed or recognized equipment
To maintain UL and CSA approvals the equipment should be installed using UL
and/or CSA listed or recognized parts of the following type: connection cables,
protective fuses/fuseholders or circuit breakers, insulation crimp terminals, and
replacement internal battery, as specified in the equipment documentation.
P63x/EN SS/D11 Safety Section
(SS) - 6
(SS) - 7
Disposal
It is recommended that incineration and disposal to water courses is avoided.
The equipment should be disposed of in a safe manner. Any equipment
containing batteries should have them removed before disposal, taking
precautions to avoid short circuits. Particular regulations within the country of
operation, may apply to the disposal of the equipment.
DANGER - CTs must NOT be fused since open circuiting them may
produce lethal hazardous voltages.
6.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet of housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
Pollution Degree - Pollution Degree 2 Compliance is demonstrated by reference to safety
Altitude - Operation up to 2000m standards.
IEC 60255-27:2005
EN 60255-27: 2006
P63x/EN SS/D11 Safety Section
(SS) - 8
SS
Introduction P63x/UK IT/A54
IT
INTRODUCTION
IT
Introduction P63x/UK IT/A54
CONTENTS
(IT) 1-
2. INTRODUCTION TO MiCOM 5
IT
3. PRODUCT SCOPE 6
3.1 Functional overview 6
FIGURES
IT
Introduction P63x/UK IT/A54
2. INTRODUCTION TO MiCOM
MiCOM is a comprehensive solution capable of meeting all electricity supply requirements.
It comprises a range of components, systems and services from AREVA T&D.
Central to the MiCOM concept is flexibility.
MiCOM provides the ability to define an application solution and, through extensive
communication capabilities, integrate it with your power supply control system.
The components within MiCOM are:
3. PRODUCT SCOPE
The P63x differential protection devices are designed for the fast and selective short-circuit
protection of transformers, motors and generators and of other two-, three- or four-winding
arrangements from distribution to transmission voltage levels. Four models are available.
The P631 and P632 are designed for the protection of two-winding arrangements, the P633
and P634 for the protection of three- or four-winding arrangements, respectively. The relay
also includes a comprehensive range of non-protection features to aid with power system
diagnosis and fault analysis.
• Fault signal recording (time-tagged signal logging with fault value recording of the phase
currents for each winding)
• Extended fault recording (fault recording of the neutral-point current for each winding as
well as the voltage)
P63x/UK IT/A54 Introduction
Application overview
Measuring inputs
Phase currents 2x3 2x3 4x3 4x3
Residual current or star-point current - 2 3 3
Inter
Communication COMM1 COMM2 IEC MiCOM
IRIG-B Self Recording
Monitoring and
to SCADA / Substation control / RTU / Modem ... Data
via RS485 or Optical Fibre Acquisition Overload rec.
using IEC 60870-5-101, -103, Modbus, DNP3, Courier
Iph resp.
via RJ45 or Fibre Optics using IEC 61850 LOGIC LIM-3 LIM-2 LIM-1 Metering
Fault rec.
V
27, 59 81 24
IY,a V<> f<> V/f
IY,b
87G 50 51
BC_4
REF_3 DTOC-3 IDMT-3
87G 50 51 49
BC _3
REF_2 DTOC-2 IDMT--2 THRM2
87G 50 51 49
Iph 87
REF_1 DTOC-1 IDMT--1 THRM1 BC_2
DIFF
BC_1
IY,c
Σ Σ Σ Σ Σ
Iph
Ivirtual
Iph
RTD,mA mA_OP always available Transformer Differential
optional or specific Protection P63x
MiCOM P631
Name Order number
Two Winding Transformer Diff. Prot. P631- 9 0 0 0 0 -305 -4xx -610 -46x -9x x -95 x -8xx
Basic device:
Basic device 40TE, pin-terminal connection, 3 -403
Basic device 40TE, ring-terminal connection, 4 -404
basic complement with 4 binary inputs and 8 output relays
Mounting option and display:
Surface-mounted, local control panel with text display
Flush-mounted, local control panel with text display
3
4 IT
Processor extension and Current transformer:
2) 8
With DSP-Coprocessor, Inom = 1 A / 5 A (T11...T13 / T21...23)
2) 9
Inom = 1 A / 5 A (T11...T13 / T21...23)
Power supply and additional outputs:
VA,nom = 24 VDC 3
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC 4
VA,nom = 24 VDC and 6 output relays, 4 with thyristor 6
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC 7
and 6 output relays, 4 with thyristor
VA,nom = 24 VDC and 6 output relays 8
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays 9
Switching threshold on binary inputs:
>18 V (standard variant) (without order extension no.)
8) -461
>90 V (60...70% of VA,nom = 125...150 V)
8) -462
>155 V (60...70% of VA,nom = 220...250 V)
8) -463
>73 V (67% of VA,nom = 110 V)
8) -464
>146 V (67% of VA,nom = 220 V)
With communication / information interface:
Only IRIG-B input for clock synchronization -90 0
Protocol IEC 60870-5-103 -91
Protocol can be switched between: -92
IEC 60870-5-101/-103, Modbus, DNP3, Courier
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)
For connection to wire, RS485, isolated 1
For connection to plastic fibre, FSMA connector 2
For connection to glass fibre, ST connector 4
Protocol IEC 61850: -94
For connection to 100 MHz Ethernet, glass fibre SC and wire RJ45 6
and 2nd interface (RS485, IEC 60870-5-103)
Language:
4) (without order extension no.)
English (German)
4) -800
Px40 English (English)
4) -801
German (English)
4) (on request) -802
French (English)
4) (on request) -803
Spanish (English)
4) (on request) -804
Polish (English)
4)
Russian (English) 7) (on request) -805
2) Switching via parameter, default setting is underlined!
4) Second included language in brackets
7) Hardware option, supports cyrillic letters instead of special West. Europe characters
8) Standard variant recommended, if higher pickup threshold not explicitly required by the application
P63x/UK IT/A54 Introduction
TD
TECHNICAL DATA
TD
Technical Data P63x/UK TD/A54
Installation Position
Vertical ±30°
Tests
Type Test
Degree of Protection Tests according to EN 60255-6 or IEC 255-6
Per EN 60529 or IEC 529 TD
IP 52; IP 20 for the rear connection area of the Electromagnetic Compatibility (EMC)
flush-mounted case
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A
Weight
Case 40 TE: approx. 7 kg
Case 84 TE: approx. 11 kg 1MHz-Burst Disturbance Test
Per IEC 255 Part 22-1 or IEC 60255-22-1,
Class III,
Dimensions
Common-mode test voltage: 2,5 kV,
See “Installation - IN, Section 7.”
Differential test voltage: 1,0 kV,
Test duration: > 2 s, Source impedance: 200 Ω
Terminal Connection Diagrams
See “Installation - IN, Section 8.”
Immunity to Electrostatic Discharge
Per EN 60255-22-2 or IEC 60255-22-2,
Terminals Level 3,
Contact discharge, single discharges : > 10,
PC Interface (X6) Holding time: > 5 s, Test voltage: 6 kV,
DIN 41652 connector, type D-Sub, 9-pin Test generator: 50...100 MΩ, 150 pF/330 Ω
Category 2, to ensure their safe operation in Switching threshold (as per order option)
gas Zones 1 and 2 hazardous areas. Standard variant: 18V (VA,nom: 24 ... 250 V DC):
Switching threshold range: 14 V ... 19 V DC
CAUTION - Equipment with this marking is not Special variant with switching thresholds from
itself suitable for operation within a potentially 58 ... 72 % of the nominal supply voltage
explosive atmosphere. (VA,nom)
Compliance demonstrated by Notified Body (definitively "low" at VA < 58 % of the nominal
certificates of compliance. supply voltage,
definitively "high" at VA > 72 % of the nominal
supply voltage):
"Special variant 73 V": nominal supply voltage
II (2) G 110 V DC
"Special variant 90 V": nominal supply voltage
127 V DC
"Special variant 146 V": nominal supply
Environmental Conditions
voltage 220 V DC TD
"Special variant 155 V": nominal supply
Ambient Temperature Range voltage 250 V DC
Recommended temperature range:
-5 °C...+55 °C, or +23 °F...+131 °F Power Consumption (as per order option):
Limit temperature range: Standard variant:
-25 °C...+70 °C, or -13 °F...+158 °F VA = 19...110V DC : 0.5 W ±30%
VA > 110V DC : VA × 5 mA ±30 %
Ambient Humidity Range Special variants:
≤ 75 % relative humidity (annual mean), VA > switching threshold: VA × 5mA ±30 %
up to 56 days at ≤ 95 % relative humidity and
40 °C, condensation not permissible Analog Inputs and Outputs
Direct Current Input
Solar Radiation Input current: 0...26 mA
Avoid exposure of the front panel to direct Value range: 0.00...1.20 IDC,nom (IDC,nom = 20
solar radiation mA)
Max. permissible continuous current: 50 mA
Maximum permissible input voltage: 17 V
Ratings Input load: 100 Ω
Measurement Inputs Open-circuit monitoring: 0...10 mA (adjustable)
Nominal frequency fnom: 50 Hz and 60 Hz Overload monitoring: > 24.8 mA
(settable) Zero suppression:
Operating range: 0.95...1.05 fnom 0.000...0.200 IDC,nom (adjustable)
Over/Underfrequency Protection: 40…70 Hz
Overexcitation Protection: 0.5…1.5 fnom Resistance Temperature Detector
For analog module only PT 100 permitted,
Current Value range: -40...+215 °C
Nominal current Inom: 1 A and 5 A (settable) 3-wire configuration: max. 20 Ω per conductor
Nominal consumption / phase: < 0.1 VA at Inom open and short-circuit input permitted
Load rating: Open circuit monitoring:
continuous: 4 Inom Θ > +215 °C (or Θ > +419 °F) and
for 10 s: 30 Inom Θ < -40 °C (or Θ > -40 °F)
for 1 s: 100 Inom
Nominal surge current: 250 Inom Direct Current Output
Output current: 0 … 20 mA
Voltage Maximum permissible load: 500 Ω
Nominal voltage Vnom: 50...130 V AC (settable) Maximum output voltage: 15 V
Nominal consumption per phase: < 0.3 VA at
Vnom = 130 V AC IRIG-B Interface
Load rating: continuous 150 V AC Min./max. input voltage level (peak-peak): 100
mVpp/20 Vpp
Binary Signal Inputs Input impedance: 33 kΩ at 1 kHz
Max. permissible voltage: 300 V DC Galvanic isolation: 2 kV
P63x/UK TD/A54 Technical Data
Currents
Dynamic range: 33 Inom
Amplitude resolution
at Inom = 1 A: 2.0 mAr.m.s.
at Inom = 5 A: 10.1 mAr.m.s.
Voltage
Dynamic range: 150 V
Amplitude resolution: 9.2 mVr.m.s.
TD
Mechanical Robustness
Vibration Test
Per IEC 60255-21-1: 1996:
Response Class 2
Endurance Class 2
Shock and Bump
Per IEC 60255-21-2: 1996:
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic Test
Per IEC 60255-21-3: 1995:
Class 2
Technical Data P63x/UK TD/A54
TD
Getting Started P63x/UK GS/A54
GS
GETTING STARTED
GS
Getting Started P63x/UK GS/A54
CONTENTS
(GS) 3-
1. GETTING STARTED 3
1.1 User interfaces and menu structure 3
1.5 HMI 8
1.5.7 Keys 11
1.9.1 PC requirements 26
FIGURES
1. GETTING STARTED
The front panel of the relay includes the following, as indicated in Figure 1:
− A 7-key keypad comprising 4 arrow keys (, , and ), an enter key
(), a clear key () and a read key ()
− 17 LEDs; 5 fixed function LEDs and 12 programmable function LEDs on the right hand
side
− The relay serial number, and the relay’s current and voltage rating information
− A 9-pin female D-type front port for communication with a PC locally to the relay
(up to 15m distance) via an EIA(RS)232 serial data connection
Trip (Red) indicates that the relay has issued a trip signal. It is reset when the associated
fault record is cleared from the front display. (Alternatively the trip LED can be configured to
be self-resetting)*.
Alarm (Yellow) flashes to indicate that the relay has registered an alarm. This may be
triggered by a fault, event or maintenance record. The LED will flash until the alarms have
been accepted (read), after which the LED will change to constant illumination, and will
extinguish, when the alarms have been cleared.
Out of service (Yellow) indicates that the relay’s protection is unavailable.
Healthy (Green) indicates that the relay is in correct working order, and should be on at all
times. It will be extinguished if the relay’s self-test facilities indicate that there is an error with
the relay’s hardware or software. The state of the healthy LED is reflected by the watchdog
contact at the back of the relay.
Edit Mode (Red) indicates the fact that the user is in the “Edit Mode”. In this mode, settings
can be changed.
Getting Started P63x/UK GS/A54
Programmable LEDs
The 12 programmable LEDs on the right hand side are suitable for programming alarm
indications.
GS
P1925ENa
GS
P1926ENa
The P63x design version can be determined from the order number. A breakdown of the
order number is given in the Introduction - IT section of this manual and in the Supporting
Documents supplied with the unit.
Once the ratings have been verified for the application, connect external power capable of
delivering the requirements specified on the label to perform the relay familiarization
procedures. Figure 2 and 3 indicates the location of the power supply terminals but please
refer to the wiring diagrams in the Installation - IN section for complete installation details
ensuring that the correct polarities are observed in the case of dc supply.
− The front panel user interface via the LCD and keypad
1.5 HMI
• Readout of cyclically updated measured operating data and logic state signals
• Readout of event logs after overload situations, ground faults, or short-circuits in the
power system
• Resetting of the device and triggering of additional control functions designed to support
testing and commissioning tasks
In addition, control via the PC interface is also possible. This requires a suitable PC and the
operating program S&R-103 for Windows.
G
GS
MiCOM P63x
Set/Func/ M+T/Meas/
Global Analogue Readings
GS Set/Func/
Common Settings
M+T/Meas/
I.O. Status Monitor
Set/Func/ M+T/Meas/
Setting Group SG1 Log. State Signals
Set/Func/
Setting Group SG2
Set/Func/
Setting Group SG3
Set/Func/
Setting Group SG4
1.5.7 Keys
Up and Down Keys
Panel Level:
By pressing the Up and Down keys, the user can switch between the Measured Value
Panels.
Menu Tree Level:
By pressing the Up and Down keys, the user can navigate up and down through the
menu tree in a vertical direction. If the unit is in input mode, the Up and Down keys
have a different function.
Input mode:
Setting values can only be changed in the input mode, which is signaled by the LED
labeled EDIT MODE. By pressing the Up and Down keys, the user can then change
the setting value. With list settings, the user can change the logic operator of the
value element by pressing the Up and Down keys. GS
Left and Right Keys
Panel Level:
By pressing the ENTER key at the Panel level, the user can go to the menu tree.
Menu Tree Level:
To enter the input mode, press the ENTER key. Press the ENTER key a second time
to accept the changes as entered and leave the input mode. The LED indicator
labeled EDIT MODE signals that the input mode is active.
Clear Key
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Getting Started P63x/UK GS/A54
Input mode:
Press the CLEAR key to reject the changes entered and leave the input mode.
Read Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
After the set return time has elapsed (setting in menu tree: “Set/Conf/HMI), the display will
automatically switch to the Panel level if a Measured Value Panel has been configured.
Illumination of the Display
If none of the control keys is pressed, the display illumination will switch off once the set
return time has elapsed (‘return time illumination’ setting in the menu tree at ‘Set/Conf/HMI’).
The display illumination is turned on again by pressing one of the control keys. In this case
the control action that is normally triggered by the key will not be Executed. Reactivation of
display illumination is also possible by way of a binary input.
If continuous illumination is desired, the user can set the ‘return time illumination’ function to
‘blocked’.
Getting Started P63x/UK GS/A54
MiCOM P63x
Set/Func/ M+T/Meas/
Global Analogue Readings
GS Set/Func/
Common Settings
M+T/Meas/
I.O. Status Monitor
Set/Func/ M+T/Meas/
Setting Group SG1 Log. State Signals
Set/Func/
Setting Group SG2
Set/Func/
Setting Group SG3
Set/Func/
Setting Group SG4
Change-Enabling Function
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
Getting Started P63x/UK GS/A54
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change only.
If several settings are to be changed, then the global change-enabling function is preferable.
In the following examples, the global change-enabling function has been activated.
Getting Started P63x/UK GS/A54
Automatic Return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Set/Conf/HMI’) has elapsed, the change-enabling function is automatically deactivated,
and the display switches to a Measured Value Panel corresponding to the current system
condition. The return time is restarted when any of the control keys is pressed.
Forced Return
The return described above can be forced from the local control panel by first pressing the
Up key and then holding it down while pressing the CLEAR key.
Note: It is important to press the Up key first and release it last in order to
avoid unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed. For
some settings it is also necessary to disable the protective function (menu tree:
Set/Func/Glob/MAIN, “Protection Enabled”). Such settings include the configuration
GS settings, by means of which the device interfaces can be adapted to the system. The
following entries in the ”Change” column of the address list (see appendix) indicate whether
values can be changed or not:
"on": The value can be changed even when the protective function is enabled.
"off": The value can only be changed when the protective function is disabled.
"-": The value can be read out but cannot be changed.
The device is factory-set so that the protection functions are disabled.
Changing Settings
If all the conditions for a value change are satisfied (see above), the desired setting can be
entered.
↓
8 If you wish to reject the new Set/Func/Glob/MAIN
setting while you are still entering Fct.Assig Trip Cmd.1
it (EDIT MODE LED is on), press #03 MAIN
the CLEAR key. The LED ?????
indicator will go out.
↓
1 Press the Down key to enter the Operat. Data Record.
operating data memory. The 01.01.97 12:05 MAIN
latest entry is displayed. Manual Trip Signal
End
2 Press the Left key repeatedly to Operat. Data Record.
display the entries one after the 01.01.97 12:05 MAIN
other in chronological order. Manual Trip Signal
Once the end of the operating Start
data memory has been reached,
pressing the Left key again will
have no effect.
GS
3 Press the Right key to display the Operat. Data Record.
previous entry. 01.01.97 12:05 MAIN
Manual Trip Signal
End
4 Press the Up key at any point M+T/Rec/OP_RC
within the operating data memory Operat. Data Record.
to return to the entry point.
↓
Resetting
All information memories - including the event memories and the monitoring signal memory -
and also the LED indicators can be reset manually. In addition, the LED indicators are
automatically cleared and initialized at the onset of a new fault - provided that the
appropriate operating mode has been selected - so that they always indicate the latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is always GS
possible in the standard control mode. This action also triggers an LED indicator test and an
LCD display test. The event memories are not affected by this action, so that inadvertent
deletion of the records associated with the reset signal pattern is reliably prevented.
Because of the ring structure of the event memories, the data for eight consecutive events
are updated automatically so that manual resetting should not be necessary, in principle. If
the event memories need to be cleared completely, however, as would be the case after
functional testing, this can be done after selecting the appropriate setting. The resetting
procedure will now be illustrated using the fault memory as an example. In this example the
global change-enabling function has already been activated.
GS
Figure 8: Relay keypad
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
Operation from the local control panel without password protection is also possible. To
select this option, immediately press the ENTER key a second time in steps 4 and 6 without
entering anything else. This will configure the local control panel without password
protection, and no control actions involving changes will be possible until the global
change-enabling function has been activated (see the section entitled ‘Change-Enabling
Function’).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
MiCOM relay
Laptop
GS
SK2
25 pin
SK1
download/monitor port
9 pin
Battery front comms port Serial communication port
(COM 1 or COM 2)
Serial data connector
(up to 15m)
P0107ENb
PC
MiCOM relay
P0108ENc
1.9.1 PC requirements
The following minimum requirements must be met for the MiCOM S1 software to properly
work on a PC.
• 64MB RAM
• 1.60GB free hard disk for the full installation, with 30MB minimum free on C:\
1 This port is actually compliant to EIA(RS)574; the 9-pin version of EIA(RS)232, see www.tiaonline.org.
Getting Started P63x/UK GS/A54
This section is intended as a quick start guide to using MiCOM S1 and assumes you have a
copy of MiCOM S1 installed on your PC. Please refer to the MiCOM S1 User Manual for
more detailed information.
To start MiCOM S1, click on the icon:
In the "Programs" menu, select "MiCOM S1" then "MiCOM S1 Start-up".
GS
The MiCOM S1 launcher is the software that gives access to the different application
programs:
GS
Select the ranges for baud rate and device address, select the parity and click the Identify
button. These settings can be checked and modified in the device in the menu tree
“Set/Conf/PC”. The default settings are Baud Rate: 19200, Bay Address: 1, Parity: Even.
Getting Started P63x/UK GS/A54
If a device is identified, the Device dialog box with information on this device is displayed.
GS
Click the Settings File button. This creates a new default settings file suitable for the data
model of the identified device.
To read out the current settings of the device, click Yes in the dialogue shown above. This
will update the default file with the device information and current settings.
Note: The default file will contain all possible hardware and software options
for the device. Reading out the active settings will configure the file to
show only those options available in the currently connected device.
Highlight the folder in the left part of the setting data window or highlight the setting you want
to read out and choose Read Value... from the Communication menu. If the first entry is
highlighted in the left part of the setting data window, that is the name of the IED, the
complete setting will be read out e.g.
Getting Started P63x/UK GS/A54
Select the relay type and firmware version required. e.g. a P634 relay, with firmware version
606 in the figure shown below. The language (in brackets) indicates the “Regional
GS Language” variant of the file. The customized English version on which this documentation
is based is indicated by (English), also as shown in figure below.
GS
To set the relay to display the “Regional Language” English on the HMI, go to
“Par/Conf/LOC: Language” (003.020) and set to “2nd language”. This setting will then be
displayed as “Set/Conf/HMI: Language” in the “Regional Language” English.
Refer to the MiCOM S1 Technical Guide section S1V23/EN HI/A21 for more information on
using the S1 S&R-103 setting software.
Getting Started P63x/UK GS/A54
GS
Settings P63x/UK ST/A54
ST
SETTINGS
ST
Settings P63x/UK ST/A54
CONTENTS
(ST) 4-
1. SETTINGS 5
1.1 Device ID 5
1.2 Configuration 9
1.3.1 Global 52
ST
P63x/UK ST/A54 Settings
ST
Settings P63x/UK ST/A54
1. SETTINGS
1.1 Device ID
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Device ID
DVICE: Device Type As per relay 631 762 1
000 000 Read only
The device type is displayed.
Not
DVICE: 655.35/
As per relay Measured/ 0.01
Software Version Overflow
0.00
002 120 Read only
Firmware version of the device. ST
DVICE: SW Date As per relay 01.01.97 - dd.mm.yy
002 122 Read only
Release date of the firmware.
Not
DVICE: SW Version 655.35/
As per relay Measured/ 0.01
Communic. Overflow
0.00
002 103 Read only
Firmware version of the communication module.
DVICE:
As per relay 0.0 899.9 0.1
Language Version
002 123 Read only
Language version of the device.
DVICE: Text Vers
As per relay 0 255 1
Data Model
002 121 Read only
Using the text replacement feature of S&R-103, the user can change the setting names
and descriptions contained within the data model and download them into the device. The
customized data models have a numeric “Text Version” field that can be updated to
indicate a customized data model. Standard data models have a factory-set default value
of 0.
DVICE:
As per relay 0.000000.0 - -
Serial Number
002 124 Read only
Serial number of the device.
DVICE: Order No. As per relay 00000000 - -
000 001 Read only
Order number of the device
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DVICE: Order ext.
0 0 999 1
No. 1 (… 27)
See table below for setting addresses.
Order extension numbers of the device. These settings can be modified by sending each
value to the device individually or via the front panel display.
Setting Address Setting Address Setting Address
Order ext. No. 1 000 003 Order ext. No. 10 000 012 Order ext. No. 19 000 021
Order ext. No. 2 000 004 Order ext. No. 11 000 013 Order ext. No. 20 000 022
Order ext. No. 3 000 005 Order ext. No. 12 000 014 Order ext. No. 21 000 023
Order ext. No. 4 000 006 Order ext. No. 13 000 015 Order ext. No. 22 000 024
Order ext. No. 5 000 007 Order ext. No. 14 000 016 Order ext. No. 23 000 025
Order ext. No. 6 000 008 Order ext. No. 15 000 017 Order ext. No. 24 000 026
Order ext. No. 7 000 009 Order ext. No. 16 000 018 Order ext. No. 25 000 027
ST Order ext. No. 8 000 010 Order ext. No. 17 000 019 Order ext. No. 26 000 028
Order ext. No. 9 000 011 Order ext. No. 18 000 020 Order ext. No. 27 000 029
Module A:
Module B:
Module L:
Module N:
DVICE: Module var. slot 1 Module P:
As per relay -
(… 21) Module T:
Module V:
Module X:
Module Y:
Not fitted
See table below for setting addresses. Read only
Stock number of the module fitted in the respective slot.
Setting Address Setting Address Setting Address
Module var. slot 1 086 050 Module var. slot 8 086 057 Module var. slot 15 086 064
Module var. slot 2 086 051 Module var. slot 9 086 058 Module var. slot 16 086 065
Module var. slot 3 086 052 Module var. slot 10 086 059 Module var. slot 17 086 066
Module var. slot 4 086 053 Module var. slot 11 086 060 Module var. slot 18 086 067
Module var. slot 5 086 054 Module var. slot 12 086 061 Module var. slot 19 086 068
Module var. slot 6 086 055 Module var. slot 13 086 062 Module var. slot 20 086 069
Module var. slot 7 086 056 Module var. slot 14 086 063 Module var. slot 21 086 070
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Version A
DVICE: Module vers. …
As per relay -
Slot 1 (… 21) Version Z
Not Fitted
See table below for setting addresses. Read only
Index letter specifying the version of the module fitted in the respective slot.
Setting Address Setting Address Setting Address
Module vers. Slot 1 086 193 Module vers. Slot 8 086 200 Module vers. Slot 15 086 207
Module vers. Slot 2 086 194 Module vers. Slot 9 086 201 Module vers. Slot 16 086 208
Module vers. Slot 3 086 195 Module vers. Slot 10 086 202 Module vers. Slot 17 086 209
Module vers. Slot 4 086 196 Module vers. Slot 11 086 203 Module vers. Slot 18 086 210
Module vers. Slot 5 086 197 Module vers. Slot 12 086 204 Module vers. Slot 19 086 211
Module vers. Slot 6 086 198 Module vers. Slot 13 086 205 Module vers. Slot 20 086 212
Module vers. Slot 7 086 199 Module vers. Slot 14 086 206 Module vers. Slot 21 086 213
DVICE:
ST
As per relay Not fitted Module A: -
Variant of Module A
086 047 Read only
Stock number of Module A in this design version.
DVICE:
As per relay Not fitted Module L: -
Variant of Module L
086 048 Read only
Stock number of Module L in this design version.
Version A
DVICE: …
As per relay -
Version of Module A Version Z
Not Fitted
086 190 Read only
Index letter specifying the version of Module A.
Version A
DVICE: …
As per relay -
Version of Module L Version Z
Not Fitted
086 191 Read only
Index letter specifying the version of Module L.
DVICE:
As per relay Not fitted Module B: -
Variant of Module B
086 049 Read only
Item number of digital bus Module B in this design version.
Version A
DVICE: …
As per relay -
Version of Module B Version Z
Not Fitted
086 192 Read only
Index letter specifying the version of the digital bus Module B.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DVICE: Variant of
As per relay Not fitted Module B: -
Module B (a)
086 046 Read only
Stock number of the analog bus Module B in this design version.
Version A
DVICE: Version of …
As per relay -
Module B (a) Version Z
Not Fitted
086 189 Read only
Index letter specifying the version of the analog bus Module B.
DVICE: MAC
As per relay -
Address Module A
104 061 Read only
MAC address for Ethernet module, where fitted.
ST DVICE: Customer ID
0.00 0.00 99.99 0.01
Data 1 (… 8)
See table below for setting addresses.
Customer configurable fields.
Setting Address Setting Address Setting Address
Customer ID Data 1 000 040 Customer ID Data 4 000 043 Customer ID Data 7 000 046
Customer ID Data 2 000 041 Customer ID Data 5 000 044 Customer ID Data 8 000 047
Customer ID Data 3 000 042 Customer ID Data 6 000 045
1.2 Configuration
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
Reference English
HMI: Language -
Language Reference Language
003 020
Language in which texts will be displayed on the local control panel.
Note: This Technical Manual is based on the 2nd Language or English setting of
this field. Relays with this data model will have a -800 order code in the
model number.
HMI: Decimal Point
Decimal Point -
Decimal Separator Comma
003 021
ST
Character to be used as decimal delimiter on the HMI.
HMI: Password - -
003 035 Displayed on HMI only (not in setting file).
The password to be used for changing settings from the HMI can be defined here. Refer to
Getting Started - GS for more information on entering/changing the password from the
HMI.
Signals from selection table
HMI: Read Key
Disabled dependent upon relay -
Assignment
configuration.
080 110
Selection of the event recording to be displayed when the read c key is pressed.
Signals from selection table
HMI:
Disabled dependent upon relay -
Operation Panel fct
configuration.
053 007 OP Fig. 83
Definition of the values to be displayed on the Measured Value Panel referred to as the
Operation Panel. This panel will be displayed during normal operation i.e. during normal
load conditions.
Signals from selection table
HMI:
Disabled dependent upon relay -
Overload Panel fct
configuration.
053 005 OP Fig. 85
Definition of the values to be displayed on the Overload Panel. This panel will be
displayed during overload conditions.
Signals from selection table
HMI: Fault Panel fct Disabled dependent upon relay -
configuration.
053 003 OP Fig. 84
Definition of the values to be displayed on the Fault Panel. This panel will be displayed
during and after fault conditions.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
HMI:
5s 1s 10 s 1s
Panel Hold-Time
031 075 OP Fig. 83
Setting for the time period for which a panel is displayed before the unit switches to the
next panel. This setting is only relevant if more values are selected for display than can be
shown on the LCD display at one time.
HMI:
60 s 60 s 60000 s 1s
Auto Return Time
003 014 OP Fig. 83
If the user does not press a key on the HMI during this set time period, the
change-enabling function is deactivated and the Operation Panel is called up provided that
values have been assigned to the Operation Panel and that there is no other event.
Blocked/
HMI: Backlight Time 60 s 60000 s 1s
60 s
ST 003 023
If the user does not press a key on the local control panel during this set time period, then
the backlighting of the LCD display is switched off.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
ALSTOM
PC: Manufacturer ALSTOM D AEG -
ALSTOM D
003 183 OP Fig. 86
Setting for the name of the device manufacturer.
Note: This setting can be changed to ensure compatibility.
PC: Bay Address 1 0 254 1
003 068 OP Fig. 86
Bay and device addresses are used to address the device in communication via the PC
(local front EIA(RS)232 port) interface. An identical setting must be selected for both
addresses.
PC: Relay Address 1 0 255 1
003 069 OP Fig. 86
Bay and device addresses are used to address the device in communication via the PC
(local front EIA(RS)232 port) interface. An identical setting must be selected for both
addresses.
300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
PC: Baud Rate 19.2 kBaud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
115.2 kBaud
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
003 081 OP Fig. 86
Baud rate of the PC (local front EIA(RS)232 port) interface.
Disabled
PC: Parity Bit Even -
Even
003 181 OP Fig. 86
Set the same parity that is set at the interface of the PC connected to the P63x.
None
PC: VDEW Only
None -
Spontan. Sig. Enable VDEW + Selected Sig.
All
003 187 OP Fig. 86
Enable for the transmission of spontaneous signals via the PC interface.
Signals from selection table
PC:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration. ST
003 189 OP Fig. 86
Selection of the spontaneous signals to be transmitted via the PC interface.
Disabled
ASDU 3.1 per IEC
ASDU 3.2 per IEC
ASDU 3.3 per IEC
ASDU 3.4 per IEC
PC: Transm Enab ASDU 9 per IEC
Disabled -
Cycl Dat ILS Message
ASDU 3.1 & 3.4 IEC
ASDU 3.2 & 3.4 IEC
ASDU 3.3 & 3.4 IEC
ASDU 9 & 3.4 per IEC
ASDU 9 & ILS telegr.
003 084 OP Fig. 86
Enable for the cyclic transmission of measured values via the PC interface.
PC:
Disabled -
Cycl. Data ILS Tel.
003 185 OP Fig. 86
Selection of the measured values that are transmitted in a user-defined message via the
PC interface.
PC: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
003 055 OP Fig. 86
A measured voltage value is transmitted via the PC interface if it differs by the set delta
quantity from the last measured value transmitted.
PC: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
003 056 OP Fig. 86
A measured current value is transmitted via the PC interface if it differs by the set delta
quantity from the last measured value transmitted.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
PC: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
003 057 OP Fig. 86
The measured frequency value is transmitted via the PC interface if it differs by the set
delta from the last measured value transmitted.
PC:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel
003 155 OP Fig. 86
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
PC: Delta t 1 min 0 min 15 min 1 min
003 058 OP Fig. 86
All measured data are transmitted again through the PC interface after this time period has
elapsed - provided that transmission has not been triggered by the other delta conditions.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
COMM1: Remote
Disabled Disabled Enabled -
Comms Port1
056 026
Enabling the COMM1 function or disabling it in the configuration. If the function is
disabled, then all associated settings and signals are hidden, with the exception of this
setting.
COMM1: General
No No Yes -
Enable USER
OP Fig. 88,
003 170 89, 90, 91,
92
Disabling or enabling the communication interface.
COMM1:
No No Yes -
IEC870-5 Enabled
003 215 OP Fig. 87
Common settings for enabling all protocols based on IEC 870-5-xxx.
COMM1:
No No Yes -
Addit. -101 Enable
003 216 OP Fig. 87
Enabling additional settings that are relevant for the protocol based on IEC 870-5-101.
COMM1:
No No Yes -
Addit. ILS Enable
003 217 OP Fig. 87
Enabling additional settings that are relevant for the ILS protocol.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
No No Yes -
MODBUS Enable
003 220 OP Fig. 87
Enabling settings relevant for the MODBUS protocol.
COMM1:
No No Yes -
DNP3 Enable
003 231 OP Fig. 87
Enabling settings relevant for the DNP 3.0 protocol.
COMM1:
No No Yes -
COURIER Enable
103 040 OP Fig. 87
Enabling settings relevant for the Courier protocol.
Signals from selection table
COMM1:
Communicat Protocol
Disabled dependent upon relay
configuration.
- ST
003 167 OP Fig. 87
Select the communication protocol that shall be used for the communication interface.
COMM1: ALSTOM
ALSTOM -
MODBUS Variant ALSTOM D
MODBUS protocol only OP Fig. 91
Select between the ALSTOM D and the ALSTOM variant of the MODBUS protocol.
COMM1: Light Off / Low
Light On / High -
Line Idle State Light On / High
003 165 OP Fig. 88,
89, 90, 91,
92
Setting for the line idle state indication.
300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
COMM1: Baud Rate 19.2 kBaud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
64.0 kBaud
OP Fig. 88,
003 071 89, 90, 91,
92
Baud rate of the communication interface.
Disabled
COMM1: Parity Bit Even Odd -
Even
003 171 OP Fig. 88,
89, 90, 91,
92
Set the same parity that is set at the interface of the control unit connected to the P63x.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Dead Time
Yes No Yes -
Monitoring
003 176 OP Fig. 88,
89, 90, 91,
92
The P63x monitors message transmission to make sure that no pause within a message
exceeds 33 bits. This monitoring function can be disabled if it is not required. This setting
is only necessary for modem transmission.
COMM1: Blocked/
25 s 254 s 1s
Mon. Time Polling 3s
003 202 OP Fig. 88,
89, 90, 91,
92
The time between two polling calls from the communication master must be less than the
time set here.
ST COMM1: Octet
Comm. Address
1 0 254 1
Setting Range
Menu Text Default Setting Step Size
Min. Max.
003 177 IEC 870-5 protocol only OP Fig. 88,
89, 90
Enable for the transmission of spontaneous signals via the communication interface.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration.
003 179 IEC 870-5 protocol only OP Fig. 88
Selection of the spontaneous signals to be transmitted via the COMM1 interface.
COMM1: Transm Disabled
Disabled -
Enab Cycl Dat ILS Message
003 074 IEC 870-5 protocol only OP Fig. 88,
89, 90
Enabling of cyclic transmission of measured values via the communication interface.
Signals from selection table
COMM1:
Cycl. Data ILS Tel.
Disabled dependent upon relay - ST
configuration.
003 175 IEC 870-5 protocol only OP Fig. 88,
89, 90
Selection of the measured values transmitted in a user-defined message via the
communication interface.
COMM1: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
003 050 IEC 870-5 protocol only OP Fig. 88,
89, 90
A measured voltage value is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
003 051 IEC 870-5 protocol only OP Fig. 88,
89, 90
A measured current value is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
003 052 IEC 870-5 protocol only OP Fig. 88,
89, 90
The measured frequency is transmitted via the communication interface if it differs by the
set delta quantity from the last measured value transmitted.
COMM1:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel
003 150 IEC 870-5 protocol only OP Fig. 88,
89, 90
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
COMM1: Delta t 1 min 0 min 15 min 1 min
003 053 IEC 870-5 protocol only OP Fig. 88,
89, 90
All measured data are transmitted again through the communication interface after this
time period has elapsed - provided that transmission has not been triggered by the other
delta conditions.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Blocked/
Blocked 9000 s 1s
Contin. General Scan 10 s
003 077 IEC 870-5 protocol only OP Fig. 88,
89, 90
A continuous or background general scan means that the P63x transmits all settings,
signals, and monitoring signals through the communication interface during slow periods
when there is not much activity. This ensures that there will be data consistency with a
connected control system. The time to be set defines the minimum time difference
between two messages.
COMM1: Comm.
1 Byte 1 Byte 2 Byte 1 Byte
Address Length
003 201 IEC 870-5-101 protocol only OP Fig. 89
Setting for the communication address length.
COMM1:
0 0 255 1
Octet 2 Comm. Addr.
ST 003 200 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the higher-order communication address.
COMM1: Cause W/o Source Address
W/o Source Address -
Transm. Length With Source Address
003 192 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the cause of transmission.
COMM1: Address
1 Byte 1 Byte 2 Byte 1 Byte
Length ASDU
003 193 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the common address for identification of message structures.
COMM1:
0 0 255 1
Octet 2 Addr. ASDU
003 194 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the common higher-order address for identification of message
structures.
COMM1:
2 Byte 2 Byte 3 Byte 1 Byte
Addr. Length Inf.Obj
003 196 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the address for information objects.
COMM1:
0 0 255 1
Oct.3 Addr. Inf.Obj.
003 197 IEC 870-5-101 protocol only OP Fig. 89
Setting for the length of the higher-order address for information objects.
COMM1:
No No Yes -
Inf.No.<-> Funct.Type
003 195 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether information numbers and function type shall be reversed in the
object address.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
3 Byte 3 Byte 7 Byte 1 Byte
Time Tag Length
003 198 IEC 870-5-101 protocol only OP Fig. 89
Setting for the time tag length.
COMM1:
Single Channel
ASDU1/ASDU20 Single Channel -
Dual Channel
Conv.
003 190 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether message structure 1 or 20 shall be converted as a single signal
or double signal.
Single Channel
COMM1:
Single Channel Dual Channel -
ASDU2 Conversion
Protection Event
003 191 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether message structure 2 shall be converted as a single signal or ST
double signal.
COMM1:
Yes No Yes -
Initializ Signal
003 199 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether an initialization signal shall be issued.
COMM1:
No No Yes -
Balanced Operation
003 226 IEC 870-5-101 protocol only OP Fig. 89
Setting specifying whether communication shall be operated in full duplex mode
(simultaneous transmission and reception).
COMM1: Direction Bit 0 0 1 1
003 227 IEC 870-5-101 protocol only OP Fig. 89
Setting for the control direction. As a rule, this value should be set to ‘1’ in the control
center and to ‘0’ in the substation.
COMM1:
0.40 s 0.10 s 2.55 s 0.01 s
Time-out Interval
003 228 IEC 870-5-101 protocol only OP Fig. 89
Setting for the maximum time before the status signal is issued for the acknowledge
command.
Signals from selection table
COMM1: Reg.asg.
Disabled dependent upon relay -
Selec. Cmds
configuration.
003 210 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 00301 to 00400 are assigned to the selected commands.
Assignment is made in the order of selection. This means that the first command is given
the register no. 00301, the second the register no. 00302, etc.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Reg.asg. Selec. Sig.
configuration.
003 211 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 10301 to 10400 are assigned to the selected signals.
Assignment is made in the order of selection. This means that the first signal is given the
register no. 10301, the second the register no. 10302, etc.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Reg.asg. Sel. m.val.
configuration.
003 212 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 30301 to 30400 are assigned to the selected measured
values. Assignment is made in the order of selection. This means that the first measured
value is given the register no. 30301, the second the register no. 30302, etc.
Signals from selection table
ST COMM1:
Reg.asg. Sel. Param.
Disabled dependent upon relay -
configuration.
003 213 MODBUS protocol only OP Fig. 91
MODBUS registers in the range 40301 to 40400 are assigned to the selected parameters.
Assignment is made in the order of selection. This means that the first measured value is
given the register no. 40301, the second the register no. 40302, etc.
COMM1:
5s 1s 120 s 1s
Delta t (MODBUS)
003 152 MODBUS protocol only OP Fig. 91
All MODBUS registers are transmitted again through the communication interface after this
time has elapsed.
COMM1: Autom
Disabled Disabled Enabled -
Event Confirm.
003 249 MODBUS protocol only OP Fig. 91
Setting as to whether an event confirmation by the master is necessary to delete an event
from the “event queue“.
COMM1:
0 Bit 0 Bit 254 Bit 1 Bit
Phys. Charact. Delay
003 241 DNP3 protocol only OP Fig. 92
Number of bits to be awaited from receiving the "Requests" to sending the "Response".
COMM1:
40 Bit 0 Bit 254 Bit 1 Bit
Phys. Char. Timeout
003 242 DNP3 protocol only OP Fig. 92
Number of bits that can be missing in the message without receive interrupt.
Never
COMM1: Multi-Frame
Multi-Frame Fragment -
Link Confirm. Mode Fragment
All Frames
003 243 DNP3 protocol only OP Fig. 92
Setting for the acknowledgement mode for confirmation within the link layer.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1:
0.10 s 0.05 s 2.54 s 0.01 s
Link Confirm.Timeout
003 244 DNP3 protocol only OP Fig. 92
Setting for the link layer timeout period. Within the link layer, the master needs to
acknowledge (confirm) within this period.
COMM1:
2 1 10 1
Link Max. Retries
003 245 DNP3 protocol only OP Fig. 92
Number of repetitions performed within the link layer after the occurrence of errors during
transmission (such as failure to acknowledge).
COMM1:
5.0 s 0.5 s 25.4 s 0.1 s
Appl Confirm.Timeout
003 246 DNP3 protocol only OP Fig. 92
Setting for the application layer timeout period. Within the application layer, the master
needs to acknowledge (confirm) within this period. ST
COMM1:
60 s 5s 254 s 1s
Appl Need Time Del.
003 247 DNP3 protocol only OP Fig. 92
Within the time interval set here, the slave cyclically issues a clock synchronization request
to the master.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. bin. Inputs
configuration.
003 232 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 1 - binary inputs. Indices are assigned
in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. bin.Outputs
configuration.
003 233 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 10 - binary outputs. Indices are
assigned in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. Analog Inp.
configuration.
003 235 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 30 - analog inputs. Indices are
assigned in the sequence of the selection and beginning with 0.
Signals from selection table
COMM1:
Disabled dependent upon relay -
Ind./cl. Analog Outp
configuration.
003 236 DNP3 protocol only OP Fig. 92
Selection of data points and data classes for object 40 - analog outputs. Indices are
assigned in the sequence of the selection and beginning with 0.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM1: Ph-Ph
16 0 255 1
Meas v. (DNP3)
003 250 DNP3 protocol only OP Fig. 92
Initialization value of the thresholds for the transmission of measured data in object 30.
The threshold values may be changed separately by the master for each measured value
by writing to object 34, "Analog Input Reporting Deadband".
COMM1: Phase
5s 1s 120 s 1s
Phase t (DNP3)
003 248 DNP3 protocol only OP Fig. 92
Cycle time of updating the DNP objects 30 (analog inputs).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Command Selection
configuration.
103 042 Courier protocol only OP Fig. 93
ST This setting is used to select from an “m out of n” selection table all the binary commands
(read/write) which are to be made available to the Courier master (e.g. ’Device online’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Signal Selection
configuration.
103 043 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the binary signals (read
only) which are to be made available to the Courier master (e.g. ’Starting I>’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Meas. val. Selection
configuration.
103 044 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the analog
measurements (read only) which are to be made available to the Courier master (e.g.
’Running time’).
Signals from selection table
COMM1:
Disabled dependent upon relay -
Parameter Selection
configuration.
103 045 Courier protocol only OP Fig. 93
This setting is used to select from an “m out of n” selection table all the analog settings
(read/write) which are to be made available to the Courier master (e.g. ’tI>’).
COMM1:
5s 1s 120 s 1s
Delta t (COURIER)
103 046 Courier protocol only OP Fig. 93
All Courier registers are transmitted again through the communication interface after this
time has elapsed.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings/Configuration
COMM2: Remote
Disabled Disabled Enabled -
Comms Port2
056 057
Enabling the COMM2 function or disabling it in the configuration. If the function is
disabled, then all associated settings and signals are hidden, with the exception of this
setting.
COMM2: General
No No Yes -
Enable USER
103 170 OP Fig. 95
Disabling or enabling the communication interface.
COMM2: Light Off/Low
Light On/High -
Line Idle State Light On/High ST
103 165 OP Fig. 95
Setting for the line idle state indication.
300 Baud
600 Baud
1200 Baud
2400 Baud
COMM2: Baud Rate 19.2 kBaud 4800 Baud -
9600 Baud
19.2 kBaud
38.4 kBaud
57.6 kBaud
103 071 OP Fig. 95
Baud rate of the communication interface.
Disabled
COMM2: Parity Bit Even Odd -
Even
103 171 OP Fig. 95
Set the same parity that is set at the interface of the control unit connected to the P63x.
COMM2: Dead Time
Yes No Yes -
Monitoring
103 176 OP Fig. 95
The P63x monitors message transmission to make sure that no pause within a message
exceeds 33 bits. This monitoring function can be disabled if it is not required. This setting
is only necessary for modem transmission.
COMM2:
25 s Blocked/3 s 254 s 1s
Mon. Time Polling
103 202 OP Fig. 95
The time between two polling calls from the communication master must be less than the
time set here.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: Octet
1 0 254 1
Comm. Address
103 072 OP Fig. 95
The communication address and the ASDU address are used to identify the device in
communication via the interface. An identical setting must be selected for both addresses.
ALSTOM
COMM2:
ALSTOM D AEG -
Manufacturer
ALSTOM D
103 161 OP Fig. 95
Setting for the name of the device manufacturer.
COMM2:
1 0 255 1
Octet Address ASDU
103 073 OP Fig. 95
The communication address and the ASDU address are used to identify the device in
ST communication via the interface. An identical setting must be selected for both addresses.
None
COMM2: VDEW Only
All -
Spontan. Sig. Enable VDEW + Selected Sig.
All
103 177 OP Fig. 95
Enable for the transmission of spontaneous signals via the communication interface.
Signals from selection table
COMM2:
Disabled dependent upon relay -
Select. Spontan.Sig.
configuration.
103 179 OP Fig. 95
Selection of the spontaneous signals to be transmitted via the COMM1 interface.
Disabled
ASDU 3.1 per IEC
ASDU 3.2 per IEC
ASDU 3.3 per IEC
ASDU 3.4 per IEC
COMM2: Transm ASDU 9 per IEC
Disabled -
Enab Cycl Dat ILS Message
ASDU 3.1 & 3.4 IEC
ASDU 3.2 & 3.4 IEC
ASDU 3.3 & 3.4 IEC
ASDU 9 & 3.4 per IEC
ASDU 9 & ILS telegr.
103 074 OP Fig. 95
Enable for the cyclic transmission of measured values via the COMM2 interface.
Signals from selection table
COMM2:
Disabled dependent upon relay -
Cycl. Data ILS Tel.
configuration.
103 175 OP Fig. 95
Selection of the measured values that are transmitted in a user-defined message via the
COMM2 interface.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: Delta V 3.0 %Vn 0.0 %Vn 15.0 %Vn 0.1 %Vn
103 050 OP Fig. 95
A measured voltage value is transmitted via the COMM2 interface if it differs by the set
delta quantity from the last measured value transmitted.
COMM2: Delta I 3.0 %In 0.0 %In 15.0 %In 0.1 %In
103 051 OP Fig. 95
A measured current value is transmitted via the COMM2 interface if it differs by the set
delta quantity from the last measured value transmitted.
COMM2: Delta f 2.0 %fn 0.0 %fn 2.0 %fn 0.1 %fn
103 052 OP Fig. 95
The measured frequency value is transmitted via the COMM2 interface if it differs by the
set delta from the last measured value transmitted.
COMM2:
3.0 0.0 15.0 0.1
Delta Meas.v.ILS Tel ST
103 150 OP Fig. 95
The message is transmitted if a measured value differs by the set delta quantity from the
last measured value transmitted.
COMM2: Delta t 1 min 0 min 15 min 1 min
103 053 OP Fig. 95
All measured data are transmitted again through the COMM2 interface after this time
period has elapsed - provided that transmission has not been triggered by the other delta
conditions.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IEC: IEC
Disabled Disabled Enabled -
Communication
056 059
Enabling or disabling Ethernet IEC 61850 communication. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
IEC: General Enable
No No Yes -
USER
104 000
Enabling and disabling IEC 61850.
IEC: Don’t Execute
Don’t Execute -
Enable Configuration Execute
104 058
This setting can only be sent individually. In order to maintain consistency of all settings in
the function groups IEC, GSSE and GOOSE, they are all enabled mutually by this
parameter.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: Inactivity Timer 15 min 1 min 30 min 1 min
104 050
Additional communication monitor for Ethernet. Should a logged-on client issue no further
request message, after this time period has elapsed that client will automatically be
logged-off, i.e. no further reports will be issued to it. To re-establish communication the
client is required to perform a new log-on procedure with the device (IED).
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 2 .255
104 019
IP address of network router # 2.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 2 .255
104 023
IP address of target network # 2.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 3 .255
104 027
IP address of network router # 3.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 3 .255 ST
104 031
IP address of target network # 3.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Router Address 4 .255
104 035
IP address of network router # 4.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
Target Network 4 .255
104 039
IP address of target network # 4.
IEC: SNTP Operating Request from Request from Server
-
Mode Server Broadcast
104 200
Operating mode for the time synchronization telegram. When set to Broadcast
synchronization occurs cyclically with the clock server transmitting a broadcast signal and,
when set to Request from Server each device (IED has client function) individually
requests a synchronization signal after its own cycle time.
