AC Resonant Test Systems are especially valuable in any
application where the load is largely capacitive with
low loss such as power cables, gas-insulated switchgear,
generator windings, and dry testing of insulator strings.
R
esonance is defined as the condition Furthermore, parallel mode allows the test Principle of Operation in
at which the net inductive reactance set to be energized to full voltage without Series Resonant Mode
cancels the net capacitive reactance. a load. This is useful for calibrating the Figure 2 is a simplified diagram of a series
The resonant circuit must have both instrumentation and checking for the partial resonant test system. A voltage regulator of
capacitance and inductance. (In addition, discharge level of the test equipment. an auto-transformer type (Toroidal, CTVT or
resistance will always be present due either Thoma) is connected to the supply voltage.
to the lack of ideal elements, or the control Principle of Operation in The regulator provides a variable voltage to
offered on the shape of the resonance Parallel Resonant Mode the exciter transformer.
curve.) Figure 1 is a simplified diagram of a parallel
When resonance occurs, the energy resonant test system. The difference between
absorbed at any instant by one reactive series and parallel mode can be seen in the
element is exactly equal to that released by connection from the exciter transformer to
another reactive element within the system. the high voltage reactor.
In other words, energy pulsates from one The start of the high voltage winding
reactive element to the other. Therefore once is grounded instead of being connected
the system has reached a state of resonance, to the high voltage output of the exciter
it requires no further reactive power since it transformer, as in the series resonant mode.
is self-sustaining. The total apparent power The output of the exciter transformer is
Reactor
is then simply equal to the average power connected to a tap provided on the high
dissipated by the resistive elements. voltage reactor. Notice that the high voltage
The average power absorbed by the system reactor is in the configuration of an auto-
will also be at a maximum at resonance. The transformer.
commonly used measure of the quality in Voltage
a resonant circuit is the quality factor, or Regulator Exciter
Q. The power source of resonant circuits
operating in the resonant mode (exciter and Figure 2 Series Resonance
regulator) is used to supply the dissipated
energy. Q is approximately equivalent to the The exciter transformer is fed by the output
ratio of the output kVA to the input kVA. of the voltage regulator. This transformer
Given kVA requirements of the load and the steps the voltage up to a usable value by the
Q of the test sytem, the input power can be Reactor high voltage portion of the circuit.
obtained by dividing the kVA by the Q. The high voltage reactor L and the load
capacitance C represent the high voltage
Parallel or Series Resonant Mode portion of the circuit. The inductance of
The proper mode of operation must be Voltage the high voltage reactor can be varied by
Exciter
chosen according to the test objects and the Regulator
changing the air gap of the iron core. The load
measurements to be carried out. Figure 1 Parallel Resonance capacitance C consists of the capacitance of
The series resonant mode is well suited for the load. The coupling capacitance for PD
sensitive partial discharge measurements. Furthermore, in this configuration the high measurement, stray capacitance and, in the
Harmonics from the supply are better voltage reactor is electronically in “parallel” case of tank-type (T), sets the high voltage
suppressed than in parallel mode. with the load capacitance. In the event of a bushing. When testing, the high voltage
The parallel resonant mode provides breakdown of the test sample, the output reactor is adjusted so that the impedance of
a more stable output voltage with test current of the test set is limited by the short- L corresponds to the impedance of C at the
specimens, such as large generator windings, circuit impedance of the regulator, exciter frequency of the supply voltage. Thus the
or other specimens with corona losses. transformer, and the “auto-transformer.” circuit is tuned to series resonance at 50 or
The test voltage rate of rise is stable in In most cases it can be said that the short- 60 Hz.
parallel mode, independent of the degree circuit current of a parallel resonant system The Q of the basic resonant circuit or
of tuning and the Q of the circuit. is below the nominal current. with a low loss test specimen (e.g. of cable,