IEC: SNTP Poll Cycle
60 s 20 s 600 s 1s
Time
104 201
Device (IED) poll cycle time for time synchronization when operating mode is set to
Request from Server.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
SNTP Server 1 IP .255
104 202
IP address of the first synchronizing clock server.
IEC: 255.255.255
0.0.0.0 0.0.0.0 -
SNTP Server 2 IP .255
104 202
IP address of the second synchronizing clock server.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IEC: Diff. Local Time 0 -1440 min + 1440 min 1 min
104 206
Time difference between UTC (Coordinated Universal Time/GMT) and local time at
installation site.
IEC:
60 min -1440 min + 1440 min 1 min
Diff. Dayl. Sav. Time
104 207
Time difference when changing to daylight saving time.
IEC: Deadband Value 100 0 10000 1
104 051
Setting to calculate the filter value for all measured value Report Control Blocks (RCB)
except the measured value for energy. Should a change occur in one of the measured
values, which is greater than the filter value, the RCB is again sent to all clients.
ST IEC:
Update Cycle Energy
Blocked 10 3600 1
104 060
Cycle time to send energy value by Report Control Block (RCB). No RCB transmission
with setting to blocked!
Setting Range
Menu Text Default Setting Step Size
Min. Max.
GOOSE:
Disabled Enabled/Disabled -
Gen.Obj.Or.SubstEvent
056 068
The parameters of this function group are only active if function group IEC has been
configured and is activated, and if the parameters of this function group have been
activated through the parameter IEC: Enable configuration or by switching the device
off-line/on-line.
GOOSE: General
No No/Yes -
Enable USER
106 001
Enabling and disabling function group GOOSE.
GOOSE:
01-0C-CD-01-00-00 - -
Multic. MAC Address
106 003
Multicast MAC address to provide identification of GOOSE to the receiving clients (IED).
The default MAC address entered is suggested as a standard according to IEC 61850.
The multicast MAC address entered in GOOSE may be modified so as to increase
transmission security or to reduce the number of "GOOSE Messages" to be read by
receiving clients (IED).
GOOSE:
12288 0…16383 1
Application ID
106 004
Application ID of GOOSE being sent by this device (IED).
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
GOOSE: GOOSE ID - - -
106 002
GOOSE ID being sent by this device (IED). GOOSE includes a Dataset with 32 binary and
configurable virtual outputs and 10 two-pole states to the maximum of 10 monitored
external devices.
GOOSE:
0 0…4094 1
VLAN Identifier
106 006
VLAN identifier of GOOSE being sent by this device (IED). The VLAN identifier makes it
possible to have switches in the network filter messages, if the switches support such a
function. Because so-called multicast MAC addresses are applied, switches are unable to
filter messages in the network if they do not include a VLAN identifier.
GOOSE:
4 0…7 1
VLAN Priority
106 007
ST
VLAN priority of GOOSE being sent by this device (IED). The VLAN priority makes it
possible to have switches in the network filter messages, if the switches support such a
function.
GOOSE: GOOSE Signals from selection table
Out 1 (… 32) Disabled dependent upon relay -
fct.assig. configuration.
See table below for setting addresses.
Function assignment of a binary logical state signal to the virtual GOOSE outputs. The
signal configured here is sent with the permanently configured Dataset of GOOSE.
Setting Address Setting Address Setting Address
GOOSE Out 1 GOOSE Out 12 GOOSE Out 23
106 011 106 033 106 055
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 2 GOOSE Out 13 GOOSE Out 24
106 013 106 035 106 057
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 3 GOOSE Out 14 GOOSE Out 25
106 015 106 037 106 059
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 4 GOOSE Out 15 GOOSE Out 26
106 017 106 039 106 061
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 5 GOOSE Out 16 GOOSE Out 27
106 019 106 041 106 063
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 6 GOOSE Out 17 GOOSE Out 28
106 021 106 043 106 065
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 7 GOOSE Out 18 GOOSE Out 29
106 023 106 045 106 067
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 8 GOOSE Out 19 GOOSE Out 30
106 025 106 047 106 069
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 9 GOOSE Out 20 GOOSE Out 31
106 027 106 049 106 071
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 10 GOOSE Out 21 GOOSE Out 32
106 029 106 051 106 073
Fct.assig. Fct.assig. Fct.assig.
GOOSE Out 11 GOOSE Out 22
106 031 106 053
Fct.assig. Fct.assig.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Blocked dependent upon relay -
1 (… 16) Applic. ID
configuration.
See table below for setting addresses.
Application ID for GOOSE, which is to be received by this device (IED) for the virtual binary
GOOSE input.
Setting Address Setting Address
GOOSE Inp 1 Applic. ID 107 000 GOOSE Inp 12Applic. ID 107 110
GOOSE Inp 2 Applic. ID 107 010 GOOSE Inp 13Applic. ID 107 120
GOOSE Inp 3 Applic. ID 107 020 GOOSE Inp 14 Applic. ID 107 130
GOOSE Inp 4 Applic. ID 107 030 GOOSE Inp 15 Applic. ID 107 140
GOOSE Inp 5 Applic. ID 107 040 GOOSE Inp 16 Applic. ID 107 150
GOOSE Inp 6 Applic. ID 107 050
GOOSE Inp 7 Applic. ID 107 060
ST GOOSE Inp 8 Applic. ID 107 070
GOOSE Inp 9 Applic. ID 107 080
GOOSE Inp 10 Applic. ID 107 090
GOOSE Inp 11 Applic. ID 107 100
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) DataSetRef
configuration.
See table below for setting addresses.
'DataSetReference' for GOOSE, which is to be received by this device (IED) for the virtual
binary GOOSE input. 'DataSetReference' consists of a chain of characters including the
full path of the state value from the device (IED) with which the P63x corresponds with the
logical device/logical node/data object/data attribute. If a path is made up of more than 20
characters, then only the first 20 characters are to be entered.
Setting Address Setting Address
GOOSE Inp 1 DataSetRef 107 002 GOOSE Inp 12 DataSetRef 107 112
GOOSE Inp 2 DataSetRef 107 012 GOOSE Inp 13 DataSetRef 107 122
GOOSE Inp 3 DataSetRef 107 022 GOOSE Inp 14 DataSetRef 107 132
GOOSE Inp 4 DataSetRef 107 032 GOOSE Inp 15 DataSetRef 107 142
GOOSE Inp 5 DataSetRef 107 042 GOOSE Inp 16 DataSetRef 107 152
GOOSE Inp 6 DataSetRef 107 052
ST
GOOSE Inp 7 DataSetRef 107 062
GOOSE Inp 8 DataSetRef 107 072
GOOSE Inp 9 DataSetRef 107 082
GOOSE Inp 10 DataSetRef 107 092
GOOSE Inp 11 DataSetRef 107 102
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) DatAttr Ind
configuration.
See table below for setting addresses.
Data attribute index of a Dataset for GOOSE, which is to be received by this device (IED)
for the virtual binary GOOSE input. A data attribute index indicates which data attribute
element in the data object is to be evaluated.
Setting Address Setting Address
GOOSE Inp 1 DatAttr Ind 107 004 GOOSE Inp 12 DatAttr Ind 107 114
GOOSE Inp 2 DatAttr Ind 107 014 GOOSE Inp 13 DatAttr Ind 107 124
GOOSE Inp 3 DatAttr Ind 107 024 GOOSE Inp 14 DatAttr Ind 107 134
GOOSE Inp 4 DatAttr Ind 107 034 GOOSE Inp 15 DatAttr Ind 107 144
GOOSE Inp 5 DatAttr Ind 107 044 GOOSE Inp 16 DatAttr Ind 107 154
GOOSE Inp 6 DatAttr Ind 107 054
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
GOOSE: GOOSE Inp
Disabled dependent upon relay -
1 (… 16) fct.assig.
configuration.
See table below for setting addresses.
Function assignment of the virtual binary GOOSE input to a binary logical state signal on
the device (IED) so that it can be processed further by the protection, control or logic
functions. The signal configured at this point will receive the state of the data attribute, as
configured above, and which was received with the Dataset of GOOSE.
Setting Address Setting Address
GOOSE Inp 1 fct.assig. 107 006 GOOSE Inp 12 fct.assig. 107 116
GOOSE Inp 2 fct.assig. 107 016 GOOSE Inp 13 fct.assig. 107 126
GOOSE Inp 3 fct.assig. 107 026 GOOSE Inp 14 fct.assig. 107 136
GOOSE Inp 4 fct.assig. 107 036 GOOSE Inp 15 fct.assig. 107 146
GOOSE Inp 5 fct.assig. 107 046 GOOSE Inp 16 fct.assig. 107 156
GOOSE Inp 6 fct.assig. 107 056
ST
GOOSE Inp 7 fct.assig. 107 066
GOOSE Inp 8 fct.assig. 107 076
GOOSE Inp 9 fct.assig. 107 086
GOOSE Inp 10 fct.assig. 107 096
GOOSE Inp 11 fct.assig. 107 106
Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE:
Disabled Enabled/Disabled -
Gen.Subst.Stat.Event
056 060
GSSE:
No No/Yes -
General Enable User
104 049
GSSE:
10 ms 1 ms 60 ms 1 ms
GSSE Min. Cycle
104 052
GSSE:
1s 1s 60 s 1s
GSSE Max. Cycle
104 053
GSSE:
900 0 999 1
GSSE Increment
104 054
GSSE: Promiscuous
Promiscuous -
GSSE Startup Broadcast
104 055
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
No selection/
GSSE: IED 0
IED 0 -
GSSE IED Name …
IED 32
104 057
No selection/
GSSE: GSSE Out 1 User Bit Pair 01
No selection -
(… 32) BitPair …
User Bit Pair 96
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Out 1 BitPair 104 101 GSSE Out 12 BitPair 104 134 GSSE Out 23 BitPair 104 167
GSSE Out 2 BitPair 104 104 GSSE Out 13 BitPair 104 137 GSSE Out 24 BitPair 104 170
GSSE Out 3 BitPair 104 107 GSSE Out 14 BitPair 104 140 GSSE Out 25 BitPair 104 173
Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE: GSSE Inp 1
No selection
(… 32) bit pair
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Inp 1 bit pair 105 001 GSSE Inp 12 bit pair 105 056 GSSE Inp 23 bit pair 105 111
GSSE Inp 2 bit pair 105 006 GSSE Inp 13 bit pair 105 061 GSSE Inp 24 bit pair 105 116
GSSE Inp 3 bit pair 105 011 GSSE Inp 14 bit pair 105 066 GSSE Inp 25 bit pair 105 121
GSSE Inp 4 bit pair 105 016 GSSE Inp 15 bit pair 105 071 GSSE Inp 26 bit pair 105 126
GSSE Inp 5 bit pair 105 021 GSSE Inp 16 bit pair 105 076 GSSE Inp 27 bit pair 105 131
GSSE Inp 6 bit pair 105 026 GSSE Inp 17 bit pair 105 081 GSSE Inp 28 bit pair 105 136
GSSE Inp 7 bit pair 105 031 GSSE Inp 18 bit pair 105 086 GSSE Inp 29 bit pair 105 141
GSSE Inp 8 bit pair 105 036 GSSE Inp 19 bit pair 105 091 GSSE Inp 30 bit pair 105 146
GSSE Inp 9 bit pair 105 041 GSSE Inp 20 bit pair 105 096 GSSE Inp 31 bit pair 105 151
GSSE Inp 10 bit pair 105 046 GSSE Inp 21 bit pair 105 101 GSSE Inp 32 bit pair 105 156
ST
GSSE Inp 11 bit pair 105 051 GSSE Inp 22 bit pair 105 106
Setting Range
Menu Text Default Setting Step Size
Min. Max.
GSSE: GSSE Inp 1
0
(… 32) default
See table below for setting addresses.
Setting Address Setting Address Setting Address
GSSE Inp 1 default 105 003 GSSE Inp 12 default 105 058 GSSE Inp 23 default 105 113
GSSE Inp 2 default 105 008 GSSE Inp 13 default 105 063 GSSE Inp 24 default 105 118
GSSE Inp 3 default 105 013 GSSE Inp 14 default 105 068 GSSE Inp 25 default 105 123
GSSE Inp 4 default 105 018 GSSE Inp 15 default 105 073 GSSE Inp 26 default 105 128
GSSE Inp 5 default 105 023 GSSE Inp 16 default 105 078 GSSE Inp 27 default 105 133
GSSE Inp 6 default 105 028 GSSE Inp 17 default 105 083 GSSE Inp 28 default 105 138
GSSE Inp 7 default 105 033 GSSE Inp 18 default 105 088 GSSE Inp 29 default 105 143
GSSE Inp 8 default 105 038 GSSE Inp 19 default 105 093 GSSE Inp 30 default 105 148
GSSE Inp 9 default 105 043 GSSE Inp 20 default 105 098 GSSE Inp 31 default 105 153
ST GSSE Inp 10 default 105 048 GSSE Inp 21 default 105 103 GSSE Inp 32 default 105 158
GSSE Inp 11 default 105 053 GSSE Inp 22 default 105 108
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IRIGB:
Disabled Disabled Enabled -
IRIG-B Time Synch
056 072
Enabling the IRIGB function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
IRIGB: General
No No Yes -
Enable USER
023 200 OP Fig. 97
Disabling and enabling the IRIG-B interface function.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting
Min. Max.
Step Size ST
Settings\Configuration
Signals from selection table
INP: Fct. U 701
Disabled dependent upon relay -
(… 2004) Assign
configuration.
See table below for setting addresses. OP Fig. 98
Assignment of opto inputs to internal relay signals. Any of the available signals can be
configured to any of the opto inputs. The addresses for opto input function assignment are
displayed in the following table:
Setting Address Setting Address Setting Address
Fct. U 701 Assign 152 109 Fct. U 821 Assign 184 082 Fct. U 1409 Assign 190 034
Fct. U 702 Assign 152 112 Fct. U 822 Assign 184 086 Fct. U 1410 Assign 190 038
Fct. U 703 Assign 152 115 Fct. U 823 Assign 184 090 Fct. U 1411 Assign 190 042
Fct. U 704 Assign 152 118 Fct. U 824 Assign 184 094 Fct. U 1412 Assign 190 046
Fct. U 705 Assign 152 121 Fct. U 901 Assign 152 145 Fct. U 1413 Assign 190 050
Fct. U 706 Assign 152 124 Fct. U 902 Assign 152 148 Fct. U 1414 Assign 190 054
Fct. U 801 Assign 184 002 Fct. U 903 Assign 152 151 Fct. U 1415 Assign 190 058
Fct. U 802 Assign 184 006 Fct. U 904 Assign 152 154 Fct. U 1416 Assign 190 062
Fct. U 803 Assign 184 010 Fct. U 1001 Assign 152 163 Fct. U 1417 Assign 190 066
Fct. U 804 Assign 184 014 Fct. U 1002 Assign 152 166 Fct. U 1418 Assign 190 070
Fct. U 805 Assign 184 018 Fct. U 1003 Assign 152 169 Fct. U 1419 Assign 190 074
Fct. U 806 Assign 184 022 Fct. U 1004 Assign 152 172 Fct. U 1420 Assign 190 078
Fct. U 807 Assign 184 026 Fct. U 1005 Assign 152 175 Fct. U 1421 Assign 190 082
Fct. U 808 Assign 184 030 Fct. U 1006 Assign 152 178 Fct. U 1422 Assign 190 086
Fct. U 809 Assign 184 034 Fct. U 1201 Assign 152 199 Fct. U 1423 Assign 190 090
Fct. U 810 Assign 184 038 Fct. U 1202 Assign 152 202 Fct. U 1424 Assign 190 094
Fct. U 811 Assign 184 042 Fct. U 1203 Assign 152 205 Fct. U 1601 Assign 192 002
Fct. U 812 Assign 184 046 Fct. U 1204 Assign 152 208 Fct. U 1602 Assign 192 006
Fct. U 813 Assign 184 050 Fct. U 1401 Assign 190 002 Fct. U 1603 Assign 192 010
Fct. U 814 Assign 184 054 Fct. U 1402 Assign 190 006 Fct. U 1604 Assign 192 014
Fct. U 815 Assign 184 058 Fct. U 1403 Assign 190 010 Fct. U 1605 Assign 192 018
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Fct. U 816 Assign 184 062 Fct. U 1404 Assign 190 014 Fct. U 1606 Assign 192 022
Fct. U 817 Assign 184 066 Fct. U 1405 Assign 190 018 Fct. U 2001 Assign 153 087
Fct. U 818 Assign 184 070 Fct. U 1406 Assign 190 022 Fct. U 2002 Assign 153 090
Fct. U 819 Assign 184 074 Fct. U 1407 Assign 190 026 Fct. U 2003 Assign 153 093
Fct. U 820 Assign 184 078 Fct. U 1408 Assign 190 030 Fct. U 2004 Assign 153 096
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
RTDmA: RTD, Curr.
Disabled Disabled Enabled -
Loop mA IN
056 030
Enabling the RTDmA function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
RTDmA: General
No No Yes -
Enable USER
011 100 OP Fig. 99
Disabling or enabling temperature and DC monitoring inputs.
RTDmA: 0.000 IDC, 0.200 IDC, 0.001 IDC,
0.000 IDC, nom
Enable IDC p.u. nom nom nom
037 190 OP Fig. ST
101, 102
Setting for the minimum current that must flow in order for the P63x to display a measured
value > 0 (zero suppression).
RTDmA: Blocked/
3.0mA 10.0 mA 0.1 mA
IDC< Open Circuit 0.0 mA
037 191 OP Fig.
102
If the input current falls below the set threshold, the P63x will issue an ‘open circuit’ signal.
IDC 1 =
0.000 IDC, nom
Blocked/
RTDmA: IDC 1 IDC 2 … 19 = 0.200 IDC, 0.001 IDC,
0.000 IDC,
(… 20) Blocked nom nom
nom
IDC 20 =
1.200 IDC, nom
See table below for setting addresses. OP Fig.
100, 101,
102
Setting for the input currents IDC xx that will pair up with the linearized values IDC, lin xx to
form the interpolation points of the characteristic for the linearization of direct current
inputs.
Note: IDC 1 and IDC 20 are the two end points of the characteristic and can not
be blocked.
Setting Address Setting Address Setting Address
RTDmA: IDC 1 037 150 RTDmA: IDC 8 037 164 RTDmA: IDC 15 037 178
RTDmA: IDC 2 037 152 RTDmA: IDC 9 037 166 RTDmA: IDC 16 037 180
RTDmA: IDC 3 037 154 RTDmA: IDC 10 037 168 RTDmA: IDC 17 037 182
RTDmA: IDC 4 037 156 RTDmA: IDC 11 037 170 RTDmA: IDC 18 037 184
RTDmA: IDC 5 037 158 RTDmA: IDC 12 037 172 RTDmA: IDC 19 037 186
RTDmA: IDC 6 037 160 RTDmA: IDC 13 037 174 RTDmA: IDC 20 037 188
RTDmA: IDC 7 037 162 RTDmA: IDC 14 037 176
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDC, lin 1 =
0.000 IDC, nom
Blocked/
RTDmA: IDC, lin 1 IDC, lin 2 … 19 = 0.200 0.001
0.000
(… 20) Blocked IDC, nom IDC, nom
IDC, nom
IDC, lin 20 =
1.200 IDC, nom
See table below for setting addresses. OP Fig.
100, 101,
102
Setting for the input currents IDC, lin xx that will pair up with the linearized values IDC xx to
form the interpolation points of the characteristic for the linearization of direct current
inputs.
Note: IDC, lin 1 and IDC, lin 20 are the two end points of the characteristic and
can not be blocked.
Setting Address Setting Address Setting Address
RTDmA: IDC, lin 1 037 151 RTDmA: IDC, lin 8 037 165 RTDmA: IDC, lin 15 037 179
ST RTDmA: IDC, lin 2 037 153 RTDmA: IDC, lin 9 037 167 RTDmA: IDC, lin 16 037 181
RTDmA: IDC, lin 3 037 155 RTDmA: IDC, lin 10 037 169 RTDmA: IDC, lin 17 037 183
RTDmA: IDC, lin 4 037 157 RTDmA: IDC, lin 11 037 171 RTDmA: IDC, lin 18 037 185
RTDmA: IDC, lin 5 037 159 RTDmA: IDC, lin 12 037 173 RTDmA: IDC, lin 19 037 187
RTDmA: IDC, lin 6 037 161 RTDmA: IDC, lin 13 037 175 RTDmA: IDC, lin 20 037 189
RTDmA: IDC, lin 7 037 163 RTDmA: IDC, lin 14 037 177
RTDmA:
0 -32768 32767 1
Scaled val. IDC, lin1
037 192 OP Fig.
102, 103
Setting for the scaled value of IDC, lin 1.
RTDmA:
1200 -32768 32767 1
Scaled val. IDC, lin20
037 193 OP Fig.
102, 103
Setting for the scaled value of IDC, lin 20.
Note: For relays with make contacts, the “Follower” mode corresponds to
normally-open operation. The “Inverted” mode means that the polarity
of the driving signal is inverted, such that a logic "0" maintains the
relay normally-closed. For relays with changeover contacts, these
more common descriptions are not applicable.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
Signals from selection table
OUTP: Fct. Assignm.
Disabled dependent upon relay -
K 701 (… 2008)
configuration.
See table below for setting addresses. OP Fig.
105
Assignment of functions to output relays.
Setting Address Setting Address Setting Address
Fct. Assignm. K 701 150 145 Fct. Assignm. K 908 150 214 Fct. Assignm. K 1607 171 026
Fct. Assignm. K 702 150 148 Fct. Assignm. K 1001 150 217 Fct. Assignm. K 1608 171 030 ST
Fct. Assignm. K 703 150 151 Fct. Assignm. K 1002 150 220 Fct. Assignm. K 1801 173 002
Fct. Assignm. K 704 150 154 Fct. Assignm. K 1003 150 223 Fct. Assignm. K 1802 173 006
Fct. Assignm. K 705 150 157 Fct. Assignm. K 1004 150 226 Fct. Assignm. K 1803 173 010
Fct. Assignm. K 706 150 160 Fct. Assignm. K 1005 150 229 Fct. Assignm. K 1804 173 014
Fct. Assignm. K 707 150 163 Fct. Assignm. K 1006 150 232 Fct. Assignm. K 1805 173 018
Fct. Assignm. K 708 150 166 Fct. Assignm. K 1007 150 235 Fct. Assignm. K 1806 173 022
Fct. Assignm. K 801 150 169 Fct. Assignm. K 1008 150 238 Fct. Assignm. K 2001 151 201
Fct. Assignm. K 802 150 172 Fct. Assignm. K 1201 151 009 Fct. Assignm. K 2002 151 204
Fct. Assignm. K 901 150 193 Fct. Assignm. K 1202 151 012 Fct. Assignm. K 2003 151 207
Fct. Assignm. K 902 150 196 Fct. Assignm. K 1601 171 002 Fct. Assignm. K 2004 151 210
Fct. Assignm. K 903 150 199 Fct. Assignm. K 1602 171 006 Fct. Assignm. K 2005 151 213
Fct. Assignm. K 904 150 202 Fct. Assignm. K 1603 171 010 Fct. Assignm. K 2006 151 216
Fct. Assignm. K 905 150 205 Fct. Assignm. K 1604 171 014 Fct. Assignm. K 2007 151 219
Fct. Assignm. K 906 150 208 Fct. Assignm. K 1605 171 018 Fct. Assignm. K 2008 151 222
Fct. Assignm. K 907 150 211 Fct. Assignm. K 1606 171 022
Follower
Follower Latching
OUTP: Oper. Mode Follower Rst on Flt
Follower -
K 701 (… 2008) Follower Rst onStart
Inverted
Inverted Latching
See table below for setting addresses. OP Fig.
105
Selection of operating mode for output relays.
Setting Address Setting Address Setting Address
Oper. Mode K 701 150 146 Oper. Mode K 908 150 215 Oper. Mode K 1607 171 027
Oper. Mode K 702 150 149 Oper. Mode K 1001 150 218 Oper. Mode K 1608 171 031
Oper. Mode K 703 150 152 Oper. Mode K 1002 150 221 Oper. Mode K 1801 173 003
Oper. Mode K 704 150 155 Oper. Mode K 1003 150 224 Oper. Mode K 1802 173 007
Oper. Mode K 705 150 158 Oper. Mode K 1004 150 227 Oper. Mode K 1803 173 011
Oper. Mode K 706 150 161 Oper. Mode K 1005 150 230 Oper. Mode K 1804 173 015
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Oper. Mode K 707 150 164 Oper. Mode K 1006 150 233 Oper. Mode K 1805 173 019
Oper. Mode K 708 150 167 Oper. Mode K 1007 150 236 Oper. Mode K 1806 173 023
Oper. Mode K 801 150 170 Oper. Mode K 1008 150 239 Oper. Mode K 2001 151 202
Oper. Mode K 802 150 173 Oper. Mode K 1201 151 010 Oper. Mode K 2002 151 205
Oper. Mode K 901 150 194 Oper. Mode K 1202 151 013 Oper. Mode K 2003 151 208
Oper. Mode K 902 150 197 Oper. Mode K 1601 171 003 Oper. Mode K 2004 151 211
Oper. Mode K 903 150 200 Oper. Mode K 1602 171 007 Oper. Mode K 2005 151 214
Oper. Mode K 904 150 203 Oper. Mode K 1603 171 011 Oper. Mode K 2006 151 217
Oper. Mode K 905 150 206 Oper. Mode K 1604 171 015 Oper. Mode K 2007 151 220
Oper. Mode K 906 150 209 Oper. Mode K 1605 171 019 Oper. Mode K 2008 151 223
Oper. Mode K 907 150 212 Oper. Mode K 1606 171 023
Setting Range
ST Menu Text Default Setting
Min. Max.
Step Size
Settings\Configuration
mA_OP: Current
Disabled Disabled Enabled -
Loop mA outp
056 020
Enabling the mA_OP function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
mA_OP: General
No No Yes -
Enable USER
031 074 OP Fig.
107
Disabling and enabling the measured data output function.
Signals from selection table
mA_OP:
Disabled dependent upon relay -
Fct. Assignm. BCD
configuration.
053 002 OP Fig.
110
Selection of the measured value to be transmitted in BCD-coded form.
mA_OP: Hold Time Blocked/
0.10 s 10.00 s 0.01 s
Output BCD 0.10 s
010 010 OP Fig.
110
Setting for the time period for transmission of the selected measured value in BCD-coded
form.
mA_OP: Scale BCD 1.00 0.01 100.00 0.01
016 082 OP Fig.
110
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Scaling factor setting for the measured value to be transmitted in BCD-coded form. The
scaling factor is calculated according to the following formula:
M x,max
scaling factor =
M x,scal
Where:
M x,scal : Scaled measured value
M x,max : Maximum transmitted value for the selected measured value
mA_OP: Blocked/
Blocked 1.000 0.001
Scaled Knee val. A-1 0.000
037 105 OP Fig.
112
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
mA_OP: Blocked/
Blocked 1.000 0.001
Scaled Knee val. A-2 0.000
037 111 OP Fig.
112
Setting for the scaled measured value for output that defines the knee point of the
characteristic. The value to be set is calculated according to the following formula:
M x,knee
M x,scal,knee =
M x,RL
Where:
M x,knee : Knee point value to be transmitted for selected measured value
mA_OP:
1.000 0.000 1.000 0.001
Scaled Max. val. A-1
Where:
Mx,max : Maximum value to be transmitted for selected measured value
M x,RL : Range limit value of selected measured value
mA_OP:
0.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Min. val. A-1
037 107 OP Fig.
112
mA_OP:
0.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Min. val. A-2
037 113 OP Fig.
112
Setting for the output current that is output for measured values less than or equal to the
minimum measured value to be transmitted.
mA_OP: AnOut Knee Blocked/
Blocked 20.00 mA 0.01 mA
Point A-1 0.00 mA
037 108 OP Fig.
112
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
mA_OP: AnOut Knee Blocked/
Blocked 20.00 mA 0.01 mA
Point A-2 0.00 mA
037 114 OP Fig.
112
Setting for the output current that is output if the measured value is in the knee point of the
characteristic.
mA_OP:
20.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Max. val. A-1
037 109 OP Fig.
112
mA_OP:
20.00 mA 0.00 mA 20.00 mA 0.01 mA
AnOut Max. val. A-2
037 115 OP Fig.
112
Setting for the output current that is output for measured values smaller than or equal to
the maximum measured value to be transmitted. ST
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 1
037 120 OP Fig.
110, 112
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 2
037 121 OP Fig.
110, 112
mA_OP:
0.00 % 0.00 % 100.00 % 0.01 %
Output Value 3
037 122 OP Fig.
110, 112
Measured values of external devices, which must be scaled to 0 to 100%, can be output.
The arrangement of the LED indicators on the HMI panel is illustrated in the dimensional
drawings of the Installation - IN section.
P63x/UK ST/A54 Settings
An operating mode can be defined for each LED indicator. Depending on the selected
operating mode, the LED will operate in either “Follower” mode or “Inverted” mode as either
latching or non-latching indicators. For LED indicators operating in latching mode, the
operating mode setting also determines when latching will be cancelled.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LED: MAIN
MAIN Blocked/Faulty -
Fct. Assignm. H 2 Blocked/Faulty
085 001 Read only OP Fig.
113
Display of the function assigned to LED indicator H 2 (‘OUT OF SERVICE’).
The MAIN: Blocked/Faulty function is permanently assigned to this LED.
LED: CHECK Alarm
CHECK Alarm (LED) -
Fct. Assignm. H 3 (LED)
085 004 Read only OP Fig.
113
ST Display of the function assigned to LED indicator H 3 (‘ALARM’). The CHECK: Alarm
(LED) function is permanently assigned to this LED.
Signals from selection table
LED: MAIN Gen Trip
dependent upon relay -
Fct. Assignm. H 4 Signal
configuration.
085 007 OP Fig.
113
Default assignment to the function MAIN: Gen Trip Signal.
Signals from selection table
LED: Fct. Assignm. Disabled dependent upon relay -
H 5 (… 16) configuration.
See table below for setting addresses. OP Fig.
113
Assignment of functions to LED indicators.
Setting Address Setting Address Setting Address
Fct. Assignm. H 5 085 010 Fct. Assignm. H 9 085 022 Fct. Assignm. H 13 085 034
Fct. Assignm. H 6 085 013 Fct. Assignm. H 10 085 025 Fct. Assignm. H 14 085 037
Fct. Assignm. H 7 085 016 Fct. Assignm. H 11 085 028 Fct. Assignm. H 15 085 040
Fct. Assignm. H 8 085 019 Fct. Assignm. H 12 085 031 Fct. Assignm. H 16 085 043
LED:
Follower Follower -
Operating Mode H 2
085 002 Read only OP Fig.
113
LED:
Follower Follower -
Operating Mode H 3
085 005 Read only OP Fig.
113
Follower
Follower Latching
LED: Follower Rst on Flt
Follower Rst on Flt -
Operating Mode H 4 Follower Rst onStart
Inverted
Inverted Latching
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
085 008
The TRIP LED may be set as a “Follower” or “Inverted” mode of operation. It can also be
set for latching. Reset of latching may be performed either via a user command,
automatically at the onset of the next fault or at the start of a system disturbance (any
protection element start).
LED: Operating Mode As per ‘LED: Operating
Follower -
H 5 (… 16) Mode H 4’
See table below for setting addresses. OP Fig.
113
Selection of operating mode for LED indicators.
Setting Address Setting Address Setting Address
Operating Mode H 5 085 011 Operating Mode H 9 085 023 Operating Mode H 13 085 035
Operating Mode H 6 085 014 Operating Mode H 10 085 026 Operating Mode H 14 085 038
Operating Mode H 7 085 017 Operating Mode H 11 085 029 Operating Mode H 15 085 041
Operating Mode H 8 085 020 Operating Mode H 12 085 032 Operating Mode H 16 085 044 ST
1.2.14 Communication and time synchronization channel assignment (MAIN)
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
MAIN: Chann Assign. COMM1->Chann.1, COMM1->Chann.1, (2-2)
-
Comm1/2 (2-2) COMM1->Chann.2, (2-1)
OP Fig.
003 169
137
Assignment of “logical” communications function groups COMM1 and COMM2 to physical
rear communications ports. This setting allows the main rear SCADA port (COMM1) to be
selected as either fiber or EIA(RS)485, with COMM2 assigned to the other physical port
where the two rear port -922 or -924 order options are present.
COMM1
MAIN: Prim.Source COMM2/PC
COMM1 -
TimeSync IRIG-B
Minute-pulse input
103 210
Selection of the primary time synchronization source. The source is monitored for valid
time synchronization commands and will be used whenever available.
MAIN: BackupSource As per ‘MAIN: Prim.Source
COMM2/PC -
TimeSync TimeSync’
103 211
Selection of a backup time synchronization source. This source will be used when the
primary source above is not available.
MAIN: Blocked /
Blocked 60 min 1 min
Time Sync. Time-Out 1 min
103 212
Time out setting for valid time synchronization commands. If set to “Blocked”, primary
source only will be used.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
OSCIL:
Current IA, end a Current IA, end a -
Dist Rec Analog Ch1
035 160 Read only OP Fig.
157
OSCIL:
Current IB, end a Current IB, end a -
Dist Rec Analog Ch2
035 161 Read only OP Fig.
157
OSCIL:
Current IC, end a Current IC, end a -
Dist Rec Analog Ch3
035 162 Read only OP Fig.
157
ST OSCIL: Current IN, end a
Current IY, end a -
Dist Rec Analog Ch4 Current IY, end a
035 163 OP Fig.
157
OSCIL:
Current IA, end b Current IA, end b -
Dist Rec Analog Ch5
035 164 Read only OP Fig.
157
OSCIL:
Current IB, end b Current IB, end b -
Dist Rec Analog Ch6
035 165 Read only OP Fig.
157
OSCIL:
Current IC, end b Current IC, end b -
Dist Rec Analog Ch7
035 166 Read only OP Fig.
157
OSCIL: Current IN, end b
Current IY, end b -
Dist Rec Analog Ch8 Current IY, end b
035 167 OP Fig.
157
OSCIL:
Voltage V Voltage V -
Dist Rec Analog Ch9
035 168 Read only OP Fig.
157
OSCIL: Dist Rec
Current IA, end c Current IA, end c -
Analog Ch10
035 169 Read only OP Fig.
157
OSCIL: Dist Rec
Current IB, end c Current IB, end c -
Analog Ch11
035 170 Read only OP Fig.
157
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
OSCIL: Dist Rec
Current IC, end c Current IC, end c -
Analog Ch12
035 171 Read only OP Fig.
157
OSCIL: Dist Rec Current IN, end c
Current IY, end c -
Analog Ch13 Current IY, end c
035 172 OP Fig.
157
OSCIL: Dist Rec
Current IA, end d Current IA, end d -
Analog Ch14
035 173 Read only OP Fig.
157
OSCIL: Dist Rec
Current IB, end d Current IB, end d -
Analog Ch15
035 174 Read only OP Fig.
157 ST
OSCIL: Dist Rec
Current IC, end d Current IC, end d -
Analog Ch16
035 175 Read only OP Fig.
157
The user specifies the channel on which each physical variable is recorded.
• None of the signals of the protection function may be assigned to a binary output or an
LED indicator
• None of the signals of the protection function may be linked to other signals by way of an
‘m out of n’ parameter
The protection function to which a setting, a signal, or a measured value belongs is defined
by the function group designation (example: ‘LIMIT’).
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
DIFF:
Disabled Disabled Enabled -
Differential PR (87)
056 027 OP Fig. 1
Enabling the DIFF function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
REF_1:
Disabled Disabled Enabled -
Restricted EF_1 (64)
056 037 OP Fig. 14
REF_2:
Disabled Disabled Enabled -
Restricted EF_2 (64)
056 038 OP Fig. 14
REF_3:
Disabled Disabled Enabled -
Restricted EF_3 (64)
056 039 OP Fig. 14
Enabling the REF_1 to REF_3 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
ST Note: Restricted earth fault protection is not available in the P631. Function
group REF_3 is available with the P633 and the P634 only.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
DTOC1:
Disabled Disabled Enabled -
I> Winding 1 (50/51)
056 031 OP Fig. 22
DTOC2:
Disabled Disabled Enabled -
I> Winding 2 (50/51)
056 032 OP Fig. 22
DTOC3:
Disabled Disabled Enabled -
I> Winding 3 (50/51)
056 053 OP Fig. 22
Enabling the DTOC1 to DTOC3 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
Note: Function group DTOC3 is available with the P633 and the P634 only.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
IDMT1:
Disabled Disabled Enabled -
IDMT Winding 1 (51)
056 051 OP Fig. 29
IDMT2:
Disabled Disabled Enabled -
IDMT Winding 2 (51)
056 061 OP Fig. 29
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3:
Disabled Disabled Enabled -
IDMT Winding 3 (51)
056 071 OP Fig. 29
Enabling the IDMT1 to IDMT3 functions or disabling them in the configuration. If a function
group is disabled, then all associated settings and signals are hidden, with the exception of
this setting.
Note: Function group IDMT3 is available with the P633 and the P634 only.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
THRM1:
Disabled Disabled Enabled -
Thermal Oload 1 (49)
056 054 OP Fig. 41
ST
THRM2:
Disabled Disabled Enabled -
Thermal Oload 2 (49)
056 055 OP Fig. 41
Enabling the THRM1 to THRM2 functions or disabling them in the configuration. If a
function group is disabled, then all associated settings and signals are hidden, with the
exception of this setting.
Note: Function group THRM2 is available with the P633 and the P634 only.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
V<>: Under Over
Disabled Disabled Enabled -
Volts V<>
056 010 OP Fig. 47
Enabling the V<> function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
Note: Time-voltage protection is not available in the P631.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
f<>:
Disabled Disabled Enabled -
Frequency Prot. (81)
056 033 OP Fig. 50
Enabling the f<> function or disabling it in the configuration. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
Note: Over/underfrequency is not available in the P631.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
V/f:
Disabled Disabled Enabled -
Overfluxing V/f (24)
056 056 OP Fig. 54
Enabling the V/f function or disabling it in the configuration. If the function is disabled, then
all associated settings and signals are hidden, with the exception of this setting.
Note: Overfluxing protection is not available in the P631.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
ST CTS: CT Supervision Disabled Disabled Enabled -
056 077 OP Fig. 64
Enabling the CTS function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
Note: CTS is only available if the DSP coprocessor is selected as an order option.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
BC_1:
Disabled Disabled Enabled -
Broken Conductor 1
056 073 OP Fig. 62
BC_2:
Disabled Disabled Enabled -
Broken Conductor 2
056 074 OP Fig. 62
BC_3:
Disabled Disabled Enabled -
Broken Conductor 3
056 075 OP Fig. 62
BC_4:
Disabled Disabled Enabled -
Broken Conductor 4
056 076 OP Fig. 62
Enabling the broken conductor detection function or disabling it in the configuration. If the
function is disabled, then all associated settings and signals are hidden, with the exception
of this setting.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LIMIT:
Disabled Disabled Enabled -
Limit Thresholds I<>
056 025
Enabling the LIMIT function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LIM_1:
Limits I<> Winding 1
Disabled Disabled Enabled - ST
056 042
LIM_2:
Disabled Disabled Enabled -
Limits I<> Winding 2
056 043
LIM_3:
Disabled Disabled Enabled -
Limits I<> Winding 3
056 050
Enabling the LIM_1 to LIM_3 functions or disabling them in the configuration. If a function
group is disabled, then all associated settings and signals are hidden, with the exception of
this setting.
Note: Function group LIM_3 is available with the P633 and the P634 only.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Configuration
LOGIC:
Programmable Disabled Disabled Enabled -
LOGIC
056 017
Enabling the LOGIC function or disabling it in the configuration. If the function is disabled,
then all associated settings and signals are hidden, with the exception of this setting.
P63x/UK ST/A54 Settings
1.3.1 Global
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
PC:
No No Yes -
Command Blocking
003 182 OP Fig. 86
When command blocking is activated, commands are rejected at the PC interface.
PC:
No No Yes -
Sig/meas. val. Block
003 086 OP Fig. 86
ST When signal and measured value blocking is activated, no signals or measured data are
transmitted through the PC interface.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
COMM1: USER
Yes No Yes -
Command Block
003 172 OP Fig. 87
When command blocking is activated, commands are rejected at the communication
interface.
COMM1: USER
No No Yes -
Sig/meas Block
003 076 OP Fig. 88,
89, 90
When signal and measured value blocking is activated, no signals or measured data are
transmitted through the communication interface.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
COMM2: USER
Yes No Yes -
Command Block
103 172
When command blocking is activated, commands are rejected at the communication
interface.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
COMM2: USER
No No Yes -
Sig/meas Block
103 076
When signal and measured value blocking is activated, no signals or measured data are
transmitted through the communication interface.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
OUTP:
USER Outp Rel No No Yes -
Block
021 014 OP Fig.
105 ST
When this blocking is activated, all output relays are blocked.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
MAIN: No Yes
No (Disabled) -
Protection Enabled (Disabled) (Enabled)
003 030 OP Fig.
129
Switching the device off-line or on-line. Parameters marked ‘off’ in the Address List can
only be changed when the device is off-line.
MAIN:
No No Yes -
USER Test Mode
003 012 OP Fig.
141
When the test mode is activated, signals or measured data for PC and communication
interfaces are labeled ‘test mode’.
50 Hz
MAIN: Frequency fn 50 Hz -
60 Hz
010 030 OP Fig. 53
Setting for the nominal frequency of the protected system.
MAIN: A–B–C
A–B–C -
Phase Rotation A–C–B
010 049 OP Fig. 5
Setting for the phase rotation of the protection system, either A-B-C (standard) or A-C-B
(reverse).
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end a
019 020 OP Fig.
119
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end b
019 021 OP Fig.
119
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end c
019 022 OP Fig.
119
MAIN:
200 A 1A 50000 A 1A
In CT. prim., end d
019 026 OP Fig.
119
Setting for the primary nominal current of the main current transformer (phase currents) of
end a, b, c or d.
MAIN:
ST In CT.Y prim, end a
200 A 1A 50000 A 1A
Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
1A 1A 5A 4A
In Device, end d
010 047 OP Fig.
115, 116
Setting for the secondary nominal current of the system transformer for measurement of
the phase currents of ends a, b, c and d. This current corresponds to the nominal current
of the device.
MAIN:
1A 1A 5A 4A
IY, nom device, end a
010 142 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
IY, nom device, end b
010 143 OP Fig.
115, 116
MAIN:
1A 1A 5A 4A
ST
IY, nom device, end c
010 144 OP Fig.
115, 116
Setting for the secondary nominal current of the system transformer for measurement of
the neutral-point-to-earth connection current of ends a, b, and c.
MAIN: Vn VT. Sec. 100 V 50 V 130 V 1V
010 009 OP Fig.
124
Setting for the secondary nominal voltage of the system transformer for voltage
measurement.
MAIN: Standard
Standard -
CT Orientation Iph, a Reversed
010 140 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, b Reversed
010 150 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, c Reversed
010 160 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation Iph, d Reversed
010 170 OP Fig.
115, 116
Instead of accounting for connection reversal applied to one end in the settings for DIFF:
Vector Grp. ends z1-z2 (where z1-z2 stands for b-a, c-a or d-a), it is possible to account for
it in the settings for connection of the measuring circuits. The connection of the
neutral/point current circuits, ends a to d, is set here as Standard if in accordance with the
connection scheme shown in the Installation - IN section, else as Reversed.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN: Standard
Standard -
CT Orientation IY, a Reversed
010 141 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation IY, b Reversed
010 151 OP Fig.
115, 116
MAIN: Standard
Standard -
CT Orientation IY, c Reversed
010 161 OP Fig.
115, 116
Connection reversal applied to one end is accounted for it in the settings for connection of
the measuring circuits. The connection of the wye/neutral current circuits, ends a to c, is
set here as Standard if in accordance with the connection scheme shown in the Installation
ST - IN section, else as Reversed.
MAIN: Minimum Iph
0.00 In 0.00 In 0.20 In 0.01 In
Meas’mt
011 030 OP Fig.
119, 123
Setting for the minimum current that must be exceeded in order for the measured operating
values of the phase currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum I2 Meas’mt
011 048
Setting for the minimum current that must be exceeded in order for the calculated values of
the negative sequence currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum I1 Meas’mt
011 058
Setting for the minimum current that must be exceeded in order for the calculated values of
the positive sequence currents to be displayed.
MAIN:
0.000 In 0.000 In 0.200 In 0.001 In
Minimum IN Meas’mt
011 031 OP Fig.
121, 122,
123
Setting for the minimum current that must be exceeded in order for the measured operating
value of the residual current to be displayed.
MAIN: 0.000 0.200 0.001
0.000 IN, nom
Minimum IY Meas’mt IN, nom IN, nom IN, nom
011 036 OP Fig.
121
Setting for the minimum current that must be exceeded in order for the measured operating
values of the currents in the neutral-point-to-earth connection to be displayed.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
MAIN:
0.00 Vn 0.00 Vn 0.20 Vn 0.01 Vn
Minimum V Meas’mt
011 032 OP Fig.
124
Setting for the minimum voltage that must be exceeded in order for the measured
operating values of the voltage to be displayed.
MAIN:
15.0 min 0.1 min 60.0 min 0.1 min
Time Const Iph Dem.
010 113 OP Fig.
119, 120
Setting for the time after which the delayed maximum current display shall reach 95% of
the maximum current IP, max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 1
configuration.
021 021 OP Fig. ST
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 2
configuration.
021 022 OP Fig.
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 3
configuration.
021 048 OP Fig.
131
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assign. Block 4
configuration.
021 049 OP Fig.
131
Assignment of functions that will be blocked together when blocking input 1, 2, 3 or 4 is
activated e.g. for blocking input 1 (MAIN: Blocking 1 EXT).
MAIN: Trip Cmd.
No No Yes -
Block USER
021 012 OP Fig.
135
Blocking of the trip commands from the local control panel.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.1
configuration.
021 001 OP Fig.
135
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.2
configuration.
021 002 OP Fig.
135
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.3
configuration.
021 046 OP Fig.
135
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct.Assig Trip Cmd.4
configuration.
021 047 OP Fig.
135
Assignment of the signals that trigger Trip Command 1, 2, 3 or 4.
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 1
021 003 OP Fig.
135
ST MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 2
021 004 OP Fig.
135
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 3
021 032 OP Fig.
135
MAIN:
0.25 s 0.10 s 10.00 s 0.01 s
tDWELL Trip Cmd 4
021 033 OP Fig.
135
Setting for the minimum duration of Trip Command 1, 2, 3 or 4.
MAIN:
No No Yes -
Latching trip cmd. 1
021 023 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 2
021 024 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 3
021 025 OP Fig.
135
MAIN:
No No Yes -
Latching trip cmd. 4
021 026 OP Fig.
135
Specification as to whether Trip Command 1, 2, 3 or 4 should latch.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
MAIN:
Disabled dependent upon relay -
Fct Assign Fault
configuration.
021 031 OP Fig.
132
Selection of the signals whose appearance shall result in a ‘Blocked/Faulty’ indication.
Signals that lead to blocking of the device are not configurable and always result in a
‘Blocked/Faulty’ indication.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
GROUP:
No No Yes -
Control via USER
ST
003 100 OP Fig.
142
If setting group selection is to be handled from the integrated local control panel rather
than via the binary signal inputs, choose the ‘Yes’ setting.
Setting Group SG1
GROUP: Setting Grp Setting Group SG2
Setting Group SG1 -
Sel USER Setting Group SG3
Setting Group SG4
003 060 OP Fig.
142
Selection of the setting group from the local control panel.
Blocked /
GROUP: Hold Timer Blocked 65.000 s 0.001 s
0.000 s
003 063 OP Fig.
142
The setting of this timer stage is relevant only if setting group selection is carried out via
the binary signal inputs. Any voltage-free pause that may occur during selection is
bridged. If, after this time period has elapsed, no binary signal input has yet been set, then
the setting group selected from the local control panel shall apply.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
Signals from selection table
CHECK:
Disabled dependent upon relay -
Fct Assign. Alarm
configuration.
021 030 OP Fig.
143
This setting defines the monitoring signals that will be entered in the monitoring signal
memory. Signals resulting from internal device faults are not configurable and always
result in a warning.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
CHECK: Blocked /
Blocked 240 hrs 1 hrs
Mon.Sig. Retention 0 hrs
021 018
Retention time of monitoring signals in the memory. After this time has elapsed any
recurrence of the signal will be processed in the same way as if it were a first occurrence.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Global
Signals from selection table
OSCIL:
Disabled dependent upon relay -
Fct Assig. Trigger
configuration.
003 085 OP Fig.
ST 155
This setting defines the signals that will trigger fault recording.
Blocked/
OSCIL: Id> Blocked 30.00 Iref 0.01 Iref
0.01 Iref
016 018 OP Fig.
155
This setting defines the threshold value of the differential current that will trigger fault
recording.
Blocked/
OSCIL: IR> Blocked 30.00 Iref 0.01 Iref
0.01 Iref
016 019 OP Fig.
155
This setting defines the threshold value of the restraining current that will trigger fault
recording.
OSCIL:
5 Cycles 1 Cycles 50 Cycles 1 Cycles
Pre-Fault Time
003 078 OP Fig.
157
Setting for the time during which data will be recorded before the onset of a fault (pre-fault
recording time).
OSCIL:
2 Cycles 1 Cycles 50 Cycles 1 Cycles
Post-Fault Time
003 079 OP Fig.
157
Setting for the time during which data will be recorded after the end of a fault (post-fault
recording time).
OSCIL:
50 Cycles 5 Cycles 300 Cycles 1 Cycles
Max Record Time
003 075 OP Fig.
157
Setting for the maximum recording time per fault. This includes pre-fault and post-fault
recording times.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end a
019 017 OP Fig. 2,
15
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end b
019 018 OP Fig. 2
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end c
019 019 OP Fig. 2
ST
MAIN:
110.0 kV 0.1 kV 1500.0 kV 0.1 kV
Vn prim., end d
019 037 OP Fig. 2
Setting for the primary nominal voltage (phase to phase = line) for each end of the
protected transformer.
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end a Measured
016 096 OP Fig.
117
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end b Measured
016 097 OP Fig.
117
MAIN: Calculated (Derived)
Calculated (Derived) -
Evaluation IN, end c Measured
016 098 OP Fig.
117
This setting specifies which current will be used by the P63x as the residual current: either
the calculated residual current based on the sum of the phase currents or the residual
current measured at the neutral transformer input.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Without
End(a) +end(b)
End(a) +end(c)
End(a) +end(d)
End(b) +end(c)
End(b) +end(d)
End(c) +end(d)
End(a) +end(b) +end(c)
MAIN:
Without End(a) +end(b) +end(d) -
Current Summation
End(a) +end(c) +end(d)
End(b) +end(c) +end(d)
End(a) -end(b)
End(a) -end(c)
End(a) -end(d)
End(b) -end(c)
End(b) -end(d)
End(c) -end(d)
019 099 OP Fig.
ST 118
Where a transformer winding is energized from two or three infeeds, such as is the case in
mesh, ring-bus, or breaker and a half feeding, the relay can summate currents to obtain the
total current for that winding. The currents for each phase and the residual currents can be
combined. This setting specifies the CT ends to be involved.
Note: This setting is available for the P633 and P634 only.
MAIN: Blocked/
Blocked 100.00 s 0.01 s
Hold Time Dyn.Settg 0.00 s
018 009 OP Fig.
130
Setting for the hold time of the “dynamic settings”. During this period, the “dynamic”
thresholds are active in place of the “normal” thresholds.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
DIFF: General
No No Yes -
Enable USER
019 080 OP Fig. 1
Disabling and enabling the differential protection function.
DIFF: Rated Ref
38.1 MVA 0.1 MVA 5000.0 MVA 0.1 MVA
Power Sref
019 016 OP Fig. 2
Setting for the reference power, usually the nominal transformer power.
DIFF: Ref. Curr. Iref,a Not Measured 0.000 kA 50.000 kA 0.001 kA
019 023 Read only OP Fig. 2
DIFF: Ref. Curr. Iref,b Not Measured 0.000 kA 50.000 kA 0.001 kA
019 024 Read only OP Fig. 2
DIFF: Ref. Curr. Iref,c Not Measured 0.000 kA 50.000 kA 0.001 kA
019 025 Read only OP Fig. 2
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: Ref. Curr. Iref,d Not Measured 0.000 kA 50.000 kA 0.001 kA
019 038 Read only OP Fig. 2
Display of the reference current calculated by the P63x for each end.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, a
004 105 Read only OP Fig. 2
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, b
004 106 Read only OP Fig. 2
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, c
004 127 Read only OP Fig. 2
ST
DIFF:
Not Measured 0.000 50.000 0.001
Matching fact. Kam, d
004 168 Read only OP Fig. 2
Display of the matching factor calculated by the P63x for each end.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
DIFF:
0.000 Iref 0.000 Iref 0.200 Iref 0.001 Iref
Minimum Id Meas’mt
011 037 OP Fig. 13
Setting for the minimum differential current that must be exceeded in order for the P63x to
display the differential currents as measured operating data.
DIFF:
0.000 Iref 0.000 Iref 0.200 Iref 0.001 Iref
Minimum IR Meas’mt
011 038 OP Fig. 13
Setting for the minimum restraining current that must be exceeded in order for the P63x to
display the restraining currents as measured operating data.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
REF_1: General
No No Yes -
Enable USER
019 050 OP Fig. 14
REF_2: General
No No Yes -
Enable USER
019 150 OP Fig. 14
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3: General
No No Yes -
Enable USER
019 250 OP Fig. 14
Disabling and enabling the ground differential protection function.
Note: Function group REF_3 is available with the P633 and the P634 only.
REF_1:
End a End a -
Select CT Input
019 100 Read only
REF_2:
End b End b -
Select CT Input
019 101 Read only
REF_3:
End c End c -
Select CT Input
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Not
REF_2: Matching 50.000/
Not Measured Measured/ 0.001
Fact. kam, N Overflow
0.000
004 161 Read only OP Fig. 15
Not
REF_3: Matching 50.000/
Not Measured Measured/ 0.001
Fact. kam, N Overflow
0.000
004 162 Read only OP Fig. 15
Display of the matching factor calculated by the P63x for the vector sum of the phase
currents.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
Not
REF_1: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 163 Read only OP Fig. 15
ST
Not
REF_2: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 164 Read only OP Fig. 15
Not
REF_3: Matching 50.000/
Not Measured Measured/ 0.001
Fact.kam, Y Overflow
0.000
004 165 Read only OP Fig. 15
Display of the matching factor calculated by the P63x for the neutral-point current.
Note: These values are automatically updated by the device itself only. In an
off-line setting file the value is not updated.
REF_1:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 039 OP Fig. 20
REF_2:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 044 OP Fig. 20
REF_3:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum Id Meas’mt
011 045 OP Fig. 20
Setting for the minimum differential current that must be exceeded in order for the P63x to
display the differential currents as measured operating data.
REF_1:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 040 OP Fig. 20
REF_2:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 046 OP Fig. 20
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3:
0.00 Iref 0.00 Iref 0.20 Iref 0.01 Iref
Minimum IR Meas’mt
011 047 OP Fig. 20
Setting for the minimum restraining current that must be exceeded in order for the P63x to
display the restraining currents as measured operating data.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
DTOC1: General
No No Yes -
Enable USER
031 135 OP Fig. 22
DTOC2: General
ST Enable USER
No No Yes -
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
IDMT1: General
No No Yes -
Enable USER
031 141 OP Fig. 29
IDMT2: General
No No Yes -
Enable USER
031 142 OP Fig. 29
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: General
No No Yes -
Enable USER
031 143 OP Fig. 29
Disabling and enabling the inverse-time overcurrent protection function.
Note: Function group IDMT3 is available with the P633 and the P634 only.
End a
End b
IDMT1:
End a End c -
Select CT Input
End d
Current Summation
019 106 OP Fig. 28
IDMT2: As per ‘IDMT1: Select
End b -
Select CT Input CT Input’
019 116 OP Fig. 28
IDMT3:
End c
As per ‘IDMT1: Select
-
ST
Select CT Input CT Input’
019 126 OP Fig. 28
Selection of the measuring input that provides the measured variables monitored by the
inverse-time overcurrent protection function.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
THRM1: General
No No Yes -
Enable USER
031 144 OP Fig. 41
THRM2: General
No No Yes -
Enable USER
031 145 OP Fig. 41
Disabling and enabling the thermal overload protection function.
Note: Function group THRM2 is available with the P633 and the P634 only.
End a
End b
THRM1:
End b End c -
Select CT Input
End d
Current Summation
019 109 OP Fig. 40
THRM2: As per ‘THRM1: Select
End c -
Select CT Input CT Input’
019 110 OP Fig. 40
Selection of the current relevant for thermal overload protection. Select from the currents
measured at the measuring input for end a, b, c, d. For the P633 and the P634, there is an
additional option, namely the selection of the value obtained according to the setting at
MAIN: Current summation.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1: Absolute Replica
Relative Replica -
Operating Mode Relative Replica
039 121 OP Fig. 45
THRM2: Absolute Replica
Relative Replica -
Operating Mode Relative Replica
039 181 OP Fig. 45
Setting for the operating mode of thermal overload protection. Select between Absolute
replica and Relative replica.
Not
THRM1: 300 °C/
Not Measured Measured/ 1 °C
O/T f Iref Persist 1 Overflow
-40 °C
004 152 Read only
Not
THRM2: 300 °C/
Not Measured Measured/ 1 °C
O/T f Iref Persist 2 Overflow
ST -40 °C
004 172 Read only
Display of the difference between the settings for the maximum permissible temperatures
of the protected object and the coolant.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
V<>: General Enable
No No Yes -
USER
023 030 OP Fig. 47
Disabling and enabling the time-voltage protection function.
Note: Time-voltage protection is not available with the P631.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
f<>: General Enable
No No Yes -
USER
023 031 OP Fig. 50
Disabling and enabling the over/underfrequency protection function.
Note: Over/underfrequency protection is not available with the P631.
f<>: Evaluation Time 4 Cycles 3 Cycles 6 Cycles 1 Cycles
018 201 OP Fig. 51
Setting for the evaluation time. The operate conditions must be met for this length of time
for a signal to be issued.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
f<>:
0.90 Vn 0.20 Vn 1.00 Vn 0.01 Vn
Undervolt. Block. V<
018 200 OP Fig. 51
Setting for the threshold of the undervoltage blocking. If the voltage falls below this
threshold, the over/underfrequency protection function will be blocked.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
V/f: General Enable
No No Yes -
USER
019 097 OP Fig. 54
Disabling and enabling the overfluxing protection function.
ST
Note: Overfluxing protection is not available with the P631.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
CTS: General Enable
No No Yes -
USER
031 085 OP Fig. 64
Disabling and enabling the CT supervision function.
Note: CT Supervision is only available with DSP coprocessor order option.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
BC_1: General
No No Yes -
Enable USER
031 146 OP Fig. 62
BC_2: General
No No Yes -
Enable USER
031 147 OP Fig. 62
BC_3: General
No No Yes -
Enable USER
031 148 OP Fig. 62
BC_4: General
No No Yes -
Enable USER
031 149 OP Fig. 62
Disabling and enabling the broken conductor detection function.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
BC_1:
End a End a -
Select CT Input
031 150 Read only
BC_2:
End b End b -
Select CT Input
031 151 Read only
BC_3:
End c End c -
Select CT Input
031 152 Read only
BC_4:
End d End d -
Select CT Input
031 153 Read only
Indication of the CT set monitored by the broken conductor detection function.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LIMIT: General
No No Yes -
Enable USER
014 010 OP Fig. 71
Enabling or disabling limit value monitoring.
Blocked/
1.100 0.001
LIMIT: IDC, lin> Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 110 OP Fig. 71
Setting for operate value IDClin> for monitoring the linearized direct current.
Blocked/
1.100 0.001
LIMIT: IDC, lin>> Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 111 OP Fig. 71
Setting for operate value IDClin>> for monitoring the linearized direct current.
Blocked/
LIMIT: tIDC, lin> Blocked 20.00 s 0.01 s
0.00 s
014 112 OP Fig. 71
Setting for the operate delay of overcurrent stage IDClin>.
Blocked/
LIMIT: tIDC, lin>> Blocked 20.00 s 0.01 s
0.00 s
014 113 OP Fig. 71
Setting for the operate delay of overcurrent stage IDClin>>.
Blocked/
1.100 0.001
LIMIT: IDC, lin< Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 114 OP Fig. 71
Setting for operate value IDClin< for monitoring the linearized direct current.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
1.100 0.001
LIMIT: IDC, lin<< Blocked 0.100
IDC, nom IDC, nom
IDC, nom
014 115 OP Fig. 71
Setting for operate value IDClin<< for monitoring the linearized direct current.
Blocked/
LIMIT: tIDC, lin< Blocked 20.00 s 0.01 s
0.00 s
014 116 OP Fig. 71
Setting for the operate delay of undercurrent stage IDClin<.
Blocked/
LIMIT: tIDC, lin<< Blocked 20.00 s 0.01 s
0.00 s
014 117 OP Fig. 71
Setting for the operate delay of the undercurrent stage IDClin<<.
LIMIT: T> 200 °C -20 °C 200 °C 1 °C ST
014 100 OP Fig. 72
Setting for the operate value of temperature monitoring T>.
LIMIT: T>> 200 °C -20 °C 200 °C 1 °C
014 101 OP Fig. 72
Setting for the operate value of temperature monitoring T>>.
Blocked/
LIMIT: tT> Blocked 1000 s 1s
0s
014 103 OP Fig. 72
Setting for the operate delay of temperature monitoring T>.
Blocked/
LIMIT: tT>> Blocked 1000 s 1s
0s
014 104 OP Fig. 72
Setting for the operate delay of temperature monitoring T>>.
LIMIT: T< -20 °C -20 °C 200 °C 1 °C
014 105 OP Fig. 72
Setting for the operate value of temperature monitoring T<.
LIMIT: T<< -20 °C -20 °C 200 °C 1 °C
014 106 OP Fig. 72
Setting for the operate value of temperature monitoring T<<.
Blocked/
LIMIT: tT< Blocked 1000 s 1s
0s
014 107 OP Fig. 72
Setting for the operate delay of temperature monitoring T<.
Blocked/
LIMIT: tT<< Blocked 1000 s 1s
0s
014 108 OP Fig. 72
Setting for the operate delay of temperature monitoring T<<.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LIM_1: General
No No Yes -
Enable USER
014 014 OP Fig. 74
LIM_2: General
No No Yes -
Enable USER
014 015 OP Fig. 74
LIM_3: General
No No Yes -
Enable USER
014 017 OP Fig. 74
Disabling and enabling the limit value monitoring function.
Note: Function group LIM_3 is available with the P633 and the P634 only.
ST
End a
End b
LIM_1:
End a End c -
Select CT Input
End d
Current Summation
019 111 OP Fig. 73
LIM_2: As per ‘LIM_1: Select
End b -
Select CT Input CT Input’
019 112 OP Fig. 73
LIM_3: As per ‘LIM_1: Select
End c -
Select CT Input CT Input’
019 113 OP Fig. 73
Selection of the measuring input that provides the measured variables monitored by limit
value monitoring function 1, 2 or 3, respectively.
Blocked/
LIM_1: I> 1.20 In 4.00 In 0.01 In
0.20 In
015 116 OP Fig. 74
Blocked/
LIM_2: I> 1.20 In 4.00 In 0.01 In
0.20 In
016 116 OP Fig. 74
Blocked/
LIM_3: I> 1.20 In 4.00 In 0.01 In
0.20 In
017 114 OP Fig. 74
Setting for the operate value of I>.
Blocked/
LIM_1: I>> Blocked 4.00 In 0.01 In
0.20 In
015 117 OP Fig. 74
Blocked/
LIM_2: I>> Blocked 4.00 In 0.01 In
0.20 In
016 117 OP Fig. 74
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
LIM_3: I>> Blocked 4.00 In 0.01 In
0.20 In
017 117 OP Fig. 74
Setting for the operate value of I>>.
Blocked/
LIM_1: tI> 5s 100 s 1s
0s
015 120 OP Fig. 74
Blocked/
LIM_2: tI> 5s 100 s 1s
0s
016 120 OP Fig. 74
Blocked/
LIM_3: tI> 5s 100 s 1s
0s
017 120 OP Fig. 74
Setting for the operate delay of I>.
ST
Blocked/
LIM_1: tI>> Blocked 100 s 1s
0s
015 121 OP Fig. 74
Blocked/
LIM_2: tI>> Blocked 100 s 1s
0s
016 121 OP Fig. 74
Blocked/
LIM_3: tI>> Blocked 100 s 1s
0s
017 121 OP Fig. 74
Setting for the operate delay of I>>.
Blocked/
LIM_1: I< 0.10 In 4.00 In 0.01 In
0.00 In
015 118 OP Fig. 74
Blocked/
LIM_2: I< 0.10 In 4.00 In 0.01 In
0.00 In
016 118 OP Fig. 74
Blocked/
LIM_3: I< 0.10 In 4.00 In 0.01 In
0.00 In
017 118 OP Fig. 74
Setting for the operate value of I<.
Blocked/
LIM_1: I<< Blocked 4.00 In 0.01 In
0.00 In
015 119 OP Fig. 74
Blocked/
LIM_2: I<< Blocked 4.00 In 0.01 In
0.00 In
016 119 OP Fig. 74
Blocked/
LIM_3: I<< Blocked 4.00 In 0.01 In
0.00 In
017 119 OP Fig. 74
Setting for the operate value of I<<.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
LIM_1: tI< 5s 100 s 1s
0s
015 122 OP Fig. 74
Blocked/
LIM_2: tI< 5s 100 s 1s
0s
016 122 OP Fig. 74
Blocked/
LIM_3: tI< 5s 100 s 1s
0s
017 122 OP Fig. 74
Setting for the operate delay of I<.
Blocked/
LIM_1: tI<< Blocked 100 s 1s
0s
015 123 OP Fig. 74
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Common Settings
LOGIC: General
No No Yes -
Enable USER
031 099 OP Fig. 76
Disabling or enabling the logic function.
LOGIC: Set 1 (… 8)
No No Yes -
USER
See table below for setting addresses. OP Fig. 75,
76
These settings define the static input conditions for the logic function.
Setting Address Setting Address Setting Address
Set 1 USER 034 030 Set 4 USER 034 033 Set 7 USER 034 036
Set 2 USER 034 031 Set 5 USER 034 034 Set 8 USER 034 037
Set 3 USER 034 032 Set 6 USER 034 035
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
LOGIC: Fct.Assignm.
Disabled dependent upon relay -
Outp. 1 (… 32)
configuration.
See table below for setting addresses. OP Fig. 76
These settings assign functions to the outputs.
Setting Address Setting Address Setting Address
Fct.Assignm. Outp. 1 030 000 Fct.Assignm. Outp. 12 030 044 Fct.Assignm. Outp. 23 030 088
Fct.Assignm. Outp. 2 030 004 Fct.Assignm. Outp. 13 030 048 Fct.Assignm. Outp. 24 030 092
Fct.Assignm. Outp. 3 030 008 Fct.Assignm. Outp. 14 030 052 Fct.Assignm. Outp. 25 030 096
Fct.Assignm. Outp. 4 030 012 Fct.Assignm. Outp. 15 030 056 Fct.Assignm. Outp. 26 031 000
Fct.Assignm. Outp. 5 030 016 Fct.Assignm. Outp. 16 030 060 Fct.Assignm. Outp. 27 031 004
Fct.Assignm. Outp. 6 030 020 Fct.Assignm. Outp. 17 030 064 Fct.Assignm. Outp. 28 031 008
Fct.Assignm. Outp. 7 030 024 Fct.Assignm. Outp. 18 030 068 Fct.Assignm. Outp. 29 031 012
Fct.Assignm. Outp. 8 030 028 Fct.Assignm. Outp. 19 030 072 Fct.Assignm. Outp. 30 031 016
Fct.Assignm. Outp. 9 030 032 Fct.Assignm. Outp. 20 030 076 Fct.Assignm. Outp. 31 031 020
ST
Fct.Assignm. Outp. 10 030 036 Fct.Assignm. Outp. 21 030 080 Fct.Assignm. Outp. 32 031 024
Fct.Assignm. Outp. 11 030 040 Fct.Assignm. Outp. 22 030 084
Setting Range
Menu Text Default Setting Step Size
Min. Max.
LOGIC: Time t1
0.00 s 0.00 s 600.00 s 0.01 s
Output 1 (… 32)
See table below for setting addresses. OP Fig. 76,
77, 78, 79,
80, 81
Settings for timer stage t1 of the respective outputs.
Setting Address Setting Address Setting Address
Time t1 Output 1 030 002 Time t1 Output 12 030 046 Time t1 Output 23 030 090
Time t1 Output 2 030 006 Time t1 Output 13 030 050 Time t1 Output 24 030 094
Time t1 Output 3 030 010 Time t1 Output 14 030 054 Time t1 Output 25 030 098
Time t1 Output 4 030 014 Time t1 Output 15 030 058 Time t1 Output 26 031 002
Time t1 Output 5 030 018 Time t1 Output 16 030 062 Time t1 Output 27 031 006
Time t1 Output 6 030 022 Time t1 Output 17 030 066 Time t1 Output 28 031 010
Time t1 Output 7 030 026 Time t1 Output 18 030 070 Time t1 Output 29 031 014
ST Time t1 Output 8 030 030 Time t1 Output 19 030 074 Time t1 Output 30 031 018
Time t1 Output 9 030 034 Time t1 Output 20 030 078 Time t1 Output 31 031 022
Time t1 Output 10 030 038 Time t1 Output 21 030 082 Time t1 Output 32 031 026
Time t1 Output 11 030 042 Time t1 Output 22 030 086
LOGIC: Time t2
0.00 s 0.00 s 600.00 s 0.01 s
Output 1 (… 32)
See table below for setting addresses. OP Fig. 76,
77, 78, 79,
80, 81
Settings for timer stage t2 of the respective outputs.
Note: This setting has no effect in the ‘Minimum Dwell’ operating mode.
Setting Address Setting Address Setting Address
Time t2 Output 1 030 003 Time t2 Output 12 030 047 Time t2 Output 23 030 091
Time t2 Output 2 030 007 Time t2 Output 13 030 051 Time t2 Output 24 030 095
Time t2 Output 3 030 011 Time t2 Output 14 030 055 Time t2 Output 25 030 099
Time t2 Output 4 030 015 Time t2 Output 15 030 059 Time t2 Output 26 031 003
Time t2 Output 5 030 019 Time t2 Output 16 030 063 Time t2 Output 27 031 007
Time t2 Output 6 030 023 Time t2 Output 17 030 067 Time t2 Output 28 031 011
Time t2 Output 7 030 027 Time t2 Output 18 030 071 Time t2 Output 29 031 015
Time t2 Output 8 030 031 Time t2 Output 19 030 075 Time t2 Output 30 031 019
Time t2 Output 9 030 035 Time t2 Output 20 030 079 Time t2 Output 31 031 023
Time t2 Output 10 030 039 Time t2 Output 21 030 083 Time t2 Output 32 031 027
Time t2 Output 11 030 043 Time t2 Output 22 030 087
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Signals from selection table
LOGIC: Sig. Assig
Disabled dependent upon relay -
Outp. 1 (… 32)
configuration.
See table below for setting addresses. OP Fig. 82
These settings assign the function of a binary input signal to the output of the logic
equation.
Setting Address Setting Address Setting Address
Sig. Assig Outp. 1 044 000 Sig. Assig Outp. 12 044 022 Sig. Assig Outp. 23 044 044
Sig. Assig Outp. 2 044 002 Sig. Assig Outp. 13 044 024 Sig. Assig Outp. 24 044 046
Sig. Assig Outp. 3 044 004 Sig. Assig Outp. 14 044 026 Sig. Assig Outp. 25 044 048
Sig. Assig Outp. 4 044 006 Sig. Assig Outp. 15 044 028 Sig. Assig Outp. 26 044 050
Sig. Assig Outp. 5 044 008 Sig. Assig Outp. 16 044 030 Sig. Assig Outp. 27 044 052
Sig. Assig Outp. 6 044 010 Sig. Assig Outp. 17 044 032 Sig. Assig Outp. 28 044 054
Sig. Assig Outp. 7 044 012 Sig. Assig Outp. 18 044 034 Sig. Assig Outp. 29 044 056
Sig. Assig Outp. 8 044 014 Sig. Assig Outp. 19 044 036 Sig. Assig Outp. 30 044 058 ST
Sig. Assig Outp. 9 044 016 Sig. Assig Outp. 20 044 038 Sig. Assig Outp. 31 044 060
Sig. Assig Outp. 10 044 018 Sig. Assig Outp. 21 044 040 Sig. Assig Outp. 32 044 062
Sig. Assig Outp. 11 044 020 Sig. Assig Outp. 22 044 042
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end a SGx B-C Swapped
C-A Swapped
010 200 010 201 010 202 010 203
Setting to determine if CT input phase-swapping shall apply in pumped storage
applications, when in motoring (pump) mode. Setting available for each CT set, in this
case for end a.
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end b SGx B-C Swapped
ST C-A Swapped
010 204 010 205 010 206 010 207
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end c SGx B-C Swapped
C-A Swapped
010 208 010 209 010 210 010 211
No Swap
MAIN: A-B Swapped
No Swap -
Reversal end d SGx B-C Swapped
C-A Swapped
010 212 010 213 010 214 010 215
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
DIFF: Enable SGx No No Yes -
072 152 073 152 074 152 075 152 OP Fig. 1
This setting specifies the setting group to be enabled for differential protection.
DIFF: Vec. Gr. ends
0 0 11 1
b-a SGx
019 010 019 040 019 041 019 042 OP Fig. 5
DIFF: Vec. Gr. ends
0 0 11 1
c-a SGx
019 011 019 043 019 044 019 045 OP Fig. 5
DIFF: Vec. Gr. ends
0 0 11 1
d-a SGx
019 014 019 046 019 047 019 048 OP Fig. 6
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
The vector group is read from the transformer rating plate, taking end "a" as the HV
reference. In the case of a Yd1 transformer, with end "b" as the delta winding the clock
notation setting required will be 1 for end b-a.
If the phase currents of the low and high voltage sides are exchanged or if the connection
of the measuring circuits is not accounted for by the settings at MAIN: CT Orientation
IPh, z (where z is end a, b, c or d) then the algorithm is:
Setting = 12 - ID
If a reverse phase rotation is present (phase sequence A-C-B) then this should be entered
as a setting at the P63x. In this case, the P63x will automatically form the complementary
value of the set vector group ID to the number 12
(vector group ID = 12 - set ID).
For application of the P63x as machine protection, the setting must be 0 or 6 depending on
the current transformer connection.
DIFF: Idiff> SGx 0.20 Iref 0.10 Iref 2.50 Iref 0.01 Iref
072 142 073 142 074 142 075 142 OP Fig. 9
Minimum pickup value of the differential protection function as referred to the reference
ST
current of the relevant transformer end.
DIFF: Idiff>> SGx 15.0 Iref 2.5 Iref 30.0 Iref 0.1 Iref
072 143 073 143 074 143 075 143 OP Fig. 9
Threshold value of the differential current for deactivation of the inrush stabilization
function (harmonic restraint) and of the overfluxing restraint.
Note: If the threshold is set too high, it is possible for the P63x not to trip in the
presence of internal faults with transformer saturation.
Blocked/
DIFF: Idiff>>> SGx 30.0 Iref 30.0 Iref 0.1 Iref
2.5 Iref
072 144 073 144 074 144 075 144 OP Fig. 9
Threshold value of the differential current for tripping by the differential protection function
independent of restraining variable, harmonic restraint, overfluxing restraint and saturation
detector.
Note: If the threshold is set too low, the P63x can trip in the presence of external
faults with transformer saturation.
DIFF:
0.20 Iref 0.10 Iref 30.00 Iref 0.01 Iref
Idiff> (CTS) SGx
080 000 081 000 082 000 083 000 OP Fig. 68
Low set threshold of differential protection when a CTS condition is detected.
DIFF: m1 SGx 0.30 0.10 1.50 0.01
072 145 073 145 074 145 075 145 OP Fig. 9
Gradient of the tripping characteristic of differential protection in the range:
0.5 ⋅ Idiff >< IR ≤ IR,m2
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: IR, m2 SGx 4.0 Iref 1.5 Iref 10.0 Iref 0.1 Iref
072 147 073 147 074 147 075 147 OP Fig. 9
This setting defines the second knee of the tripping characteristic. Above this knee, the
gradient is m2.
Disabled
DIFF:
Not Phase-Selective Not Phase-Selective -
Op. Mode Inrush SGx
Phase-Selective
072 148 073 148 074 148 075 148 OP Fig. 9
Setting for the operating mode of the inrush stabilization function (harmonic blocking or
harmonic restraint).
For application of the P63x as machine protection, the harmonic restraint can be
deactivated by way of this setting.
For application of the P63x as transformer protection, the user can select whether the
harmonic restraint should operate in cross-blocking mode or selectively for one measuring
system.
ST
DIFF: Inrush 2nd
20 % 10 % 50 % 1%
Harmon SGx
072 159 073 159 074 159 075 159 OP Fig. 10
Operate value of the inrush stabilization function (harmonic restraint) of differential
protection, as ratio of the second harmonic component to the fundamental for the
differential current, in percent.
DIFF:
Yes No Yes -
I0 filt a Enab SGx
072 155 073 155 074 155 075 155 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt b Enab SGx
072 156 073 156 074 156 075 156 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt c Enab SGx
072 157 073 157 074 157 075 157 OP Fig. 5
DIFF:
Yes No Yes -
I0 filt d Enab SGx
072 154 073 154 074 154 075 154 OP Fig. 6
Enabling or disabling the zero-sequence filtering of winding a, b, c or d.
DIFF:
No No Yes -
O/Flux Blk Enab SGx
072 158 073 158 074 158 075 158 OP Fig. 12
Enabling or disabling the overfluxing restraint.
DIFF: O/Flux 5th
20 % 10 % 80 % 1%
Harmon SGx
072 160 073 160 074 160 075 160 OP Fig. 12
Operate value of the overfluxing restraint of differential protection as ratio of the fifth
harmonic component to the fundamental for the differential current, in percent.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DIFF: Op.del., trip
0.00 s 0.00 s 100.00 s 0.01 s
sig. SGx
010 162 010 163 010 164 010 165
Tripping of the restraint differential protection may be delayed via a settable timer stage.
DIFF: Hyst. Effective
Yes No Yes -
SGx
072 006 073 006 074 006 075 006
Hysteresis of the tripping characteristic at the rate of 10% be disabled.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
REF_1: Enable SGx No No Yes - ST
072 141 073 141 074 141 075 141 OP Fig. 14
REF_2: Enable SGx No No Yes -
072 161 073 161 074 161 075 161 OP Fig. 14
REF_3: Enable SGx No No Yes -
072 031 073 031 074 031 075 031 OP Fig. 14
This setting allows restricted earth fault protection to be enabled or disabled on the
associated winding for each setting group.
Low-Z Iph Sum Bias
REF_1:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 149 073 149 074 149 075 149 OP Fig. 16,
18, 19
Low-Z Iph Sum Bias
REF_2:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 169 073 169 074 169 075 169 OP Fig. 16,
18, 19
Low-Z Iph Sum Bias
REF_3:
Low-Z Iph Sum Bias Low-Z Iph Max. Bias -
Operating Mode SGx
High Impedance
072 049 073 049 074 049 075 049 OP Fig. 16,
18, 19
This setting specifies the mode of operation for the restricted earth fault protection. The
protection may be biased by residual current or the maximum phase current. Alternatively,
operation as a high impedance element may be selected.
REF_1:
No No Yes -
CTS Effective SGx
080 003 081 003 082 003 083 003
REF_2:
No No Yes -
CTS Effective SGx
080 004 081 004 082 004 083 004
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3:
No No Yes -
CTS Effective SGx
080 005 081 005 082 005 083 005
Blocking of REF protection when a CTS condition is detected.
REF_1: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 150 073 150 074 150 075 150 OP Fig. 17
REF_2: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 170 073 170 074 170 075 170 OP Fig. 17
REF_3: Idiff> SGx 0.20 Iref 0.10 Iref 1.00 Iref 0.01 Iref
072 040 073 040 074 040 075 040 OP Fig. 17
Pickup value of the restricted earth fault protection as referred to the reference current of
the relevant transformer end.
Blocked/
ST REF_1: Idiff>>> SGx 10.0 Iref
2.5 Iref
30.0 Iref 0.1 Iref
Setting Range
Menu Text Default Setting Step Size
Min. Max.
REF_3: IR, m2 SGx 1.00 Iref 0.10 Iref 1.50 Iref 0.01 Iref
072 194 073 194 074 194 075 194 OP Fig. 18
Bias current threshold setting above which the gradient of the tripping characteristic is m2
for restricted earth fault protection when operating in a low impedance biased mode.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
DTOC1: Enable SGx No No Yes -
076 050 077 050 078 050 079 050
DTOC2: Enable SGx No No Yes -
076 070 077 070 078 070 079 070
DTOC3: Enable SGx No No Yes -
ST
076 180 077 180 078 180 079 180
This setting specifies the setting group to be enabled for definite-time overcurrent
protection.
Disabled
DTOC1:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 067 077 067 078 067 079 067 OP Fig. 25
Disabled
DTOC2:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 087 077 087 078 087 079 087 OP Fig. 25
Disabled
DTOC3:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
076 108 077 108 078 108 079 108 OP Fig. 25
This setting defines whether blocking of the residual current stages will take place for
single-pole or multi-pole phase current starting.
DTOC1: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 066 077 066 078 066 079 066 OP Fig. 26
DTOC2: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 086 077 086 078 086 079 086 OP Fig. 26
DTOC3: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
076 106 077 106 078 106 079 106 OP Fig. 26
This setting defines whether starting of the negative-sequence and residual current stages
will be included in the general starting signal of DTOC protection.
Blocked/
DTOC1: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 065 077 065 078 065 079 065 OP Fig. 26
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC2: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 085 077 085 078 085 079 085 OP Fig. 26
Blocked/
DTOC3: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
076 107 077 107 078 107 079 107 OP Fig. 26
Setting for the operate delay of the general starting signal of DTOC protection.
DTOC1: Inrush Restr
No No Yes -
Enab SGx
076 063 077 063 078 063 079 063 OP Fig. 24
DTOC2: Inrush Restr
No No Yes -
Enab SGx
076 083 077 083 078 083 079 083 OP Fig. 24
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC3: I>>> SGx Blocked 30.00 In 0.01 In
0.10 In
076 183 077 183 078 183 079 183 OP Fig. 23
Setting for the operate value I>>>.
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 151 077 151 078 151 079 151 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 161 077 161 078 161 079 161 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I> dynamic SGx 0.10 In
076 181 077 181 078 181 079 181 OP Fig. 23
Setting for the operate value I> in dynamic mode. This operate value is only effective while
the hold time for dynamic settings is elapsing.
ST
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 152 077 152 078 152 079 152 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 162 077 162 078 162 079 162 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I>> dynamic SGx 0.10 In
076 182 077 182 078 182 079 182 OP Fig. 23
Setting for the operate value I>> in dynamic mode. This operate value is only effective
while the hold time for dynamic settings is elapsing.
DTOC1: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 153 077 153 078 153 079 153 OP Fig. 23
DTOC2: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 173 077 173 078 173 079 173 OP Fig. 23
DTOC3: Blocked/
1.00 In 30.00 In 0.01 In
I>>> dynamic SGx 0.10 In
076 109 077 109 078 109 079 109 OP Fig. 23
Setting for the operate value I>>> in dynamic mode. This operate value is only effective
while the hold time for dynamic settings is elapsing.
Blocked/
DTOC1: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 057 077 057 078 057 079 057 OP Fig. 23
Blocked/
DTOC2: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 077 077 077 078 077 079 077 OP Fig. 23
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC3: tI> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 187 077 187 078 187 079 187 OP Fig. 23
Setting for the operate delay of the I> stage.
Blocked/
DTOC1: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 058 077 058 078 058 079 058 OP Fig. 23
Blocked/
DTOC2: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 078 077 078 078 078 079 078 OP Fig. 23
Blocked/
DTOC3: tI>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 188 077 188 078 188 079 188 OP Fig. 23
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC1: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 199 077 199 078 199 079 199 OP Fig. 24
Blocked/
DTOC2: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 209 077 209 078 209 079 209 OP Fig. 24
Blocked/
DTOC3: I2>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 219 077 219 078 219 079 219 OP Fig. 24
Setting for the operate value of the I2>>> stage for negative sequence current.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2> dynamic SGx 0.10 In
076 200 077 200 078 200 079 200 OP Fig. 24
DTOC2:
I2> dynamic SGx
1.00 In
Blocked/
0.10 In
8.00 In 0.01 In ST
076 210 077 210 078 210 079 210 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2> dynamic SGx 0.10 In
076 220 077 220 078 220 079 220 OP Fig. 24
Setting for the operate value of the I2> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 201 077 201 078 201 079 201 OP Fig. 24
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 211 077 211 078 211 079 211 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2>> dynamic SGx 0.10 In
076 221 077 221 078 221 079 221 OP Fig. 24
Setting for the operate value of the I2>> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
DTOC1: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 202 077 202 078 202 079 202 OP Fig. 24
DTOC2: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 212 077 212 078 212 079 212 OP Fig. 24
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
I2>>> dynamic SGx 0.10 In
076 222 077 222 078 222 079 222 OP Fig. 24
Setting for the operate value of the I2>>> stage for negative sequence current in dynamic
mode. This operate value is only effective while the hold time for dynamic settings is
elapsing.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC1: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 203 077 203 078 203 079 203 OP Fig. 24
Blocked/
DTOC2: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 213 077 213 078 213 079 213 OP Fig. 24
Blocked/
DTOC3: tI2> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 223 077 223 078 223 079 223 OP Fig. 24
Setting for the operate delay of the I2> stage for negative sequence current.
Blocked/
DTOC1: tI2>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 204 077 204 078 204 079 204 OP Fig. 24
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
DTOC2: IN>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 165 077 165 078 165 079 165 OP Fig. 25
Blocked/
DTOC3: IN>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 185 077 185 078 185 079 185 OP Fig. 25
Setting for the operate value IN>> for residual current.
Blocked/
DTOC1: IN>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 056 077 056 078 056 079 056 OP Fig. 25
Blocked/
DTOC2: IN>>> SGx Blocked 8.00 In 0.01 In
0.10 In
076 166 077 166 078 166 079 166 OP Fig. 25
Setting Range
Menu Text Default Setting Step Size
Min. Max.
DTOC3: Blocked/
1.00 In 8.00 In 0.01 In
IN>>> dynamic SGx 0.10 In
076 196 077 196 078 196 079 196 OP Fig. 25
Setting for the operate value IN>>> for residual current in dynamic mode. This operate
value is only effective while the hold time for dynamic settings is elapsing.
Blocked/
DTOC1: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 060 077 060 078 060 079 060 OP Fig. 25
Blocked/
DTOC2: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 170 077 170 078 170 079 170 OP Fig. 25
Blocked/
DTOC3: tIN> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 190 077 190 078 190 079 190 OP Fig. 25
ST Setting for the operate delay of the IN> for residual current stage.
Blocked/
DTOC1: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 061 077 061 078 061 079 061 OP Fig. 25
Blocked/
DTOC2: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 171 077 171 078 171 079 171 OP Fig. 25
Blocked/
DTOC3: tIN>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 191 077 191 078 191 079 191 OP Fig. 25
Setting for the operate delay of the IN>> for residual current stage.
Blocked/
DTOC1: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 062 077 062 078 062 079 062 OP Fig. 25
Blocked/
DTOC2: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 172 077 172 078 172 079 172 OP Fig. 25
Blocked/
DTOC3: tIN>>> SGx 0.50 s 100.00 s 0.01 s
0.00 s
076 192 077 192 078 192 079 192 OP Fig. 25
Setting for the operate delay of the IN>>> for residual current stage.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
IDMT1: Enable SGx No No Yes -
081 050 082 050 083 050 084 050 OP Fig. 29
IDMT2: Enable SGx No No Yes -
081 170 082 170 083 170 084 170 OP Fig. 29
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: Enable SGx No No Yes -
081 190 082 190 083 190 084 190 OP Fig. 29
This setting specifies the setting group to be enabled for inverse-time overcurrent
protection.
Disabled
IDMT1:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
081 068 082 068 083 068 084 068 OP Fig. 36
Disabled
IDMT2:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
081 188 082 188 083 188 084 188 OP Fig. 36
Disabled
IDMT3:
Disabled For Single-Ph. Start -
Block Tim. st IN SGx
For Multi-Ph. Start.
ST
081 208 082 208 083 208 084 208 OP Fig. 36
This setting defines whether blocking of the residual current stages will take place for
single-pole or multi-pole phase current starting.
IDMT1: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 059 082 059 083 059 084 059 OP Fig. 35,
36, 38
IDMT2: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 179 082 179 083 179 084 179 OP Fig. 35,
36, 38
IDMT3: Gen.Starting W/o Start. IN/I2
With Start. IN/I2 -
Mode SGx With Start. IN/I2
081 199 082 199 083 199 084 199 OP Fig. 35,
36, 38
This setting defines whether starting of the negative-sequence and residual current stages
will be included in the general starting signal of IDMT protection.
Blocked/
IDMT1: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 058 082 058 083 058 084 058 OP Fig. 38
Blocked/
IDMT2: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 178 082 178 083 178 084 178 OP Fig. 38
Blocked/
IDMT3: tGS SGx 0.00 s 100.00 s 0.01 s
0.00 s
081 198 082 198 083 198 084 198 OP Fig. 38
Setting for the operate delay of the general starting signal of IDMT protection.
IDMT1: Inrush Restr
No No Yes -
Enab SGx
081 060 082 060 083 060 084 060 OP Fig. 34,
35
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT2: Inrush Restr
No No Yes -
Enab SGx
081 180 082 180 083 180 084 180 OP Fig. 34,
35
IDMT3: Inrush Restr
No No Yes -
Enab SGx
081 200 082 200 083 200 084 200 OP Fig. 34,
35
Setting as to whether the inrush restraint of differential protection shall be able to block the
inverse-time overcurrent protection function.
Blocked/
IDMT1: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
081 051 082 051 083 051 084 051 OP Fig. 34
Blocked/
IDMT2: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
ST
081 171 082 171 083 171 084 171 OP Fig. 34
Blocked/
IDMT3: Iref, Ph SGx 1.00 In 4.00 In 0.01 In
0.10 In
081 191 082 191 083 191 084 191 OP Fig. 34
Setting for the reference current (phase overcurrent pickup).
IDMT1: Blocked/
1.00 In 4.00 In 0.01 In
Iref, Ph dynamic SGx 0.10 In
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: As per ‘IDMT1: Phase
Definite Time -
Phase Charac SGx Charac SGx’
081 193 082 193 083 193 084 193 OP Fig. 34
Setting for the tripping characteristic (phase current system).
IDMT1: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 054 082 054 083 054 084 054 OP Fig. 34
IDMT2: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 174 082 174 083 174 084 174 OP Fig. 34
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 194 082 194 083 194 084 194 OP Fig. 34
TMS or time dial setting of the starting characteristic (phase current system).
ST
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 057 082 057 083 057 084 057 OP Fig. 34
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 177 082 177 083 177 084 177 OP Fig. 34
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t Ph SGx
081 197 082 197 083 197 084 197 OP Fig. 34
Setting for the minimum trip time (phase current system).
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 055 082 055 083 055 084 055 OP Fig. 34
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 175 082 175 083 175 084 175 OP Fig. 34
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time Ph SGx
081 195 082 195 083 195 084 195 OP Fig. 34
Setting for the hold time for storing the starting time once the starting has dropped out
(phase current system).
IDMT1: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 056 082 056 083 056 084 056 OP Fig. 34
IDMT2: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 176 082 176 083 176 084 176 OP Fig. 34
IDMT3: Instantaneous
Instantaneous -
Release Ph SGx Delayed as per Char.
081 196 082 196 083 196 084 196 OP Fig. 34
Setting for the release characteristic (phase current system).
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
IDMT1: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 111 082 111 083 111 084 111 OP Fig. 35
Blocked/
IDMT2: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 121 082 121 083 121 084 121 OP Fig. 35
Blocked/
IDMT3: Iref, I2 SGx Blocked 0.80 In 0.01 In
0.01 In
081 131 082 131 083 131 084 131 OP Fig. 35
Setting for the pickup current (negative-sequence current system).
IDMT1: Blocked/
Blocked 0.80 In 0.01 In
Iref, I2 dynamic SGx 0.01 In
081 112 082 112 083 112 084 112 OP Fig. 35
ST IDMT2:
Iref, I2 dynamic SGx
Blocked
Blocked/
0.01 In
0.80 In 0.01 In
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 134 082 134 083 134 084 134 OP Fig. 35
TMS or time dial setting of the starting characteristic (negative-sequence current system).
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 117 082 117 083 117 084 117 OP Fig. 35
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 127 082 127 083 127 084 127 OP Fig. 35
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t I2 SGx
081 137 082 137 083 137 084 137 OP Fig. 35
Setting for the minimum trip time characteristic (negative-sequence current system).
ST
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 115 082 115 083 115 084 115 OP Fig. 35
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 125 082 125 083 125 084 125 OP Fig. 35
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time I2 SGx
081 135 082 135 083 135 084 135 OP Fig. 35
Setting for the hold time for storing the starting time once the starting has dropped out
characteristic (negative-sequence current system).
IDMT1: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 116 082 116 083 116 084 116 OP Fig. 35
IDMT2: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 126 082 126 083 126 084 126 OP Fig. 35
IDMT3: Instantaneous
Instantaneous -
Release I2 SGx Delayed as per Char.
081 136 082 136 083 136 084 136 OP Fig. 35
Setting for the release characteristic (negative-sequence current system).
Blocked/
IDMT1: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 061 082 061 083 061 084 061 OP Fig. 36
Blocked/
IDMT2: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 181 082 181 083 181 084 181 OP Fig. 36
Blocked/
IDMT3: Iref, N SGx Blocked 0.80 In 0.01 In
0.01 In
081 201 082 201 083 201 084 201 OP Fig. 36
Setting for the pickup current (residual current system).
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT1: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 062 082 062 083 062 084 062 OP Fig. 36
IDMT2: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 182 082 182 083 182 084 182 OP Fig. 36
IDMT3: Blocked/
Blocked 0.80 In 0.01 In
Iref, N dynamic SGx 0.01 In
081 202 082 202 083 202 084 202 OP Fig. 36
Setting for the pickup current (residual current system) in dynamic mode. This operate
value is only effective while the hold time for dynamic settings is elapsing.
Definite Time
IEC Standard Inverse
IEC Very Inverse
ST IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IDMT1: IEC Standard
IEEE Very Inverse -
N Charac SGx Inverse
IEEE Extr. Inverse
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
081 063 082 063 083 063 084 063 OP Fig. 36
IDMT2: IEC Standard As per ‘IDMT1:
-
N Charac SGx Inverse N Charac SGx’
081 183 082 183 083 183 084 183 OP Fig. 36
IDMT3: IEC Standard As per ‘IDMT1:
-
N Charac SGx Inverse N Charac SGx’
081 203 082 203 083 203 084 203 OP Fig. 36
Setting for the tripping characteristic (residual current system).
IDMT1: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 064 082 064 083 064 084 064 OP Fig. 36
IDMT2: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 184 082 184 083 184 084 184 OP Fig. 36
IDMT3: kt Time
1.00 0.05 10.00 0.01
Dial/TMS SGx
081 204 082 204 083 204 084 204 OP Fig. 36
TMS or time dial setting of the starting characteristic (residual current system).
IDMT1:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 067 082 067 083 067 084 067 OP Fig. 36
IDMT2:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 187 082 187 083 187 084 187 OP Fig. 36
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
IDMT3:
1.00 s 0.00 s 10.00 s 0.01 s
Min. Trip t N SGx
081 207 082 207 083 207 084 207 OP Fig. 36
Setting for the minimum trip time (residual current system).
IDMT1:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 065 082 065 083 065 084 065 OP Fig. 36
IDMT2:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 185 082 185 083 185 084 185 OP Fig. 36
IDMT3:
0.00 s 0.00 s 600.00 s 0.01 s
Hold Time N SGx
081 205 082 205 083 205 084 205 OP Fig. 36
Setting for the hold time for storing the starting time once the starting has dropped out
(residual current system).
ST
IDMT1: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 066 082 066 083 066 084 066 OP Fig. 36
IDMT2: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 186 082 186 083 186 084 186 OP Fig. 36
IDMT3: Instantaneous
Instantaneous -
Release N SGx Delayed as per Char.
081 206 082 206 083 206 084 206 OP Fig. 36
Setting for the release characteristic (residual current system).
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
THRM1:
No No Yes -
Enable SGx
081 070 082 070 083 070 084 070 OP Fig. 41
THRM2:
No No Yes -
Enable SGx
081 090 082 090 083 090 084 090 OP Fig. 41
This setting specifies the setting group to be enabled for thermal overload protection.
THRM1:
1.00 In 0.10 In 4.00 In 0.01 In
Iref Rating SGx
081 074 082 074 083 074 084 074 OP Fig. 45
THRM2:
1.00 In 0.10 In 4.00 In 0.01 In
Iref Rating SGx
081 094 082 094 083 094 084 094 OP Fig. 45
Setting for the reference current.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1: Start
1.15 1.05 1.50 0.01
Fact.OL_RC SGx
081 075 082 075 083 075 084 075 OP Fig. 45
THRM2: Start
1.15 1.05 1.50 0.01
Fact.OL_RC SGx
081 095 082 095 083 095 084 095 OP Fig. 45
The starting factor k must be set in accordance with the maximum permissible continuous
thermal current of the protected object:
I therm,prot.object
k=
Inom,prot.object
THRM1: Tim.const
30.0 min 1.0 min 1000.0 min 0.1 min
1(heat) SGx
081 082 082 082 083 082 084 082 OP Fig. 45
THRM2: Tim.const
ST 1(heat) SGx
30.0 min 1.0 min 1000.0 min 0.1 min
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Default Temp. Value
THRM1: Select CT
Default Temp. Value From PT100 -
Ambient SGx
From 20 mA Input
081 072 082 072 083 072 084 072 OP Fig. 44
Default Temp. Value
THRM2: Select CT
Default Temp. Value From PT100 -
Ambient SGx
From 20 mA Input
081 092 082 092 083 092 084 092 OP Fig. 44
Select the mode of the coolant temperature acquisition. Select from:
• No data acquisition. A default temperature value is used instead
• Data acquisition via the PT 100 input
• Data acquisition via the 20 mA input
THRM1:
40 °C -40 °C 70 °C 1 °C
Default CT Amb SGx
081 081 082 081 083 081 084 081 OP Fig. 45 ST
THRM2:
40 °C -40 °C 70 °C 1 °C
Default CT Amb SGx
081 101 082 101 083 101 084 101 OP Fig. 45
Setting for the coolant temperature to be used for calculation of the trip time if there is no
data acquisition for the coolant temperature.
THRM1:
Yes No Yes -
Blk for CTA Fail SGx
081 073 082 073 083 073 084 073 OP Fig. 44
THRM2:
Yes No Yes -
Blk for CTA Fail SGx
081 093 082 093 083 093 084 093 OP Fig. 44
This setting specifies whether the thermal overload protection function will be blocked in
the event of faulty coolant temperature acquisition.
THRM1: T> Alarm
95 % 50 % 200 % 1%
Reset,% SGx
081 079 082 079 083 079 084 079 OP Fig. 45
THRM2: T> Alarm
95 % 50 % 200 % 1%
Reset,% SGx
081 099 082 099 083 099 084 099 OP Fig. 45
Setting for the operate value of the warning stage.
THRM1: T> Trip
100 % 50 % 200 % 1%
Reset,% SGx
081 076 082 076 083 076 084 076 OP Fig. 45
THRM2: T> Trip
100 % 50 % 200 % 1%
Reset,% SGx
081 096 082 096 083 096 084 096 OP Fig. 45
Setting for the operate value of the trip stage.
Note: If the operating mode has been set to Absolute Replica, the setting here will
be automatically set to 100% and this parameter is hidden as far as the
local control panel is concerned.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
THRM1:
2% 2% 30 % 1%
Trip Hysteresis SGx
081 078 082 078 083 078 084 078 OP Fig. 45
THRM2:
2% 2% 30 % 1%
Trip Hysteresis SGx
081 098 082 098 083 098 084 098 OP Fig. 45
Setting for the hysteresis of the trip stage.
THRM1: Blocked/
30.0 min 1000.0 min 0.1 min
Pre-Trip Alarm SGx 0.0 min
081 085 082 085 083 085 084 085 OP Fig. 45
THRM2: Blocked/
30.0 min 1000.0 min 0.1 min
Pre-Trip Alarm SGx 0.0 min
081 105 082 105 083 105 084 105 OP Fig. 45
ST A warning will be given in advance of the trip. The time difference between the warning
time and the trip time is set here.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
V<>: Enable SGx No No Yes -
076 000 077 000 078 000 079 000 OP Fig. 47
The time-voltage protection will be enabled in the setting group selected with this setting.
Blocked/
V<>: V> SGx 1.10 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 003 077 003 078 003 079 003 OP Fig. 48
Setting for the operate value V>.
Blocked/
V<>: V>> SGx 1.10 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 004 077 004 078 004 079 004 OP Fig. 48
Setting for the operate value V>>.
Blocked/
V<>: tV> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 005 077 005 078 005 079 005 OP Fig. 48
Setting for the operate delay of time-overvoltage stage V>.
Blocked/
V<>: tV>> SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 006 077 006 078 006 079 006 OP Fig. 48
Setting for the operate delay of time-overvoltage stage V>>.
Blocked/
V<>: V< SGx 0.80 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 007 077 007 078 007 079 007 OP Fig. 49
Setting for the operate value V<.
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
V<>: V<< SGx 0.80 Vn 1.50 Vn 0.01 Vn
0.20 Vn
076 008 077 008 078 008 079 008 OP Fig. 49
Setting for the operate value V<<.
Blocked/
V<>: Vmin> SGx 0.25 Vn 0.60 Vn 0.01 Vn
0.00 Vn
076 046 077 046 078 046 079 046 OP Fig. 49
Setting for Vmin>. Can be used to prevent undervoltage stages operating when the VT is
dead, restricting operation to low voltage conditions only.
Blocked/
V<>: tV< SGx 1.00 s 100.00 s 0.01 s
0.00 s
076 009 077 009 078 009 079 009 OP Fig. 49
Setting for the operate delay of time-undervoltage stage V<.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
f<>: Enable SGx No No Yes -
018 196 018 197 018 198 018 199 OP Fig. 50
This setting specifies the setting group to be enabled for over/underfrequency protection.
f
f<>:
f f with df/dt -
Oper. Mode f1 SGx
f + Delta f/Delta t
018 120 018 121 018 122 018 123 OP Fig. 53
f
f<>:
f f with df/dt -
Oper. Mode f2 SGx
f + Delta f/Delta t
018 144 018 145 018 146 018 147 OP Fig. 53
f
f<>:
f f with df/dt -
Oper. Mode f3 SGx
f + Delta f/Delta t
018 168 018 169 018 170 018 171 OP Fig. 53
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
f
f<>:
f f with df/dt -
Oper. Mode f4 SGx
f + Delta f/Delta t
018 192 018 193 018 194 018 195 OP Fig. 53
Setting for the operating mode of the timer stages of over/underfrequency protection, and
whether instantaneous rate of change of frequency, or average frequency gradient shall
supervize.
Blocked/
f<>: f1 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 100 018 101 018 102 018 103 OP Fig. 53
Blocked/
f<>: f2 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 124 018 125 018 126 018 127 OP Fig. 53
Blocked/
f<>: f3 SGx 49.80 Hz 70.00 Hz 0.01 Hz
ST 40.00 Hz
018 148 018 149 018 150 018 151 OP Fig. 53
Blocked/
f<>: f4 SGx 49.80 Hz 70.00 Hz 0.01 Hz
40.00 Hz
018 172 018 173 018 174 018 175 OP Fig. 53
Setting for the frequency threshold. The over/underfrequency protection function operates
if one of the following two conditions applies:
• The threshold is higher than the set nominal frequency and the frequency
exceeds this threshold
• The threshold is lower than the set nominal frequency and the frequency falls
below this threshold
Depending on the selected operating mode, a signal will be issued without further
monitoring or, alternatively, further monitoring mechanisms will be triggered.
Blocked/
f<>: tf1 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 104 018 105 018 106 018 107 OP Fig. 53
Blocked/
f<>: tf2 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 128 018 129 018 130 018 131 OP Fig. 53
Blocked/
f<>: tf3 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 152 018 153 018 154 018 155 OP Fig. 53
Blocked/
f<>: tf4 SGx 0.00 s 10.00 s 0.01 s
0.00 s
018 176 018 177 018 178 018 179 OP Fig. 53
Setting for the operate delay of over/underfrequency protection.
Blocked/
f<>: df1/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 108 018 109 018 110 018 111 OP Fig. 53
Blocked/
f<>: df2/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 132 018 133 018 134 018 135 OP Fig. 53
Settings P63x/UK ST/A54
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Blocked/
f<>: df3/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 156 018 157 018 158 018 159 OP Fig. 53
Blocked/
f<>: df4/dt SGx 2.0 Hz/s 10.0 Hz/s 0.1 Hz/s
0.1 Hz/s
018 180 018 181 018 182 018 183 OP Fig. 53
Setting for the frequency gradient to be monitored.
Note: This setting is ineffective unless the operating mode f with df/dt has been
selected.
Blocked/
f<>: Delta f1 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 112 018 113 018 114 018 115 OP Fig. 53
Blocked/
f<>: Delta f2 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 136 018 137 018 138 018 139 OP Fig. 53
ST
Blocked/
f<>: Delta f3 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 160 018 161 018 162 018 163 OP Fig. 53
Blocked/
f<>: Delta f4 SGx 0.30 Hz 5.00 Hz 0.01 Hz
0.01 Hz
018 184 018 185 018 186 018 187 OP Fig. 53
Setting for delta f.
Note: This setting is ineffective unless the operating mode f with Delta f/Delta t
has been selected.
f<>: Delta t1 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 116 018 117 018 118 018 119 OP Fig. 53
f<>: Delta t2 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 140 018 141 018 142 018 143 OP Fig. 53
f<>: Delta t3 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 164 018 165 018 166 018 167 OP Fig. 53
f<>: Delta t4 SGx 0.30 s 0.04 s 3.00 s 0.01 s
018 188 018 189 018 190 018 191 OP Fig. 53
Setting for delta t.
Note: This setting is ineffective unless the operating mode f with Delta f/Delta t
has been selected.
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
V/f: Enable SGx No No Yes -
018 210 082 210 083 210 084 210 OP Fig. 54
This setting specifies the setting group to be enabled for overfluxing protection.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
V/f: Blocked/
1.05 Vn/fn 1.20 Vn/fn 0.01 Vn/fn
V/f> (Alarm) SGx 1.00 Vn/fn
Setting Range
Menu Text Default Setting Step Size
Min. Max.
V/f: t at V/f=1.55 SGx 1.4 s 1.0 s 1000.0 s 0.1 s
018 227 082 227 083 227 084 227 OP Fig. 58,
60
V/f: t at V/f=1.60 SGx 1.3 s 1.0 s 1000.0 s 0.1 s
018 228 082 228 083 228 084 228 OP Fig. 58,
60
Time delay settings to configure the overfluxing protection characteristic for V/f values from
1.05 to 1.60 in 0.05 V/Hz steps.
V/f: Reset Time SGx 0s 0s 10000 s 1s
018 230 082 230 083 230 084 230 OP Fig. 60
Reset delay for the variable time tripping characteristic of overfluxing protection.
V/f: tV/f>> SGx Blocked Blocked/0 s 10000 s 1s
018 229 082 229 083 229 084 229
Time delay for definite time tripping stage of overfluxing protection. ST
1.3.3.10 Current transformer supervision (CTS)
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
CTS: Enable SGx No No Yes -
001 118 001 119 001 120 001 121 OP Fig. 64
This setting specifies the setting group to be enabled for CT supervision.
CTS: I1> SGx 0.10 Iref 0.05 Iref 4.00 Iref 0.01 Iref
001 111 001 115 001 116 001 117 OP Fig. 66
Positive sequence current threshold to be exceeded in order to determine CTS condition.
CTS: I2/I1> SGx 0.05 0.05 1.00 0.01
001 102 001 103 001 104 001 105 OP Fig. 66
Low set negative to positive sequence current ratio that is not to be exceeded in order to
determine CTS condition.
CTS: I2/I1>> SGx 0.40 0.05 1.00 0.01
001 122 001 123 001 124 001 125 OP Fig. 66
High set negative to positive sequence current ratio to be exceeded at exactly one end in
order to determine CTS condition.
CTS: t(Alarm) SGx 1.00 s 0.00 s 10.00 s 0.01 s
001 126 001 127 001 128 001 129 OP Fig. 69
Alarming delay timer for CTS indication.
Blocked/
CTS: t(Latch) SGx 1.00 s 10.00 s 0.01 s
0.00 s
001 130 001 131 001 132 001 133 OP Fig. 69
Latching alarm delay timer for CTS indication.
P63x/UK ST/A54 Settings
Setting Range
Menu Text Default Setting Step Size
Min. Max.
Settings\Function Settings\Setting Group SGx
BC_1: Enable SGx No No Yes -
081 038 082 038 083 038 084 038 OP Fig. 62
BC_2: Enable SGx No No Yes -
081 039 082 039 083 039 084 039 OP Fig. 62
BC_3: Enable SGx No No Yes -
081 040 082 040 083 040 084 040 OP Fig. 62
BC_4: Enable SGx No No Yes -
081 041 082 041 083 041 084 041 OP Fig. 62
This setting specifies the end to be enabled for broken conductor detection for each setting
group.
ST BC_1: I2/I1> SGx 0.30 0.20 1.00 0.01
081 042 082 042 083 042 084 042 OP Fig. 63
BC_2: I2/I1> SGx 0.30 0.20 1.00 0.01
081 043 082 043 083 043 084 043 OP Fig. 63
BC_3: I2/I1> SGx 0.30 0.20 1.00 0.01
081 044 082 044 083 044 084 044 OP Fig. 63
BC_4: I2/I1> SGx 0.30 0.20 1.00 0.01
081 045 082 045 083 045 084 045 OP Fig. 63
Pickup level of broken conductor detection based on ratio of negative to positive sequence
current.
BC_1:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 046 082 046 083 046 084 046 OP Fig. 63
BC_2:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 047 082 047 083 047 084 047 OP Fig. 63
BC_3:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 048 082 048 083 048 084 048 OP Fig. 63
BC_4:
5.00 s 0.10 s 100.00 s 0.01 s
Operate Delay SGx
081 049 082 049 083 049 084 049 OP Fig. 63
Operate delay for broken conductor detection.
Operation P63x/UK OP/A54
OP
OPERATION
OP
Operation P63x/UK OP/A54
CONTENTS
(OP) 5-
1.5.4 Warning 54
2.1.5 Resetting 73
2.12 Configuration, operating mode and blocking of the output relays (OUTP) 100
2.13.2 Enabling the analog output channel via an opto input 103
2.15.7 Stored maximum phase current display (thermal max. demand) 118
2.20.2 Acquisition of the measured overload data of thermal overload protection 138
FIGURES
OP Figure 13: Measured operating data of the differential and restraining currents 26
Figure 14: Enabling or disabling restricted earth fault protection 27
Figure 15: Calculating and monitoring the matching factors 28
Figure 16: Tripping characteristic of restricted earth fault protection biased by residual current 29
Figure 17: Measuring system of the P63x 30
Figure 18: Tripping characteristic of restricted earth fault protection biased by maximum phase current 31
Figure 19: High impedance restricted earth fault protection 32
Figure 20: Measured operating data of the differential and restraining currents 32
Figure 21: Selection of measured variables for DTOC protection 33
Figure 22: Enabling or disabling DTOC protection 34
Figure 23: Phase current stages 35
Figure 24: Negative sequence current stages 37
Figure 25: Residual current stages 38
Figure 26: General starting 39
Figure 27: Counters of the DTOC protection function 39
Figure 28: Selection of measured variables for IDMT protection 40
Figure 29: Enabling or disabling IDMT protection 40
Figure 30: Tripping characteristics per IEC 255-3 42
Figure 31: Tripping characteristics per IEEE C37.112 43
Figure 32: Tripping characteristics per ANSI 44
Figure 33: Tripping characteristics for RI and RXIDG type inverse 44
Figure 34: Phase current stage 45
Figure 35: Negative sequence current stage 47
Figure 36: Residual current stage 48
Operation P63x/UK OP/A54
Figure 37: Example demonstrating the effect of holding time on the phase current stage 49
Figure 38: General starting 50
Figure 39: Counters of the IDMT protection function 50
Figure 40: Selection of measured variables for thermal overload protection 51
Figure 41: Enabling or disabling thermal overload protection 51
Figure 42: Thermal overload protection ready 52
Figure 43: Tripping characteristic of thermal overload protection 53
Figure 44: Monitoring the coolant temperature acquisition 54
Figure 45: Thermal overload protection 55
Figure 46: Thermal replica reset 55
Figure 47: Enabling or disabling V<> protection 56
Figure 48: Overvoltage monitoring 57
Figure 49: Undervoltage monitoring 58
Figure 50: Enabling or disabling frequency protection 59
Figure 51: Undervoltage blocking and evaluation time setting 59
OP
Figure 52: Operation of frequency monitoring with average rate of change (Δf/Δt) monitoring 61
Figure 53: First stage of the frequency protection function 62
Figure 54: Enabling or disabling the overfluxing protection function 63
Figure 55: Conditioning the measured variable 63
Figure 56: Warning stage 64
Figure 57: Fixed-time tripping stage 64
Figure 58: Tripping characteristic for default settings 65
Figure 59: Change of buffer content during an interrupted starting 66
Figure 60: Variable-time tripping stage 67
Figure 61: Resetting of the V/f replica 68
Figure 62: Enabling or disabling broken conductor detection 68
Figure 63: Broken conductor detection for end a 69
Figure 64: Enabling or disabling CTS 70
Figure 65: CTS blocking 71
Figure 66: Current evaluation per end (y = a,b,c,d) 71
Figure 67: CTS operating condition 72
Figure 68: Modification of differential characteristic during CTS condition 73
Figure 69: Overall signaling of CTS 74
Figure 70: Per end signaling of CTS 74
Figure 71: Monitoring the linearized DC values 75
Figure 72: Monitoring the measured temperature value 76
Figure 73: Selection of the measured variables for phase current monitoring (LIM_1 shown) 77
Figure 74: Monitoring of minimum and maximum phase current for the selected transformer end 78
P63x/UK OP/A54 Operation
Figure 75: Control of logic operations via settings or stored input signals 79
Figure 76: Setting options for programmable logic (output 1 shown) 80
Figure 77: Operating mode 1: pickup & reset delay 81
Figure 78: Operating mode 2: pulse delayed pickup 81
Figure 79: Operating mode 3: pickup & rst.retrig 81
Figure 80: Operating mode 4: delayed pulse retrig 82
Figure 81: Operating mode 5: minimum dwell 82
Figure 82: Signal assignment to outputs of Boolean logic equations 83
Figure 83: Operation panel 84
Figure 84: Fault panel 85
Figure 85: Overload panel 85
Figure 86: PC interface settings 86
Figure 87: Selecting the serial protocol 87
Figure 88: Settings for the IEC 60870-5-103 protocol 88
Figure 89: Settings for the IEC 60870-5-101 protocol 89
OP Figure 90: Settings for the ILS_C protocol 90
Figure 91: Settings for the MODBUS protocol 91
Figure 92: Settings for the DNP3.0 protocol 91
Figure 93: Settings for the Courier protocol 92
Figure 94: Checking spontaneous signaling 92
Figure 95: Settings for COMM2 93
Figure 96: Checking spontaneous signaling 94
Figure 97: Enabling or disabling IRIG-B time synchronization 95
Figure 98: Configuration and operating mode of the opto inputs 96
Figure 99: Enabling or disabling the temperature and DC monitoring inputs 96
Figure 100: Example of the conversion of a 4-10mA input current to 0-20mA monitored current,
IDC,lin 97
Figure 101: Example of a characteristic with five interpolation points (characteristic with zero
suppression setting of 0.1 IDC,nom is shown as a dotted line) 98
Figure 102: Analog DC input 99
Figure 103: Scaling of the linearized measured value 100
Figure 104: Temperature measurement using a RTD 100
Figure 105: Configuration, operating mode and blocking of the output relays 102
Figure 106: Testing the output relays 103
Figure 107: Enabling or disabling the analog output channel 103
Figure 108: Enabling the analog output channel via an opto input 104
Figure 109: Resetting the analog output channel function 104
Figure 110: BCD-coded measured data output 106
Figure 111: Example of a characteristic curve for analog output of measured data 108
Operation P63x/UK OP/A54
Figure 147: Measured overload data of thermal overload protection (THRM1 shown) 138
Figure 148: Counting overload events 138
Figure 149: Overload memory 139
Figure 150: Running time and fault duration 140
Figure 151: Determination of the fault data acquisition time 142
Figure 152: Acquisition of the fault currents 143
Figure 153: Acquisition of the differential and restraining currents of differential protection 144
Figure 154: Acquisition of the differential and restraining currents of restricted earth fault protection 145
Figure 155: Start of fault recording and fault counter 146
Figure 156: Fault memory 147
Figure 157: Fault data recording 149
OP
Operation P63x/UK OP/A54
SGx
Setting
Group SGx
SG1
SG2
SG3
SG4
OP P1758ENa
S ref S ref
Iref ,a = Iref ,b =
3 ⋅ Vnom,a 3 ⋅ Vnom,b
S ref S ref
Iref ,c = Iref ,d =
3 ⋅ Vnom,c 3 ⋅ Vnom,d
With
Kam, a, b, c or d: amplitude-matching factor of winding a, b, c or d
Inom, a, b, c or d: primary nominal currents of the main current transformers
Reference currents and matching factors are calculated by the P63x.
Operation P63x/UK OP/A54
The P63x checks that the reference currents and matching factors are within their
permissible ranges. The matching factors must satisfy the following conditions:
• The value of the lower matching factors must be ≥ 0.5. i.e. k amp,max −1 ≥ 0.5
In three or four-winding protection, the “weakest“ end, that is the end with the smallest
primary nominal transformer current, is not associated with any restriction of the settings for
the amplitude matching.
Should the P63x calculate reference currents or matching factors not satisfying the above
conditions then a warning will be issued and the P63x will be blocked automatically.
The measured values of the phase currents of the windings of the protected object are
multiplied by the relevant matching factors and are then available for further processing.
Consequently, all threshold values and measured values always refer back to the relevant
reference currents rather than to the transformer nominal currents or the nominal currents of
the device.
OP
P63x/UK OP/A54 Operation
Rated Ref
Power Sref
CHECK:
CHECK:
CHECK:
CHECK:
OP CHECK:
CHECK:
CHECK:
CHECK:
CHECK:
CHECK:
P1759ENa
OP
Figure 4: Vector diagram for vector group matching with a Yd5 transformer
No operation is carried out on the high-voltage side in connection with vector group
matching. However, one should note that the phase windings are connected in a wye
configuration, the neutral of which is operationally earthed. In the event of system faults to
earth, the zero-sequence component of the fault current would flow via the earthed neutral
that lies within the transformer differential protection zone and would thus appear in the
OP measuring systems as differential current. The consequence would be undesirable tripping.
For this reason the zero-sequence component of the three-phase system must be eliminated
from the phase currents on the high-voltage side. In accordance with its definition, the
zero-sequence current is determined as follows from the amplitude-matched phase currents:
Iamp,zero,z =
1
(
⋅I +I +I
3 amp,A,z amp,B,z amp,C,z
)
On the low-voltage side, the zero-sequence current in the example shown above is
automatically filtered out based on the mathematical phasor operations. This is not always
necessary and also not always desired, but is basically the result of any subtraction of two
phase current phasors:
( )
Iamp,A,z − Iamp,B,z = 1 − a ⋅ Iamp,pos,z + (1 − a ) ⋅ Iamp,neg,z
2
= (a − a )⋅ I ( )
2 2
Iamp,B,z − Iamp,C,z amp,pos,z + a − a ⋅ Iamp,neg,z
( )
Iamp,C,z − Iamp,A,z = (a − 1) ⋅ Iamp,pos,z + a − 1 ⋅ Iamp,neg,z
2
The following tables show that for all odd-numbered vector group characteristics the
zero-sequence current on the low-voltage side is basically always filtered out, whereas for
even-numbered vector group characteristics the zero-sequence current on the low-voltage
side is never filtered out automatically. The latter is also true for the high-voltage side since
in that case, as explained above, no mathematical phasor operations are performed.
Vector group matching and zero-sequence current filtering must therefore always be viewed
in combination. The following tables list all the mathematical phasor operations.
Operation P63x/UK OP/A54
2 (
Ivec,y,z = − Iamp,x +1,z − Iamp,zero,z ) Ivec,y,z = −Iamp,x +1,z
10 (
Ivec,y,z = − Iamp,x −1,z − Iamp,zero,z ) Ivec,y,z = −Iamp,x −1,z
1 Ivec,y,z =
1
(
⋅ Iamp,x,z − Iamp,x +1,z ) Ivec,y,z =
1
( )
⋅ Iamp,x,z − Iamp,x +1,z + Iamp,zero,z
3 3
3 Ivec,y,z =
1
(
⋅ Iamp,x −1,z − Iamp,x +1,z ) Ivec, y, z =
1
( )
⋅ Iamp, x −1, z − Iamp, x +1, z + Iamp,zero, z
3 3
5 Ivec,y,z =
1
(
⋅ Iamp,x −1,z − Iamp,x,z ) Ivec, y, z =
1
( )
⋅ Iamp, x −1,z − Iamp, x, z + Iamp, zero, z
3 3
7 Ivec,y,z =
1
(
⋅ Iamp,x +1,z − Iamp,x,z ) Ivec, y, z =
1
( )
⋅ Iamp, x +1, z − Iamp, x, z + Iamp, zero, z
3 3
9 Ivec,y,z =
1
(
⋅ Iamp,x +1,z − Iamp,x −1,z ) Ivec, y, z =
1
( )
⋅ Iamp, x +1, z − Iamp, x −1, z + Iamp,zero, z
3 3
11 Ivec,y,z =
1
(
⋅ Iamp,x,z − Iamp,x −1,z ) Ivec,y,z =
1
( )
⋅ Iamp,x,z − Iamp,x −1,z + Iamp,zero,z
3 3
Vector group matching is via input of the vector group identification number provided that the
phase currents of the high and low voltage side(s) are connected in standard configuration.
For other configurations, special considerations may apply. A reverse phase rotation (phase
sequence A-C-B) needs to be taken into account by making the appropriate setting at the
P63x/UK OP/A54 Operation
P63x. The P63x will then automatically form the complementary value of the set vector
group ID to the number 12 (vector group ID = 12 - set ID).
OP
OP
Figure 6: Vector group matching and zero-sequence filtering, end d
[
IR,y = 0.5 ⋅ Is,y,a + Is,y,b + Is,y,c + Is,y,d ]
The tripping characteristic of the differential protection device P63x has two knees. The first
knee is dependent on the setting of the basic threshold value DIFF: Idiff> SGx and is on the
load line for single-side feed. The second knee of the tripping characteristic is defined by the
setting DIFF: IR,m2 SGx.
The characteristic equations for the three different ranges are given below. Figure 7 shows
the tripping characteristic.
Id I >
= diff
Iref Iref
P63x/UK OP/A54 Operation
Id I I >
= m1 ⋅ R + diff ⋅ (1 − 0.5 ⋅ m1 )
Iref Iref Iref
IR,m2 < IR
Characteristic equation for the range: :
Id I I IR,m2
= m 2 ⋅ R + diff > ⋅ (1 − 0.5 ⋅ m1 ) + ⋅ (m1 − m 2 )
Iref Iref Iref Iref
OP
tic
ris
fee cte
a
ar
d
ch
gle ent
de
rr
-si
for lt cu
u
sin
Fa
Figure 8: Forming the differential and restraining currents for the three measuring
systems OP
P63x/UK OP/A54 Operation
OP
OP
OP
OP
Figure 13: Measured operating data of the differential and restraining currents
OP
Figure 14: Enabling or disabling restricted earth fault protection
S ref
Iref ,N,a =
3 ⋅ Vnom,a
Inom,a Inom,Y,a
k am,N,a = k am,Y,a =
Iref ,N,a Iref ,N,a
Where:
am: amplitude-matched
In,a: primary nominal current of the main CT
In,Y,a: primary nominal current of CT in the neutral-point-to-earth connections
Reference currents and matching factors are calculated by the P63x.
The P63x checks that the reference current and matching factor are within their permissible
ranges. The following conditions apply:
Should the P63x calculate a reference current or matching factors not satisfying the above
conditions then a warning will be issued and the P63x will be blocked automatically.
The measured values are multiplied by the relevant matching factors and are then available
for further processing. Consequently, all threshold values and measured values always refer
back to the relevant reference current rather than to the transformer nominal current or the
nominal current of the device.
Rated
Ref Power Sref
CHECK
OP CHECK
CHECK
CHECK Min
Mtch f inv REF_1
CHECK Rat
Mtch f inv REF_1
P1770ENa
• Low impedance REF biased by residual current (Low-Z Iph Sum Bias)
• Low impedance REF biased by maximum phase current (Low-Z Iph Max. Bias)
From the amplitude-matched resultant currents Iam,N,a and Iam,Y,a, the differential and
restraining currents are calculated as follows:
IR,N,a = Iam,N,a
Again, the equation for the differential current applies under the condition of uniformly
defined current arrows relative to the protected object. Both current arrows, that is, point
either towards the protected object or away from it.
Figure 16 shows the tripping characteristic of the restricted earth fault protection function.
The characteristic equation is as follows:
Where:
Idiff>,N,a: setting REF_1: Idiff> SGx
rm
er
s OP
n sfo
t ra
nt
rre
cu
in
e ma
o f th
on
r ati
5 atu
.00 nts
=1 ns
ie
m t ra
for
tic
te ris
ac
h ar
tc
rr en
cu
ult
Fa 12201e.DS4
OP
Figure 17: Measuring system of the P63x
Low-Z Iph Max. Bias
Using this operating mode differential current Id and restraining current IR are defined as
follows:
IR =
1
2
( { }
⋅ k amp,P ⋅ max IA , IB , IC + k amp,Y ⋅ IY )
1.5
m2
0.5 m1
Idiff>
IR,m2
P1845ENa
OP
Figure 18: Tripping characteristic of restricted earth fault protection biased by
maximum phase current
High Impedance
This operating mode offers restricted earth fault protection using the high impedance
measuring principle. Sensitivity may be set via the Idiff> setting.
This mode has the advantage of being universally applicable for conventional star winding
REF, and also balanced earth fault protection of delta windings.
P63x/UK OP/A54 Operation
Healthy CT Saturated CT
Protected
circuit
Zm Zm AG
R CT1 R CT2
IF
R L1 R L3
VS R ST
R L2 R R L4
Figure 20: Measured operating data of the differential and restraining currents
Operation P63x/UK OP/A54
Select
CT Input
OP
P1774ENa
OP
Figure 22: Enabling or disabling DTOC protection
Inrush
Restr Enab SGx
SGx
SGx
Dynam.
Setts. Active
SGx
SGx
SGx
SGx
OP
SGx
SGx
SGx
Inrush
Setting SGx SGx SGx SGx Restr Enab SGx
SG 1
SG 2
SG 3
SG 4
P1776ENa
Ineg =
1
(
2
⋅ I + a ⋅ IB + a ⋅ IC
3 A
)
P63x/UK OP/A54 Operation
Ineg =
1
3
( 2
⋅ I A + a ⋅ IB + a ⋅ IC )
a = e j120°
a 2 = e j240°
The negative-sequence current is monitored by the P63x with three-stage functions to detect
when they exceed the set thresholds. One of two different threshold types can be active.
The “dynamic” thresholds are active for the set hold time of the “dynamic settings” (see
“Activation of Dynamic Settings”); the “normal” thresholds are active when no hold time is
running. If the current exceeds the set thresholds in one phase, timer stages are started.
Once these stages have elapsed, a trip signal is issued. These timer stages can be blocked
by way of appropriately configured binary signal inputs.
The first stage of the DTOC protection function can optionally be blocked by the inrush
stabilization function of differential protection.
OP
Operation P63x/UK OP/A54
OP
OP
Gen.
starting mode SGx
tGS
SGx
I2
I2
Starting
I2>
General
Starting Start
I2>>
Starting
I2>>>
P1779ENa
Select
CT Input
OP P1781ENa
11 RI-Type Inverse 1
t =k⋅
0.236
0.339 −
⎛ I ⎞
⎜ ⎟
⎜I ⎟
⎝ ref ⎠
12 RXIDG-Type Inverse
⎛ I ⎞
t = k ⋅ ⎜⎜ 5.8 − 1.35 ⋅ ln ⎟
⎟
⎝ I ref ⎠
P63x/UK OP/A54 Operation
1000 1000
100 100
k=10
10 10 k=10
t/s t/s
k=1
1 1 k=1
k=0.1
0.1 k=0.05 0.1
k=0.1
k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
S8Z50K1A S8Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
OP 1
k=1
1
k=0.1
k=0.05
0.1 0.1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
S8Z50K3A S8Z50K4A
P1784ENa
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
S8Z50K5C S8Z50K6C
1000
100
10
t/s
k=10
1
OP
k=1
0.1
k=0.1
0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K7C
Characteristic No. 7
P1785ENa
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1 k=0.1
0.01 k=0.05 0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K8C S8Z50K9C
1000
100
k=10
10
t/s k=1
OP 1
k=0.1
0.1 k=0.05
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50KAC
Characteristic No. 10
P1786ENa
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
k=0.05
0.1 0.1 k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
I/Iref I/Iref
S8Z50KBA S8Z50KCA
P1787ENa
Inrush
Restr Enab SGx
Iref,Ph
OP
SGx
Dynam.
Setts. Active Iref,Ph
dynamic SGx
Starting
Iref,Ph>
Kt Time Dial/
TMS SGx
Min. Trip
t. Ph SGx
Hold Time
Ph SGx
Release Ph SGx
Definite Time Release Ph
SGx
Block.
tIref,Ph> EXT
tIref,Ph>
Elapsed
Hold Time
Ph running
Memory Ph
Clear
P1788ENa
Ineg =
1
( 2
⋅ I + a ⋅ IB + a ⋅ IC
3 A
)
A-C-B (reverse phase rotation):
Ineg =
1
( 2
⋅ I + a ⋅ IB + a ⋅ IC
3 A
)
a = e j120°
a 2 = e j240°
The negative-sequence current is monitored by the P63x to detect when it exceeds the set
thresholds. One of two different threshold types can be active. The “dynamic” thresholds
are active for the set hold time of the “dynamic settings” (see “Activation of Dynamic
Settings”); the “normal” thresholds are active when no hold time is running. The IDMT
protection function issues a starting signal if 1.05 times the set reference current is
exceeded. As a function of the negative-sequence current and of the set characteristic, the
OP P63x will determine the tripping time. Moreover, a minimum trip time can be set. The trip
time will not fall below this minimum independent of the magnitude of the current.
The negative-sequence stage of the IDMT protection function can optionally be blocked by
the inrush stabilization function of differential protection.
Operation P63x/UK OP/A54
Inrush
Restr Enab SGx
Iref,I2
SGx
Dynam.
Setts. Active
Iref,I2
dynamic SGx
Starting
Iref,I2>
Phase
Rotation
I2 I2 Charac
SGx
I2 Charac SGx
Kt Time Dial/
TMS SGx
Min. Trip
t. I2 SGx
Release I2 SGx
Hold Time
I2 SGx
Definite Time
SGx
Release I2
OP
Block.
tIref,I2> EXT
tIref,I2>
Elapsed
Memory I2
Gen. Clear
Starting Mode SGx
Trip Sig.
tIref,I2
I2
Block Tim.
St. IN SGx
Definite Time
Iref,N
SGx
Dynam.
Setts. Active
Iref,N
dynamic SGx
N Charac
SGx N Charac SGx
Kt Time Dial/
TMS SGx
Min. Trip
t. N SGx
OP N
Hold Time
SGx
Release N SGx
Definite Time Release N
SGx
Gen.
Starting Mode SGx
I2
Setting Block Tim. Iref,N Iref,N
St. IN SGx SGx dynamic SGx N Charac SGx
SG 1
SG 2
SG 3
SG 4
Starting
Iref,Ph>
Hold Time
Ph Running
Instantaneous
tIref,Ph>
Elapsed
Starting
Iref,Ph>
Hold Time
Ph Running
Instantaneous
OP
tIref,Ph>
Elapsed
Figure 37: Example demonstrating the effect of holding time on the phase current
stage
OP
With the P633 or P634, the THRM2 function can be assigned to a weaker transformer end or
to a combination of two weaker transformer ends (by assigning the virtual end) with an
appropriate choice of tripping characteristics for function THRM2.
Operation P63x/UK OP/A54
THRM1 will serve as an example to illustrate the operation of the thermal overload protection
functions; function group THRM2 is equivalent.
Select
CT Input
OP
P1794ENa
P1846ENa
• The set thermal time constant (τ) of the protected object THRM1: Tim.const 1(heat)SGx
• The maximum permissible coolant temperature Θc,max set at THRM1: Max perm cool
tmpSGx
• The maximum permissible object temperature Θmax set at THRM1: Max perm obj
tmp.SGx
The object temperature is calculated from the current IPh,max.y and can be displayed at
THRM1: Object Temperat., TH1. The coolant temperature is either measured via the PT
100 input or via the 20 mA input or a default temperature value is used instead. This choice
is governed by the setting at THRM1: Select CT Ambient SGx. The menu point for the
display of the resulting coolant temperature is THRM1: Coolant Temp. TH1.
The tripping characteristics are then defined by the equation:
2
⎛ I ⎞
⎜⎜ ⎟⎟ − Θ P
t = τ ⋅ ln ⎝ Iref ⎠
2
⎛ I ⎞ ⎛ Θ c − Θ c,max ⎞
⎜⎜ ⎟⎟ − Θ trip ⋅ ⎜1 − ⎟
⎜ Θ ⎟
⎝ Iref ⎠ ⎝ max − Θ c,max ⎠
Figure 43 shows the tripping characteristics for ΘP = 0 % and with identical settings for the
maximum permissible coolant temperature and the maximum permissible object
temperature.
The setting for the operating mode selects an ‘absolute’ or ‘relative’ replica. If the setting is
for Absolute Replica, the P63x will operate with a fixed trip threshold Θtrip of 100 %.
Operation P63x/UK OP/A54
OP
OP
Figure 44: Monitoring the coolant temperature acquisition
1.5.4 Warning
A warning signal is issued when the thermal load reaches the set warning level
THRM1: Θ Alarm SGx{1><1}. Moreover, a pre-trip warning time can be defined. The time
difference between the warning time and the trip time is set at THRM1: Alarm pre-trip SGx.
The time remaining until the thermal overload protection function THRM1 will reach the
tripping threshold can be displayed at OL_DA: Pre-trip t. left THRM1.
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the set
time constant THRM1: Tim.const 2(cool)SGx). The thermal replica may be reset either from
the local control panel or via an appropriately configured binary signal input. Resetting is
effective even when the thermal overload protection is disabled. Thermal overload
protection can be blocked via an appropriately configured binary signal input.
Operation P63x/UK OP/A54
SGx
SGx
CT Amb SGx
T> Alarm
Reset, % SGx
T> Trip
Reset, % SGx
Trip
Hysteresis SGx
CHECK
Pre-Trip
Alarm SGx
Alarm
OP
Enable
SGx
OP
Setting Enable
SGx
SG 1
SG 2
SG 3
SG 4
P1799ENa
V>
SGx
Hyst. V<>
Meas. SGx
tV>>
SGx
V>>
SGx
Setting
SG 1
SGx
V>
SGx
tV>
SGx
V>>
SGx
tV>> Hyst. V<>
Meas. SGx
OP
SG 2
SG 3
SG 4
P1800ENa
Hyst. V<>
Meas. SGx V< tV<
SGx SGx
tV<<
SGx
V<<
SGx
OP
Vmin>
SGx
tTransient
SGx
P1801ENa
Enable
SGx
Setting Enable
SGx
SG 1
SG 2
SG 3
SG 4
P1802ENa
P1803ENa
• Frequency monitoring
P1804ENa OP
Figure 52: Operation of frequency monitoring with average rate of change (Δf/Δt)
monitoring
P63x/UK OP/A54 Operation
Oper.
mode f1 SGx
f1
SGx
Frequency fn
tf1
SGx
df1/dt
SGx
OP
CHECK
Delta f1
SGx
Delta t1
SGx
P1805ENa
P1849ENa
The variable-time tripping characteristic is set by defining 12 pairs of overfluxing values and
associated tripping time values. Intermediate values are obtained by interpolation. The
setting of the characteristic is checked for plausibility - it must have a continuous falling
profile, with no rising points. For values of V/f > 1.6, the tripping time is limited to the value
set for
V/f = 1.6. Figure 58 shows the characteristic as calculated with the P63x default values.
100
t/s 10
OP
1
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
V/f P1852ENa
OP
Setting SGx
SG 1
SG 2
SG 3
SG 4
P1853ENa
SGx
SGx
SGx
SGx
SGx
SGx
SGx
SGx
SGx
SGx
SGx
SGx
OP
SGx
SGx
Setting
SGx SGx
SG 1
SG 2
SG 3
SG 4
Setting
SGx SGx SGx SGx SGx SGx
SG 1
SG 2
SG 3
SG 4
P1854ENa
P1855ENa
BC_1 : Enabled
c
[ 036 194]
IA,a >1
IB,a 2 > 0, 02 Inom
IC,a
1 > 0, 02 Inom
BC_1 : 2/ 1 > SGx BC_1: Operate delay SGx
c c
[ * ] [ * ]
5s 0
BC_1 : CT Fail Alarm
2 1
[ 036 198]
P1857ENa
OP
P63x/UK OP/A54 Operation
Note: CTS function requires the new processor board with DSP
coprocessor. This is an order option.
0
CTS : Enabled
1 [ 036 080]
&
0 : No
1 : Yes
OP
CTS : Enable SGx
[ * ]
0 : No
1 : Yes y GROUP : SG y active * Setting CTS : Enable SGx
1 036 090 SG 1 001 118
2 036 091 SG 2 001 119
3 036 092 SG 3 001 120
GROUP : SG y active 4 036 093 SG 4 001 121
[ * ]
P1858ENa
• The positive sequence current in at least two ends exceeds the set release threshold OP
I1>. This also means that CTS can only operate if minimum load current of the
protected object is present
• On exactly one end a high set ratio of negative to positive sequence current I2/I1>> is
exceeded
• On all other ends the ratio of negative to positive sequence current is less than a low set
value I2/I1> or no significant current is present (i.e. positive sequence current is below
the release threshold I1>)
Under this condition a fault in the CT secondaries of the end with high negative sequence
current is present.
Because of evaluating negative sequence currents only unsymmetrical CT failures can be
determined. In practice this is not a significant problem as the probability of symmetrical
three-phase failures is very low.
OP
2.1.5 Resetting
Latched CTS signals can be reset via command from the HMI or any communication
interface or via an opto-input signal. They are also reset by executing the general reset
command.
P63x/UK OP/A54 Operation
OP
RTDmA:
OP
P1807ENa
OP
Figure 73: Selection of the measured variables for phase current monitoring (LIM_1
shown)
P63x/UK OP/A54 Operation
OP
P1809ENa
Figure 74: Monitoring of minimum and maximum phase current for the selected
transformer end
Fct.
U xxx Assign
P1810ENa OP
Figure 75: Control of logic operations via settings or stored input signals
The signal LOGIC: Trigger n is a ‘triggering function’ that causes a 100 ms pulse to be
issued.
P63x/UK OP/A54 Operation
INPUT 40
034 109
P1811ENa
OP
P1814ENa
OP
P1816ENa
Fct.
U xxx Assign
OP
Fct.
U xxx Assign
P1817ENa
OP
OP
• MODBUS
• DNP3.0
OP
P1866ENa
OP
OP
P1868ENa
OP
P1870ENa
OP
Figure 91: Settings for the MODBUS protocol
OP
Figure 93: Settings for the Courier protocol
OP
P1874ENa
OP
Figure 96: Checking spontaneous signaling
RTDmA:
RTDmA:
P1823ENa
OP
IDClin/IDC,nom
0.8
Interpolation points
IDClin20 0.7
0.6
IDClin4 0.5
0.4
IDClin3 0.3
IDClin2 0.2
IDClin1 0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 IDC/IDC,nom
OP IDC1 IDC2 IDC3 IDC4 IDC20
Enable IDC p.u.
P1825ENa
RTDmA:
OP
CHECK:
RTDmA:
CHECK:
RTDmA:
CHECK:
RTDmA:
RTDmA:
RTDmA:
P1826ENa
OP
2.12 Configuration, operating mode and blocking of the output relays (OUTP)
The P63x has output relays for the output of binary signals. The binary signals to be issued
are defined by configuration.
inverted, such that a logic "0" maintains the relay normally-closed. For relays with
changeover contacts, these more common descriptions are not applicable.
Latching is disabled manually from the local control panel or through an appropriately
configured binary signal input either at the onset of a new fault or at the onset of a new
system disturbance, depending on the operating mode selected.
OP
P63x/UK OP/A54 Operation
USER Outp
rel Block
CHECK:
Follower
Follower Latching
Inverted
OP Inverted Latching
OSCIL:
OSCIL:
P1828ENa
Figure 105: Configuration, operating mode and blocking of the output relays
P1829ENa
mA_OP:
mA_OP:
P1830ENa
Figure 108: Enabling the analog output channel via an opto input
• The mA_OP function is reset from the local control panel or through an appropriately
configured binary signal input
2.13.7 Scaling
The resolution for measured data output, is defined by setting the scaling factor. The scaling
factor should be selected so that the value 399 is not exceeded by the maximum measured
value to be output. If this should occur, however, or if the measured value is outside the
acceptable measuring range, then the value for ‘Overflow’ (all relays triggered) is
transmitted.
Mx,max
Mx,scal =
scaling factor
Where:
Mx,scal
: Scaled measured value
Mx,max
: Maximum transmitted value for the selected measured value
OP
P63x/UK OP/A54 Operation
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP: mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
OP
mA_OP:
mA_OP:
mA_OP:
P1833ENa
2.13.12 Scaling
The minimum and maximum values to be transmitted for the selected measured value and
one additional value for the knee point must be scaled to the range limit value of the
measured value. By setting the following parameters the user can obtain an analog output
characteristic like the one shown in Figure 111.
Formulas Example
Key to the Formulas:
Mx,RL Range limit value of selected Let voltage V12 be selected as the
: measured value measured value to be transmitted. Let the
measuring range be 0 to 1.5 Vn.
Mx,min Minimum value to be
: transmitted for selected When Vn = 100 V, the range limit value in
measured value the assumed example is 150 V.
Mx,knee Knee point value to be Range to be transmitted:
: transmitted for selected 0.02 to 1 Vn = 2 to 100 V
measured value
Knee point:
M x,max Maximum value to be 0.1 Vn = 10 V
: transmitted for selected
measured value
Mx,scal,min Scaled minimum value
:
M x,scal,knee Scaled knee point value
:
M x,scal,max Scaled maximum value
:
M x,min 2V
M x,scal,min = M x,scal,min = = 0.013
M x,RL 150 V
M x,knee 10 V
M x,scal,knee = M x,scal,knee = = 0.067
M x,RL 150 V
P63x/UK OP/A54 Operation
Formulas Example
M x,max 100 V
M x,scal,max = M x,scal,max = = 0.67
M x,RL 150 V
By setting mA_OP: AnOut Min. val A-x, the user can specify the output current that will be
output when values are smaller than or equal to the set minimum measured value to be
transmitted. The setting at mA_OP: AnOut Max. val. A-x defines the output current that is
output for the maximum measured value to be transmitted. By defining the knee point, the
user can obtain two characteristic curve sections with different slopes. When making this
setting the user must keep in mind that only a rising-rising, or falling-falling curve sense is
allowed (no peaks or vee shapes). If the wrong setting is entered, the signal CHECK: Invalid
Scaling A-x will be generated.
Note: After this setting, the new characteristics will be checked and
implemented after enabling at MAIN: Protection Enabled.
OP
Figure 111: Example of a characteristic curve for analog output of measured data
Operation P63x/UK OP/A54
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
OP
CHECK:
mA_OP:
mA_OP:
mA_OP:
mA_OP:
P1878ENa
OP
P631:
• Current inputs (three phases) for the processing of measured variables for two ends of
the transformer
P632:
• Current inputs (three phases) for the processing of measured variables for two ends of
the transformer
• Two current inputs for the measurement of the residual currents (see Figure 115 and
116), or for connection as high impedance REF
• Current inputs (three phases) for the processing of measured variables for three (P633)
or four (P634) ends of the transformer
• Current inputs for up to three neutral-point-to-earth connections (see Figure 114) or for
looping into the earth connections of the phase current transformers, or for connection as
high impedance REF
OP
P63x/UK OP/A54 Operation
OP
Figure 114: Connection of the analog inputs to the P63x, showing connection of
the fourth CT set to the transformers of the star point earth connection
Note: "Dot" convention for winding polarities shown. When using P1-P2,
S1-S2 standard notation.
OP
Figure 115: Connection of the analog inputs to the P63x, showing residual
connection input to earth fault CT, Part 1 of 2
P63x/UK OP/A54 Operation
CT Orientation In Device,
Iph, b end b
CT Orientation
IY, b
Reversed
OP
CT Orientation In Device,
Iph, c end c
CT Orientation
IY, c
Reversed
CT Orientation In Device,
Iph, d end d
Reversed
P1882ENa
Figure 116: Connection of the analog inputs to the P63x, showing residual
connection input to earth fault CT, Part 2 of 2
OP
OP
• Phase currents of all three phases of all four ends of the transformer
• Delayed and stored maximum phase current of each end of the transformer
Operation P63x/UK OP/A54
• Current IN calculated by the P63x from the sum of the phase currents for each end of
the transformer
• Phase currents of all three phases of the virtual end of the transformer. The virtual end
is formed by adding the corresponding currents of two transformer ends selected by the
user at MAIN: Current Summation
• Voltage
• Frequency
• Angle between the phase currents for a given end of the transformer
• Angle between the currents of the same phase between two ends of the transformer
• Angle between calculated IN and the current measured at transformer -Tx4 (x: 1, 2 or 3)
The measured data are updated at 1 s intervals. Updating is interrupted if a general starting
state occurs or if the self-monitoring (CHECK) function detects a hardware fault.
OP
2.15.5 Measured current values
The measured values for the current are displayed both as quantities referred to the nominal
current of the P63x and as primary quantities. To allow a display in primary values, the
primary nominal current of the transformers connected to the P63x needs to be set.
P63x/UK OP/A54 Operation
Minimum Iph
Meas’mt
Curr Iph,
Max now, zpu
Iph pu
Thermal peakz
Iph pu
Thermal dem. z
Current Imin,
z p.u.
In CT.
Prim., end z In CT.
Prim., end z
Iph Therm
pk z prim
Current Imin,
z prim
OP
Curr Iph,
Max now, zpu
the stored maximum phase current to the actual value of the delayed maximum phase
current (see lower curve in Figure 120).
Curr Iph,
Max now, zpu
Iph pu
Thermal dem. z
Curr Iph,
Max now, zpu
Iph pu
Thermal peakz
Curr Iph,
Max now, zpu
Iph pu
Thermal peakz OP
Reset Iph,
Max Demand
Curr Iph,
Max now, zpu
Iph pu
Thermal peakz
Iph pu
Thermal dem. z
P1886ENa
Figure 120: Operation of delayed and stored maximum phase current display
P63x/UK OP/A54 Operation
OP
Figure 122: Measured operating data for residual current, end d (P634 only)
Operation P63x/UK OP/A54
OP
Figure 123: Measured operating data for the phase currents and the residual current
for the virtual winding (formed by current summation, P633 and P634
only)
Minimum
V Meas’mt
Vn VT. Sec.
Vn V.T. prim.
P1890ENa
2.15.9 Frequency
The P63x determines the frequency from the voltage. The voltage needs to exceed a
minimum threshold of 0.65 Vn in order for the frequency to be determined.
P63x/UK OP/A54 Operation
• Angle between the phase currents for each end of the transformer
• Angle between the currents of the same phase between two ends of the transformer
• Angle between the calculated residual current and the current measured at the
OP transformer -Tx4 (x: 1, 2 or 3) for each end of the transformer
OP
Figure 127: Determination of the angle between the phase currents of the
transformer ends
P63x/UK OP/A54 Operation
OP
Figure 128: Determination of the angle between the calculated residual current and
the current measured at transformer - Tx4
• None of the signals of the protection function may be assigned to a binary output or to
an LED indicator
If the above conditions are met, proceed through the Settings/Configuration branch of the
menu tree to access the setting relevant for the device function to be disabled. If you wish to
disable the LIMIT function group, for example, access the setting LIMIT: Limit Thresholds I<>
and set its value to Disabled. Should you wish to re-include the function group in the device
configuration, set the value to Enabled. The assignment of a setting, a signal or a measured
value to a protection function is defined by a function group descriptor such as ‘LIMIT’.
Operation P63x/UK OP/A54
Note: If the protection device is disabled via the binary signal input
configured to MAIN: Disable Protect. EXT there will be no MAIN:
Blocked/Faulty signal.
OP
OP
P1897ENa
2.15.16 Blocked/faulty
If the protective functions are blocked, this condition is signaled by a steady light from yellow
LED indicator H 2 on the local control panel and also by a signal through the output relay
configured for MAIN: Blocked/Faulty. In addition, the user can select the functions that will
produce the MAIN: Blocked/Faulty signal by setting an ‘m out of n’ setting.
Operation P63x/UK OP/A54
CHECK:
Starting
[ 041 106 ]
P1899ENa
Trip command
The P63x has four trip commands. The functions to effect a trip can be selected by setting
an ‘m out of n’ setting independently for each of the four trip commands. The minimum trip
command time may be set. The trip signals are present only as long as the conditions for
the signal are satisfied.
Manual trip command
A manual trip command may be issued via the local control panel or a signal input
configured accordingly. It is not executed, however, unless the manual trip is included in the
selection of possible functions to effect a trip.
Latching of the trip commands
For each of the four trip commands, the user can specify by way of the appropriate setting
whether it will operate in latching mode. If the latching mode is selected, the trip command
persists until it is reset from the local control panel or via an appropriately configured binary
signal.
Blocking of the trip commands
The trip commands may be blocked via the integrated local control panel or via an
appropriately configured binary signal input. The blocking is effective for all four trip
commands. The trip signals are not affected by the blocking. If the trip commands are
blocked this is indicated by a steady light at yellow LED indicator H 2 on the local control
panel and by an output relay configured to ‘Blocked/Faulty’.
OP
Operation P63x/UK OP/A54
tDWELL Trip
Cmd y
OP
tDWELL Trip
Cmd y
P1901ENa
P1902ENa
P1904ENa
• Automatic resetting of the event signals indicated by LED indicators (provided that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel whenever a new event occurs
• Resetting of LED indicators and measured event data on the local control panel by
OP pressing the ‘Clear’ key located on the panel
• Selective resetting of a particular memory type (only the fault memory, for example) from
the local control panel or through appropriately configured binary signal inputs
• General Reset
In the first two cases listed above only the displays on the local control panel are cleared but
not the internal memories such as the fault memory.
In the event of a cold restart, namely simultaneous failure of both internal battery and power
supply, all stored signals and values will be lost.
Figure 140: General reset, LED reset and measured event data reset from the local
control panel
Operation P63x/UK OP/A54
OP
2.17.3 Signaling
The monitoring signals are also signaled via the output relay configured CHECK: Alarm. The
output relay operates as long as an internal fault is detected.
OP
• Signaling only
If there is no malfunction associated with the monitoring signal, then only a signal is issued,
and there are no further consequences. This situation exists, for example, when internal
data acquisition memories overflow.
• Selective blocking
If a fault is diagnosed solely in an area that does not affect the protective functions, then only
the affected area is blocked. This would apply, for example, to the detection of a fault on the
communication module or in the area of the PC interface.
• Warm restart
If the self-monitoring function detects a fault that might be eliminated by a system restart, for
example a fault in the hardware, then a procedure called a warm restart is automatically
initiated. During this procedure, as with any startup, the computer system is reset to a
defined state. A warm restart is characterized by the fact that no stored data and, in
particular, no setting parameters are affected by the procedure. A warm restart can also be
triggered manually by control action. During a warm restart sequence the protective
functions and the communication through serial interfaces will be blocked. If the same fault
is detected after a warm restart has been triggered by the self-monitoring system, then the
protective functions remain blocked but communication through the serial interfaces will
usually be possible again.
P63x/UK OP/A54 Operation
• Cold restart
If a corrupted setting group is diagnosed in the checksum test during self-monitoring, then a
cold restart is carried out. This is necessary because the protection device cannot identify
which setting in the group is corrupt. A cold restart causes all internal memories to be reset
to a defined state. This means that all the protection device settings are also erased after a
cold restart. In order to establish a safe initial state, the default values have been selected
so that the protective functions are blocked. Both the monitoring signal that triggered the
cold restart and the value indicating setting loss are entered in the monitoring signal
memory.
OP
Figure 144: Operating data recording and the counter of signals relevant to system
operation
Figure 145: Monitoring signal recording and the counter of monitoring signals
• Measured overload data derived from the measured operating data of the thermal
overload protection functions THRM1 and THRM2. For each of these two functions, the
following values are determined:
• Load current
• Object temperature
• Coolant temperature
OP
P1913ENa
Figure 147: Measured overload data of thermal overload protection (THRM1 shown)
P1914ENa
OP
• Running time
• Fault duration
• Fault currents
OSCIL:
P1916ENa
The difference in time between the start of the fault and the fault data acquisition time is
determined by the P63x and displayed.
OP
P63x/UK OP/A54 Operation
OSCIL:
OP
P1917ENa
OP
OSCIL:
I (2*fn), 1
1 (2*fn)
I (5*fn), 1
1 (5*fn)
I (2*fn), 2
2 (2*fn)
I (5*fn), 2
2 (5*fn)
OP
I (2*fn), 3
3 (2*fn)
I (5*fn), 3
3 (5*fn)
P1919ENa
OSCIL:
P1920ENa OP
Figure 154: Acquisition of the differential and restraining currents of restricted earth
fault protection
OP
OP
• The voltage
The signals are recorded before, during and after a fault. The times for recording before and
after the fault can be set. A maximum time period of 16.4 s (for 50 Hz) or 13.7 s (for 60 Hz)
is available for recording. This period can be divided among a maximum of eight faults. The
maximum recording time per fault can be set. If a fault, including the set pre-fault and
post-fault times, lasts longer than the set maximum recording time, then recording will
terminate when the set maximum recording time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording time.
Otherwise; the pre-fault time is set to the maximum recording time minus a sampling
increment and the post-fault time is set to zero.
If the maximum recording time is exceeded, the analog values for the oldest fault are
overwritten, but not the binary values. If more than eight faults have occurred since the last
reset, then all data for the oldest fault are overwritten.
The analog data of the fault record can only be read out through the PC or communication
interfaces.
OP
When the supply voltage is interrupted or after a warm restart, the values of all faults remain
stored.
Operation P63x/UK OP/A54
OSCIL:
OSCIL:
OSCIL:
OSCIL:
OP
OSCIL:
P1923ENa
OP
Application Notes P63x/UK AP/A54
AP
APPLICATION NOTES
AP
Application Notes P63x/UK AP/A54
CONTENTS
(AP) 6-
1. INTRODUCTION 5
1.1 Protection of transformers 5
1.1.1 Introduction 5
3. SETTING RECOMMENDATIONS 33
3.1 Introduction 33
FIGURES
AP
P63x/UK AP/A54 Application Notes
AP
Application Notes P63x/UK AP/A54
1. INTRODUCTION
1.1.1 Introduction
The development of modern power systems has been reflected in the advances in
transformer design. This has resulted in a wide range of transformers with sizes from a few
kVA to several hundred MVA being available for use in a wide variety of applications.
The considerations for transformer protection vary with the application and importance of the
transformer. To reduce the effects of thermal stress and electrodynamic forces it is
advisable for the overall protection to minimize the time that a fault is present within a
transformer.
On smaller distribution transformers effective and economically justifiable protection can be
achieved by using either fuse protection or IDMT/instantaneous overcurrent relays. Due to
the requirements of co-ordination with the downstream power system protection this results
in time delayed fault clearance for some low level faults. Time delayed clearance of major
faults is unacceptable on larger distribution, transmission and generator transformers, where
the effects on system operation and stability must be considered. High speed protection is
desirable for all faults.
Transformer faults are generally classified into four categories:
• Core faults
• Winding arrangements
• Winding connections
WT B OT
51
50N
51N
ICT
64 WT = Winding temp'
B = Buchholz
OT = Oil temp'
64 = REF
87 = Biased diff'
51N = Standby E/F
50N = Inst' earth fault
87
51 = IDMT overcurrent
24 = Overfluxing relay
AP
P1937ENa
The protection scheme may be further enhanced by the use of other protective devices
associated with the transformer, such as the Buchholz, pressure relief and winding
temperature devices. These devices can act as another main protective system for large
transformers and they may also provide clearance for some faults which might be difficult to
detect by protection devices operating from line current transformers, e.g. winding inter turn
faults or core lamination faults. These devices are connected to directly trip the breaker in
addition to operating auxiliary relays for indication purposes.
WT B OT
64
24 51N
ICT
64 WT = Winding temp'
B = Buchholz
OT = Oil temp'
64 = REF
87 = Biased diff'
51N = Standby E/F
87 51 = IDMT overcurrent
24 = Overfluxing relay
P1938ENa
AP
Figure 2: Typical protection package for a generator transformer
The protection of a generator transformer is similar to that for any other large transformer.
High speed protection is provided for phase to phase faults by the provision of biased
differential protection. In addition, for large generators, the transformer is commonly
included within an overall second main differential arrangement, which incorporates the
generator and transformer within the overall zone of protection. Earth fault protection is
provided by a restricted earth fault element on the star winding.
Overfluxing protection is commonly applied to generator circuits to prevent generator or
transformer damage from prolonged overfluxing conditions.
Other protection devices will again complement the main relay protection.
Auto-transformers are commonly used to couple EHV and HV power networks if the ratio of
their voltages is moderate. The protection arrangements for an auto-transformer are similar
in most respects to the protection of a two winding transformer. Protection of all windings
can be offered by a biased differential relay such as the P63x, this is further discussed in
section 2.4.
• Opto-isolated inputs and programmable logic for alarm/trip indication of external devices
* These protection functions are not available in the P631.
The biased differential element has a triple slope bias characteristic to ensure sensitivity,
with load current, to internal faults and stability under heavy through fault conditions.
The differential element can be blocked for magnetizing inrush conditions based on the ratio
of second harmonic to fundamental current. In addition, the differential element can be
AP blocked during transient overfluxing conditions based on the ratio of fifth harmonic to
fundamental current. Fast operating times for heavy internal faults can be achieved by use
of the unrestrained instantaneous differential high set elements.
Restricted earth fault protection is available for up to three transformer windings to offer
increased sensitivity to low-level winding earth faults. The principle of operation is selectable
and allows either the high impedance or biased (low impedance) restricted earth fault
method to be implemented.
Both the definite-time and the inverse-time overcurrent protection operate with separate
measuring systems for the evaluation of the three phase currents, the negative-sequence
current and the residual current. Three stages each are provided for the three measuring
systems of the definite-time overcurrent protection. The inverse-time overcurrent protection
offers a multitude of tripping characteristics for the individual measuring systems.
Thermal overload protection can be used to prevent electrical plant from operating at
temperatures in excess of the designed maximum withstand. Prolonged overloading causes
excessive heating, which may result in premature ageing of the insulation, or in extreme
cases, insulation failure. The relay incorporates a current based thermal replica, using rms
load current to model heating and cooling of the protected plant. The element can be set
with both alarm and trip stages.
The V/f overfluxing element provides protection against transformer damage that may result
from prolonged operation at increased voltages and/or decreased frequency. Independent
alarm and trip characteristics are provided to enable corrective action to be undertaken prior
to tripping being initiated.
Use of the opto-inputs as trip repeat and alarm paths for other transformer protection
devices, (Buchholz, Oil pressure, winding temperature etc.,) allows operation of these
devices to be event-logged. Interrogation of the relay fault, event and disturbance records
offers an overall picture of an event or fault, of the transformer protection performance and
sequences of operation.
All models of the P63x are three phase units with internal phase compensation, CT ratio
correction and zero sequence filtering, thus eliminating the need for external interposing
transformers. Up to four biased inputs can be provided to cater for power transformers with
more than two windings and/or more than one set of CT’s associated with each winding, e.g.
in mesh or one-and-a-half circuit breaker substation arrangements.
Application Notes P63x/UK AP/A54
The variety of protective functions offered by the P63x makes it ideal not only for the
protection of power transformers but also for a variety of applications where biased
differential or high impedance protection is commonly applied, these include:
• Busbars/mesh corners
• Generators
• Reactors
• Disturbance records (record of analogue wave forms and operation of opto-inputs and
output relays)
• Relay menu displayed as standard English or Regional English language variant -800
P63x/UK AP/A54 Application Notes
AP The number of biased differential inputs required for an application depends upon the
transformer and its primary connections. It is recommended that, where ever possible, a set
of biased CT inputs is used per set of current transformers.
There are four basic models of the P63x relay;
• P631 Two biased differential inputs (without REF or voltage based protection)
HV
3 P633 or P634
LV1 LV2
HV
3 P633 or P634
LV
HV
3 P633 or P634
LV
Application Notes P63x/UK AP/A54
HV
HV
4 P634 only
LV
I d / I ref
Tripping area
6.00
AP
ic t
ris
fee cte
4.00
a
ar
d
ch
.7
gle ent
=0
de
rr
m
-s i
2
for lt cu
u
sin
Fa
2.00
Blocking area
m 1
= 0.3
12200e.DS4
I R ,m2 / I ref = 4.0
I d > / I ref = 0.2
When the infeed to an internal fault from both ends is exactly equal as regards amplitude
and angle, then both currents cancel one another out, i.e. the restraining current becomes
zero and the restraining effect disappears. Disappearance of the restraining effect when
there is an internal fault is a desirable result since in this case transformer differential
protection attains maximum sensitivity.
Calculation of differential and restraining currents for three or four-winding protection:
[
IR,y = 0.5 ⋅ Is,y,a + Is,y,b + Is,y,c + Is,y,d ]
In this case the restraining effect never disappears when there is an internal fault; the
restraining effect is even reinforced in the case of multi-end infeed. However, the restraining
current factor ½ means that the differential current Id has twice the value of the restraining
current IR so that safe and reliable tripping is also guaranteed in the case of multi-end infeed.
The tripping characteristic of the differential protection device P63x has two knees. The first
knee is dependent on the setting of the basic threshold value DIFF: Idiff> SGx and is on the
load line for single-side feed. The second knee of the tripping characteristic is defined by the
setting DIFF: IR,m2 SGx.
The characteristic equations for the three different ranges are given below. Figure3: shows
the tripping characteristic.
The first section (Area I) represents the most sensitive region of the tripping characteristic in
the form of the settable basic threshold value Id>. The default setting of 0.2 takes into
account the magnetizing current of the transformer, which flows even in a no-load condition
AP and is generally less than 5% of the nominal transformer current. When protecting
generators and other items of plant, where shunt magnetizing current is not present, a lower
differential setting can be used and 0.1 would be more typical.
Characteristic equation for the range 0 ≤ I R ≤ 0 .5 ⋅ I diff > : (Area I)
Id I >
= diff
Iref Iref
The second section (Area II) of the tripping curve covers the load current range, so that in
this section we must account for not only the transformer magnetizing current, which
appears as differential current, but also with differential currents that can be attributed to the
transformation errors of the current transformer sets.
If we calculate the worst case with IEC class 10P current transformers, then the maximum
allowable amplitude error according to IEC 60044-1 is 3 % for nominal current. The
phase-angle error can be assumed to be 2° for nominal current. The maximum allowable
total error for nominal current is then obtained, in approximation, as (0.0-3 + sin 2°) ≈ 6.5 %.
If the current is increased to the nominal accuracy limit current, then the total error for
Class 10P current transformers can be 10 % maximum. Beyond the nominal accuracy limit
current, the transformation error can be of any magnitude.
The dependence of the total error of a current transformer on current is therefore non-linear.
In the operating current range, i.e., in the current range below the nominal accuracy limit
current, we can expect a worst case total error of approximately 10 % per current
transformer set.
The second section of the tripping characteristic forms a straight line, the slope of which
should correspond to the cumulative total error of the participating current transformer sets.
The curve slope m1 can be set. The default setting for m1 is defined as 0.3 with respect to
protection of three-winding transformers, i.e. 3 x 10%.
Characteristic equation for the range 0,5 ⋅ I an < I H ≤ 4 ⋅ I B : (Area II)
I >
= m1 ⋅ R + diff ⋅ (1 − 0.5 ⋅ m1 )
Id I
Iref Iref Iref
Application Notes P63x/UK AP/A54
The second knee point of the tripping characteristic determines the end of the overcurrent
zone in the direction of increasing restraining current in fault-free operation. It can be as
high as four times the nominal current in certain operating cases - such as when a parallel
transformer has failed.
Therefore, the second knee point can be set (IR,m2) for a default setting of 4·Iref. IR,m2 must be
set in accordance with the maximum possible operating current.
Restraining currents that go beyond the set knee point are then evaluated as continuous
fault currents. For truly continuous fault currents, the third section of the tripping
characteristic could therefore be given an infinitely large slope. Since, however, we also
need to take into account the possibility that a fault can occur in the transformer differential
protection zone as the result of the system fault, a finite slope m2 is provided for the third
section of the tripping curve. The default setting for m2 is 0.7.
Characteristic equation for the range 4⋅ I < I : (Area III)
B H
IR,m2
= m 2 ⋅ R + diff > ⋅ (1 − 0.5 ⋅ m1 ) + ⋅ (m1 − m 2 )
Id I I
Iref Iref Iref Iref
S ref S ref
Iref ,a = Iref ,b =
3 ⋅ Vnom,a 3 ⋅ Vnom,b
S ref S ref
Iref ,c = Iref ,d =
3 ⋅ Vnom,c 3 ⋅ Vnom,d
Note: Where on-load tap changing is used, the nominal voltage chosen
should be that for the middle tap position.
P63x/UK AP/A54 Application Notes
Winding a Winding b
C
C
B
B
A
A
k amp,a kamp,b
With:
Basically, this matching operation can be carried out regardless of the phase winding
connections, since the phase relation is described unambiguously by the characteristic
vector group number.
Vector group matching is therefore performed solely by mathematical phasor operations on
the amplitude-matched phase currents of the low-voltage side in accordance with the
characteristic vector group number. The vector group is the clock-face hour position of the
LV A-phase voltage, with respect to the A-phase HV voltage at 12-o’clock (zero) reference.
Phase correction is provided in the P63x via “Settings/Function Settings/Common
Settings/DIFF: Vector Grp. ends b-a” [019.010] for phase shift between windings a and b.
Similar settings are provided for phase shift between further windings in the P633 and P634
relays.
This is shown in the following figure for vector group characteristic number 5, where vector
group Yd5 is used as the example:
AP
An external earth fault on the star side of a Dyn11 transformer will result in zero sequence
current flowing in the current transformers associated with the star winding but, due to the
effect of the delta winding, there will be no corresponding zero sequence current in the
current transformers associated with the delta winding.
In order to ensure stability of the protection, the LV zero sequence current must be
eliminated from the differential current. Traditionally this has been achieved by either delta
connected line CT’s or by the inclusion of a delta winding in the connection of an interposing
current transformer.
In accordance with its definition, the zero-sequence current is determined as follows from the
amplitude-matched phase currents:
Iamp,zero,z =
1
(
⋅I +I +I
3 amp,A,z amp,B,z amp,C,z
)
The following tables show that for all odd-numbered vector group characteristics the
zero-sequence current on the low-voltage side is basically always filtered out, whereas for
even-numbered vector group characteristics the zero-sequence current on the low-voltage
side is basically never filtered out automatically. The latter is also true for the high-voltage
side since in that case, as explained above, no mathematical phasor operations are
performed.
Vector group matching and zero-sequence current filtering must therefore always be viewed
in combination. The following tables list all the mathematical phasor operations.
Mathematical operations on the high-voltage side:
2 (
Ivec,y,z = − Iamp,x +1,z − Iamp,zero,z ) Ivec,y,z = −Iamp,x +1,z
6 (
Ivec,y,z = − Iamp,x,z − Iamp,zero,z ) Ivec,y,z = −Iamp,x,z
10 (
Ivec,y,z = − Iamp,x −1,z − Iamp,zero,z ) Ivec,y,z = −Iamp,x −1,z
Application Notes P63x/UK AP/A54
Setting the vector group matching function is very simple and does not require any
calculations. Only the characteristic vector group number needs to be set:
AP
Y/Y Y0 - Y0 Yy0 0
Y/Y Y0 - Y6 Yy6 6
Setting the zero-sequence current filtering function is very simple and does not require any
calculations. Zero-sequence current filtering should only be activated for those ends where
there is operational earthing of a neutral point:
P63x/UK AP/A54 Application Notes
A setting range of 2.5 - 30Iref (RMS values) is provided on the P63x relay. The high set
setting should be set in excess of the anticipated or estimated peak value of inrush current
after ratio correction.
If If
Source Source
Is Is
If If
64 64
1.0 10
I Current 8
I
F (x full load)
F
Current
6
(x full load)
4
0.2 IS IS
2
independent REF protection may not have previously been considered necessary for a
solidly earthed winding; especially where an additional relay would have been required. With
the P63x, the REF protection is available at no extra cost if a neutral CT is available.
Restricted earth fault protection is also commonly applied to Delta windings of large power
transformers, to improve the operating speed and sensitivity of the protection package to
winding earth faults. When applied to a Delta winding this protection is commonly referred to
as “balanced earth fault protection”. It is inherently restricted in its zone of operation when it
is stabilized for CT spill current during inrush or during phase faults. The value of fault
current flowing will again be dependant upon system earthing arrangements and the fault
point voltage.
• Low impedance REF biased by residual current (Low-Z Iph Sum Bias)
• Low impedance REF biased by maximum phase current (Low-Z Iph Max. Bias)
Note: The Low-Z Iph Sum Bias mode cannot be used for balanced earth
fault protection of delta windings.
Rl Rl
If(prim) If(prim)
Rct Rl
R stab'
64
Rl
The high impedance REF element shall maintain stability for through faults and operate in
less than 40ms for internal faults provided the following conditions are met in determining the
CT requirements and value of associated stabilizing resistor:
45
40
35
Operating time (ms)
30
25
20
15
AP
10
0
0 5 10 15 20
Vk / (Idiff> × Rs)
Note: The diagram is the result of investigations which were carried out for
impedance ratios in the range of 5 to 120 and for fault currents in the
range of 0.5 to 40 In.
Vp = 2 2Vk ( Vf - Vk )
Where:
Vp = Peak voltage developed by the CT under internal fault conditions
Vk = Current transformer kneepoint voltage
Vf = Maximum voltage that would be produced if CT saturation did not occur
V = CΙ0.25
Where:
V = Instantaneous voltage applied to the non-linear resistor (Metrosil)
C = Constant of the non-linear resistor (Metrosil)
AP I = Instantaneous current through the non-linear resistor (Metrosil)
With a sinusoidal voltage applied across the Metrosil, the RMS current would be
approximately 0.52 x the peak current. This current value can be calculated as follows:
⎛ Vs (rms) x 2 ⎞ 4
Ι(rms) = 0.52 ⎜ ⎟
⎝ C ⎠
Where:
Vs(rms) = rms value of the sinusoidal voltage applied across the Metrosil
This is due to the fact that the current waveform through the Metrosil is not sinusoidal but
appreciably distorted.
For satisfactory application of a non-linear resistor (Metrosil), its characteristic should be
such that it complies with the following requirements:
1. At the relay voltage setting, the non-linear resistor (metrosil) current should be as low
as possible, but no greater than approximately 30mA rms for 1A current transformers
and approximately 100mA rms for 5A current transformers
2. At the maximum secondary current, the non-linear resistor (metrosil) should limit the
voltage to 1500V rms or 2120V peak for 0.25 second. At higher relay voltage settings,
it is not always possible to limit the fault voltage to 1500V rms, so higher fault voltages
may have to be tolerated
The following tables show the typical Metrosil types that will be required, depending on relay
current rating, REF voltage setting etc.
Metrosil Units for Relays with a 1 Amp CT
The Metrosil units with 1 Amp CTs have been designed to comply with the following
restrictions:
3. At the relay voltage setting, the Metrosil current should be less than 30mA rms
4. At the maximum secondary internal fault current the Metrosil unit should limit the
voltage to 1500V rms if possible
Application Notes P63x/UK AP/A54
The Metrosil units normally recommended for use with 1Amp CT's are as shown in the
following table:
Nominal
Relay Voltage Recommended Metrosil Type
Characteristic
Setting
C β Single Pole Relay Triple Pole Relay
Up to 125V rms 450 0.25 600A/S1/S256 600A/S3/1/S802
125 to 300V rms 900 0.25 600A/S1/S1088 600A/S3/1/S1195
Note: Single pole Metrosil units are normally supplied without mounting
brackets unless otherwise specified by the customer.
Metrosil units for relays with a 5 amp CT
These Metrosil units have been designed to comply with the following requirements:
1. At the relay voltage setting, the Metrosil current should be less than 100mA rms (the
actual maximum currents passed by the units shown below their type description
2. At the maximum secondary internal fault current the Metrosil unit should limit the
voltage to 1500V rms for 0.25secs. At the higher relay settings, it is not possible to
limit the fault voltage to 1500V rms hence higher fault voltages have to be tolerated
(indicated by *, **, ***)
3. The Metrosil units normally recommended for use with 5 Amp CTs and single pole
relays are as shown in the following table:
Secondary
Internal
Recommended Metrosil Type
AP
Fault Relay Voltage Setting
Current
Amps rms Up to 200V rms 250V rms 275V rms 300V rms
600A/S1/S1213 600A/S1/S1214 600A/S1/S1214 600A/S1/S1223
50A C = 540/640 C = 670/800 C =670/800 C = 740/870*
35mA rms 40mA rms 50mA rms 50mA rms
600A/S2/P/S121 600A/S2/P/S1215 600A/S2/P/S1215 600A/S2/P/S1196
100A 7 C = 470/540 C = 570/670 C =570/670 C =620/740*
70mA rms 75mA rms 100mA rms 100mA rms
600A/S3/P/S121 600A/S3/P/S1220 600A/S3/P/S1221 600A/S3/P/S1222
150A 9 C = 430/500 C = 520/620 C = 570/670** C =620/740***
100mA rms 100mA rms 100mA rms 100mA rms
Note: *2400V peak **2200V peak ***2600V peak
In some situations single disc assemblies may be acceptable, contact AREVA T&D for
detailed applications.
Note:
1. The Metrosil units recommended for use with 5 Amp CTs can also be applied for use
with triple pole relays and consist of three single pole units mounted on the same
central stud but electrically insulated from each other. To order these units please
specify "Triple pole Metrosil type", followed by the single pole type reference
2. Metrosil units for higher relay voltage settings and fault currents can be supplied if
required
P63x/UK AP/A54 Application Notes
AP
AP
C C
B B
A A
Serial
Energizing
winding
winding
Common Regulating
winding winding
-60°/0°/+60°
phase-angle
Delta
Tertiary
connection
winding
C
B
A
Unloaded Delta
Neutral Earthing CTs in Series
CTs Outside Delta
AP
With Phase- With Delta
Tertiary Winding Tertiary Winding
Segregated CTs Tertiary Winding
Differential
Two-end Three-end Three-end Three-end
protection
Amplitude Vnom,a = Vnom,b
Vnom,a ≠ Vnom,b √3·Vnom,c Vnom,c
matching = Vnom,c
Vector group VGa-b = 0 VGa-b = 0 VGa-b = 0
VGa-b = 0
matching VGa-c = 0 VGa-c = 0 VGa-c = odd
Zero sequence
Enabled Disabled Disabled Enabled
current filtering
Inrush stabilization Enabled Disabled Enabled Enabled
Phase-segregation No Yes Yes No
Affected by voltage
Yes No No Yes
adjustment
Sensitivity for earth
Low High High Low
faults
Protection against
Yes No Yes Yes
turn-to-turn faults
Protection of the
delta tertiary No No Yes Yes
winding
C C
B B
A A
I d/I
C C
B B
A A
I d/I
Figure 15: Auto-transformer - neutral earthing with per phase neutral CTs
The differential protection described above operates strictly phase-segregated particularly
due to the fact that inrush stabilization is not required. Sensitivity for earth fault detection is
high. However turn-to-turn faults and faults on the tertiary winding cannot be detected in
principle. AP
2.4.3 CTs in series with delta tertiary winding
If the corresponding current through the tertiary winding is measured instead of the
neutral-to-earth current per phase a transformer coupling will be given.
C C
B B
A A
I d/I
C
B
A
P634
BB1
P633
AP
3. SETTING RECOMMENDATIONS
3.1 Introduction
By default all protection, logic and I/O settings are disabled in the P63x when delivered from
the manufacturer. The following sections are intended to provide recommendations on the
setup of auxiliary functions available in all relay configurations. The settings may be
configured in the MiCOM S1 S&R-103 setting software with out the need to access the relay.
The configured file may be saved as a standard “default” and used as a starting point when
applying the P63x to specific installations requiring calculated protection and logic settings.
The relevant sections of the application notes should be cross referenced prior to applying
the settings ensuring they are correct for the application.
2. Then the differential protection must be enabled across the setting groups globally:
(019.080) “Settings/Function Settings/Common Settings/DIFF: General Enable USER” set to “Yes”
AP
3. Differential protection must then be enabled in the required setting group, e.g. SG1:
(072.152) “Settings/ Function Settings/Setting Group 1/DIFF: Enable SG1” set to “Yes”
The protection system settings for differential protection can then be set as required for the
particular installation with reference to the appropriate sections of this Technical Guide. The
above procedure is also required for configuring other types of protection such as
overcurrent, restricted earth fault, etc.
Having assigned the trip command, the corresponding signal may be assigned to the desired
output relay. It is recommended to use output relay 01 on the power supply module which
provides 2 N/O contacts, although any available contact in a P63x may be configured for
circuit breaker tripping.
For P632/P633/P634:
(151.201) “Settings/Configuration/OUTP: Fct. Assignm. K 2001” set to “Gen. Trip Command 1”
For P631:
(150.193) “Settings/Configuration/OUTP: Fct. Assignm. K 901” set to “Gen. Trip Command 1”
The closing pulse time of the output contact is then controlled by the setting:
(021.003) “Settings/Function Settings/Global/MAIN: tDWELL Trip Cmd 1”
P63x/UK AP/A54 Application Notes
The logic equations should not be used for fast operating protection tripping functions, as
they may introduce a small delay in operation. Any grouping of trip commands should be
performed in the trip command described above.
For P631:
(150.214) “Settings/Configuration/OUTP: Fct. Assignm. K 908” set to “MAIN Blocked/Faulty”
This output relay provides a C/O contact which should be programmed to changeover when
auxiliary power is applied and the relay has not detected any conditions preventing correct
operation of protection.
The operation mode for P632/P633/P634:
(151.223) “Settings/Configuration/OUTP: Oper. Mode K 2008” set to “Inverted”
For P631:
(150.215) “Settings/Configuration/OUTP: Oper. Mode K 908” set to “Inverted”
This enables display of e.g. load current, voltage, frequency measurements on the front
panel display during normal operation. When more than two measurements are selected the
HMI will cycle through the configured measurements at a rate set by:
(031.075) “Settings/Configuration/HMI: Panel Hold-Time”
Application Notes P63x/UK AP/A54
Vk ≥ K × (Rct + Rl )
Phase fault differential protection
K is a constant depending on the maximum value of through fault current (as a multiple of In)
and the primary system X/R ratio. For phase faults, K is determined as follows:
K = 0.14 × (If × X / R)
K = 70 AP
For earth faults, Ke is determined as follows:
K e = 0.14 × (Ife × X / R)
K e = 70
Vk ≥ If × (Rct + 2Rl )
(Rct + 2Rl )
Vk ≥
Xt
45
40
35
Operating time (ms)
30
25
20
AP 15
10
0
0 5 10 15 20
Vk / (Idiff> × Rs)
Note: The diagram is the result of investigations which were carried out for
impedance ratios in the range of 5 to 120 and for fault currents in the
range of 0.5 to 40 In.
AP
P63x/UK AP/A54 Application Notes
AP
Measurements and Recording P63x/UK MR/A54
MEASUREMENTS AND MR
RECORDING
MR
Measurements and Recording P63x/UK MR/A54
CONTENTS
(MR) 7-
1. MEASUREMENTS + TESTS 5
1.1 Measurements 5
1.2.2 Main rear port communication control and testing commands (COMM1) 63
1.2.3 2nd rear port communication control and testing commands (COMM2) 63
MR
P63x/UK MR/A54 Measurements and Recording
MR
Measurements and Recording P63x/UK MR/A54
1. MEASUREMENTS + TESTS
1.1 Measurements
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
RTDmA: Current IDC 0.00 mA 24.00 mA 0.01 mA
OP Fig.
004 134 Read only
102
Display of the input current.
0.00 1.20 0.01
RTDmA: Current IDC p.u.
IDC,nom IDC,nom IDC,nom
OP Fig.
004 135 Read only
102
Display of the input current referred to IDC,nom.
0.00 1.20 0.01
RTDmA: Curr. IDC,lin. p.u.
IDC,nom IDC,nom IDC,nom
OP Fig.
004 136 Read only
102
Display of the linearized input current referred to IDC,nom. MR
RTDmA: Scaled Value IDC,lin -32000 32000 1
OP Fig.
004 180 Read only
103
Display of the scaled linearized value.
RTDmA: Temperature -40.0 °C 215.0 °C 0.1 °C
OP Fig.
004 133 Read only
104
Display of the temperature measured by the resistance thermometer.
RTDmA: Temperature p.u. -0.40 2.15 0.01
OP Fig.
004 221 Read only
104
Display of the temperature measured by the resistance thermometer as a per unit value.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
mA_OP: Current A-1 0.00 mA 20.00 mA 0.01 mA
OP Fig.
005 100 Read only
112
mA_OP: Current A-2 0.00 mA 20.00 mA 0.01 mA
OP Fig.
005 099 Read only
112
Display of the output current for analog measured value output (A-1: channel 1, A-2:
channel 2)
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
MAIN: Date - - dd.mm.yy
OP Fig.
003 090
138
Date display.
Standard Time
MAIN: Time Switching -
Daylight Saving Time
OP Fig.
003 095
138
Setting for standard time or daylight saving time.
This setting is necessary in order to avoid misinterpretation of the times assigned to signals
and event data that can be read out through the PC or communication interfaces.
MAIN: Frequency f 40.00 Hz 70.00 Hz 0.01 Hz
OP Fig.
004 040 Read only
125
Display of system frequency.
MAIN: Iph, Max now, a prim 0A 25000 A 1A
OP Fig.
005 101 Read only
119
MAIN: Iph, Max now, b prim 0A 25000 A 1A
OP Fig.
005 102 Read only
119
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Iph, Max now, c prim 0A 25000 A 1A
OP Fig.
005 103 Read only
119
MAIN: Iph, Max now, d prim 0A 25000 A 1A
OP Fig.
005 115 Read only
119
Display of the maximum phase current as a primary quantity for each end.
MAIN: Iph Therm dem a prim 0A 25000 A 1A
OP Fig.
005 162 Read only
119
MAIN: Iph Therm dem b prim 0A 25000 A 1A
OP Fig.
006 162 Read only
119
MAIN: Iph Therm dem c prim 0A 25000 A 1A
OP Fig.
007 162 Read only
119
MAIN: Iph Therm dem d prim 0A 25000 A 1A
OP Fig.
008 162 Read only
119
Display of the delayed maximum current of end a, b, c or d, respectively, as a primary
quantity. Alternatively known as a “thermal ammeter”.
MAIN: Iph Therm pk a prim 0A 25000 A 1A MR
OP Fig.
005 161 Read only
119
MAIN: Iph Therm pk b prim 0A 25000 A 1A
OP Fig.
006 161 Read only
119
MAIN: Iph Therm pk c prim 0A 25000 A 1A
OP Fig.
007 161 Read only
119
MAIN: Iph Therm pk d prim 0A 25000 A 1A
OP Fig.
008 161 Read only
119
Display of the delayed stored maximum phase current of end a, b, c or d, respectively, as a
primary quantity (thermal maximum demand).
MAIN: Current Imin,a prim 0A 25000 A 1A
OP Fig.
005 104 Read only
119
MAIN: Current Imin,b prim 0A 25000 A 1A
OP Fig.
005 105 Read only
119
MAIN: Current Imin,c prim 0A 25000 A 1A
OP Fig.
005 106 Read only
119
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current Imin,d prim 0A 25000 A 1A
OP Fig.
005 117 Read only
119
Display of the minimum phase current of end a, b, c or d, respectively, as a primary
quantity.
MAIN: Current IA,a prim. 0A 25000 A 1A
OP Fig.
005 021 Read only
119
MAIN: Current IB,a prim. 0A 25000 A 1A
OP Fig.
006 021 Read only
119
MAIN: Current IC,a prim. 0A 25000 A 1A
OP Fig.
007 021 Read only
119
Display of phase currents as a primary quantity, end a.
MAIN: Current IA,b prim. 0A 25000 A 1A
OP Fig.
005 022 Read only
119
MAIN: Current IB,b prim. 0A 25000 A 1A
OP Fig.
006 022 Read only
119
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current I2 a prim. 0A 25000 A 1A
005 125 Read only
MAIN: Current I2 b prim. 0A 25000 A 1A
005 129 Read only
MAIN: Current I2 c prim. 0A 25000 A 1A
005 136 Read only
MAIN: Current I2 d prim. 0A 25000 A 1A
005 140 Read only
Display of negative sequence currents as a primary quantity for each end.
MAIN: Current I1 a prim. 0A 25000 A 1A
005 127 Read only
MAIN: Current I1 b prim. 0A 25000 A 1A
005 134 Read only
MAIN: Current I1 c prim. 0A 25000 A 1A
005 138 Read only
MAIN: Current I1 d prim. 0A 25000 A 1A
005 146 Read only
Display of positive sequence currents as a primary quantity for each end.
MAIN: Current IN,a prim. 0A 25000 A 1A
MR
OP Fig.
005 121 Read only
121
MAIN: Current IN,b prim. 0A 25000 A 1A
OP Fig.
005 122 Read only
121
MAIN: Current IN,c prim. 0A 25000 A 1A
OP Fig.
005 123 Read only
121
MAIN: Current IN,d prim. 0A 25000 A 1A
OP Fig.
005 124 Read only
122
Display of the residual current calculated by the P63x from the sum of the phase currents
as a primary quantity for each end.
MAIN: Current IY,a prim. 0A 25000 A 1A
OP Fig.
005 131 Read only
121
MAIN: Current IY,b prim. 0A 25000 A 1A
OP Fig.
005 132 Read only
121
MAIN: Current IY,c prim. 0A 25000 A 1A
OP Fig.
005 133 Read only
121
Display of the current measured by the P63x at transformer T14 as a primary quantity for
each end.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Voltage V prim. 0.0 kV 2500.0 kV 0.1 kV
OP Fig.
005 118 Read only
124
Display of the voltage measured by the P63x, as a primary quantity.
MAIN: Curr Iph,Max now,apu 0.00 In 25.00 In 0.01 In
OP Fig.
005 111 Read only
119, 120
MAIN: Curr Iph,Max now,bpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 112 Read only
119, 120
MAIN: Curr Iph,Max now,cpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 113 Read only
119, 120
MAIN: Curr Iph,Max now,dpu 0.00 In 25.00 In 0.01 In
OP Fig.
005 116 Read only
119, 120
Display of the maximum phase current for each end as referred to In, or per unit.
MAIN: Iph pu Thermal dem.a 0.00 In 25.00 In 0.01 In
OP Fig.
005 163 Read only
119, 120
MAIN: Iph pu Thermal dem.b 0.00 In 25.00 In 0.01 In
MR OP Fig.
006 163 Read only
119, 120
MAIN: Iph pu Thermal dem.c 0.00 In 25.00 In 0.01 In
OP Fig.
007 163 Read only
119, 120
MAIN: Iph pu Thermal dem.d 0.00 In 25.00 In 0.01 In
OP Fig.
008 163 Read only
119, 120
Display of the delayed maximum phase current for each end as referred to In.
MAIN: Iph pu Thermal peaka 0.00 In 25.00 In 0.01 In
OP Fig.
005 160 Read only
119, 120
MAIN: Iph pu Thermal peakb 0.00 In 25.00 In 0.01 In
OP Fig.
006 160 Read only
119, 120
MAIN: Iph pu Thermal peakc 0.00 In 25.00 In 0.01 In
OP Fig.
007 160 Read only
119, 120
MAIN: Iph pu Thermal peakd 0.00 In 25.00 In 0.01 In
OP Fig.
008 160 Read only
119, 120
Display of the delayed stored maximum phase current for each end as referred to In.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current Imin,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 107 Read only
119
MAIN: Current Imin,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 108 Read only
119
MAIN: Current Imin,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 109 Read only
119
MAIN: Current Imin,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 118 Read only
119
Display of the minimum phase current for each end as referred to In.
MAIN: Current IA,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 031 Read only
119
MAIN: Current IB,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 031 Read only
119
MAIN: Current IC,a p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 031 Read only
119 MR
Display of phase currents, end a, as referred to In.
MAIN: Current IA,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 032 Read only
119
MAIN: Current IB,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 032 Read only
119
MAIN: Current IC,b p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 032 Read only
119
Display of phase currents, end b, as referred to In.
MAIN: Current IA,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 033 Read only
119
MAIN: Current IB,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 033 Read only
119
MAIN: Current IC,c p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 033 Read only
119
Display of phase currents, end c, as referred to In.
MAIN: Current IA,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 039 Read only
119
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current IB,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
006 034 Read only
119
MAIN: Current IC,d p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 034 Read only
119
Display of phase currents, end d, as referred to In.
MAIN: Current I2 a p.u. 0.00 In 25.00 In 0.01 In
005 126 Read only
MAIN: Current I2 b p.u. 0.00 In 25.00 In 0.01 In
005 130 Read only
MAIN: Current I2 c p.u. 0.00 In 25.00 In 0.01 In
005 137 Read only
MAIN: Current I2 d p.u. 0.00 In 25.00 In 0.01 In
005 145 Read only
Display of negative sequence currents for each end in per unit.
MAIN: Current I1 a p.u. 0.00 In 25.00 In 0.01 In
005 128 Read only
MAIN: Current I1 b p.u. 0.00 In 25.00 In 0.01 In
MR 005 135 Read only
MAIN: Current I1 c p.u. 0.00 In 25.00 In 0.01 In
005 139 Read only
MAIN: Current I1 d p.u. 0.00 In 25.00 In 0.01 In
005 147 Read only
Display of positive sequence currents for each end in per unit.
MAIN: Current IN,a p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 141 Read only
121
MAIN: Current IN,b p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 142 Read only
121
MAIN: Current IN,c p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 143 Read only
121
MAIN: Current IN,d p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 144 Read only
122
Display of the residual current calculated by the P63x from the sum of the phase currents
for each end as referred to In.
MAIN: Current IY,a p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 151 Read only
121
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Current IY,b p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 152 Read only
121
MAIN: Current IY,c p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 153 Read only
121
Display of the current measured by the P63x at transformer T14 for each end as referred to
In.
MAIN: Iph,max,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 114 Read only
123
Display of the maximum phase current for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Iph,min,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 110 Read only
123
Display of the minimum phase current for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Current IA,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
005 038 Read only
123
MAIN: Current IB,add p.u. 0.00 In 25.00 In 0.01 In
MR
OP Fig.
006 038 Read only
123
MAIN: Current IC,add p.u. 0.00 In 25.00 In 0.01 In
OP Fig.
007 038 Read only
123
Display of phase currents for the virtual end, as referred to In. The virtual end is formed
according to the selection at MAIN: Current Summation.
MAIN: Curr. I2, add p.u. 0.00 In 25.00 In 0.01 In
005 149 Read only
Display of negative sequence currents for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Curr. I1, add p.u. 0.00 In 25.00 In 0.01 In
005 150 Read only
Display of positive sequence currents for the virtual end, as referred to In. The virtual end
is formed according to the selection at MAIN: Current Summation.
MAIN: Current IN,add p.u. 0.000 In 25.000 In 0.001 In
OP Fig.
005 155 Read only
123
Display of residual current for the virtual end, as referred to In. The virtual end is formed
according to the selection at MAIN: Current Summation.
MAIN: Voltage V p.u. 0.00 Vn 25.00 Vn 0.01 Vn
OP Fig.
005 019 Read only
123
Display of the voltage measured by the P63x, as referred to Vn.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Angle phi AB, end a -180 ° 180 ° 1°
OP Fig.
005 089 Read only
126
MAIN: Angle phi BC, end a -180 ° 180 ° 1°
OP Fig.
006 089 Read only
126
MAIN: Angle phi CA, end a -180 ° 180 ° 1°
OP Fig.
007 089 Read only
126
Display of the phase shift between phases, end a.
MAIN: Angle phi AB, end b -180 ° 180 ° 1°
OP Fig.
005 092 Read only
126
MAIN: Angle phi BC, end b -180 ° 180 ° 1°
OP Fig.
006 092 Read only
126
MAIN: Angle phi CA, end b -180 ° 180 ° 1°
OP Fig.
007 092 Read only
126
Display of the phase shift between phases, end b.
MAIN: Angle phi AB, end c -180 ° 180 ° 1°
MR OP Fig.
005 093 Read only
126
MAIN: Angle phi BC, end c -180 ° 180 ° 1°
OP Fig.
006 093 Read only
126
MAIN: Angle phi CA, end c -180 ° 180 ° 1°
OP Fig.
007 093 Read only
126
Display of the phase shift between phases, end c.
MAIN: Angle phi AB, end d -180 ° 180 ° 1°
OP Fig.
005 095 Read only
126
MAIN: Angle phi BC, end d -180 ° 180 ° 1°
OP Fig.
006 095 Read only
126
MAIN: Angle phi CA, end d -180 ° 180 ° 1°
OP Fig.
007 095 Read only
126
Display of the phase shift between phases, end d.
MAIN: Angle phi A, end b-a -180 ° 180 ° 1°
OP Fig.
005 090 Read only
127
MAIN: Angle phi A, end c-a -180 ° 180 ° 1°
OP Fig.
005 091 Read only
127
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Angle phi A, end d-a -180 ° 180 ° 1°
OP Fig.
005 094 Read only
127
Display of the phase shift between ends for phase A.
MAIN: Angle phi B, end b-a -180 ° 180 ° 1°
OP Fig.
006 090 Read only
127
MAIN: Angle phi B, end c-a -180 ° 180 ° 1°
OP Fig.
006 091 Read only
127
MAIN: Angle phi B, end d-a -180 ° 180 ° 1°
OP Fig.
006 094 Read only
127
Display of the phase shift between ends for phase B.
MAIN: Angle phi C, end b-a -180 ° 180 ° 1°
OP Fig.
007 090 Read only
127
MAIN: Angle phi C, end c-a -180 ° 180 ° 1°
OP Fig.
007 091 Read only
127
MAIN: Angle phi C, end d-a -180 ° 180 ° 1°
OP Fig. MR
007 094 Read only
127
Display of the phase shift between ends for phase C.
MAIN: Angle phi NY, end a -180 ° 180 ° 1°
OP Fig.
005 077 Read only
128
MAIN: Angle phi NY, end b -180 ° 180 ° 1°
OP Fig.
005 078 Read only
128
MAIN: Angle phi NY, end c -180 ° 180 ° 1°
OP Fig.
005 079 Read only
128
Display of the phase shift between the residual current calculated by the P63x from the
sum of the phase currents at each end and the current measured at transformer T14.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
DIFF: Diff Current 1 0.000 Iref 40.000 Iref 0.001 Iref
005 080 Read only OP Fig. 13
DIFF: Diff Current 2 0.000 Iref 40.000 Iref 0.001 Iref
006 080 Read only OP Fig. 13
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
DIFF: Diff Current 3 0.000 Iref 40.000 Iref 0.001 Iref
007 080 Read only OP Fig. 13
Display of the differential current for each measuring system, as referred to Iref.
DIFF: Restrain Current 1 0.000 Iref 40.000 Iref 0.001 Iref
005 081 Read only OP Fig. 13
DIFF: Restrain Current 2 0.000 Iref 40.000 Iref 0.001 Iref
006 081 Read only OP Fig. 13
DIFF: Restrain Current 3 0.000 Iref 40.000 Iref 0.001 Iref
007 081 Read only OP Fig. 13
Display of the restraining current for each measuring system, as referred to Iref.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
REF_1: Diff. Current, REF_1 0.00 Iref 20.00 Iref 0.01 Iref
008 080 Read only OP Fig. 20
REF_2: Diff. Current, REF_2 0.00 Iref 20.00 Iref 0.01 Iref
008 070 Read only OP Fig. 20
MR REF_3: Diff. Current, REF_3 0.00 Iref 20.00 Iref 0.01 Iref
008 060 Read only OP Fig. 20
Display of the differential current, as referred to Iref.
REF_1: Restrain Curr.,REF_1 0.00 Iref 20.00 Iref 0.01 Iref
008 081 Read only OP Fig. 20
REF_2: Restrain Curr.,REF_2 0.00 Iref 20.00 Iref 0.01 Iref
008 071 Read only OP Fig. 20
REF_3: Restrain Curr.,REF_3 0.00 Iref 20.00 Iref 0.01 Iref
008 061 Read only OP Fig. 20
Display of the restraining current, as referred to Iref.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
THRM1: Status Replica, TH1 -25000 % 25000 % 1%
004 150 Read only OP Fig. 45
THRM2: Status Replica, TH2 -25000 % 25000 % 1%
004 175 Read only OP Fig. 45
Measurement Range
Menu Text Step Size
Min. Max.
THRM2: Object Temperat.,TH2 -40 °C 300 °C 1 °C
004 171 Read only OP Fig. 45
Display of the temperature of the protected object as determined by function THRM1.
THRM1: Coolant Temp. TH1 -40 °C 200 °C 1 °C
004 154 Read only OP Fig. 45
THRM2: Object Temp. p.u. 2 -0.04 100°C 0.30 100°C 0.01 100°C
004 208 Read only OP Fig. 45
THRM1: Coolant Temp. p.u. 1 -0.04 100°C 0.20 100°C 0.01 100°C
004 206 Read only OP Fig. 45
THRM2: Coolant Temp. p.u. 2 -0.04 100°C 0.20 100°C 0.01 100°C
004 209 Read only OP Fig. 45
THRM1: Temp. Offset Repl. 1 -25000 % 25000 % 1%
004 170 Read only OP Fig. 45
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
THRM2: Temp. Offset Repl. 2 -25000 % 25000 % 1%
004 190 Read only OP Fig. 45
Display of the additional reserve if the coolant temperature is taken into account. This
display is relevant if the coolant temperature has been set to a value below the maximum
permissible coolant temperature or, in other words, if the thermal model has been shifted
downwards.
If, on the other hand, the coolant temperature and the maximum permissible coolant
temperature have been set to the same value, then the coolant temperature is not taken
into account and the characteristic is a function of the current only. The additional reserve
amounts to 0 in this case.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Analog Readings
V/f: Excitation V/f p.u. 0.00 10.00 0.01
004 220 Read only OP Fig. 55
V/f: Status Replica in % 0% 100 % 1%
004 222 Read only OP Fig. 60
V/f: Status Replica p.u. 0.00 1.00 0.01
004 223 Read only OP Fig. 60
MR 1.1.2 I.O. status monitor
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
GOOSE: Out 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GOOSE output state.
Menu Text Address Menu Text Address Menu Text Address
GOOSE Out 1 State 106 010 GOOSE Out 12 State 106 032 GOOSE Out 23 State 106 054
GOOSE Out 2 State 106 012 GOOSE Out 13 State 106 034 GOOSE Out 24 State 106 056
GOOSE Out 3 State 106 014 GOOSE Out 14 State 106 036 GOOSE Out 25 State 106 058
GOOSE Out 4 State 106 016 GOOSE Out 15 State 106 038 GOOSE Out 26 State 106 060
GOOSE Out 5 State 106 018 GOOSE Out 16 State 106 040 GOOSE Out 27 State 106 062
GOOSE Out 6 State 106 020 GOOSE Out 17 State 106 042 GOOSE Out 28 State 106 064
GOOSE Out 7 State 106 022 GOOSE Out 18 State 106 044 GOOSE Out 29 State 106 066
GOOSE Out 8 State 106 024 GOOSE Out 19 State 106 046 GOOSE Out 30 State 106 068
GOOSE Out 9 State 106 026 GOOSE Out 20 State 106 048 GOOSE Out 31 State 106 070
GOOSE Out 10 State 106 028 GOOSE Out 21 State 106 050 GOOSE Out 32 State 106 072
GOOSE Out 11 State 106 030 GOOSE Out 22 State 106 052
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
GOOSE: Inp 1 (…16) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GOOSE input state.
Menu Text Address Menu Text Address
GOOSE Inp 1 State 106 200 GOOSE Inp 12 State 106 211
GOOSE Inp 2 State 106 201 GOOSE Inp 13 State 106 212
GOOSE Inp 3 State 106 202 GOOSE Inp 14 State 106 213
GOOSE Inp 4 State 106 203 GOOSE Inp 15 State 106 214
GOOSE Inp 5 State 106 204 GOOSE Inp 16 State 106 215
GOOSE Inp 6 State 106 205
GOOSE Inp 7 State 106 206
GOOSE Inp 8 State 106 207
GOOSE Inp 9 State 106 208
GOOSE Inp 10 State 106 209
GOOSE Inp 11 State 106 210
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor MR
GSSE: Out 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GSSE output state.
Menu Text Address Menu Text Address Menu Text Address
GSSE Out 1 State 104 100 GSSE Out 12 State 104 133 GSSE Out 23 State 104 166
GSSE Out 2 State 104 103 GSSE Out 13 State 104 136 GSSE Out 24 State 104 169
GSSE Out 3 State 104 106 GSSE Out 14 State 104 139 GSSE Out 25 State 104 172
GSSE Out 4 State 104 109 GSSE Out 15 State 104 142 GSSE Out 26 State 104 175
GSSE Out 5 State 104 112 GSSE Out 16 State 104 145 GSSE Out 27 State 104 178
GSSE Out 6 State 104 115 GSSE Out 17 State 104 148 GSSE Out 28 State 104 181
GSSE Out 7 State 104 118 GSSE Out 18 State 104 151 GSSE Out 29 State 104 184
GSSE Out 8 State 104 121 GSSE Out 19 State 104 154 GSSE Out 30 State 104 187
GSSE Out 9 State 104 124 GSSE Out 20 State 104 157 GSSE Out 31 State 104 190
GSSE Out 10 State 104 127 GSSE Out 21 State 104 160 GSSE Out 32 State 104 193
GSSE Out 11 State 104 130 GSSE Out 22 State 104 163
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
GSSE: Inp 1 (…32) State 0 1 1
See table below for status addresses. Read only
Display of the virtual binary GSSE input state.
Menu Text Address Menu Text Address Menu Text Address
GSSE Inp 1 State 105 000 GSSE Inp 12 State 105 055 GSSE Inp 23 State 105 110
GSSE Inp 2 State 105 005 GSSE Inp 13 State 105 060 GSSE Inp 24 State 105 115
GSSE Inp 3 State 105 010 GSSE Inp 14 State 105 065 GSSE Inp 25 State 105 120
GSSE Inp 4 State 105 015 GSSE Inp 15 State 105 070 GSSE Inp 26 State 105 125
GSSE Inp 5 State 105 020 GSSE Inp 16 State 105 075 GSSE Inp 27 State 105 130
GSSE Inp 6 State 105 025 GSSE Inp 17 State 105 080 GSSE Inp 28 State 105 135
GSSE Inp 7 State 105 030 GSSE Inp 18 State 105 085 GSSE Inp 29 State 105 140
GSSE Inp 8 State 105 035 GSSE Inp 19 State 105 090 GSSE Inp 30 State 105 145
GSSE Inp 9 State 105 040 GSSE Inp 20 State 105 095 GSSE Inp 31 State 105 150
GSSE Inp 10 State 105 045 GSSE Inp 21 State 105 100 GSSE Inp 32 State 105 155
GSSE Inp 11 State 105 050 GSSE Inp 22 State 105 105
MR
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
INP: State U 701 (…2004) Low -
High
See table below for status addresses. Read only OP Fig. 98
The state of the binary signal inputs is displayed as follows:
Disabled: No functions are assigned to the binary signal input
Low: Not energized
High: Energized
This display appears regardless of the setting for the binary signal input mode.
Menu Text Address Menu Text Address Menu Text Address
State U 701 152 108 State U 821 184 081 State U 1409 190 033
State U 702 152 111 State U 822 184 085 State U 1410 190 037
State U 703 152 114 State U 823 184 089 State U 1411 190 041
State U 704 152 117 State U 824 184 093 State U 1412 190 045
State U 705 152 120 State U 901 152 144 State U 1413 190 049
State U 706 152 123 State U 902 152 147 State U 1414 190 053
State U 801 184 001 State U 903 152 150 State U 1415 190 057
State U 802 184 005 State U 904 152 153 State U 1416 190 061
State U 803 184 009 State U 1001 152 162 State U 1417 190 065
MR
State U 804 184 013 State U 1002 152 165 State U 1418 190 069
State U 805 184 017 State U 1003 152 168 State U 1419 190 073
State U 806 184 021 State U 1004 152 171 State U 1420 190 077
State U 807 184 025 State U 1005 152 174 State U 1421 190 081
State U 808 184 029 State U 1006 152 177 State U 1422 190 085
State U 809 184 033 State U 1201 152 198 State U 1423 190 089
State U 810 184 037 State U 1202 152 201 State U 1424 190 093
State U 811 184 041 State U 1203 152 204 State U 1601 192 001
State U 812 184 045 State U 1204 152 207 State U 1602 192 005
State U 813 184 049 State U 1401 190 001 State U 1603 192 009
State U 814 184 053 State U 1402 190 005 State U 1604 192 013
State U 815 184 057 State U 1403 190 009 State U 1605 192 017
State U 816 184 061 State U 1404 190 013 State U 1606 192 021
State U 817 184 065 State U 1405 190 017 State U 2001 153 086
State U 818 184 069 State U 1406 190 021 State U 2002 153 089
State U 819 184 073 State U 1407 190 025 State U 2003 153 092
State U 820 184 077 State U 1408 190 029 State U 2004 153 095
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
OUTP: State K 701 (…2008) -
Enabled
OP Fig.
See table below for status addresses. Read only
105
The state of the output relays is displayed as follows:
Disabled: No functions are assigned to the output relay
Low: The output relay is not energized
High: The output relay is energized
This display appears regardless of the operating mode set for the output relay.
Menu Text Address Menu Text Address Menu Text Address
State K 701 150 144 State K 908 150 213 State K 1607 171 025
State K 702 150 147 State K 1001 150 216 State K 1608 171 029
State K 703 150 150 State K 1002 150 219 State K 1801 173 001
State K 704 150 153 State K 1003 150 222 State K 1802 173 005
State K 705 150 156 State K 1004 150 225 State K 1803 173 009
State K 706 150 159 State K 1005 150 228 State K 1804 173 013
State K 707 150 162 State K 1006 150 231 State K 1805 173 017
State K 708 150 165 State K 1007 150 234 State K 1806 173 021
MR State K 801 150 168 State K 1008 150 237 State K 2001 151 200
State K 802 150 171 State K 1201 151 008 State K 2002 151 203
State K 901 150 192 State K 1202 151 011 State K 2003 151 206
State K 902 150 195 State K 1601 171 001 State K 2004 151 209
State K 903 150 198 State K 1602 171 005 State K 2005 151 212
State K 904 150 201 State K 1603 171 009 State K 2006 151 215
State K 905 150 204 State K 1604 171 013 State K 2007 151 218
State K 906 150 207 State K 1605 171 017 State K 2008 151 221
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\I.O. Status Monitor
Disabled
LED: State H 2 (…16) -
Enabled
OP Fig.
See table below for status addresses. Read only
113
The state of the LED indicators is displayed as follows:
Disabled: The LED indicator is not energized
Enabled: The LED indicator is energized
Menu Text Address Menu Text Address Menu Text Address
State H 2 085 000 State H 7 085 015 State H 12 085 030
State H 3 085 003 State H 8 085 018 State H 13 085 033
State H 4 085 006 State H 9 085 021 State H 14 085 036
State H 5 085 009 State H 10 085 024 State H 15 085 039
State H 6 085 012 State H 11 085 027 State H 16 085 042
Measurement Range
Menu Text Step Size
Min. Max.
MR
Measurements + Tests\Measurements\Log. State Signals
HMI: Illumination on EXT No Yes -
037 101 Read only
Binary input/other logic is asserting switch-on of the LCD backlight.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
COMM1: Command Block. EXT No Yes -
003 173 Read only OP Fig. 87
Binary input/other logic is asserting a block on all command (remote) operations for COMM
port 1. Prevents remote control via COMM1.
COMM1: Sig/meas. Block EXT No Yes -
OP Fig. 88,
037 074 Read only
89, 90
Binary input/other logic is asserting a block on all transmission of data/measurements via
COMM1.
COMM1: Command Blocking No Yes -
003 174 Read only OP Fig. 87
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
COMM1: Sig/meas. val.Block No Yes -
OP Fig. 88,
037 075 Read only
89, 90
The two addresses above indicate the overall status of read (signal/measured value) and
write (command) permission via protocol, for COMM1.
COMM1: IEC 870-5-103 No Yes -
003 219 Read only OP Fig. 88
COMM1: IEC 870-5-101 No Yes -
003 218 Read only OP Fig. 89
COMM1: IEC 870-5,ILS No Yes -
003 221 Read only OP Fig. 90
COMM1: MODBUS No Yes -
003 223 Read only OP Fig. 91
COMM1: DNP3 No Yes -
003 230 Read only OP Fig. 92
COMM1: COURIER No Yes -
103 041 Read only OP Fig. 93
Addresses to indicate the protocol in operation for COMMS port 1.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
IRIGB: Enabled No Yes -
023 201 Read only OP Fig. 97
IRIGB: Synchron. Ready No Yes -
023 202 Read only OP Fig. 97
IRIG-B time synchronizing signals are being received correctly.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
RTDmA: Enabled No Yes -
035 008 Read only OP Fig. 99
RTDmA: PT100 Faulty No Yes -
OP Fig.
040 190 Read only
104
RTDmA: Overload 20mA Input No Yes -
OP Fig.
040 191 Read only
102
MR
RTDmA: Open Circ. 20mA inp. No Yes -
OP Fig.
040 192 Read only
102
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OUTP: Block Outp.Rel. EXT No Yes -
OP Fig.
040 014 Read only
105
Binary input/other logic is asserting a block on operation of output contacts possibly as
required for a commissioning/test operation.
OUTP: Reset Latch. EXT No Yes -
OP Fig.
040 015 Read only
105
Binary input/other logic is acting to reset latched output contacts.
OUTP: Outp. Relays Blocked No Yes -
OP Fig.
021 015 Read only
105
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
OUTP: Latching Reset No Yes -
OP Fig.
040 088 Read only
105
The two addresses above indicate the global status of relay contact blocking, and the
command to reset latched contacts.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
mA_OP: Enabled No Yes -
OP Fig.
037 102 Read only
107
mA_OP: Outp. Enabled EXT No Yes -
OP Fig.
036 085 Read only
108
mA_OP: Reset Output EXT No Yes -
OP Fig.
036 087 Read only
109
mA_OP: Output Reset No Yes -
OP Fig.
037 117 Read only
MR 109
mA_OP: Valid BCD Value No Yes -
OP Fig.
037 050 Read only
110
mA_OP: 1-digit Bit 0 (BCD) No Yes -
OP Fig.
037 051 Read only
110
mA_OP: 1-digit Bit 1 (BCD) No Yes -
OP Fig.
037 052 Read only
110
mA_OP: 1-digit Bit 2 (BCD) No Yes -
OP Fig.
037 053 Read only
110
mA_OP: 1-digit Bit 3 (BCD) No Yes -
OP Fig.
037 054 Read only
110
mA_OP: 10-digit Bit 0 (BCD) No Yes -
OP Fig.
037 055 Read only
110
mA_OP: 10-digit Bit 1 (BCD) No Yes -
OP Fig.
037 056 Read only
110
mA_OP: 10-digit Bit 2 (BCD) No Yes -
OP Fig.
037 057 Read only
110
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
mA_OP: 10-digit Bit 3 (BCD) No Yes -
OP Fig.
037 058 Read only
110
mA_OP: 100-dig. Bit 0 (BCD) No Yes -
OP Fig.
037 059 Read only
110
mA_OP: 100-dig. Bit 1 (BCD) No Yes -
OP Fig.
037 060 Read only
110
Previous addresses indicate the current loop output of units, tens and hundreds for
binary-coded decimal.
mA_OP: Value A-1 Valid No Yes -
OP Fig.
069 014 Read only
112
mA_OP: Value A-2 Valid No Yes -
OP Fig.
069 015 Read only
112
mA_OP: Value A-1 Output No Yes -
OP Fig.
037 118 Read only
112
mA_OP: Value A-2 Output No Yes -
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
MAIN: Trip sig.REF1 & REF2 No Yes -
036 174 Read only OP Fig. 17
MAIN: Trip sig.REF2 & REF3 No Yes -
036 175 Read only OP Fig. 17
MAIN: Trip sig.REF1 & REF3 No Yes -
036 176 Read only OP Fig. 17
Trip signals for application of REF on auto-transformers.
MAIN: Phase Reversal Activ No Yes -
036 220 Read only
Indicates whether phase swapping for CTs is in force.
No
MAIN: Enable Protect. EXT Yes -
Not Configured
OP Fig.
003 027 Read only
129
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
No
MAIN: Disable Protect. EXT Yes -
Not Configured
OP Fig.
003 026 Read only
129
MAIN: Blocking 1 EXT No Yes -
OP Fig.
040 060 Read only
131
MAIN: Blocking 2 EXT No Yes -
OP Fig.
040 061 Read only
131
MAIN: Blocking 3 EXT No Yes -
OP Fig.
040 116 Read only
131
MAIN: Blocking 4 EXT No Yes -
OP Fig.
040 117 Read only
131
MAIN: Reset Latch.Trip EXT No Yes -
OP Fig.
040 138 Read only
135
MAIN: Trip Cmd. Block. EXT No Yes -
OP Fig.
MR 036 045 Read only
135
MAIN: M.c.b. Trip V EXT No Yes -
OP Fig. 47,
004 061 Read only
53
An auxiliary contact from an external MCB indicates that the VT input may be unreliable.
MAIN: Switch Dyn Param.EXT No Yes -
OP Fig.
036 033 Read only
130
MAIN: Man. Trip Cmd. EXT No Yes -
OP Fig.
037 018 Read only
135
MAIN: Test Mode EXT No Yes -
OP Fig.
037 070 Read only
141
Binary input/other logic is being used to signal via IEC-60870-5-103 protocol that the relay
is undergoing some kind of testing operation, and the remote operator’s need to be
notified.
MAIN: Reset Indicat. EXT No Yes -
OP Fig.
065 001 Read only
140
MAIN: Min-Pulse Clock EXT No Yes -
OP Fig.
060 060 Read only
138
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Prot. Ext. Enabled No Yes -
OP Fig.
003 028 Read only
129
MAIN: Prot. Ext. Disabled No Yes -
OP Fig.
038 046 Read only
129
MAIN: Protect. Not Ready No Yes -
OP Fig.
004 060 Read only
132
MAIN: Test Mode No Yes -
OP Fig.
037 071 Read only
141
MAIN: Blocked/Faulty No Yes -
OP Fig.
004 065 Read only
132
MAIN: CT Fail Alarm No Yes -
036 155 Read only
MAIN: Trip Cmd. Blocked No Yes -
OP Fig.
021 013 Read only
135
MAIN: Latch. Trip c Reset No Yes -
OP Fig. MR
040 139 Read only
135
MAIN: Manual Trip Signal No Yes -
OP Fig.
034 017 Read only
135
MAIN: Gen Trip Signal No Yes -
OP Fig.
036 251 Read only
135
MAIN: Gen Trip Signal 1 No Yes -
OP Fig.
036 005 Read only
135
MAIN: Gen Trip Signal 2 No Yes -
OP Fig.
036 023 Read only
135
MAIN: Gen Trip Signal 3 No Yes -
OP Fig.
036 108 Read only
135
MAIN: Gen Trip Signal 4 No Yes -
OP Fig.
036 109 Read only
135
MAIN: Gen. Trip Command 1 No Yes -
OP Fig.
036 071 Read only
135
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
MAIN: Gen. Trip Command 2 No Yes -
OP Fig.
036 022 Read only
135
MAIN: Gen. Trip Command 3 No Yes -
OP Fig.
036 113 Read only
135
MAIN: Gen. Trip Command 4 No Yes -
OP Fig.
036 114 Read only
135
MAIN: General Start No Yes -
OP Fig.
036 000 Read only
133
MAIN: Dynam. Setts. Active No Yes -
OP Fig.
040 090 Read only
130
MAIN: Disabled No Yes -
060 000 Read only
MAIN: Disabled No Yes -
061 000 Read only
Unused.
MAIN: Auxiliary Address No Yes -
MR
038 000 Read only
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
GROUP: Control Via User EXT No Yes -
OP Fig.
036 101 Read only
142
No
GROUP: Activate Grp 1 EXT Yes -
Not Configured
OP Fig.
065 002 Read only
142
No
GROUP: Activate Grp 2 EXT Yes -
Not Configured
OP Fig.
065 003 Read only
142
No
GROUP: Activate Grp 3 EXT Yes -
Not Configured
OP Fig.
065 004 Read only
142
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
No
GROUP: Activate Grp 4 EXT Yes -
Not Configured
OP Fig.
065 005 Read only
142
GROUP: Control Via user No Yes -
OP Fig.
036 102 Read only
142
No Set Grp Selected
Setting Group SG1
GROUP: Ext.sel. Settg. Grp Setting Group SG2 -
Setting Group SG3
Setting Group SG4
OP Fig.
003 061 Read only
142
GROUP: Grp1 Activated Ext. No Yes -
OP Fig.
036 094 Read only
142
GROUP: Grp2 Activated Ext. No Yes -
OP Fig.
036 095 Read only
142
GROUP: Grp3 Activated Ext. No Yes -
OP Fig.
036 096 Read only
142 MR
GROUP: Grp4 Activated Ext. No Yes -
OP Fig.
036 097 Read only
142
Setting Group SG1
Setting Group SG2
GROUP: Actual Setting Group -
Setting Group SG3
Setting Group SG4
OP Fig.
003 062 Read only
142
GROUP: Group 1 Active No Yes -
OP Fig.
036 090 Read only
142
GROUP: Group 2 Active No Yes -
OP Fig.
036 091 Read only
142
GROUP: Group 3 Active No Yes -
OP Fig.
036 092 Read only
142
GROUP: Group 4 Active No Yes -
OP Fig.
036 093 Read only
142
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
CHECK: Faulty DSP No Yes -
093 127 Read only
CHECK: Invalid SW Vers. DSP No Yes -
093 128 Read only
CHECK: Alarm (LED) No Yes -
OP Fig.
036 070 Read only
143
Alarm configured for LED H3.
CHECK: Alarm (Relay) No Yes -
OP Fig.
036 100 Read only
143
Alarm configured for an output relay.
CHECK: Warm Restart Exec. No Yes -
041 202 Read only
CHECK: Cold Restart Exec. No Yes -
041 201 Read only
CHECK: Cold Restart No Yes -
MR 093 024 Read only
A cold restart has been carried out on account of a checksum error in the memory
(NOVRAM).
CHECK: Cold Rest /SW Update No Yes -
093 025 Read only
A cold restart has been carried out following a software update.
CHECK: Blocking /HW Failure No Yes -
090 019 Read only
Supplementary warning that this device is blocked.
CHECK: Relay Kxx Faulty No Yes -
041 200 Read only
Multiple signal: output relay defective.
CHECK: Hardware Clock Fail No Yes -
093 040 Read only
The hardware clock has failed.
CHECK: Battery Failure No Yes -
090 010 Read only
Battery voltage too low. Replace battery inside power supply module “V”.
CHECK: Invalid SW DnLoaded No Yes -
096 121 Read only
Wrong or invalid software has been downloaded.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: +15V Supply Faulty No Yes -
093 081 Read only
The + 15 V internal supply voltage has dropped below a minimum value.
CHECK: +24V Supply Faulty No Yes -
093 082 Read only
The +24 V internal supply voltage has dropped below a minimum value.
CHECK: -15V Supply Faulty No Yes -
093 080 Read only
The -15 V internal supply voltage has dropped below a minimum value.
CHECK: Wrong Module Slot 1 (…21) No Yes -
See table below for measurement
Read only
addresses.
Module in wrong slot.
Setting Address Setting Address Setting Address
Wrong Module Slot 1 096 100 Wrong Module Slot 8 096 107 Wrong Module Slot 15 096 114
Wrong Module Slot 2 096 101 Wrong Module Slot 9 096 108 Wrong Module Slot 16 096 115
Wrong Module Slot 3 096 102 Wrong Module Slot 10 096 109 Wrong Module Slot 17 096 116
Wrong Module Slot 4 096 103 Wrong Module Slot 11 096 110 Wrong Module Slot 18 096 117
Wrong Module Slot 5 096 104 Wrong Module Slot 12 096 111 Wrong Module Slot 19 096 118
Wrong Module Slot 6 096 105 Wrong Module Slot 13 096 112 Wrong Module Slot 20 096 119
MR
Wrong Module Slot 7 096 106 Wrong Module Slot 14 096 113 Wrong Module Slot 21 096 120
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Module Y DPR Faulty No Yes -
093 110 Read only
The checksum feature of analog I/O module Y has detected a fault in the data transmission
of the Dual-Port-RAM.
CHECK: Module Y RAM Faulty No Yes -
093 111 Read only
Fault in the program or data memory of the analog I/O module.
CHECK: Error K 701 (…2008) No Yes -
See table below for measurement
Read only
addresses.
Self checking error indication of output relays. Output relay K xxx defective.
Setting Address Setting Address Setting Address
Error K 701 097 078 Error K 908 097 101 Error K 1607 097 156
Error K 702 097 079 Error K 1001 097 102 Error K 1608 097 157
Error K 703 097 080 Error K 1002 097 103 Error K 1801 097 166
Error K 704 097 081 Error K 1003 097 104 Error K 1802 097 167
Error K 705 097 082 Error K 1004 097 105 Error K 1803 097 168
Error K 706 097 083 Error K 1005 097 106 Error K 1804 097 169
Error K 707 097 084 Error K 1006 097 107 Error K 1805 097 170
Error K 708 097 085 Error K 1007 097 108 Error K 1806 097 171
MR Error K 801 097 086 Error K 1008 097 109 Error K 2001 097 182
Error K 802 097 087 Error K 1201 097 118 Error K 2002 097 183
Error K 901 097 094 Error K 1202 097 119 Error K 2003 097 184
Error K 902 097 095 Error K 1601 097 150 Error K 2004 097 185
Error K 903 097 096 Error K 1602 097 151 Error K 2005 097 186
Error K 904 097 097 Error K 1603 097 152 Error K 2006 097 187
Error K 905 097 098 Error K 1604 097 153 Error K 2007 097 188
Error K 906 097 099 Error K 1605 097 154 Error K 2008 097 189
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Protection Failure No Yes -
090 021 Read only
Watchdog is monitoring the periodic start of protection routine. It has detected an error.
CHECK: Checksum Sett Error No Yes -
090 003 Read only
A checksum error involving the parameters in the memory (NOVRAM) has been detected.
CHECK: Clock Sync. Error No Yes -
093 041 Read only
In 10 consecutive clock synchronization telegrams, the difference between the time of day
given in the telegram and that of the hardware clock is greater than 10 ms.
CHECK: Interm Volt Fail RAM No Yes -
093 026 Read only
Faulty test pattern in the RAM. This can occur, for example, if the processor module or the
power supply module is removed from the bus module (digital). This fault is only detected
during device startup. After the fault is detected, the software initializes the RAM. This
means that all records are deleted.
CHECK: Overflow MT_RC No Yes -
OP Fig.
090 012 Read only
145
Last entry in the monitoring signal memory in the event of overflow.
CHECK: Semaph. MT_RC Block. No Yes - MR
093 015 Read only
Software overload.
CHECK: Inval. SW vers.comm. No Yes -
093 075 Read only
Incorrect or invalid communication software has been downloaded.
CHECK: Invalid SW Vers. Y No Yes -
093 113 Read only
Incorrect or invalid software for analog I/O module has been downloaded.
CHECK: Time-out Module Y No Yes -
093 112 Read only
CHECK: M.c.b. Trip V No Yes -
098 000 Read only
The voltage transformer m.c.b. has tripped.
CHECK: CT Fail Alarm No Yes -
091 018 Read only
CHECK: CT Fail Alarm, end a No Yes -
091 026 Read only
CHECK: CT Fail Alarm, end b No Yes -
091 027 Read only
CHECK: CT Fail Alarm, end c No Yes -
091 028 Read only
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: CT Fail Alarm, end d No Yes -
091 029 Read only
CHECK: Invalid Charact. V/f No Yes -
091 011 Read only
CHECK: Invalid Scaling A-1 No Yes -
OP Fig.
093 114 Read only
112
CHECK: Invalid Scaling A-2 No Yes -
OP Fig.
093 115 Read only
112
An invalid characteristic has been set for one of the analog output channels of analog I/O
module Y.
CHECK: Invalid Scaling IDC No Yes -
OP Fig.
093 116 Read only
102
An invalid characteristic has been set for the analog input channel of analog I/O module Y.
CHECK: PT100 open Circuit No Yes -
OP Fig.
098 024 Read only
104
The P63x has detected an open circuit in the connection of the resistance thermometer.
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Output 30 No Yes -
098 053 Read only
CHECK: Output 31 No Yes -
098 055 Read only
CHECK: Output 32 No Yes -
098 057 Read only
CHECK: Output 30 (t) No Yes -
098 054 Read only
CHECK: Output 31 (t) No Yes -
098 056 Read only
CHECK: Output 32 (t) No Yes -
098 058 Read only
CHECK: Matching Fail. end a No Yes -
091 000 Read only OP Fig. 2
CHECK: Matching Fail. end b No Yes -
091 001 Read only OP Fig. 2
CHECK: Matching Fail. end c No Yes -
091 002 Read only OP Fig. 2
CHECK: Matching Fail. end d No Yes -
MR
091 017 Read only OP Fig. 2
The calculated amplitude matching factor of the differential protection function is outside
the permissible range.
CHECK: Ratio mtch.Fact.inv. No Yes -
091 004 Read only OP Fig. 2
The ratio of the amplitude matching factors of the differential protection function is above
the permissible range.
CHECK: 2nd Match.Fact. inv. No Yes -
091 006 Read only OP Fig. 2
The medium amplitude matching factor of the differential protection function is lower than
permitted.
CHECK: Inv.Range Iref REF_1 No Yes -
091 105 Read only OP Fig. 15
CHECK: Inv.Range Iref REF_2 No Yes -
091 115 Read only OP Fig. 15
CHECK: Inv.Range Iref REF_3 No Yes -
091 125 Read only OP Fig. 15
The reference current determined by the P63x for restricted earth fault protection is not
within the permissible range.
CHECK: Match.f. kam,N REF_1 No Yes -
091 101 Read only OP Fig. 15
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Match.f. kam,N REF_2 No Yes -
091 111 Read only OP Fig. 15
CHECK: Match.f. kam,N REF_3 No Yes -
091 121 Read only OP Fig. 15
The calculated amplitude matching factor of the restricted earth fault protection function is
outside the permissible range.
CHECK: Match.f. kam,Y REF_1 No Yes -
091 102 Read only OP Fig. 15
CHECK: Match.f. kam,Y REF_2 No Yes -
091 112 Read only OP Fig. 15
CHECK: Match.f. kam,Y REF_3 No Yes -
091 122 Read only OP Fig. 15
The calculated amplitude matching factor of the restricted earth fault protection function is
outside the permissible range.
CHECK: Rat Mtch f inv REF_1 No Yes -
091 103 Read only OP Fig. 15
CHECK: Rat Mtch f inv REF_2 No Yes -
091 113 Read only OP Fig. 15
CHECK: Rat Mtch f inv REF_3 No Yes -
MR 091 123 Read only OP Fig. 15
The ratio of the amplitude matching factors of the restricted earth fault protection function is
above the permissible range.
CHECK: Min Mtch f inv REF_1 No Yes -
091 104 Read only OP Fig. 15
CHECK: Min Mtch f inv REF_2 No Yes -
091 114 Read only OP Fig. 15
CHECK: Min Mtch f inv REF_3 No Yes -
091 124 Read only OP Fig. 15
The lowest amplitude matching factor of the restricted earth fault protection function is
lower than permitted.
CHECK: CTA Error THRM1 No Yes -
098 036 Read only OP Fig. 44
CHECK: CTA Error THRM2 No Yes -
098 037 Read only OP Fig. 44
Faulty coolant temperature acquisition.
CHECK: Setting Error THRM1 No Yes -
098 038 Read only OP Fig. 45
CHECK: Setting Error THRM2 No Yes -
098 039 Read only OP Fig. 45
The maximum permissible object temperature and the maximum permissible coolant
temperature have been set to the same value. This setting is not valid.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
CHECK: Inv Inp f Clock Sync No Yes -
093 120 Read only
Function MAIN: Min-Pulse Clock EXT has been configured to a binary input of analog I/O
module Y.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OL_RC: Record. in Progress No Yes -
OP Fig.
035 003 Read only
148
OL_RC: Overl. Mem. Overflow No Yes -
OP Fig.
035 007 Read only
149
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
OSCIL: Trigger EXT No Yes - MR
OP Fig.
036 089 Read only
155
OSCIL: Trigger No Yes -
OP Fig.
037 076 Read only
155
OSCIL: Id> Triggered No Yes -
OP Fig.
035 018 Read only
155
OSCIL: IR> Triggered No Yes -
OP Fig.
035 019 Read only
155
OSCIL: Record. in Progress No Yes -
OP Fig.
035 000 Read only
155
OSCIL: System Disturb. Runn No Yes -
OP Fig.
035 004 Read only
155
OSCIL: Fault Mem. Overflow No Yes -
OP Fig.
035 001 Read only
156
OSCIL: Faulty Time Tag No Yes -
OP Fig.
035 002 Read only
149
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
DIFF: Enabled No Yes -
041 210 Read only OP Fig. 1
DIFF: Starting No Yes -
041 106 Read only
Instantaneous start indication of the differential protection.
DIFF: Meas System 1 Trigg. No Yes -
041 124 Read only OP Fig. 9
DIFF: Meas System 2 Trigg. No Yes -
041 125 Read only OP Fig. 9
DIFF: Meas System 3 Trigg. No Yes -
041 126 Read only OP Fig. 9
DIFF: Id>> Triggered No Yes -
041 221 Read only OP Fig. 9
DIFF: Id>>> Triggered No Yes -
041 222 Read only OP Fig. 9
DIFF: Harm. Block 1 Trigg. No Yes -
MR 041 118 Read only OP Fig. 10
DIFF: Harm. Block 2 Trigg. No Yes -
041 119 Read only OP Fig. 10
DIFF: Harm. Block 3 Trigg. No Yes -
041 120 Read only OP Fig. 10
DIFF: Overflux.bl.1 Trigg. No Yes -
041 121 Read only OP Fig. 12
DIFF: Overflux.bl.2 Trigg. No Yes -
041 122 Read only OP Fig. 12
DIFF: Overflux.bl.3 Trigg. No Yes -
041 123 Read only OP Fig. 12
DIFF: Sat.Discr. 1 Trigg. No Yes -
041 115 Read only OP Fig. 11
DIFF: Sat.Discr. 2 Trigg. No Yes -
041 116 Read only OP Fig. 11
DIFF: Sat.Discr. 3 Trigg. No Yes -
041 117 Read only OP Fig. 11
DIFF: Trip Signal No Yes -
041 075 Read only OP Fig. 9
DIFF: Trip Signal 1 No Yes -
041 002 Read only OP Fig. 9
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
DIFF: Trip Signal 2 No Yes -
041 003 Read only OP Fig. 9
DIFF: Trip Signal 3 No Yes -
041 004 Read only OP Fig. 9
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
REF_1: Enabled No Yes -
041 132 Read only OP Fig. 14
REF_2: Enabled No Yes -
041 133 Read only OP Fig. 14
REF_3: Enabled No Yes -
041 134 Read only OP Fig. 14
REF_1: Trip Signal No Yes -
041 005 Read only OP Fig. 17
REF_2: Trip Signal No Yes -
OP Fig.
041 016 Read only
133 MR
REF_3: Trip Signal No Yes -
OP Fig.
041 067 Read only
133
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
DTOC1: Block. tI> EXT No Yes -
035 120 Read only OP Fig. 23
DTOC2: Block. tI> EXT No Yes -
035 150 Read only OP Fig. 23
DTOC3: Block. tI> EXT No Yes -
035 237 Read only OP Fig. 23
DTOC1: Block. tI>> EXT No Yes -
035 121 Read only OP Fig. 23
DTOC2: Block. tI>> EXT No Yes -
035 151 Read only OP Fig. 23
DTOC3: Block. tI>> EXT No Yes -
035 238 Read only OP Fig. 23
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
DTOC1: Block. tI>>> EXT No Yes -
035 122 Read only OP Fig. 23
DTOC2: Block. tI>>> EXT No Yes -
035 229 Read only OP Fig. 23
DTOC3: Block. tI>>> EXT No Yes -
035 239 Read only OP Fig. 23
DTOC1: Block. tI2> EXT No Yes -
036 141 Read only OP Fig. 24
DTOC2: Block. tI2> EXT No Yes -
036 161 Read only OP Fig. 24
DTOC3: Block. tI2> EXT No Yes -
036 181 Read only OP Fig. 24
DTOC1: Block. tI2>> EXT No Yes -
036 142 Read only OP Fig. 24
DTOC2: Block. tI2>> EXT No Yes -
036 162 Read only OP Fig. 24
DTOC3: Block. tI2>> EXT No Yes -
036 182 Read only OP Fig. 24
Measurement Range
Menu Text Step Size
Min. Max.
DTOC3: Block. tIN>>> EXT No Yes -
035 242 Read only OP Fig. 25
DTOC1: Enabled No Yes -
035 102 Read only OP Fig. 22
DTOC2: Enabled No Yes -
035 132 Read only OP Fig. 22
DTOC3: Enabled No Yes -
035 136 Read only OP Fig. 22
DTOC1: General Start No Yes -
035 128 Read only OP Fig. 26
DTOC2: General Start No Yes -
035 234 Read only OP Fig. 26
DTOC3: General Start No Yes -
035 244 Read only OP Fig. 26
DTOC1: tGS Elapsed No Yes -
035 129 Read only OP Fig. 26
DTOC2: tGS Elapsed No Yes -
035 245 Read only OP Fig. 26
DTOC3: tGS Elapsed No Yes -
MR
035 250 Read only OP Fig. 26
DTOC1: Starting A No Yes -
035 104 Read only OP Fig. 23
DTOC2: Starting A No Yes -
035 134 Read only OP Fig. 23
DTOC3: Starting A No Yes -
035 180 Read only OP Fig. 23
DTOC1: Starting B No Yes -
035 105 Read only OP Fig. 23
DTOC2: Starting B No Yes -
035 135 Read only OP Fig. 23
DTOC3: Starting B No Yes -
035 185 Read only OP Fig. 23
DTOC1: Starting C No Yes -
035 106 Read only OP Fig. 23
DTOC2: Starting C No Yes -
035 141 Read only OP Fig. 23
DTOC3: Starting C No Yes -
035 186 Read only OP Fig. 23
DTOC1: Starting N No Yes -
035 107 Read only OP Fig. 25
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
DTOC2: Starting N No Yes -
035 146 Read only OP Fig. 25
DTOC3: Starting N No Yes -
035 187 Read only OP Fig. 25
DTOC1: Starting I> No Yes -
035 108 Read only OP Fig. 23
DTOC2: Starting I> No Yes -
035 138 Read only OP Fig. 23
DTOC3: Starting I> No Yes -
035 188 Read only OP Fig. 23
DTOC1: Starting I>> No Yes -
035 109 Read only OP Fig. 23
DTOC2: Starting I>> No Yes -
035 139 Read only OP Fig. 23
DTOC3: Starting I>> No Yes -
035 189 Read only OP Fig. 23
DTOC1: Starting I>>> No Yes -
035 110 Read only OP Fig. 23
Measurement Range
Menu Text Step Size
Min. Max.
DTOC1: Starting I2 No Yes -
036 144 Read only OP Fig. 24
DTOC2: Starting I2 No Yes -
036 164 Read only OP Fig. 24
DTOC3: Starting I2 No Yes -
036 184 Read only OP Fig. 24
DTOC1: Starting I2> No Yes -
036 145 Read only OP Fig. 24
DTOC2: Starting I2> No Yes -
036 165 Read only OP Fig. 24
DTOC3: Starting I2> No Yes -
036 185 Read only OP Fig. 24
DTOC1: Starting I2>> No Yes -
036 146 Read only OP Fig. 24
DTOC2: Starting I2>> No Yes -
036 166 Read only OP Fig. 24
DTOC3: Starting I2>> No Yes -
036 186 Read only OP Fig. 24
DTOC1: Starting I2>>> No Yes -
MR
036 147 Read only OP Fig. 24
DTOC2: Starting I2>>> No Yes -
036 167 Read only OP Fig. 24
DTOC3: Starting I2>>> No Yes -
036 187 Read only OP Fig. 24
DTOC1: tI2> Elapsed No Yes -
036 148 Read only OP Fig. 24
DTOC2: tI2> Elapsed No Yes -
036 168 Read only OP Fig. 24
DTOC3: tI2> Elapsed No Yes -
036 188 Read only OP Fig. 24
DTOC1: tI2>> Elapsed No Yes -
036 149 Read only OP Fig. 24
DTOC2: tI2>> Elapsed No Yes -
036 169 Read only OP Fig. 24
DTOC3: tI2>> Elapsed No Yes -
036 189 Read only OP Fig. 24
DTOC1: tI2>>> Elapsed No Yes -
036 150 Read only OP Fig. 24
DTOC2: tI2>>> Elapsed No Yes -
036 170 Read only OP Fig. 24
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
DTOC3: tI2>>> Elapsed No Yes -
036 190 Read only OP Fig. 24
DTOC1: Trip Signal tI2> No Yes -
036 151 Read only OP Fig. 24
DTOC2: Trip Signal tI2> No Yes -
036 171 Read only OP Fig. 24
DTOC3: Trip Signal tI2> No Yes -
036 191 Read only OP Fig. 24
DTOC1: Trip Signal tI2>> No Yes -
036 152 Read only OP Fig. 24
DTOC2: Trip Signal tI2>> No Yes -
036 172 Read only OP Fig. 24
DTOC3: Trip Signal tI2>> No Yes -
036 192 Read only OP Fig. 24
DTOC1: Trip Signal tI2>>> No Yes -
036 153 Read only OP Fig. 24
DTOC2: Trip Signal tI2>>> No Yes -
036 173 Read only OP Fig. 24
Measurement Range
Menu Text Step Size
Min. Max.
DTOC2: tIN> Elapsed No Yes -
035 159 Read only OP Fig. 25
DTOC3: tIN> Elapsed No Yes -
035 209 Read only OP Fig. 25
DTOC1: tIN>> Elapsed No Yes -
035 118 Read only OP Fig. 25
DTOC2: tIN>> Elapsed No Yes -
035 225 Read only OP Fig. 25
DTOC3: tIN>> Elapsed No Yes -
035 235 Read only OP Fig. 25
DTOC1: tIN>>> Elapsed No Yes -
035 119 Read only OP Fig. 25
DTOC2: tIN>>> Elapsed No Yes -
035 226 Read only OP Fig. 25
DTOC3: tIN>>> Elapsed No Yes -
035 236 Read only OP Fig. 25
DTOC1: Trip Signal tIN> No Yes -
035 126 Read only OP Fig. 25
DTOC2: Trip Signal tIN> No Yes -
MR
035 233 Read only OP Fig. 25
DTOC3: Trip Signal tIN> No Yes -
035 243 Read only OP Fig. 25
DTOC1: Trip Signal tIN>> No Yes -
035 130 Read only OP Fig. 25
DTOC2: Trip Signal tIN>> No Yes -
035 246 Read only OP Fig. 25
DTOC3: Trip Signal tIN>> No Yes -
035 251 Read only OP Fig. 25
DTOC1: Trip Signal tIN>>> No Yes -
035 131 Read only OP Fig. 25
DTOC2: Trip Signal tIN>>> No Yes -
035 247 Read only OP Fig. 25
DTOC3: Trip Signal tIN>>> No Yes -
035 252 Read only OP Fig. 25
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
IDMT1: Block. tIref,Ph> EXT No Yes -
038 114 Read only OP Fig. 34
IDMT2: Block. tIref,Ph> EXT No Yes -
038 134 Read only OP Fig. 34
IDMT3: Block. tIref,Ph> EXT No Yes -
038 154 Read only OP Fig. 34
IDMT1: Block. tIref,I2> EXT No Yes -
038 178 Read only OP Fig. 35
IDMT2: Block. tIref,I2> EXT No Yes -
038 188 Read only OP Fig. 35
IDMT3: Block. tIref,I2> EXT No Yes -
038 198 Read only OP Fig. 35
IDMT1: Block. tIref,N> EXT No Yes -
038 124 Read only OP Fig. 36
IDMT2: Block. tIref,N> EXT No Yes -
038 144 Read only OP Fig. 36
MR IDMT3: Block. tIref,N> EXT No Yes -
038 164 Read only OP Fig. 36
IDMT1: Enabled No Yes -
038 125 Read only OP Fig. 29
IDMT2: Enabled No Yes -
038 145 Read only OP Fig. 29
IDMT3: Enabled No Yes -
038 165 Read only OP Fig. 29
IDMT1: General Start No Yes -
038 115 Read only OP Fig. 26
IDMT2: General Start No Yes -
038 135 Read only OP Fig. 26
IDMT3: General Start No Yes -
038 155 Read only OP Fig. 26
IDMT1: tGS Elapsed No Yes -
038 116 Read only OP Fig. 26
IDMT2: tGS Elapsed No Yes -
038 136 Read only OP Fig. 26
IDMT3: tGS Elapsed No Yes -
038 156 Read only OP Fig. 26
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
IDMT1: Starting Iref,Ph> No Yes -
038 110 Read only OP Fig. 34
IDMT2: Starting Iref,Ph> No Yes -
038 130 Read only OP Fig. 34
IDMT3: Starting Iref,Ph> No Yes -
038 150 Read only OP Fig. 34
IDMT1: Starting Iref,A> No Yes -
038 117 Read only OP Fig. 34
IDMT2: Starting Iref,A> No Yes -
038 137 Read only OP Fig. 34
IDMT3: Starting Iref,A> No Yes -
038 157 Read only OP Fig. 34
IDMT1: Starting Iref,B> No Yes -
038 118 Read only OP Fig. 34
IDMT2: Starting Iref,B> No Yes -
038 138 Read only OP Fig. 34
IDMT3: Starting Iref,B> No Yes -
038 158 Read only OP Fig. 34
IDMT1: Starting Iref,C> No Yes -
MR
038 119 Read only OP Fig. 34
IDMT2: Starting Iref,C> No Yes -
038 139 Read only OP Fig. 34
IDMT3: Starting Iref,C> No Yes -
038 159 Read only OP Fig. 34
IDMT1: tIref, Ph> Elapsed No Yes -
038 111 Read only OP Fig. 34
IDMT2: tIref, Ph> Elapsed No Yes -
038 131 Read only OP Fig. 34
IDMT3: tIref, Ph> Elapsed No Yes -
038 151 Read only OP Fig. 34
IDMT1: Hold Time Ph Running No Yes -
038 112 Read only OP Fig. 34
IDMT2: Hold Time Ph Running No Yes -
038 132 Read only OP Fig. 34
IDMT3: Hold Time Ph Running No Yes -
038 152 Read only OP Fig. 34
IDMT1: Memory Ph Clear No Yes -
038 113 Read only OP Fig. 34
IDMT2: Memory Ph Clear No Yes -
038 133 Read only OP Fig. 34
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
IDMT3: Memory Ph Clear No Yes -
038 153 Read only OP Fig. 34
IDMT1: Starting Iref, I2> No Yes -
038 173 Read only OP Fig. 35
IDMT2: Starting Iref, I2> No Yes -
038 183 Read only OP Fig. 35
IDMT3: Starting Iref, I2> No Yes -
038 193 Read only OP Fig. 35
IDMT1: tIref, I2> Elapsed No Yes -
038 174 Read only OP Fig. 35
IDMT2: tIref, I2> Elapsed No Yes -
038 184 Read only OP Fig. 35
IDMT3: tIref, I2> Elapsed No Yes -
038 194 Read only OP Fig. 35
IDMT1: Trip Sig. tIref, I2> No Yes -
038 177 Read only OP Fig. 35
IDMT2: Trip Sig. tIref, I2> No Yes -
038 187 Read only OP Fig. 35
Measurement Range
Menu Text Step Size
Min. Max.
IDMT2: tIref,N> Elapsed No Yes -
038 141 Read only OP Fig. 36
IDMT3: tIref,N> Elapsed No Yes -
038 161 Read only OP Fig. 36
IDMT1: Trip Signal tIref,N> No Yes -
038 126 Read only OP Fig. 36
IDMT2: Trip Signal tIref,N> No Yes -
038 146 Read only OP Fig. 36
IDMT3: Trip Signal tIref,N> No Yes -
038 166 Read only OP Fig. 36
IDMT1: Hold Time N Running No Yes -
038 122 Read only OP Fig. 36
IDMT2: Hold Time N Running No Yes -
038 142 Read only OP Fig. 36
IDMT3: Hold Time N Running No Yes -
038 162 Read only OP Fig. 36
IDMT1: Memory N Clear No Yes -
038 123 Read only OP Fig. 36
IDMT2: Memory N Clear No Yes -
MR
038 143 Read only OP Fig. 36
IDMT3: Memory N Clear No Yes -
038 163 Read only OP Fig. 36
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
THRM1: Replica Block EXT No Yes -
039 150 Read only OP Fig. 45
THRM2: Replica Block EXT No Yes -
039 170 Read only OP Fig. 45
THRM1: CTA Error EXT No Yes -
039 152 Read only OP Fig. 44
THRM2: CTA Error EXT No Yes -
039 172 Read only OP Fig. 44
THRM1: Reset Replica EXT No Yes -
039 122 Read only OP Fig. 46
THRM2: Reset Replica EXT No Yes -
039 182 Read only OP Fig. 46
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
THRM1: Enabled No Yes -
039 129 Read only OP Fig. 41
THRM2: Enabled No Yes -
039 189 Read only OP Fig. 41
THRM1: Not Ready No Yes -
039 154 Read only OP Fig. 41
THRM2: Not Ready No Yes -
039 174 Read only OP Fig. 41
THRM1: Reset Replica No Yes -
039 125 Read only OP Fig. 46
THRM2: Reset Replica No Yes -
039 185 Read only OP Fig. 46
THRM1: Buffer Empty No Yes -
039 128 Read only OP Fig. 46
THRM2: Buffer Empty No Yes -
039 188 Read only OP Fig. 46
THRM1: CTA Error No Yes -
039 127 Read only OP Fig. 44
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
V<>: Blocking tV> EXT No Yes -
041 068 Read only OP Fig. 48
V<>: Blocking tV>> EXT No Yes -
041 069 Read only OP Fig. 48
V<>: Blocking tV< EXT No Yes -
041 070 Read only OP Fig. 49
V<>: Blocking tV<< EXT No Yes -
041 071 Read only OP Fig. 49
V<>: Enabled No Yes -
040 066 Read only OP Fig. 47
V<>: Ready No Yes -
042 003 Read only OP Fig. 47
V<>: Not Ready No Yes -
042 004 Read only OP Fig. 47
V<>: Starting V> No Yes -
041 030 Read only OP Fig. 48
V<>: Starting V>> No Yes - MR
041 096 Read only OP Fig. 48
V<>: tV> Elapsed No Yes -
041 034 Read only OP Fig. 48
V<>: tV>> Elapsed No Yes -
041 035 Read only OP Fig. 48
V<>: Starting V< No Yes -
041 037 Read only OP Fig. 49
V<>: Starting V<< No Yes -
041 099 Read only OP Fig. 49
V<>: tV< Elapsed No Yes -
041 041 Read only OP Fig. 49
V<>: tV< Elapsed & Vmin> No Yes -
041 026 Read only OP Fig. 49
V<>: tV< Elaps. Transient No Yes -
042 023 Read only OP Fig. 49
V<>: Fault V< No Yes -
041 110 Read only OP Fig. 49
V<>: tV<< Elapsed No Yes -
041 042 Read only OP Fig. 49
V<>: tV<< Elapsed & Vmin> No Yes -
041 066 Read only OP Fig. 49
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
V<>: tV<< Elapsed Trans. No Yes -
042 025 Read only OP Fig. 49
V<>: Fault V<< No Yes -
041 112 Read only OP Fig. 49
V<>: tV</<< Elaps. Trans. No Yes -
042 007 Read only OP Fig. 49
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
f<>: Blocking f1 EXT No Yes -
042 103 Read only OP Fig. 53
f<>: Blocking f2 EXT No Yes -
042 104 Read only OP Fig. 53
f<>: Blocking f3 EXT No Yes -
042 105 Read only OP Fig. 53
f<>: Blocking f4 EXT No Yes -
042 106 Read only OP Fig. 53
MR f<>: Enabled No Yes -
042 100 Read only OP Fig. 50
f<>: Ready No Yes -
042 101 Read only OP Fig. 50
f<>: Not Ready No Yes -
042 140 Read only OP Fig. 50
f<>: Blocked by V< No Yes -
042 102 Read only OP Fig. 51
f<>: Starting f1 No Yes -
042 107 Read only OP Fig. 53
f<>: Starting f2 No Yes -
042 115 Read only OP Fig. 53
f<>: Starting f3 No Yes -
042 123 Read only OP Fig. 53
f<>: Starting f4 No Yes -
042 131 Read only OP Fig. 53
f<>: Starting f1/df1 No Yes -
042 108 Read only OP Fig. 53
f<>: Starting f2/df2 No Yes -
042 116 Read only OP Fig. 53
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
f<>: Starting f3/df3 No Yes -
042 124 Read only OP Fig. 53
f<>: Starting f4/df4 No Yes -
042 132 Read only OP Fig. 53
f<>: Delta f1 Triggered No Yes -
042 109 Read only OP Fig. 53
f<>: Delta f2 Triggered No Yes -
042 117 Read only OP Fig. 53
f<>: Delta f3 Triggered No Yes -
042 125 Read only OP Fig. 53
f<>: Delta f4 Triggered No Yes -
042 133 Read only OP Fig. 53
f<>: Delta t1 Elapsed No Yes -
042 110 Read only OP Fig. 53
f<>: Delta t2 Elapsed No Yes -
042 118 Read only OP Fig. 53
f<>: Delta t3 Elapsed No Yes -
042 126 Read only OP Fig. 53
f<>: Delta t4 Elapsed No Yes -
MR
042 134 Read only OP Fig. 53
f<>: Trip Signal f1 No Yes -
042 111 Read only OP Fig. 53
f<>: Trip Signal f2 No Yes -
042 119 Read only OP Fig. 53
f<>: Trip Signal f3 No Yes -
042 127 Read only OP Fig. 53
f<>: Trip Signal f4 No Yes -
042 135 Read only OP Fig. 53
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
V/f: Block. tV/f> EXT No Yes -
035 196 Read only OP Fig. 60
V/f: Block. Replica EXT No Yes -
035 197 Read only OP Fig. 60
V/f: Block. tV/f>> EXT No Yes -
035 199 Read only OP Fig. 60
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
V/f: Reset Replica EXT No Yes -
035 182 Read only OP Fig. 61
V/f: Enabled No Yes -
041 229 Read only OP Fig. 57
V/f: Reset Replica No Yes -
035 184 Read only OP Fig. 60
V/f: Starting V/f> No Yes -
041 230 Read only OP Fig. 56
V/f: tV/f> Elapsed No Yes -
041 231 Read only OP Fig. 56
V/f: Starting V/f(t) No Yes -
041 232 Read only OP Fig. 60
V/f: Trip Signal tV/f(t) No Yes -
041 233 Read only OP Fig. 60
V/f: Starting V/f>> No Yes -
041 234 Read only OP Fig. 57
V/f: tV/f>> Elapsed No Yes -
041 235 Read only OP Fig. 57
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
CTS: Blocking EXT No Yes -
036 160 Read only OP Fig. 65
CTS: Reset Latching EXT No Yes -
036 158 Read only OP Fig. 69
CTS: Enabled No Yes -
036 080 Read only OP Fig. 64
CTS: Reset Latching No Yes -
036 159 Read only OP Fig. 69
CTS: Operated (Updating) No Yes -
036 099 Read only OP Fig. 69
CTS: Operated (Latched) No Yes -
036 202 Read only OP Fig. 69
CTS: Idiff> (CTS) Active No Yes -
036 203 Read only OP Fig. 69
Indication of whether the pick-up threshold of the differential has been moved from Idiff> to
Idiff> (CTS), upon detection of a CT failure.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
CTS: Alarm End a (Updat.) No Yes -
036 081 Read only OP Fig. 67
CTS: Alarm End b (Updat.) No Yes -
036 082 Read only OP Fig. 67
CTS: Alarm End c (Updat.) No Yes -
036 083 Read only OP Fig. 67
CTS: Alarm End d (Updat.) No Yes -
036 084 Read only OP Fig. 67
CTS: Alarm End a (Latch.) No Yes -
036 204 Read only OP Fig. 67
CTS: Alarm End b (Latch.) No Yes -
036 206 Read only OP Fig. 67
CTS: Alarm End c (Latch.) No Yes -
036 208 Read only OP Fig. 67
CTS: Alarm End d (Latch.) No Yes -
036 210 Read only OP Fig. 67
CTS: Alarm End a No Yes -
036 205 Read only OP Fig. 67
CTS: Alarm End b No Yes -
MR
036 207 Read only OP Fig. 67
CTS: Alarm End c No Yes -
036 209 Read only OP Fig. 67
CTS: Alarm End d No Yes -
036 211 Read only OP Fig. 67
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
BC_1: Blocking EXT No Yes -
036 213 Read only OP Fig. 63
BC_2: Blocking EXT No Yes -
036 215 Read only OP Fig. 63
BC_3: Blocking EXT No Yes -
036 217 Read only OP Fig. 63
BC_4: Blocking EXT No Yes -
036 219 Read only OP Fig. 63
BC_1: Enabled No Yes -
036 194 Read only OP Fig. 62
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
BC_2: Enabled No Yes -
036 195 Read only OP Fig. 62
BC_3: Enabled No Yes -
036 196 Read only OP Fig. 62
BC_4: Enabled No Yes -
036 197 Read only OP Fig. 62
BC_1: CT Fail Alarm No Yes -
036 198 Read only OP Fig. 63
BC_2: CT Fail Alarm No Yes -
036 199 Read only OP Fig. 63
BC_3: CT Fail Alarm No Yes -
036 200 Read only OP Fig. 63
BC_4: CT Fail Alarm No Yes -
036 201 Read only OP Fig. 63
BC_1: Starting No Yes -
036 212 Read only OP Fig. 63
BC_2: Starting No Yes -
036 214 Read only OP Fig. 63
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LIMIT: Enabled No Yes -
040 074 Read only OP Fig. 71
LIMIT: Starting IDC,lin> No Yes -
040 180 Read only OP Fig. 71
LIMIT: Starting IDC,lin>> No Yes -
040 181 Read only OP Fig. 71
LIMIT: tIDC,lin> Elapsed No Yes -
040 182 Read only OP Fig. 71
LIMIT: tIDC,lin>> Elapsed No Yes -
040 183 Read only OP Fig. 71
LIMIT: Starting IDC,lin< No Yes -
040 184 Read only OP Fig. 71
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
LIMIT: Starting IDC,lin<< No Yes -
040 185 Read only OP Fig. 71
LIMIT: tIDC,lin< Elapsed No Yes -
040 186 Read only OP Fig. 71
LIMIT: tIDC,lin<< Elapsed No Yes -
040 187 Read only OP Fig. 71
LIMIT: Starting T> No Yes -
040 170 Read only OP Fig. 72
LIMIT: Starting T>> No Yes -
040 171 Read only OP Fig. 72
LIMIT: tT> Elapsed No Yes -
040 172 Read only OP Fig. 72
LIMIT: tT>> Elapsed No Yes -
040 173 Read only OP Fig. 72
LIMIT: Starting T< No Yes -
040 174 Read only OP Fig. 72
LIMIT: Starting T<< No Yes -
040 175 Read only OP Fig. 72
LIMIT: tT< Elapsed No Yes -
MR
040 176 Read only OP Fig. 72
LIMIT: tT<< Elapsed No Yes -
040 177 Read only OP Fig. 72
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LIM_1: Enabled No Yes -
040 123 Read only OP Fig. 74
LIM_2: Enabled No Yes -
040 125 Read only OP Fig. 74
LIM_3: Enabled No Yes -
040 127 Read only OP Fig. 74
LIM_1: tI> Elapsed No Yes -
040 122 Read only OP Fig. 74
LIM_2: tI> Elapsed No Yes -
040 124 Read only OP Fig. 74
LIM_3: tI> Elapsed No Yes -
040 126 Read only OP Fig. 74
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
LIM_1: tI>> Elapsed No Yes -
037 201 Read only OP Fig. 74
LIM_2: tI>> Elapsed No Yes -
038 201 Read only OP Fig. 74
LIM_3: tI>> Elapsed No Yes -
039 201 Read only OP Fig. 74
LIM_1: tI< Elapsed No Yes -
037 202 Read only OP Fig. 74
LIM_2: tI< Elapsed No Yes -
038 202 Read only OP Fig. 74
LIM_3: tI< Elapsed No Yes -
039 202 Read only OP Fig. 74
LIM_1: tI<< Elapsed No Yes -
037 203 Read only OP Fig. 74
LIM_2: tI<< Elapsed No Yes -
038 203 Read only OP Fig. 74
LIM_3: tI<< Elapsed No Yes -
039 203 Read only OP Fig. 74
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Measurements\Log. State Signals
LOGIC: Input 1 (…40) EXT No Yes -
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Input 1 EXT 034 000 Input 15 EXT 034 014 Input 29 EXT 034 098
Input 2 EXT 034 001 Input 16 EXT 034 015 Input 30 EXT 034 099
Input 3 EXT 034 002 Input 17 EXT 034 086 Input 31 EXT 034 100
Input 4 EXT 034 003 Input 18 EXT 034 087 Input 32 EXT 034 101
Input 5 EXT 034 004 Input 19 EXT 034 088 Input 33 EXT 034 102
Input 6 EXT 034 005 Input 20 EXT 034 089 Input 34 EXT 034 103
Input 7 EXT 034 006 Input 21 EXT 034 090 Input 35 EXT 034 104
Input 8 EXT 034 007 Input 22 EXT 034 091 Input 36 EXT 034 105
Input 9 EXT 034 008 Input 23 EXT 034 092 Input 37 EXT 034 106
Input 10 EXT 034 009 Input 24 EXT 034 093 Input 38 EXT 034 107
Input 11 EXT 034 010 Input 25 EXT 034 094 Input 39 EXT 034 108
Input 12 EXT 034 011 Input 26 EXT 034 095 Input 40 EXT 034 109
Measurement Range
Menu Text Step Size
Min. Max.
No
LOGIC: Set 1 (…8) EXT Yes -
Not Configured
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Set 1 EXT 034 051 Set 4 EXT 034 054 Set 7 EXT 034 057
Set 2 EXT 034 052 Set 5 EXT 034 055 Set 8 EXT 034 058
No
LOGIC: Reset 1 (…8) EXT Yes -
Not Configured
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Reset 1 EXT 034 059 Reset 4 EXT 034 062 Reset 7 EXT 034 065
Reset 2 EXT 034 060 Reset 5 EXT 034 063 Reset 8 EXT 034 066
Measurement Range
Menu Text Step Size
Min. Max.
LOGIC: Output 1 (…32) No Yes -
See table below for status addresses. Read only OP Fig. 76
Menu Text Address Menu Text Address Menu Text Address
Output 1 042 032 Output 12 042 054 Output 23 042 076
Output 2 042 034 Output 13 042 056 Output 24 042 078
Output 3 042 036 Output 14 042 058 Output 25 042 080
Output 4 042 038 Output 15 042 060 Output 26 042 082
Output 5 042 040 Output 16 042 062 Output 27 042 084
Output 6 042 042 Output 17 042 064 Output 28 042 086
Output 7 042 044 Output 18 042 066 Output 29 042 088
Output 8 042 046 Output 19 042 068 Output 30 042 090
Output 9 042 048 Output 20 042 070 Output 31 042 092
Output 10 042 050 Output 21 042 072 Output 32 042 094
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
HMI: Param. Change Enabl. No Yes -
003 010
Setting the permission for changing values from the HMI.
Measurements and Recording P63x/UK MR/A54
1.2.2 Main rear port communication control and testing commands (COMM1)
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Signals from selection table
COMM1: Sel.Spontan.Sig.Test dependent upon relay -
configuration
003 180
Don’t Execute
COMM1: Test Spont.Sig.Start -
Execute
003 184
Don’t Execute
COMM1: Test Spont.Sig. End -
Execute
003 186
1.2.3 2nd rear port communication control and testing commands (COMM2)
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Signals from selection table
COMM2: Sel.Spontan.Sig.Test dependent upon relay -
configuration
103 180 OP Fig. 94
Don’t Execute
MR
COMM2: Test Spont.Sig.Start -
Execute
103 184 OP Fig. 94
Don’t Execute
COMM2: Test Spont.Sig. End -
Execute
103 186 OP Fig. 94
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
GSSE: Reset Statistics -
Execute
105 171
Not
GSSE: GSSE Enroll.Flags L 65535 1
Measured/0
105 160 Read only
Not
GSSE: GSSE Enroll. Flags H 65535 1
Measured/0
105 161 Read only
Not
GSSE: GSSE Tx Msg Counter 65535 1
Measured/0
105 162 Read only
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Not
GSSE: GSSE Rx Msg Counter 65535 1
Measured/0
105 163 Read only
Not
GSSE: No. Bin State Chang. 65535 1
Measured/0
105 164 Read only
Not
GSSE: Tx Last Sequence 65535 1
Measured/0
105 165 Read only
Not
GSSE: Tx Last Message 65535 1
Measured/0
105 166 Read only
Not
GSSE: No. Reject. Messages 65535 1
Measured/0
105 167 Read only
GSSE: IED View Selection Remote IED -
105 170
Not
GSSE: GSSE IED Recvd Msgs 65535 1
Measured/0
105 172 Read only
Not
MR GSSE: GSSE IED Last SeqRx
Measured/0
65535 1
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OUTP: Reset Latch. USER -
Execute
OP Fig.
021 009
105
Reset of latched output relays from the local control panel.
Signals from selection table
OUTP: Relay Assign. f.Test dependent upon relay -
configuration
OP Fig.
003 042
106
Selection of the relay to be tested.
Don’t Execute
OUTP: Relay Test -
Execute
OP Fig.
003 043
106
The relay selected for testing is triggered for the set time (OU T P: Ho ld -T im e for Tes t).
OUTP: Hold-Time for Test 1s 10 s 1s
OP Fig.
003 044
106
Setting for the time period for which the selected output relay is triggered for functional
testing.
MR
1.2.6 Analog output channel control and testing commands (mA_OP)
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
mA_OP: Reset Output USER -
Execute
OP Fig.
037 116
109
Resetting the measured data output function.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
MAIN: General Reset -
Execute
OP Fig.
003 002
140
Reset of the following memories:
All counters
LED indicators
Operating data memory
All event memories
Event counters
Measured overload data
Fault, OLoad records
Recorded fault values
Don’t Execute
MAIN: Reset Indicat. USER -
Execute
OP Fig.
021 010
140
Reset of the following displays:
MR
LED indicators
Fault, OLoad Records
Don’t Execute
MAIN: Rset Latch Trip USER -
Execute
OP Fig.
021 005
135
Reset latched trip commands using the local control panel.
Don’t Execute
MAIN: Reset c. cl./Trip c. -
Execute
OP Fig.
003 007
136
The counters for close and trip commands are reset.
Don’t Execute
MAIN: Reset IPh,Max Demand -
Execute
OP Fig.
003 033
119, 120
The values for the delayed stored maximum phase current, ends a to d, are reset.
Don’t Execute
MAIN: Man. Trip Cmd. USER -
Execute
OP Fig.
003 040
135
A trip command is issued from the local control panel for 100 ms.
Note: The command is only executed if the manual trip command is included in the
configuration of trip commands.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Don’t Execute
MAIN: Warm Restart -
Execute
003 039
A warm restart is carried out. The device functions as it does when the power supply is
turned on.
Don’t Execute
MAIN: Cold Restart -
Execute
000 085 Password Protected
A cold restart is executed. A cold restart means that all settings and recordings are
cleared. The values with which the device operates after a cold restart are the default
settings given in the Settings - ST section. They are selected so as to block the device
after a cold restart.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OP_RC: Reset Recording -
Execute
OP Fig.
100 001
144
The operating data memory and the counter for operation signals are reset.
MR
1.2.9 Monitoring signal control and testing commands (MT_RC)
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
MT_RC: Reset Recording -
Execute
OP Fig.
003 008
145
Reset of the monitoring signal memory.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OL_RC: Reset Recording -
Execute
OP Fig.
100 003
148
Reset of the overload memory.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
OSCIL: Trigger USER -
Execute
OP Fig.
003 041
155
Fault recording and fault value recording are triggered from the local control panel for
500 ms.
Don’t Execute
OSCIL: Reset Recording -
Execute
OP Fig.
003 006
156
Reset of the following memories:
LED indicators
Fault memory
Fault counter
Fault, OLoad Records
Recorded fault values
Measurement Range
MR Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
THRM1: Reset Replica USER -
Execute
039 120 OP Fig. 46
Don’t Execute
THRM2: Reset Replica USER -
Execute
039 180
Thermal overload memory reset.
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
f<>: Reset meas.val. USER -
Execute
003 080
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
V/f: Reset Replica USER -
Execute
035 183
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
CTS: Reset Latch. USER -
Execute
036 157
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Control and Testing
Don’t Execute
LOGIC: Trigger 1 (…8) -
Execute
See table below for command addresses. OP Fig. 76
MR
Intervention in the logic at the appropriate point by a 100 ms pulse.
Menu Text Address Menu Text Address Menu Text Address
Trigger 1 034 038 Trigger 4 034 041 Trigger 7 034 044
Trigger 2 034 039 Trigger 5 034 042 Trigger 8 034 045
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Operating Data Rec.
OP_RC: Operat. Data Record. 0 100 1
OP Fig.
003 024 Read only
144
Point of entry into the operating data log.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Measurements + Tests\Operating Data Rec.
MT_RC: Mon. Signal Record. 0 30 1
OP Fig.
003 001 Read only
145
Point of entry into the monitoring signal log.
MR
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
MAIN: No. General Start. 0 1
Overflow
OP Fig.
004 000
134
Number of general starting signals.
9999/
MAIN: No. Gen. Trip Cmds.1 0 1
Overflow
OP Fig.
004 006
136
9999/
MAIN: No. Gen. Trip Cmds.2 0 1
Overflow
OP Fig.
009 050
136
9999/
MAIN: No. Gen. Trip Cmds.3 0 1
Overflow
OP Fig.
009 056
136 MR
9999/
MAIN: No. Gen. Trip Cmds.4 0 1
Overflow
OP Fig.
009 057
136
Number of general trip commands 1 to 4.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OP_RC: No. Oper. Data Sig. 0 100 1
OP Fig.
100 002 Read only
144
Number of signals stored in the operating data memory.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
MT_RC: No. Monit. Signals 0 30 1
OP Fig.
004 019 Read only
145
Number of signals stored in the monitoring signal memory.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OL_RC: No. Overload 0 9999 1
OP Fig.
004 101 Read only
148
Number of overload states.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
OSCIL: No. of Faults 0 9999 1
004 020 Read only OP Fig. 84
Number of faults.
OSCIL: No. System Disturb. 0 9999 1
004 010 Read only OP Fig. 84
Number of system disturbances (trips, plus starts which may not have resulted in trips).
Measurement Range
MR Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
DTOC1: No. General Start. 0 1
Overflow
009 150 Read only OP Fig. 27
9999/
DTOC2: No. General Start. 0 1
Overflow
009 160 Read only OP Fig. 27
9999/
DTOC3: No. General Start. 0 1
Overflow
009 170 Read only OP Fig. 27
Number of general starting signals.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, Event Counters
9999/
IDMT1: No. General Start. 0 1
Overflow
009 151 Read only OP Fig. 39
9999/
IDMT2: No. General Start. 0 1
Overflow
009 161 Read only OP Fig. 39
9999/
IDMT3: No. General Start. 0 1
Overflow
009 171 Read only OP Fig. 39
Number of general starting signals.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records
Not
6500.0 s/
OL_DA: Overload Duration Measured/ 0.1 s
0.0 s
Overflow MR
OP Fig.
004 102 Read only
146
Duration of the overload event.
Not
250%/
OL_DA: Status THRM1 Replica Measured/ 1%
Overflow
0%
OP Fig.
004 155 Read only
147
Not
250%/
OL_DA: Status THRM2 Replica Measured/ 1%
Overflow
0%
OP Fig.
004 185 Read only
147
Display of the buffer content of the thermal overload protection function THRM1 or THRM2,
respectively.
Not
3.00 In/
OL_DA: Load Current THRM1 Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
004 159 Read only
147
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Not
3.00 In/
OL_DA: Load Current THRM2 Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
004 189 Read only
147
Display of the load current used by the thermal overload protection function to calculate the
tripping time.
Not
300 °C/
OL_DA: Object Temp. THRM1 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 156 Read only
147
Not
300 °C/
OL_DA: Object Temp. THRM2 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 186 Read only
147
Display of the temperature of the protected object as determined by function THRM1 or
THRM2, respectively.
Not
215 °C/
OL_DA: Coolant Temp.THRM1 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 157 Read only
MR 147
Not
215 °C/
OL_DA: Coolant Temp.THRM2 Measured/ 1 °C
Overflow
-40 °C
OP Fig.
004 187 Read only
147
Display of the coolant temperature. Depending on the setting at THR M1 : Se lec t CT
Am bi en t or at T HRM 2 : Se lec t C T Am bi en t, respectively, for the coolant
temperature acquisition, one of the following values will be displayed:
• Setting Default Temp. Value: Display of the set temperature value
Not
1000.0 min/
OL_DA: Pre-trip t.leftTHRM1 Measured/ 0.1 min
Overflow
0.0 min
OP Fig.
004 158 Read only
147
Not
1000.0 min/
OL_DA: Pre-trip t.leftTHRM2 Measured/ 0.1 min
Overflow
0.0 min
OP Fig.
004 188 Read only
147
Display of the time remaining before the thermal overload protection function THRM1 or
THRM2, respectively, will reach the tripping threshold.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Not
25000%/
OL_DA: Offset THRM1 Replica Measured/ 1%
Overflow
-25000 %
OP Fig.
004 191 Read only
147
Not
25000%/
OL_DA: Offset THRM2 Replica Measured/ 1%
Overflow
-25000 %
OP Fig.
004 192 Read only
147
Display of the additional reserve if the coolant temperature is taken into account. This
display is relevant if the coolant temperature has been set to a value below the maximum
permissible coolant temperature or, in other words, if the thermal model has been shifted
downwards.
If, on the other hand, the coolant temperature and the maximum permissible coolant
temperature have been set to the same value, then the coolant temperature is not taken
into account and the characteristic is a function of the current only. The additional reserve
amounts to 0 in this case.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records
Not
6500.0 s/
MR
FT_DA: Fault Duration Measured/ 0.1 s
Overflow
0.0 s
OP Fig.
008 010 Read only
150
Display of the fault duration.
Not
65.00 s/
FT_DA: Running Time Measured/ 0.01 s
Overflow
0.00 s
OP Fig.
004 021 Read only
150
Display of the running time.
No Fault
Max. diff. Current
Max. Idiff, REF_1
FT_DA: Fault Determ. With Max. Idiff, REF_2 -
Max. Idiff, REF_3
Max Restrain Current
Other Trigger
OP Fig.
004 198 Read only
151
This display indicates when the fault data were stored.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Not
65.000 s/
FT_DA: Run Time to Meas. Measured/ 0.001 s
Overflow
0.000 s
OP Fig.
004 199 Read only
151
This display indicates when the fault data were stored.
Not
99.00 In/
FT_DA: Fault Curr.Iph,a p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,b p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,c p.u Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 086 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.Iph,d p.u Measured/ 0.01 In
Overflow
MR 0.00 In
OP Fig.
028 086 Read only
152
Display of the maximum phase current at the data acquisition time for each end, referred to
In.
Not
99.00 In/
FT_DA: Fault Curr.IN,a p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,b p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,c p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 087 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IN,d p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
028 087 Read only
152
Display of the residual current calculated by the P63x at the data acquisition time based on
the sum of the phase currents for each end, referred to In.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 In/
FT_DA: Fault Curr.IY,a p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
025 088 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IY,b p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
026 088 Read only
152
Not
99.00 In/
FT_DA: Fault Curr.IY,c p.u. Measured/ 0.01 In
Overflow
0.00 In
OP Fig.
027 088 Read only
152
Display of the residual current measured at the T14 transformer by the P63x at the data
acquisition time, referred to In.
Not
99.00 Iref/
FT_DA: Diff Current 1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 082 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2 Measured/
0.00 Iref
Overflow
0.01 Iref
MR
OP Fig.
006 082 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 082 Read only
153
Display of the differential current for each measuring system, referred to Iref.
Not
99.00 Iref/
FT_DA: Diff Current 1(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 084 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
006 084 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3(2*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 084 Read only
153
Display of the second harmonic component of the differential current for each measuring
system, referred to Iref.
P63x/UK MR/A54 Measurements and Recording
Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 Iref/
FT_DA: Diff Current 1(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 085 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 2(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
006 085 Read only
153
Not
99.00 Iref/
FT_DA: Diff Current 3(5*fn) Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 085 Read only
153
Display of the fifth harmonic component of the differential current for each measuring
system, referred to Iref.
Not
99.00 Iref/
FT_DA: Restrain Current 1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
005 083 Read only
153
Not
99.00 Iref/
MR FT_DA: Restrain Current 2 Measured/
0.00 Iref
Overflow
0.01 Iref
OP Fig.
006 083 Read only
153
Not
99.00 Iref/
FT_DA: Restrain Current 3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
007 083 Read only
153
Display of the restraining current for each measuring system, referred to Iref.
Not
99.00 Iref/
FT_DA: Diff Current REF_1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
025 082 Read only
154
Not
99.00 Iref/
FT_DA: Diff Current REF_2 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
026 082 Read only
154
Not
99.00 Iref/
FT_DA: Diff Current REF_3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
027 082 Read only
154
Display of the differential current, determined by the restricted earth fault protection
function (REF_1), referred to Iref.
Measurements and Recording P63x/UK MR/A54
Measurement Range
Menu Text Step Size
Min. Max.
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_1 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
025 083 Read only
154
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_2 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
026 083 Read only
154
Not
99.00 Iref/
FT_DA: Restrain. Curr. REF_3 Measured/ 0.01 Iref
Overflow
0.00 Iref
OP Fig.
027 083 Read only
154
Display of the restraining current, determined by the restricted earth fault protection
function (REF_1), referred to Iref.
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Fault, OLoad Records
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Disturbance Oscillo.
OL_RC: Overload Recording 1 (…8) 0 9999 1
See table below for status addresses. Read only
Point of entry into the overload log.
Menu Text Address Menu Text Address Menu Text Address
Overload Recording 1 003 020 Overload Recording 4 003 023 Overload Recording 7 003 026
Overload Recording 2 003 021 Overload Recording 5 003 024 Overload Recording 8 003 027
Measurement Range
Menu Text Step Size
Min. Max.
Fault + Event Record\Disturbance Oscillo.
OSCIL: Fault Recording 1 (…8) 0 9999 1
See table below for status addresses. Read only
Point of entry into the fault log.
Menu Text Address Menu Text Address Menu Text Address
Fault Recording 1 003 000 Fault Recording 4 033 003 Fault Recording 7 033 006
Fault Recording 2 033 001 Fault Recording 5 033 004 Fault Recording 8 033 007
MR
Firmware Design P63x/UK FD/A54
FIRMWARE DESIGN
FD
FD
Firmware Design P63x/UK FD/A54
CONTENTS
(FD) 8-
1. FIRMWARE DESIGN 3
1.1 Relay structure overview 3
FIGURES
FD
Firmware Design P63x/UK FD/A54
1. FIRMWARE DESIGN
P1952ENa
FD
Fixed Logic:
Configuration: Configuration:
DTOC, IDMT, DIFF, ...
INP OUTP
HMI LED
PC HMI
COMM1 PC
COMM2 COMM1
GOOSE Programmable Logic: COMM2
GSSE GOOSE
LOGIC GSSE
P1953ENa
• System alarms
System alarms do not affect the protection and control tasks and therefore the device
remains in operation. As an example, overflow of communication buffers or a low voltage of
the internal battery result in an alarm only.
• System errors
System errors affect the protection and control function and require further processing. At
the first instance the device will perform a warm restart to recover from the error. If the error
already present before (i.e. already entered in the monitoring signal memory), then the
device will become blocked (004.065 MAIN: Blocked/Faulty = Yes). Examples for system
errors are checksum errors, defective module errors etc.
Both, alarms and errors, could be either spontaneous (which means that only the occurrence
of the alarm/error could be detected, e.g. any checksum error) or testable (which means start
and end of the alarm/error condition could be detected, e.g. defective output relay).
Peripheral faults like fuse failure are always “testable alarms”.
• Flag “updated”
= Yes: the error is still present;
= No: the error is no longer present. Spontaneous alarms/errors are always indicated
as “updated = yes”.
• Flag “acknowledged”
= Yes: the warning was already acknowledged but the error is still present;
= No: the warning was not yet acknowledged.
Firmware Design P63x/UK FD/A54
• Signaling only
If there is no malfunction associated with the monitoring signal (= upon system alarms), then
only a signal is issued, and there are no further consequences. This situation exists, for
example, when internal data acquisition memories overflow or if the internal battery voltage
is low.
• Selective blocking
If a system error is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the detection of a
fault on the communication module or in the area of the PC interface or if an individual output
relay is faulty.
• Warm restart
If the self-monitoring function detects a system error that might be eliminated by a system
restart - such as a hardware error, e.g. DPRAM read error, or a software error, e.g. zero
division error, then a procedure called a warm restart is automatically initiated. During this
procedure, as with any startup, the computer system is reset to a defined state. A warm
restart is characterized by the fact that no stored data and, in particular, no settings are
affected by the procedure. A warm restart can also be triggered manually by a control
action. During a warm restart sequence, both the protective functions and communication
through serial interfaces will be blocked. If the same system error is detected after a warm
restart has been triggered by the self-monitoring system, then the protective functions
remain blocked, but communication through the serial interfaces will usually be possible
again.
• Cold restart
If corrupted settings are diagnosed during the checksum test, which is part of the
self-monitoring procedure, then a cold restart is carried out. This is necessary because the
unit cannot identify which setting in the group is corrupted. A cold restart causes all internal
FD
memories to be reset to predefined default values. This means that all device settings are
also erased after a cold restart. In order for a safe initial state to be established, the default
values have been selected so that the protective functions are blocked. Both the monitoring
signal that triggered the cold restart and the signal indicating parameter loss are entered in
the monitoring signal memory. Beside corrupted settings, a cold restart is initiated only after
a software download procedure (either download of a new firmware version or download of a
customized data model) or manually (as a means to get the device in a predefined
condition). Manual cold restart can only be initiated from the local HMI. The device must be
in offline mode. The initiation is password protected.
Refer to Troubleshooting - TS section of this manual, which lists possible warning signals
and the device response/reaction upon detection of each alarm/error.
P63x/UK FD/A54 Firmware Design
FD
Commissioning P63x/UK CM/A54
COMMISSIONING
CM
CM
Commissioning P63x/UK CM/A54
CONTENTS
(CM) 9-
1. INTRODUCTION 3
2. PRODUCT FAMILIARISATION 4
2.1 Settings 4
4. PRODUCT CHECKS 6
4.1 With the relay de-energized 6
5. SETTING CHECKS 13
5.1 Demonstrate correct relay operation 13
5.2.6 Dd applications 16
5.4.5 Ensuring that all records and memories have been reset 20
6. ON-LOAD CHECKS 21
6.1 Confirm current and voltage transformer wiring 21
7. FINAL CHECKS 21
1. INTRODUCTION
MiCOM P63x transformer protection relays are fully numerical in their design, implementing
all protection and non-protection functions in software. The relays employ a high degree of
self-checking and, in the unlikely event of a failure, will give an alarm. As a result of this, the
commissioning tests do not need to be as extensive as with non-numeric electronic or
electro-mechanical relays.
To commission numeric relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay. It is
considered unnecessary to test every function of the relay if the settings have been verified
by one of the following methods:
• Extracting the settings applied to the relay using appropriate setting software (preferred
method - using MiCOM S1)
CM
P63x/UK CM/A54 Commissioning
2. PRODUCT FAMILIARISATION
2.1 Settings
When commissioning a MiCOM P63x relay for the first time, sufficient time should be
allowed to become familiar with the method by which the settings are applied.
With the secondary front cover in place all keys except the ENTER key are accessible. With
the cover fitted, no protection or configuration settings can be changed.
Removing the secondary front cover allows access to all keys so that settings can be
changed, LED’s and alarms reset, and fault and event records cleared. However, for setting
and configuration cells, the appropriate password has to be entered before changes can be
made.
Alternatively, if a portable PC is available together with suitable setting software (such as
MiCOM S1), the menu can be viewed a page at a time to display a full column of data and
text. This PC software also allows settings to be entered more easily, saved to a file on disk
for future reference or printed to produce a setting record. Refer to the PC software user
manual for details. If the software is being used for the first time, allow sufficient time to
become familiar with its operation.
CM
P63x/UK CM/A54 Commissioning
4. PRODUCT CHECKS
These product checks cover all aspects of the relay which should be checked to ensure that
it has not been physically damaged prior to commissioning, is functioning correctly and all
input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow their restoration later. This could be
done by:
• Obtaining a setting file on a diskette from the customer (this requires a portable PC with
appropriate setting software for transferring the settings from the PC to the relay)
• Extracting the settings from the relay itself (this again requires a portable PC with
appropriate setting software)
• Relay output contacts, situated on V and X/Y (populated slots). Also, milliamp current
loop measured inputs and outputs, situated on module Y.
The current and voltage transformer connections must remain isolated from the relay for
these checks. The trip circuit should also remain isolated to prevent accidental operation of
the associated circuit breaker.
• Transferring them from a pre-prepared setting file to the relay using a portable PC
running the appropriate software via the relay’s front EIA(RS)232 port, located under the
bottom access cover, or rear communications port. This method is preferred for
transferring function settings as it is much faster and there is less margin for error.
If a setting file has been created for the particular application and provided on a diskette,
this will further reduce the commissioning time and should always be the case where
application-specific programmable scheme logic is to be applied to the relay.
CM
Commissioning P63x/UK CM/A54
5. SETTING CHECKS
The setting checks ensure that all of the application-specific relay settings (i.e. both the
relay’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the relay.
Note (1): The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
Note (2): If the user wishes the relay to be incapable of tripping the circuit
breaker by means of inhibiting the trip output contact(s), this can be
set at:
• To determine that the primary protection function of the relay, differential protection, can
trip according to the correct application settings
• The customer’s desired setting group to be left in-service after testing is used. This is
generally Setting Group SG1, and verification that the relay has the correct group
applied should be done by reading cell [003.062: Measurements +
Tests/Measurements/Log. State Signals/GROUP, Actual Setting Group]
To enable the protection elements, ensure that the Protection is “Yes (Enabled)” at
cell [003.030: Settings/Function Settings/Global/MAIN, Protection Enabled]
Apply balanced three-phase current slightly less than the Idiff> setting to the HV side CT
inputs only (these CTs are usually the input designated as “End a“). Observe that no trip
should occur, and the red Trip LED remains extinguished.
Ramp up the current until a trip occurs and the Trip LED illuminates.
Record the current at which the relay tripped. The measured current should be within +/-
10% of the Idiff> setting (relay accuracy 5%, plus test set accuracy 5%).
To balance, a current is applied to two phase CT inputs (delta side). The magnitude should
be a current equal to Kb / (√3.Ka) x INOM, and at the phase angles as shown below:
Star End
Current Delta Side
Injected Current
(Star) Injected Loop
Phase
IA = INOM . Kb / √3Ka ∠0o
Dy1 or Yd11 A INOM ∠-180o A-B
IB = INOM . Kb / √3Ka ∠-180o
IC = INOM . Kb / √3Ka ∠0o
Dy3 or Yd9 A INOM ∠-180 o
C-B
IB = INOM . Kb / √3Ka ∠-180o
IC = INOM . Kb / √3Ka ∠0o
Dy5 or Yd7 A INOM ∠-180 o
C-A
IA = INOM . Kb / √3Ka ∠-180o
IB = INOM . Kb / √3Ka ∠0o
Dy7 or Yd5 A INOM ∠-180o B-A
IA = INOM . Kb / √3Ka ∠-180o
IB = INOM . Kb / √3Ka ∠0o
Dy9 or Yd3 A INOM ∠-180o B-C
IC = INOM . Kb / √3Ka ∠-180o
IA = INOM . Kb / √3Ka ∠0o
Dy11 or Yd1 A INOM ∠-180 o
A-C
IC = INOM . Kb / √3Ka ∠-180o
5.2.6 Dd applications
This test simulates current flowing through the transformer to an out-of-zone external fault.
In many such applications, there may be in-zone earthing transformers, so it easiest to
simulate an external phase-phase fault, to avoid simulating a zero sequence current. If the
current simulated is 1 per unit (1 p.u.) out of end b, the input current to balance at end a is
easy to determine. In the simplest application of a Dd0 transformer, an A-B fault is simulated
flowing out of the LV side, fed by an A-B loop input on the HV side.
For ease of injection, a loop current equal to the CT secondary rating (1A or 5A) is simulated
to flow OUT on phase A, end b, and looping back through phase B, end b. On an automatic
test set, use INOM ∠-180o. Because four phase CT inputs to the relay will be energized at
once, it is necessary that the test set output current for this LV side is set as a single phase
but looping through two phase CT inputs.
Commissioning P63x/UK CM/A54
To balance, a loop current is applied at end a (the HV winding). The magnitude should be a
current equal to Kb/Ka x INOM, and at a phase angle as shown below. Again, the test set is
configured to generate only one single phase output for this winding, looped through two
phase CT inputs - thus in total the output requirements can be satisfied by a test set typically
having only up to 3 current outputs.
• For a P633 protecting a Yd transformer with an HV winding fed from two ring-bus CT
inputs (summated HV from end a + end b), the stability test would be performed 2 times:
(1) End a-b, (2) End a-c. The Yy test would be used for (1), and the Yd test for (2)
• Extract the settings from the relay using a portable PC running MiCOM S1 software via
the front EIA(RS)232 port, located under the bottom access cover, or rear
communications port. Compare the settings transferred from the relay with the original
written application-specific setting record. (For cases where the customer has only
provided a printed copy of the required settings but a portable PC is available)
• Step through the settings using the relay’s operator interface and compare them with the
original application-specific setting record
It is very important that the key settings below are investigated:
5.4.5 Ensuring that all records and memories have been reset
In the menu, navigate to both of the following addresses to execute resetting. The general
reset is password protected… (Input the password, which by default is a press of the four
arrow keys <>∧∨, left-right-up-down in sequence. Press ENTER, and if the password has
been accepted the EDIT mode LED will light. The up or down key can now be used to
toggle the setting to “Execute”, then press ENTER.)
CM
Commissioning P63x/UK CM/A54
6. ON-LOAD CHECKS
The objectives of the on-load checks are to:
• Confirm the external wiring to the current and voltage inputs is correct
However, these checks can only be carried out if there are no restrictions preventing the
energisation of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that
has been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the relay in
order to perform any of the foregoing tests, it should be ensured that all connections
are replaced in accordance with the relevant external connection or scheme diagram.
When advised by the system operator that it is permitted to energise the primary
circuit, arrange for the protected transformer to be made live by closing the circuit
breaker. This will make VT and CT circuits live.
7. FINAL CHECKS
The tests are now complete.
Remove all test or temporary shorting leads, etc. If it has been necessary to CM
disconnect any of the external wiring from the relay in order to perform the wiring
verification tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram.
If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the
cover so that the protection is put into service.
If applicable, replace the secondary front cover on the relay.
The green HEALTHY LED must be illuminated
P63x/UK CM/A54 Commissioning
Substation: Circuit:
System Frequency:
This section should be completed to allow future identification of protective devices that have been
commissioned using equipment that is later found to be defective or incompatible but may not be
detected during the commissioning procedure.
Model:
Injection test set
Serial No:
CM Model:
Multimeter
Serial No:
Model:
Insulation tester
Serial No:
Type: MiCOM S1
Setting software
Version:
Commissioning P63x/UK CM/A54
*Tick as appropriate
Have all relevant safety instructions
Yes* No*
been followed?
Product Checks
With the Relay De-Energized
Visual inspection
Visual inspection
Relay damaged? Yes* No*
Rating information correct for installation? Yes* No*
Case earth installed? Yes* No*
Insulation resistance >100MΩ at 500V dc Yes* No* Not Tested*
External Wiring
Wiring checked against diagram? Yes* No*
Test block connections checked? Yes* No* N/A*
Setting Checks
Application-specific function settings applied? Yes* No*
Current Inputs
In end a CT Ratio (HV winding) / (prim/sec)
In end b CT Ratio / (prim/sec)
In end c CT Ratio / (prim/sec)
In end d CT Ratio / (prim/sec)
End a neutral CT Ratio / (prim/sec)
End b neutral CT Ratio / (prim/sec)
End c neutral CT Ratio / (prim/sec)
Voltage Input
VT Ratio N/A* / (prim/sec)
On-Load Checks
Test wiring removed? Yes* No* N/A*
Disturbed customer wiring re-checked? Yes* No* N/A*
Per unit voltage reading as expected? Yes* No* N/A*
Per unit current readings as expected? Yes* No*
Commissioning P63x/UK CM/A54
Final Checks
Test wiring removed? Yes* No* N/A*
Disturbed customer wiring re-checked? Yes* No* N/A*
HEALTHY LED still showing? Yes* No*
Secondary front cover replaced? Yes* No* N/A*
CM
Date: Date:
P63x/UK CM/A54 Commissioning
CM
Maintenance P63x/UK MT/A54
MAINTENANCE
MT
MT
Maintenance P63x/UK MT/A54
CONTENTS
(MT) 10-
1. MAINTENANCE 3
1.1 Maintenance period 3
1.2.1 Alarms 3
1.2.2 Opto-isolators 3
1.5 Cleaning 7
MT
FIGURES
MT
Maintenance P63x/UK MT/A54
1. MAINTENANCE
1.2.1 Alarms
The alarm status LED should first be checked to identify if any alarm conditions exist. If so,
examine the “Measurements + Tests/Measurements/Log. State Signals/CHECK” folder to
determine if any internal self-monitoring faults have been detected. Details of all alarm
conditions can be obtained by a “Readout of Logs” from the Communication menu in
MT
S&R-103.
Clear the alarms to extinguish the LED.
1.2.2 Opto-isolators
The binary inputs are not checked by the self-monitoring function. However, a testing
function is integrated into the software so that the trigger state of each input can be read out
(‘Measurements + Tests/Measurements/I.O. Status Monitor/INP’ folder). This check should
be performed for each input being used and can be done, if necessary, without
disconnecting any device wiring.
Before testing, open any triggering circuits for external devices so that no inadvertent
switching operations will take place.
Note: The MiCOM P63x range of relays with ring-terminals have integral
current transformer shorting switches which will close when the heavy
duty terminal block is removed.
Maintenance P63x/UK MT/A54
Disconnect the relay earth, IRIG-B and fiber optic connections, as appropriate, from the rear
of the relay.
There are two types of terminal block used on the relay, medium and heavy duty, which are
fastened to the rear panel using crosshead screws.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
The relevant components are located on the following modules:
• Electrolytic capacitor:
On power supply module V
• Lithium battery:
On power supply module V
P1843ENa
1.5 Cleaning
Before cleaning the equipment ensure that all ac and dc supplies, current transformer and
voltage transformer connections are isolated to prevent any chance of an electric shock
whilst cleaning.
The equipment may be cleaned using a lint-free cloth moistened with clean water. The use
of detergents, solvents or abrasive cleaners is not recommended as they may damage the
relay’s surface and leave a conductive residue.
MT
P63x/UK MT/A54 Maintenance
MT
Troubleshooting P63x/UK TS/A54
TROUBLESHOOTING
TS
TS
Troubleshooting P63x/UK TS/A54
CONTENTS
(TS) 11-
1. INTRODUCTION 3
3. POWER UP ERRORS 3
TS
P63x/UK TS/A54 Troubleshooting
TS
Troubleshooting P63x/UK TS/A54
1. INTRODUCTION
Before carrying out any work on the equipment, the user should be familiar with the
contents of the Safety Guide (SFTY/4L M/C11) or later issue, or the Safety and
Technical Data sections of this Technical Manual and also the ratings on the
equipment’s rating label.
The purpose of this section of the service manual is to allow an error condition on the relay
to be identified so that appropriate corrective action can be taken.
Should the relay have developed a fault, it should be possible in most cases to identify which
relay module requires attention. The Maintenance section (P63x/UK MT), advises on the
recommended method of repair where faulty modules need replacing. It is not possible to
perform an on-site repair to a faulted module.
In cases where a faulty relay/module is being returned to the manufacturer or one of their
approved service centers, completed copy of the Repair/Modification Return Authorization
Form located at the end of this section should be included.
Symptom Refer To
Relay fails to power up Section 3
Relay powers up - but indicates error and halts during
Section 4
power-up sequence
Relay powers up but Out of Service LED is illuminated Section 5
Error during normal operation Section 6
Mal-operation of the relay during testing Section 7
3. POWER UP ERRORS
If the relay does not appear to power up then the following procedure can be used to
determine whether the fault is in the external wiring, auxiliary fuse, power supply module of
the relay or the relay front panel.
• Checksum test (calculate actual ROM checksum and compare with stored checksum)
• Check hardware (test real time clock, test counters, test A/D converter)
• Check bus and fitted modules (identify device type, verify correct modules fitted:
type/version/location)
• Check “intelligent” devices on fitted modules (if applicable) (write/read DPRAM on comm
module or transient ground fault module)
• Check software (compare compatibility of device type, data model information, processor
operating system and protection and control software)
• The output relays are blocked (021.014 OUTP: USER Outp rel Block = Yes);
• The trip command is blocked (021.012 MAIN: Trip Cmd.Block. USER = Yes).
Furthermore the setting (021.031 MAIN: Fct Assign Fault) may be used to allocate additional
internal alarms/errors to raise the blocked/faulty signal for high prior alarming of operational
personnel. A typical example is to configure the system alarm “CHECK: Error Kxx” with Kxx
being the output relay on which the trip command is configured. Please note that the
configuration of any signal to 021.031 only raises the “blocked/faulty” signal but does not
cause any blocking of protection or control functions.
Device Action
Menu Text
On First Instance Subsequent Action
Measurements + Tests\Measurements\Log. State Signals
CHECK: Faulty DSP
CHECK: Invalid SW Vers. DSP
CHECK: Warm Restart Exec.
CHECK: Cold Restart Exec.
CHECK: Cold Restart Warm restart Device blocking
TS CHECK: Cold Rest /SW Update Warm restart Device blocking
CHECK: Blocking /HW Failure - -
CHECK: Relay Kxx Faulty - -
CHECK: Hardware Clock Fail - -
CHECK: Battery Failure - -
CHECK: Invalid SW DnLoaded Warm restart Device blocking
CHECK: +15V Supply Faulty Warm restart Device blocking
CHECK: +24V Supply Faulty Warm restart Device blocking
CHECK: -15V Supply Faulty Warm restart Device blocking
CHECK: Wrong Module Slot 1 (…21) Warm restart Device blocking
CHECK: Defect.Module Slot 1 (…21) - -
CHECK: Module A DPR Faulty - -
Troubleshooting P63x/UK TS/A54
Device Action
Menu Text
On First Instance Subsequent Action
CHECK: Module A RAM Faulty - -
CHECK: Module Y DPR Faulty - -
CHECK: Module Y RAM Faulty - -
CHECK: Error K 1201 (…2008) - -
CHECK: Undefined Op Code Warm restart Device blocking
CHECK: Invalid Op Warm restart Device blocking
CHECK: Undefined Interrupt Warm restart Device blocking
CHECK: Exception Oper.Syst. Warm restart Device blocking
CHECK: Protection Failure Warm restart Device blocking
CHECK: Checksum Sett Error Warm restart Device blocking
CHECK: Clock Sync. Error - -
CHECK: Interm Volt Fail RAM Warm restart Device blocking
CHECK: Overflow MT_RC - -
CHECK: Semaph. MT_RC Block - -
CHECK: Inval. SW vers.comm. - -
CHECK: Invalid SW Vers. Y - -
CHECK: Time-out Module Y
CHECK: M.c.b. Trip V Blocking of f<> and V<> protection
CHECK: CT Fail Alarm
CHECK: CT Fail Alarm, end a
CHECK: CT Fail Alarm, end b
CHECK: CT Fail Alarm, end c
CHECK: CT Fail Alarm, end d
CHECK: Invalid Charact. V/f
CHECK: Invalid Scaling A-1 Fault dependent
CHECK: Invalid Scaling A-2 Fault dependent
CHECK: Invalid Scaling IDC Fault dependent TS
CHECK: PT100 open Circuit Fault dependent
CHECK: Overload 20 mA input Fault dependent
CHECK: Open Circ. 20mA inp. Fault dependent
CHECK: Setting Error f<> Blocking of f<> protection
CHECK: Iref, a Inval. Range Device blocking
CHECK: Output 30 - -
CHECK: Output 31 - -
CHECK: Output 32 - -
CHECK: Output 30 (t) - -
CHECK: Output 31 (t) - -
CHECK: Output 32 (t) - -
CHECK: Iref, b Inval. Range Device blocking
P63x/UK TS/A54 Troubleshooting
Device Action
Menu Text
On First Instance Subsequent Action
CHECK: Iref, c Inval. Range Device blocking
CHECK: Iref, d Inval. Range Device blocking
CHECK: Matching Fail. end a Device blocking
CHECK: Matching Fail. end b Device blocking
CHECK: Matching Fail. end c Device blocking
CHECK: Matching Fail. end d Device blocking
CHECK: Ratio mtch.Fact.inv. Device blocking
CHECK: 2nd Match.Fact. inv. Device blocking
CHECK: Inv.Range Iref REF_1 Device blocking
CHECK: Inv.Range Iref REF_2 Device blocking
CHECK: Inv.Range Iref REF_3 Device blocking
CHECK: Match.f. kam,N REF_1 Device blocking
CHECK: Match.f. kam,N REF_2 Device blocking
CHECK: Match.f. kam,N REF_3 Device blocking
CHECK: Match.f. kam,Y REF_1 Device blocking
CHECK: Match.f. kam,Y REF_2 Device blocking
CHECK: Match.f. kam,Y REF_3 Device blocking
CHECK: Rat Mtch f inv REF_1 Device blocking
CHECK: Rat Mtch f inv REF_2 Device blocking
CHECK: Rat Mtch f inv REF_3 Device blocking
CHECK: Min Mtch f inv REF_1 Device blocking
CHECK: Min Mtch f inv REF_2 Device blocking
CHECK: Min Mtch f inv REF_3 Device blocking
CHECK: CTA Error THRM1 - -
CHECK: CTA Error THRM2 - -
CHECK: Setting Error THRM1 Blocking of THRM1 protection
TS CHECK: Setting Error THRM2 Blocking of THRM2 protection
CHECK: Inv Inp f Clock Sync Clock synchronization failure
• High: Energized
TS
P63x/UK TS/A54 Troubleshooting
4. Receive from local service contact, the information required to ship the product
Your local service contact will provide you with all the information:
¾ Pricing details
¾ RMA n°
¾ Repair center address
If required, an acceptance of the quote must be delivered before going to next stage.
TS
5. Send the product to the repair center
¾ Address the shipment to the repair center specified by your local contact
¾ Ensure all items are protected by appropriate packaging: anti-static bag and foam
protection
¾ Ensure a copy of the import invoice is attached with the unit being returned
¾ Ensure a copy of the RMA form is attached with the unit being returned
¾ E-mail or fax a copy of the import invoice and airway bill document to your local
contact
Troubleshooting P63x/UK TS/A54
NORTH AMERICA
Tel: (1) 450 923 7084
Canada CANADA : Brossard
Fax: (1) 450 923 9571
CENTRAL AMERICA
Anguilla, Antigua &
Barbuda, Aruba,
Barbados, Belize,
Cayman Islands,
Colombia, Costa Rica,
Cuba, Dominica,
Dominican Republic,
El Salvador, Grenada,
Guatemala, Guyana,
Honduras, Jamaica, Tel: (52) 55 5387 4309
Kiribati, Mexico, MEXICO : support.automation-mexico@areva-td.com
Montserrat, Netherlands Fax: (52) 55 5387 4317
Antilles, Nicaragua,
Panama, Republic of
Haiti, Saint Kitts & Nevis,
Santa Lucia, Saint
Vincent and the
Grenadines, Suriname,
Trinidad and Tobago,
Turks and Caicos Islands,
Venezuela.
SOUTH AMERICA
Argentina, Bolivia, Brazil,
Chile, Ecuador, Falkland Tel: (55) 11 3491 7271
BRAZIL : Sao Paulo automationrepair.southamerica@areva-td.com
Islands, Paraguay, Peru, Fax: (55) 11 3491 7256
Uruguay.
EUROPE
(MEDITERRANEAN)
Albania, Andorra,
Belgium, Bulgaria, Bosnia
and Herzegovinia,
Croatia, Cyprus, France, Tel: (33) 4 67 20 55 55
French DOM-TOM, FRANCE : Lattes automationrepair.medaf@areva-td.com
Greece, Israel, Fax: (33) 4 67 20 56 00
Macedonia, Malta,
Mauritius, Romania,
Yugoslavia.
EUROPE (EAST)
EUROPE (NORTH)
UNITED KINGDOM
EUROPE (OTHER)
Tel: (39) 0345 28 111
Italy ITALY : Bergamo automationrepair.italy@areva-td.com
Fax: (39) 0345 22 590
AFRICA
Tel: (33) 4 67 20 55 55
All African countries FRANCE : Lattes automationrepair.medaf@areva-td.com
Fax: (33) 4 67 20 56 00
MIDDLE EAST
ASIA
Tel: (971) 6556 0559
Afghanistan, Pakistan UAE : Dubai automationrepair.middleeast@areva-td.com
Fax: (971) 6556 1082
EASTERN ASIA
Bangladesh, British Indian
Ocean Territory, Brunei,
Cambodia, Cocos Islands,
Democratic People’s
Republic of Korea, East
Timor, Hong Kong,
Indonesia, Japan, Laos, Tel: (65) 6749 0777
SINGAPORE : automationrepair.seasia@areva-td.com
Macau, Malaysia, Fax: (65) 6846 1796
Myanmar, Palau, Papua
New Guinea, Philippines,
Singapore, Solomon
Islands, South Korea,
Taiwan, Thailand,
Tokelau, Tuvalu, Vietnam.
OCEANIA
TS American Samoa,
Australia, Christmas
Islands, Cook Islands, Fiji,
Guam, Heard and Mac
Donalds Islands, Marshall Tel: (61) 2 9739 3071
AUSTRALIA : Sydney automationrepair.pacific@areva-td.com
Islands, Micronesia, Fax: (61) 2 9739 3092
Nauru, New Zealand,
Niue, Norfolk Island,
Northern Mariana Islands,
Pitcairn, Samoa, Vanuatu.
REPAIR/MODIFICATION RETURN AUTHORIZATION FORM
Retrofit
Warranty
Paid service
Wrong supply
Name:
Telephone No.:
Fax No.:
E-mail:
IDENTIFICATION OF UNIT
Fields marked (M) are mandatory, delays in return will occur if not completed.
FAULT INFORMATION
Other:
Fault Reproducibility
Fault persists after removing, checking on test bench
Fault persists after re-energization
Intermittent fault
Description of Failure Observed or Modification Required - Please be specific (M)
Would you like us to install an updated firmware version after repair? Yes No
E-mail: E-mail:
REPAIR TERMS
1. Please ensure that a copy of the import invoice is attached with the returned unit, together with the
airway bill document. Please fax/e-mail a copy of the appropriate documentation (M).
2. Please ensure the Purchase Order is released, for paid service, to allow the unit to be shipped.
3. Submission of equipment to AREVA T&D is deemed as authorization to repair and acceptance of quote.
4. Please ensure all items returned are marked as Returned for ‘Repair/Modification’ and protected by
appropriate packaging (anti-static bag for each board and foam protection).
SCADA Communications P63x/UK SC/A54
SCADA COMMUNICATIONS
SC
SC
SCADA Communications P63x/UK SC/A54
CONTENTS
(SC) 12-
1. COURIER INTERFACE 5
1.1 Courier communication settings 5
2. MODBUS INTERFACE 11
2.1 MODBUS communication settings 11
2.6 Procedures 15
3.3 Initialization 33
3.8 Commands 33
4. DNP3.0 INTERFACE 35
4.1 DNP3.0 communication settings 35
4.3.1 General 38
4.5.1 Startup 45
5.7 Communication with the operating program MiCOM S1 via the Ethernet interface 50
FIGURES
SC
SCADA Communications P63x/UK SC/A54
1. COURIER INTERFACE
A general description of the Courier protocol can be found in the Courier specification.
The Px30 series supports Courier over EIA(RS)485 connection (d.c., polarity-sensitive), not
the K-BUS format which is a transformer-coupled "a.c." connection.
Set/Conf/COMM1
Remote Comms Port1
Address: 056 026
Enabled
Canceling function group COMM1 or including it in the configuration. If the function group is
cancelled, then all associated settings and signals are hidden, with the exception of this
setting.
Set/Conf/COMM1
General Enable USER
Address: 003 170
Yes
Set/Conf/COMM1
COURIER Enable
Address: 103 040
Yes
Set/Conf/COMM1
Communicat Protocol
Address: 003 167
COMM1
COURIER
Select the communication protocol that shall be used for the communication interface. SC
Note: The above 4 settings must be set as shown to enable the Courier
protocol. The following settings are used to configure the Courier
protocol and will be dependant upon the system within which the
device will be communicating.
Set/Conf/COMM1
Baud Rate
Address: 003 071
19.2 kBaud
Set/Conf/COMM1
Parity Bit
Address: 003 171
Even
Set the same parity that is set at the interface of the control unit connected to the P63x.
Set/Conf/COMM1
Octet Comm. Address
Address: 003 072
1
The unique communication address used to identify the device over communications via the
rear port.
Values in the P63x device data model which are to be made available to the Courier protocol
must be configured using the following settings:
Set/Conf/COMM1
Command Selection
Address: 103 042
↓
The above setting is used to select from an “m out of n” selection table all the binary
commands (read/write) which are to be made available to the Courier master (e.g. ‘Device
online’).
Set/Conf/COMM1
Signal Selection
Address: 103 043
↓
The above setting is used to select from an “m out of n” selection table all the binary signals
(read only) which are to be made available to the Courier master (e.g. ’Starting I>’).
Set/Conf/COMM1
Meas. val. Selection
Address: 103 044
↓
The above setting is used to select from an “m out of n” selection table all the analog
measurements (read only) which are to be made available to the Courier master (e.g.
’Running time’).
Set/Conf/COMM1
Parameter Selection
Address: 103 045
↓
SC The above setting is used to select from an “m out of n” selection table all the analog settings
(read/write) which are to be made available to the Courier master (e.g. ’tI>’).
The selected data items are written to four lists in the order in which they have been selected
and the Courier master can access any of the information which has been configured in this
way. In the Courier protocol these lists are referred to as “columns”. The entries in the lists
are numbered consecutively. In the Courier protocol these numbers are referred to as
“rows”.
In the Courier protocol each data item is called a “cell”. It is addressed by its column and
row. The first cell in each list (row 0) is called a “heading” and it contains only the text of the
corresponding P63x device data model configuration setting.
Some system data information is always accessible to the Courier master but cannot be
changed.
SCADA Communications P63x/UK SC/A54
cell 00.00 cell 10.00 cell 20.00 cell 30.00 cell 40.00
… cell 10.01 cell 20.01 cell 30.01 …
… … … … …
… … … … …
cell 00.08 … … … cell 40.nn
… … …
cell 10.nn … cell 30.nn
…
cell 20.nn
System data cells have fixed Courier addresses (column, row). In the Courier
implementation for P63x devices the data has been simulated because the data does not
exist in the required format in the P63x device data model. The implemented data items are
as follows:
The Courier master displays the value according to the formatting information (number of
decimal places, sign etc.).
Cell description text for a cell which contains a text:
Note: The unit in the P63x device data model is up to 10 characters long.
However, the Courier master program PAS&T cannot handle texts of
this length and so the last 5 characters of the unit field are truncated.
A text which is used as the contents of a cell is 26 characters long. Space has been
reserved for future use for the function group:
The length is the number of bytes in the information field. The checksum is the byte sum of
all bytes in the information field.
SCADA Communications P63x/UK SC/A54
The control byte in a message from the Courier master to a P63x slave device has either the
value “7B” (hex) or “5B” (hex). The FCB (frame check bit, bit 5) is set to “1” in the first
message from the master (‘Reset Remote Link’ command) and is toggled in each
subsequent message, meaning that the control byte alternates between “7B” and “5B”. By
evaluating this byte it is possible for a P63x slave device to detect that a message has been
lost. In response messages to the Courier master the control byte is always set to “08”.
Code
Command Description
(hex)
.. Reset Remote Link Reset/start communication in slave device
10 Poll Buffer Poll for last command while device busy
11 Poll Status Poll for status only
12 Get Text Get text for menu location
14 Get Value Read the value of a menu location
15 Enter Setting Mode Get setting limits and enter setting mode
16 Get Column Headings Read all column headings
17 Get Column Text Read all texts for a menu column
18 Get Column Values Read all values for a menu column
19 Get Strings Get setting strings for a menu location
21 Send Block Send next block in a blocked transaction
23 Send Event Send and event
24 Accept Event Acknowledge receipt of event SC
40 Preload Setting Preload a new value before setting
45 Set Real Time Set the devices real time clock
4A Abort Setting Abort the current setting
4E Execute Setting Execute the preloaded setting
Using these commands it is possible to read any information from a P63x device data model
which has been configured to be accessible to the Courier master. Courier events (i.e.
changes in the value of a cell or stored fault values) can be read out from a slave device.
The data and time can be changed so that timestamps in messages from slave devices are
synchronized.
P63x/UK SC/A54 SCADA Communications
SC Each event must be acknowledged by the Courier master with an ‘Accept Event’ command,
otherwise the event remains in the event buffer until a subsequent ‘Send Event’ command
followed by an ‘Accept Event’ command is received.
2. MODBUS INTERFACE
The MODBUS interface is a master/slave protocol and it is defined by MODBUS.org: See
www.modbus.org
MODBUS Serial Protocol Reference Guide: PI-MBUS-300 Rev. E
Set/Conf/COMM1
Remote Comms Port1
Address: 056 026
Enabled
Canceling function group COMM1 or including it in the configuration. If the function group is
cancelled, then all associated settings and signals are hidden, with the exception of this
setting.
Set/Conf/COMM1
General Enable USER
Address: 003 170
Yes
Set/Conf/COMM1
MODBUS Enable
Address: 003 220
Yes
Select the communication protocol that shall be used for the communication interface.
Note: The above 4 settings must be set as shown to enable the MODBUS
protocol. The following settings are used to configure the MODBUS
protocol and will be dependant upon the system within which the
device will be communicating.
P63x/UK SC/A54 SCADA Communications
Set/Conf/COMM1
Baud Rate
Address: 003 071
19.2 kBaud
Set/Conf/COMM1
Parity Bit
Address: 003 171
Even
Set the same parity that is set at the interface of the control unit connected to the P63x.
Set/Conf/COMM1
Octet Comm. Address
Address: 003 072
1
The unique communication address used to identify the device over communications via the
rear port.
The following device setting is used to select which MODBUS variant is to be used.
Set/Conf/COMM1
MODBUS Variant
Address: 003 214
ALSTOM D
• ALSTOM
• ALSTOM D
The main difference between the two variants is the allocation of the MODBUS registers.
The first command in the actual configured list of “Reg.asg. Selec. Cmds” is addressable by
the “ALSTOM D” MODBUS register 00301, the second by 00302, etc. The first measurement
SC value by 30301, etc.
MODBUS register areas are defined contiguously so that more than one item of information
may be accessed in a single query.
Values in the device data model which are to be made available to the MODBUS protocol
must be configured using the following settings:
Set/Conf/COMM1
Reg.asg. Selec. Cmds
Address: 003 210
↓
This setting is used to select from an “m out of n” selection table all the binary commands
(read/write) which are to be made available to the MODBUS master.
SCADA Communications P63x/UK SC/A54
Set/Conf/COMM1
Reg.asg. Selec. Sig.
Address: 003 211
↓
This setting is used to select from an “m out of n” selection table all the binary signals (read
only) which are to be made available to the MODBUS master.
Set/Conf/COMM1
Reg.asg. Sel. m.val.
Address: 003 212
↓
This setting is used to select from an “m out of n” selection table all the analog
measurements (read only) which are to be made available to the MODBUS master.
Set/Conf/COMM1
Reg.asg. Sel. Param.
Address: 003 213
↓
This setting is used to select from an “m out of n” selection table all the analog settings
(read/write) which are to be made available to the MODBUS master.
In the case of MODBUS variant “ALSTOM”, the following setting is used to define whether
automatic event acknowledgement is to be used.
Set/Conf/COMM1
Autom Event Confirm.
Address: 003 249
Disabled
The following setting is used to configure the behavior of the device when refreshing
measurement values:
Set/Conf/COMM1
Delta t (MODBUS)
Address: 003 152
5 s
This setting defines the time in seconds after which measurement values are refreshed by
the protection software in the device. The value of this setting should be chosen carefully
because changes in the value of a measurement within the configured time period are not
registered.
• If the slave device receives the query without a communication error and can handle the
query normally, it returns a normal response
• If the slave does not receive the query due to a communication error, no response is
returned
• If the slave receives the query but detects a communication error (parity or CRC), no
response is returned
• If the slave receives the query without a communication error, but cannot handle it (for
example if the request is to a non-existent coil or register), the slave returns an exception
response informing the master of the nature of the error. In exception responses, the
slave sets the most-significant bit of the function code to 1
SCADA Communications P63x/UK SC/A54
Code
Name Meaning
(dec)
The function code received in the query is not
01 Illegal Function
an allowable action for the slave
The data address received in the query is not
02 Illegal Data Address
an allowable address for the slave
A value contained in the query is not an
03 Illegal Data Value
allowable value for the slave
04 Slave Device Failure The slave has an internal communication error
The slave is processing a long duration
06 Slave Device Busy
command
2.6 Procedures
For this MODBUS variant there are two possible modes for event transmission:
MODUS MODUS
Master Slave
Read Event
Send Event
P1927ENa
QUERY RESPONSE
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 36 (hex) Byte Count (Data) 12 (hex)
Starting Address Lo 00 (hex) Data 1 Hi Event
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 09 (hex) …
CRC Lo xx Data 9 Hi
CRC Hi xx Data 9 Lo
CRC Lo xx
CRC Hi xx
Acknowledging an Event
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 06 Function Code 06
Register Address Hi 04 (hex) Register Address Hi 04 (hex)
Register Address Lo 00 (hex) Register Address Lo 00 (hex)
Preset Data Hi 20 (hex) Preset Data Hi 20 (hex)
Preset Data Lo 00 (hex) Preset Data Lo 00 (hex)
CRC Lo xx CRC Lo xx
CRC Hi xx CRC Hi xx
Event Structure
Data 1 Reserved
Data 2 Value
Data 3 Register
Data 4 Reserved
Data 5 Time stamp (inverted CP56Time2a)
Data 6
Data 7
SC
Data 8
Data 9 Reserved
The following figure shows the basic logic for event transmission with automatic
acknowledgement:
MODUS MODUS
Master Slave
Read Event
Send Event
P1928ENa
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 07 Function Code 07
CRC Lo xx Coil Data Bit 2 = 1
CRC Hi xx CRC Lo xx
CRC Hi xx
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 36 (hex) Byte Count (Data) 12 (hex)
Starting Address Lo 00 / 01 (hex) Data 1 Hi Event
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 09 (hex) …
CRC Lo xx Data 9 Hi
SC CRC Hi xx Data 9 Lo
CRC Lo xx
CRC Hi xx
SCADA Communications P63x/UK SC/A54
Event Structure
Data 1 Reserved
Data 2 Value
Data 3 Register
Data 4 Reserved
Data 5 Time stamp (inverted CP56Time2a)
Data 6
Data 7
Data 8
Data 9 Reserved
Register
Register Content Meaning
(dec)
Number of Events 30101 Number of events in ring buffer
Hi: default = 0, buffer overflow = FF (hex)
Function Code 30102
Lo: function code depending on register range
Event Register Number 30103 Register or bit address of the event
Binary: bit 0 = value, bit 1 to 15 = 0
Event Data 30104
Analog: register contents
Year 30105 Event time stamp
Month/Day 30106
Hour/Minute 30107
Milliseconds 30108
Register SC
Register Content Meaning
(dec)
Event command register
0000 (hex) - Read next event
Event command 40005
0001 (hex) - Reread last event
FFFF (hex) - Delete ring buffer
The ‘number of events’ register 30101 (dec) contains the number of event messages
currently stored in the ring buffer. The master can cyclically poll this register to check for
events. Registers 30102 (dec) to 30108 (dec) contain the data from the last event which
was read.
The event command is initialized to 0.
P63x/UK SC/A54 SCADA Communications
When registers 30101 (dec) to 30108 (dec) have been read and there is at least one event
present in the ring buffer, the oldest event is copied to these registers and the number of
events is decremented.
The master can reread the previous event by setting the event command register to 0001
(hex). This is useful when a transmission error has occurred.
The master can also reread registers outside the range 30101 (dec) to 30108 (dec).
• File upload
Recorded Data Upload by Column
The following figure shows the basic logic for mode ‘upload by column’:
SC
SCADA Communications P63x/UK SC/A54
MODUS MODUS
Master Slave
...
...
...
...
...
...
P1929ENa
SC
Figure 3: Logic for transmission of recorded data in mode ‘upload by column’
The following tables show the contents of the messages for mode ‘upload by column’:
Reading and Sending the Device Status (Recorded Data Present)
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 07 Function Code 07
CRC Lo xx Coil Data Bit 4 = 1
CRC Hi xx CRC Lo xx
CRC Hi xx
P63x/UK SC/A54 SCADA Communications
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 60 (hex) Byte Count (Data) 0C (hex)
Starting Address Lo 00 (hex) Data 1 Hi
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 06 (hex) …
CRC Lo xx Data 6 Hi
CRC Hi xx Data 6 Lo
CRC Lo xx
CRC Hi xx
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
Reading and Sending of the Data for a Channel
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi Channel inf. Byte Count (Data) 1C (hex)
Starting Address Lo register Data 1 Hi Channel data
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 0E (hex) …
SC CRC Lo xx Data 14 Hi
CRC Hi xx Data 14 Lo
CRC Lo xx
CRC Hi xx
SCADA Communications P63x/UK SC/A54
Contents of the ‘Channel Type’ Field (Channel Information Data Item 14)
Value Meaning
1 IA
2 IB
3 IC
4 IN
5 VA-G
6 VB-G
7 VC-G
8 VN-G
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
Reading and Sending a Block of Samples for a Channel
QUERY RESPONSE
Slave Address xx Slave Address xx SC
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi Byte Count (Data) xx
Block register
Starting Address Lo Data 1 Hi
Value of sample 1
No. of Points Hi No. of samples Data 1 Lo
No. of Points Lo in block …
CRC Lo xx Data n Hi
Value of sample n
CRC Hi xx Data n Lo
CRC Lo xx
CRC Hi xx
P63x/UK SC/A54 SCADA Communications
When a block of samples for a channel is read, all samples must be read. This means that
the number of samples is always 100. For the last block, the number of samples is the value
in the field ‘number of samples in last block’ (channel information data item 12).
A primary measurement value is calculated by multiplying the value of the sample by the
internal scaling factor of the voltage or current.
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
Reading and Sending the Recording Index
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 61 (hex) Byte Count (Data) 12 (hex)
Starting Address Lo 80 (hex) Data 1 Hi
Recording index
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 09 (hex) …
CRC Lo xx Data 9 Hi
CRC Hi xx Data 9 Lo
CRC Lo xx
CRC Hi xx
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
SC Sending and Confirming Acknowledgement of Reading of Recording
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 06 Function Code 06
Register Address Hi 04 (hex) Register Address Hi 04 (hex)
Register Address Lo 00 (hex) Register Address Lo 00 (hex)
Preset Data Hi 10 (hex) Preset Data Hi 10 (hex)
Preset Data Lo 00 (hex) Preset Data Lo 00 (hex)
CRC Lo xx CRC Lo xx
CRC Hi xx CRC Hi xx
SCADA Communications P63x/UK SC/A54
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
File Upload
The following figure shows the basic logic for mode ‘file upload’:
MODUS MODUS
Master Slave
Read Header
Send Header
...
...
P1930ENa
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 07 Function Code 07
SC
CRC Lo xx Coil Data Bit 4 = 1
CRC Hi xx CRC Lo xx
CRC Hi xx
P63x/UK SC/A54 SCADA Communications
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 61 (hex) Byte Count (Data) 30 (hex)
Starting Address Lo 90 (hex) Data 1 Hi Header
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 18 (hex) …
CRC Lo xx Data 24 Hi
CRC Hi xx Data 24 Lo
CRC Lo xx
CRC Hi xx
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
SCADA Communications P63x/UK SC/A54
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi 61 (hex) Byte Count (Data) 48 (hex)
Starting Address Lo B0 (hex) Data 1 Hi Channel inf.
No. of Points Hi 00 (hex) Data 1 Lo
No. of Points Lo 24 (hex) …
CRC Lo xx Data 36 Hi
CRC Hi xx Data 36 Lo
CRC Lo xx
CRC Hi xx
Contents of the ‘Channel Type’ Field (Channel Information Data Items 2, 6, 10, 14, 18, 22,
26, 30)
Value Meaning
1 IA
2 IB
3 IC
4 IN
5 VA-G
6 VB-G
7 VC-G
8 VN-G
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
Reading and Sending a Block of Samples
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 03 or 04 Function Code 03 or 04
Starting Address Hi Byte Count (Data) xx
Block register
Starting Address Lo Data 1 Hi Value of sample
No. of Points Hi Data 1 Lo 1
No. of samples
No. of Points Lo in block …
SC CRC Lo xx Data n Hi Value of sample
CRC Hi xx Data n Lo n
CRC Lo xx
CRC Hi xx
When a block of samples for a channel is read, all samples must be read. This means that
the number of samples is always 100, with the exception of the last block which may have
fewer samples.
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
SCADA Communications P63x/UK SC/A54
QUERY RESPONSE
Slave Address xx Slave Address xx
Function Code 06 Function Code 06
Register Address Hi 04 (hex) Register Address Hi 04 (hex)
Register Address Lo 00 (hex) Register Address Lo 00 (hex)
Preset Data Hi 10 (hex) Preset Data Hi 10 (hex)
Preset Data Lo 00 (hex) Preset Data Lo 00 (hex)
CRC Lo xx CRC Lo xx
CRC Hi xx CRC Hi xx
If the slave device has no events to send, it will respond with an exception response code 04
(see 2.5.1 Exception codes).
• Binary data
• Disturbance measurements
• Analog samples
Transmission of recorded data is done by reading the disturbance or long-time recording
information from the recorded data registers and by writing the command or
acknowledgement messages to the recorded data command registers.
The following registers are used for the transmission of recorded data:
Recorded Data Message Registers
Register
Register Content Meaning
(dec)
Transfer command register
0000 (hex) - Read next message
Command 40006
0001 (hex) - Reread previous message
FFFF (hex) - Initialize transfer
P63x/UK SC/A54 SCADA Communications
The messages for information transfer are kept in a ring buffer. The number of messages
can be read from register 30110 (dec). After initialization, the message ‘list of recordings’ is
present in the ring buffer.
The procedures for reading from the recorded data message registers use the same
mechanisms as the event handling logic, depending on the contents of the recorded data
command register. The next message can be read by writing a read command to registers
30110 (dec) to 30132 (dec).
The MODBUS master writes ASDU 24 (‘recorded data transfer order’) and ASDU 25
(‘recorded data transfer acknowledgement’) commands to the recorded data order registers
in IEC 60870-5-103 format.
SC
SCADA Communications P63x/UK SC/A54
− Initialization (reset)
− Time synchronization
− General interrogation
− Cyclic measurements
− General commands
− Private codes
Set/Conf/COMM1
Remote Comms Port1
Address: 056 026
Enabled
Canceling function group COMM1 or including it in the configuration. If the function group is
cancelled, then all associated settings and signals are hidden, with the exception of this
SC
setting.
Set/Conf/COMM1
General Enable USER
Address: 003 170
Yes
Set/Conf/COMM1
IEC870-5 Enabled
Address: 003 215
Yes
Set/Conf/COMM1
Communicat Protocol
Address: 003 167
COMM1
IEC 870-5-103
Select the communication protocol that shall be used for the communication interface.
Set/Conf/COMM1
Baud Rate
Address: 003 071
19.2 kBaud
Set/Conf/COMM1
Parity Bit
Address: 003 171
Even
Set the same parity that is set at the interface of the control unit connected to the P63x.
Set/Conf/COMM1
Octet Comm. Address
Address: 003 072
1
The unique communication address used to identify the device over communications via the
rear port.
Values in the P63x device data model which are to be made available to the
IEC 60870-5-103 protocol must be configured using the following settings:
Set/Conf/COMM1
Select. Spontan.Sig.
Address: 003 179
↓
The above setting is used to select from an “m out of n” selection table all the binary signals
(read only) which are to be made available to the IEC 60870-5-103 master (e.g. ’Starting I>’).
Set/Conf/COMM1
Cycl. Data ILS Tel.
Address: 003 175
SC ↓
The above setting is used to select from an “m out of n” selection table all the analog
measurements (read only) which are to be made available to the IEC 60870-5-103 master
(e.g. ’Running time’).
3.3 Initialization
Whenever the relay has been powered up, or if the communication settings have been
changed a reset command is required to initialize the communications. The relay will
respond to either of the two reset commands (Reset CU or Reset FCB), the difference being
that the Reset CU will clear any unsent messages in the relay’s transmit buffer.
The relay will respond to the reset command with an identification message ASDU 5, the
Cause of Transmission COT of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command. The content of ASDU 5 is described in the
IEC 60870-5-103 section of the “ACA” document noted above.
In addition to the above identification message, if the relay has been powered up it will also
produce a power up event.
Set/Conf/MAIN
Prim.Source TimeSync
Address: 103 210
− Function type
− Information number
The IEC 60870-5-103 profile in the Telegram documentation contains a complete listing of all
events produced by the relay.
3.8 Commands
A list of the supported commands is contained in the Telegram documentation. The relay
will respond to other commands with an ASDU 1, with a Cause of Transmission (COT)
indicating ‘negative acknowledgement’.
P63x/UK SC/A54 SCADA Communications
SC
SCADA Communications P63x/UK SC/A54
4. DNP3.0 INTERFACE
The DNP3.0 protocol is not described in its entirety here, please refer to the documentation
available from the user group. The device profile document specifies the full details of the
DNP3.0 implementation for the relay. This is the standard format DNP3.0 document that
specifies which objects, variations and qualifiers are supported. The device profile document
also specifies what data is available from the relay via DNP3.0. The relay operates as a
DNP3.0 slave and supports subset level 2 of the protocol.
Set/Conf/COMM1
Remote Comms Port1
Address: 056 026
Enabled
Canceling function group COMM1 or including it in the configuration. If the function group is
cancelled, then all associated settings and signals are hidden, with the exception of this
setting.
Set/Conf/COMM1
General Enable USER
Address: 003 170
Yes
Set/Conf/COMM1
DNP3 Enable
Address: 003 231
Yes
Set/Conf/COMM1
Communicat Protocol
Address: 003 167
COMM1 SC
DNP3
Select the communication protocol that shall be used for the communication interface.
Note: The above 4 settings must be set as shown to enable the DNP3.0
protocol. The following settings are used to configure the DNP 3.0
protocol and will be dependant upon the system within which the
device will be communicating.
Set/Conf/COMM1
Baud Rate
Address: 003 071
19.2 kBaud
Set/Conf/COMM1
Parity Bit
Address: 003 171
Even
Set the same parity that is set at the interface of the control unit connected to the P63x.
Set/Conf/COMM1
Octet Comm. Address
Address: 003 072
1
The unique communication address used to identify the device over communications via the
rear port.
All values in the device data model which are to be made available to the DNP3.0 protocol
must be configured using the following settings:
Set/Conf/COMM1
Ind./cl. bin. Inputs
Address: 003 232
↓
This setting is used to select from an “m out of n” selection table all the binary signals (read
only) which are to be made available to the DNP3.0 master. A data class may be assigned
to each selected item (no class, or class 0 to 3).
Set/Conf/COMM1
Ind./cl. bin.Outputs
Address: 003 233
↓
This setting is used to select from an “m out of n” selection table all the binary commands
(read/write) from the device data model which are to be made available to the DNP3.0
master. Since all “m out of n” settings use the same software mechanism, a data class may
be assigned to each selected item, but data classes 1 to 3 are not evaluated.
Set/Conf/COMM1
Ind./cl. Analog Inp.
Address: 003 235
↓
This setting is used to select from an “m out of n” selection table all the analog
measurements (read only) from the device data model which are to be made available to the
DNP3.0 master. A data class may be assigned to each selected item (no class, or class 0 to
3).
Set/Conf/COMM1
Ind./cl. Analog Outp
SC Address: 003 236
↓
This setting is used to select from an “m out of n” selection table all the analog settings
(read/write) from the device data model which are to be made available to the DNP3.0
master. Since all “m out of n” settings use the same software mechanism, a data class may
be assigned to each selected item, but data classes 1 to 3 are not evaluated.
The data class defines the event reporting behavior and allows the user to retrieve data by
class as well as by data type.
SCADA Communications P63x/UK SC/A54
Two settings are used to configure the behavior of the device when refreshing measurement
values:
Set/Conf/COMM1
Ph-Ph Meas v.(DNP3)
Address: 003 250
16
The value of this setting is used as the default reporting deadband for all measurements.
The master can change the reporting deadband value for each measurement individually. A
measurement is reported only when its value changes by a magnitude greater than the
configured value.
Set/Conf/COMM1
PhasePhase t (DNP3)
Address: 003 248
5 s
This setting defines the time in seconds after which measurement values are refreshed by
the device. The value of this setting should be chosen carefully because changes to a
measurement within the configured time period are not registered.
User Layer
Application Layer
Transport Layer
Data Link Layer
Physical Layer
In order to guarantee as far as possible that P63x devices conform to the DNP3.0 standard,
a library from Triangle MicroWorks Inc. has been used in the implementation of the software.
This library supports DNP 3.0 Level 2.
• Fiber optic
This document describes the specifics of the DNP3.0 implementation for P63x devices. The
document “DNP V3.00 Transport Functions” contains a detailed description of the transport
layer.
4.3.1 General
DNP3.0 uses the concept of data objects as an interface for devices which support the
DNP3.0 protocol. These objects have been defined in such a way that any device should be
able to map the data which it wants to make available to a DNP3.0 master to the data
objects which are defined in the protocol specification.
The master specifies variations when handling data objects (see the Device Profile
Document for a complete list of implemented data objects, variations, and function and
qualifier codes which use these objects).
The document “DNP V3:00 Data Object Library” contains a detailed description of the data
objects and their variations.
In the implementation for P63x devices only 2 types of data objects are supported:
• Static objects
Static objects reflect the current value of data items.
•
SC Event objects
Event objects are generated as a result of a data change, e.g. a signal or fault measurement.
Event data reflects the value of data at some time in the past, and is stored in a queue in the
device.
SCADA Communications P63x/UK SC/A54
The software reduces the size of data object 1 to the number of values selected from the “m
out of n” selection tables.
Every value can be assigned data class 0 (static) and data classes 1, 2 or 3 for the SC
corresponding event message. Assigning of the data class is done in the “m out of n”
selection list. If an event data class (1, 2 or 3) is selected, data class 0 is set implicitly. The
master can change the data class using the ‘Assign Class’ function.
These outputs represent binary settings (e.g. MAIN: Protection Enabled). The state of these
signals can be read in the binary output object.
Data object 10 is allocated as follows:
The software reduces the size of data object 10 to the number of values selected from the
“m out of n” selection tables.
Data class assignment is not relevant for data object 10.
(*) Note: These codes are currently only documented in a recommendation by the technical
committee.
The control relay output block information object offers a wide variety of possibilities for
controlling outputs. Among DNP vendors there are discussions about the interpretation of
control operations. The technical committee of the DNP Users Group has published a
number of recommendations in an attempt to improve compatibility.
The discussions have made clear that DNP masters on the market differ greatly in their
implementation of the control relay output block. An attempt has therefore been made to
offer as many possibilities as possible in order to achieve compatibility to as many masters
as possible.
Destination of Operation
2-pole OFF- 2-pole ON-
Operation Single Pole Logical Output contact/ contact/
Device (e.g. setting) transformer transformer
raise lower
set persistent
Pulse ON pulse on switch off/raise switch on/lower
logical 1
Pulse OFF not supported not supported not supported not supported
persistent output set persistent
Latch ON switch off/raise switch on/lower
on logical 1
persistent output set persistent
Latch OFF not supported not supported
off logical 0
Trip/Raise not supported not supported switch off/raise switch off/raise
Close/Low
not supported not supported switch on/lower switch on/lower
er
The software reduces the size of data object 10 to the number of values selected from the
“m out of n” selection tables.
The method of data class assignment is the same as for data object 1, except that only static
data class 0 may be assigned. This is because counter events are not supported.
The software reduces the size of data object 30 to the number of values selected from the
“m out of n” selection tables.
The method of data class assignment is the same as for data object 1.
P63x/UK SC/A54 SCADA Communications
Event Handling
• Normal measurements
Event handling is done using CURRENT mode, i.e. for each measurement only one entry
per change is made in the queue and identical entries are overwritten. An analog event has
the current value and timestamp at the time of the request.
The software reduces the size of data object 40 to the number of selected data points.
Data class assignment is not relevant to data object 40.
The analog output block is used for changing settings in a device. This is done in a similar
way to the control of a logical binary output, i.e. the command is echoed with status code set.
(*) Note: Freeze and clear functions are currently not implemented.
P63x/UK SC/A54 SCADA Communications
Any read errors are flagged in the internal indications in the response.
• Select a combination of bits which indicate the operations supported by a binary output
• Select a combination of bits which indicate the operations supported by an analog output
4.5.1 Startup
It is important to note that changes in the “m out of n” selection tables will result in the
initialization of the communications module of a device.
• Fault measurements
These are measurements which are calculated when a fault occurs (e.g. fault duration).
SOE mode is used, i.e. all events are stored in the queue.
An event message is generated only if the data is configured in one of the data classes 1 to
3. The allocation of data classes is done during configuration of the signals in the “m out of
n” selection lists.
• By the master sending the ‘Assign Class’ command (function code 22)
SC Assignment of classes 1, 2 and 3 (used for event messages) is mutually exclusive. All data
which is assigned a class 1, 2 or 3 is also implicitly assigned class 0.
The possible data classes are ‘No Class’, ‘Class 0’, ‘Class 1’, ‘Class 2’ or ‘Class 3’.
Below is a list of the default configuration and valid values for each data object:
Object No. (dec) Description Default Data Class Valid Data Classes
1 Binary Input 1 none, 0, 1, 2, 3
10 Binary Output none none
20 Binary Counter none none, 0
21 Frozen Counter none none, 0
30 Analog Input 2 none, 0, 1, 2, 3
40 Analog Output none none
SCADA Communications P63x/UK SC/A54
SC
P63x/UK SC/A54 SCADA Communications
• ICD file based on XML in the SCL (Substation Configuration Description Language) with
a description of data, properties and services, available from the device, that are to be
imported into the system configurator
The optional Ethernet module additionally provides a EIA(RS)485 interface for remote
access with the operating program MiCOM S1 (function group COMM2).
Notes: The P63x may only be equipped with the optional Ethernet module as
an alternative to the other optional communication modules.
Therefore the Ethernet based communication protocol IEC 61850 is
only available as an alternative to function group COMM1.
The Ethernet module can be applied in conjunction with all processor
modules P for P63x. The item numbers of these processor modules
are:
SCADA Communications P63x/UK SC/A54
5.7 Communication with the operating program MiCOM S1 via the Ethernet interface
Direct access by the operating program MiCOM S1 via the Ethernet interface on the device
may occur through the "tunneling principle". Transmission is carried out by an Ethernet
Standard Protocol, but this is only supported by the associated operating program MiCOM
S1 (specific manufacturer solution). Such transmission is accomplished over the same
hardware for the network, which is used for server-client communication and "GOOSE
Messages". Available are all the familiar functions offered by the operating program MiCOM
S1 such as reading/writing of settings or retrieving stored data.
SC
SCADA Communications P63x/UK SC/A54
SC
P63x/UK SC/A54 SCADA Communications
SC
SCADA Communications P63x/UK SC/A54
SC
Symbols and Glossary P63x/UK SG/A54
SG
Symbols and Glossary P63x/UK SG/A54
Logic Symbols
Symbols Explanation
t Time duration
V Voltage, potential difference
V Complex voltage
I Electrical current
I Complex current
Z Complex impedance
|Z| Modulus of complex impedance
f Frequency
δ Temperature in °C
Σ Sum, result
Ω Unit of electrical resistance
α Angle
Phase angle. With subscripts indicates a specific angle between a defined current
ϕ
and a defined voltage.
τ Time constant
ΔT Temperature difference in K
SG
P63x/UK SG/A54 Symbols and Glossary
Symbol Explanation
Components of a symbol
A symbol consists of a contour or contour combination and one or
more qualifiers.
Control block
A control block contains an input function common to several
symbols. It is used for the collective setting of several trigger
elements, for example.
Output block
An output block contains an output function common to several
symbols.
Static input
Only the state of the binary input variable is effective.
Symbols and Glossary P63x/UK SG/A54
Symbol Explanation
Dynamic input
Only the transition from value 0 to value 1 is effective.
Negation of an output
The value up to the border line is negated at the output.
Negation of an input
The input value is negated before the border line.
AND element
The output variable will be 1 only if all input variables are 1.
OR element
The output variable will be 1 only if at least one input variable is 1.
Threshold element
The output variable will be 1 only if at least two input variables are 1.
The number in the symbol may be replaced by any other number.
(m out of n) element
The output variable will be 1 only if just one input variable is 1.
Delay element
The transition from value 0 to 1 at the output occurs after a time delay
of t1 relative to the corresponding transition at the input.
The transition from value 1 to 0 at the output occurs after a time delay
of t2 relative to the corresponding transition at the input.
Monostable flip-flop
The output variable will be 1 only if the input variable changes to 1.
The output variable will remain 1 for 100 ms, independent of the SG
duration of the input value 1 (non-retriggerable).
Analog-digital converter
An analog input signal is converted to a binary signal.
P63x/UK SG/A54 Symbols and Glossary
Symbol Explanation
Subtractor
The output variable is the difference between the two input variables.
A summing element is obtained by changing the minus sign to a plus
sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
Non-stable flip-flop
When the input variable changes to 1, a pulse sequence is generated
at the output.
The ! to the left of the G indicates that the pulse sequence starts with
the input variable transition (synchronized start).
If there is a ! to the right of the G, the pulse sequence ends with the
ending of the 1 signal at the input (synchronized stop).
Amplifier
The output variable is 1 only if the input variable is also 1.
Counter
At the + input the input variable transitions from 0 to 1 are counted
and stored in the function block.
At the R(eset) input a transition of the input variable from 0 to 1
resets the counter to 0.
Electromechanical drive
In general, here a relay, for example.
Symbol Explanation
Change-over contact
With item identifier.
Special symbol
Output relay in normally-energized arrangement (‘closed-circuit
operation’).
PC interface
With pin connections.
SG
Multiplier
The output variable is the result of the multiplication of the two input
variables.
Divider
The output variable is the result of the division of the two input
variables.
P63x/UK SG/A54 Symbols and Glossary
Symbol Explanation
Comparator
The output variable becomes 1 only if the input variable(s) are equal
to the function in the function block.
Formula block
The output variable becomes 1 only if the input variable(s) satisfy the
equation in the function block.
SG
Installation P63x/UK IN/A54
INSTALLATION
IN
Installation P63x/UK IN/A54
CONTENTS
(IN) 14-
1. RECEIPT OF RELAYS 3
3. STORAGE 4
4. UNPACKING 4
5. RELAY MOUNTING 5
5.1 Rack mounting 5
6. RELAY WIRING 12
6.1 Medium and heavy duty ring terminal block connections 12
IN
Installation P63x/UK IN/A54
FIGURES
IN
Installation P63x/UK IN/A54
1. RECEIPT OF RELAYS
Upon receipt, relays should be examined immediately to ensure no external damage has
been sustained in transit. If damage has been sustained, a claim should be made to the
transport contractor and AREVA T&D should be promptly notified.
Relays that are supplied unmounted and not intended for immediate installation should be
returned to their protective polythene bags and delivery carton. Section 3 of P63x/UK IN
gives more information about the storage of relays.
3. STORAGE
If relays are not to be installed immediately upon receipt, they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have been
included in the packing they should be retained.
Care should be taken on subsequent unpacking that any dust, which has collected on the
carton, does not fall inside. In locations of high humidity the carton and packing may
become impregnated with moisture and the de-humidifier crystals will lose their efficiency.
Prior to installation, relays should be stored at a temperature of between –25˚C to +70˚C
(-13˚F to +158˚F).
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be reformed every 4 years. Reform the
capacitors by connecting auxiliary voltage to the P63x for approximately 10 minutes.
4. UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts are
damaged and additional components are not accidentally left in the packing or lost. Ensure
that any User’s CDROM or technical documentation is NOT discarded - this should
accompany the relay to its destination substation.
Relays must only be handled by skilled persons.
The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust
and excessive vibration.
IN
Installation P63x/UK IN/A54
5. RELAY MOUNTING
The P63x has been designed to conform to EN 60255-6. It is important when choosing the
installation location to ensure that it provides suitable conditions as specified in the Technical
Data - TD section, in particular the sections detailing environmental, mechanical and
electromagnetic conditions.
MiCOM relays are dispatched either individually or as part of a panel/rack assembly.
Individual relays are normally supplied with an outline diagram showing the dimensions for
panel cutouts and hole centers.
Secondary front covers can also be supplied as an option item to prevent unauthorized
changing of settings and alarm status. They are available in size 40TE (GN0181 001)
suitable to fit the 40TE case model, or 84TE (GN0183 001) to fit the 84TE case model.
The design of the relay is such that the fixing holes in the mounting flanges are only
accessible when the access covers are open and hidden from sight when the covers are
closed.
If a P991 or MMLG test block is to be included, it is recommended that, when viewed from
the front, it be positioned on the right-hand side of the relay (or relays) with which it is
associated. This minimizes the wiring between the relay and test block, and allows the
correct test block to be easily identified during commissioning and maintenance tests.
IN
IN
Figure 3: Panel cutout for the 40TE panel mounted case, panel mount method 1
(without the angle brackets and frame)
Installation P63x/UK IN/A54
Figure 4: Panel cutout for the 40TE panel mounted case, panel mount method 2
(using the angle brackets and frame)
Figure 5: Panel cutout for the 84TE panel mounted case, panel mount method 1
(without the angle brackets and frame)
IN
Installation P63x/UK IN/A54
Figure 6: Panel cutout for the 84TE panel mounted case, panel mount method 2
(using the angle brackets and frame)
Prior to flush panel mounting of the P63x using panel mount method 1, the local control
panel needs to be removed in the following manner:
• Remove the upper and lower covering flap. (Turn the upper/lower flap by 180° up/down.
Take hold of the middle part and bend the flap. The side fastenings can now be
unhinged.)
• Next, undo the lower M4 bolts completely and loosen the upper M4 bolts (see Figures 7
and 8). Now hang the P63x into the panel cutout from behind supported by the upper
M4 bolts. Tighten all M4 bolts. Mount the local control panel.
IN
Installation P63x/UK IN/A54
Figure 7: Installation of the 40TE case without cover frame, (panel mount method 1)
IN
Installation P63x/UK IN/A54
Figure 8: Installation of the 84TE case without cover frame, (panel mount method 1)
Panel mount method 2 (using the angle brackets and frame) is only an option for the 40TE
case width. When installing units in accordance with panel mount method 2, proceed as
follows:
• Remove the bolts shown in Figure 9, c, and mount the enclosed angle bracket using
these bolts
• Slide the unit into the panel opening from the front
• Fasten the unit to the control panel using the enclosed M6 bolts (see Figure 10)
• Assemble the cover frame and snap it onto the mounting bolts
IN
P1842ENa
Figure 10: Installation of the 40TE case with cover frame (panel mount method 2)
IN
Installation P63x/UK IN/A54
6. RELAY WIRING
This section serves as a guide to selecting the appropriate cable and connector type for
each terminal on the MiCOM relay.
The IRIG-B input and BNC connector have a characteristic impedance of 50Ω. It is
recommended that connections between the IRIG-B equipment and the relay are made
using coaxial cable of type RG59LSF with a halogen free, fire retardant sheath.
P1842ENa
IN
Installation P63x/UK IN/A54
Figure 12: Case dimensions for 40TE panel mount method 1 (without the angle
brackets and frame)
IN
P1933ENa
Figure 13: Case dimensions for 40TE panel mount method 2 (using angle brackets
and frame)
Installation P63x/UK IN/A54
Figure 14: Case dimensions for 84TE panel mount method 1 (without the angle
brackets and frame)
IN
Installation P63x/UK IN/A54
P1951ENa
Note: "Dot" convention for winding polarities shown. When using P1-P2,
S1-S2 standard notation. IN
• Dot on CT primary signifies P1 terminal
Blank Page
IN
Installation P63x/UK IN/A54
P1739ENa
IN
Figure 16: P631 ring terminal connections (with all options shown)
Installation P63x/UK IN/A54
P1740ENa
IN
Figure 17: P632 ring terminal connections (with 24I type X option shown) - Part 1 of 2
Note 1: Slot 8 may contain either 24I type X input module or 4I type Y input
module. See Fig. 18 for type Y connections.
Installation P63x/UK IN/A54
P1742ENa
IN
Figure 18: P632 ring terminal connections (with 24I type X option shown) - Part 2 of 2
Installation P63x/UK IN/A54
IN P1741ENa
Figure 19: P632 ring terminal connections (with 4I type Y option shown) - Part 1 of 2
Note 1: Slot 8 may contain either 24I type X input module or 4I type Y input
module. See Fig. 16 for type X connections.
Installation P63x/UK IN/A54
P1742ENa
IN
Figure 20: P632 ring terminal connections (with 4I type Y option shown) - Part 2 of 2
Installation P63x/UK IN/A54
P1743ENa
Figure 21: P633 ring terminal connections (with all options shown) - Part 1 of 2
IN
Installation P63x/UK IN/A54
P1744ENa
Figure 22: P633 ring terminal connections (with all options shown) - Part 2 of 2
IN
Installation P63x/UK IN/A54
P1745ENa
IN Figure 23: P634 ring terminal connections (with all options shown) - Part 1 of 2
Installation P63x/UK IN/A54
P1746ENa
Figure 24: P634 ring terminal connections (with all options shown) - Part 2 of 2 IN
Installation P63x/UK IN/A54
IN
Firmware and Service Manual P63x/UK VH/A54
Version History
MiCOM P631, P632, P633, P634
VH
MiCOM P631, P632, P633, P634
Version History
Firmware and Service Manual
Relay type: P631, P632, P633, P634
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
- 15 Jan 2001 9 Original Issue
9 COMM1 software integration with switchable protocol
- 701 3 Apr 2001 9 Analog module software integration
9 Improved IRIG-B software
P63x/UK VH/A54
THRM1 and THRM2 p.u. measured values added
9 Signal for THRMx: Not Ready added
(VH) 15-1
9 Broken conductor detection function BC_x added
9 Overfluxing protection function V/f added
VH
VH
(VH) 15-2
P63x/UK VH/A54
Relay type: P631, P632, P633, P634
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
- 25 Jan 2002 9 External logic input signals increased from 16 to 40
-602 Previous
- 705 -302 22 Feb 2002 9 Improved disturbance recording handler Documents +
Cont. P63x/EN AD/B22
- 706 6 Jun 2002 9 Russian character font correction
9 Order extension number entry correction
9 DIFF and REF_x amplitude matching factor restrictions
relaxed
9 DIFF zero sequence current filtering for odd numbered vector
groups is improved
9 DIFF setting ranges for tripping characteristic and
unrestrained element increased
9 DIFF setting to allow disabling of hysteresis for tripping
characteristic
Version History
values added to measured fault data
9 Setting range of V/f>> increased
-707 25 Mar 2003 9 Improved DTOC with faster trip command
MiCOM P631, P632, P633, P634
Version History
Firmware and Service Manual
Relay type: P631, P632, P633, P634
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
-603 9 Trip characteristic correction
-708 16 May 2003
Cont. 9 Improved saturation discriminator
P634 only
Previous
-604 - -303 9 Oct 2003 9 UCA2 software integration with Ethernet hardware documents +
P63x/EN AD/A43
9 Optional increased voltage thresholds for opto-inputs
9 Extended UCA2 software integration with Ethernet hardware
for all P63x Previous
-605 - -303 30 Apr 2004 documents +
9 Optional increased voltage thresholds for opto-inputs
P63x/EN AD/A43
9 Improved sensitivity in saturation stabilization
9 CTS function added
9 Disturbance recording maximum timer added
9 COMM1 software enhancement of clock time message from
4bit to 7bit
9 Optional new voltage thresholds for opto-inputs Previous
-606 - -304 20 May 2005 9 Positive and negative sequence p.u. current measurements documents +
added P63x/EN AD/A54
P63x/UK VH/A54
9 Setting range of m1 and m2 increased to 0.10 - 1.50
(VH) 15-3
VH
VH
(VH) 15-4
P63x/UK VH/A54
Relay type: P631, P632, P633, P634
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
9 Regional English language data model with modified setting
texts similar to Px40 platform English texts (-800 option)
9 Implementation of new substation communication protocol
IEC 61850
9 IEC 61850 introduces function groups “IEC”, “GOOSE” and
“GSSE”
P63x/UK M/A54
-610 - -305 Jun 2006
9 MAIN: Phase reversal logic now available, for phase swapping (Regional English)
where generator/motor sets may operate bi-directionally
9 MAIN: Vector group numbers are now settable in each setting
group, allowing use for phase angle regulating transformers
9 IDMTn: Trip time accuracy improved
9 UCA2 protocol no longer supported
-610
P63x/UK VH/A54
* Incompatible settings files should be converted to the required relay software version prior to sending to the relay. This can be achieved using the
(VH) 15-5
Tools\Convert Settings File… command in S&R-103.
VH
P63x/UK VH/A54 Firmware and Service Manual
Version History
(VH) 15-6 MiCOM P631, P632, P633, P634
VH
INDEX
A Cold restart
(OP) 5-136
Address mode (FD) 8-7
(GS) 3-14 (TS) 11-6
Alarms Commissioning
(GS) 3-4 (CM) 9-3
(OP) 5-135 Commissioning test record
(FD) 8-5
(CM) 9-22
(TS) 11-6
Communications
Amplitude matching
Courier interface
(OP) 5-12, 27
(AP) 6-13 (SC) 12-5
Differential protection
(ST) 4-47, 62, 78 G
(OP) 5-11
(AP) 6-10 Getting started
(MR) 7-15 (GS) 3-3
(CM) 9-13 Glossary
Dimensions (SG) 13-1
(IN) 14-15 GOOSE (see Communications)
Display and keypad Ground overcurrent (see Definite time overcurrent and
(GS) 3-8 Inverse time overcurrent)
Disturbance recorder GSSE (see Communications)
(ST) 4-60
(MR) 7-79
H
Disturbance recording
(OP) 5-145 Hardware overview
DNP3.0 interface (see Communications) (FD) 8-4
Dynamic settings Harmonic restraint
(ST) 4-85, 87, 89 (ST) 4-80
(OP) 5-22
High impedance
E
(ST) 4-81
Earth fault (see Definite time overcurrent and Inverse time (OP) 5-31
overcurrent) (AP) 6-20, 36
Environmental conditions (EMC) (CM) 9-18
(TS) 11-4
Ethernet port (see Communications) I
External connection diagrams IDMT (see Inverse time overcurrent)
(IN) 14-19
IEC60870-5-103 interface (see Communications)
IEC61850 interface (see Communications)
F
Installation
Fault data acquisition (Fault records) (GS) 3-7
(OP) 5-140 (IN) 14-3
(MR) 7-75 Introduction
Fault panel (IT) 1-5
(ST) 4-9 Inverse time overcurrent
(OP) 5-84 (ST) 4-48, 66, 90
Firmware design (OP) 5-39
(FD) 8-3 (MR) 7-48
Firmware history IRIG-B time synchronization
(VH) 15-1 (ST) 4-34
Index (OP) 5-94
Frequency gradient monitoring
(MR) 7-24
(OP) 5-60
K O
Vector group
(ST) 4-78
(OP) 5-15
(AP) 6-14
Version history
(VH) 15-1
Virtual winding
(ST) 4-62
(OP) 5-117
Voltage protection
(ST) 4-49, 68, 100
(OP) 5-56
(MR) 7-53
Warm restart
(OP) 5-135
(FD) 8-7
(TS) 11-6
Weight
(TD) 2-1
Index
Index
Publication: P63x/UK M/A54