Professional Documents
Culture Documents
Phase-Space-Based Symmetrical Fault Detection During Power Swing
Phase-Space-Based Symmetrical Fault Detection During Power Swing
Research Article
ISSN 1751-8687
Phase-space-based symmetrical fault Received on 14th October 2015
Revised on 6th December 2015
detection during power swing Accepted on 17th January 2016
doi: 10.1049/iet-gtd.2015.1245
www.ietdl.org
Rahul Dubey 1 ✉, Subhransu Ranjan Samantaray 2, Bijay Ketan Panigrahi 1, Vijendran G. Venkoparao 3
1
Department of Electrical Engineering, Indian Institute of Technology, Delhi, India
2
School of Electrical Sciences, Indian Institute of Technology, Bhubaneswar, India
3
Robert Bosch Engineering and Business Solutions Ltd., Bengaluru, India
✉ E-mail: rahul.dubey2011@gmail.com
Abstract: This study proposes an effective symmetrical fault detection technique during power swing in distance relaying
using phase-space (PS) method. This is based on an embedding theorem which shows that a time series can be mapped
to a higher-dimensional space called PS through embedding. Thus, a sampled signal can be transformed into the PS so
that its features can be more clearly viewed. The process starts at retrieving the current signal samples and process
through PS, the original signal is decoupled into two parts such as power swing and symmetrical fault part. The
symmetrical fault detection during power swing is easily achieved as the symmetrical fault part of the signal produces
an irregular shape compared with the shape produced during from the power swing condition. The symmetrical fault
detection signal using PS (FDPS) detects the symmetrical fault during power swing in the transmission line with wide
variations in operating conditions and the results from extensive studies indicate that the proposed FDPS can reliably
detect the faults during power swing.
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
& The Institution of Engineering and Technology 2016 1947
Fig. 1 Impedance trajectory during power swing enters zone-1 of the relay
a Impedance trajectory during power swing
b Voltage
c Current
d Impedance for phase-a in case of symmetrical (a-b-c) fault during power swing
The impedance trajectory during power swing enters zone-1 of the a time series can be mapped to a higher-dimensional space called
relay, as shown in Fig. 1a. Here, the MHO operating characteristics PS through embedding [20, 21]. Thus, a sampled signal can be
of distance protections parameterised are same as discussed in [16]. transformed to the PS and its features can be more clearly viewed.
This corresponds to a stable/unstable power swing as the impedance The embedding theorem was originally proposed for dynamical
trajectories enter zone-1 in case of unstable power swing. It gives an systems. In mathematics and physics, a dynamical system is
indication of the existence of the electrical centre in the studied line. usually described by a state space, each orthogonal coordinate of
However, for stable or unstable swings, relays should not operate, as which represents one of the variables needed to specify the
they derive a PS analysis-based fault detector based on which trip/ instantaneous state of the system [22]. Hence, all the possible
block command can be given to the distance relay. Figs. 1b–d states of the dynamical system are represented in the state space
show the respective voltage, current, and apparent impedance for a and each possible state corresponds to a unique point. However, in
three-phase fault during power swing. practice, it is usually impossible to measure all the variables of a
dynamical system. However, some studies conducted [20] has
proved that it can be reconstructed from a time series of a
3 Proposed scheme collection of the states using the embedding theorem. It can be
seen further that the d-dimensional dynamical systems is mapped
This paper proposes an effective symmetrical fault detection to a dE-dimensional PS, where dE ≥ 2d + 1. A d-dimensional
technique during power swing in distance relaying using PS dynamical system can be expressed by d-first-order differential
method. This is based on an embedding theorem which shows that equations. The solution of these equations s ∈ f d is a state in the
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
1948 & The Institution of Engineering and Technology 2016
Fig. 3 WSCC 3-machine, 9-bus system
c(h · F · t)(s) = k (s) · k F t (s) , . . . , k F(dE −1)t (s) (1)
Fig. 2 Flowchart of the proposed method
Fig. 4 Phase-a
a Voltage
b Current waveforms during power swing
c Relay end voltage
d Current waveforms for symmetrical fault during power swing (160° inception angle, 65% line, 50 Ω fault resistance)
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
& The Institution of Engineering and Technology 2016 1949
For specific si, (1) becomes
c(k · F · t)(s) = k si · k si+t , . . . , k s(i+dE −1)t
= xi ·xi+t , . . . , x(i+dE −1)t = Xi (2)
x2 + y2 = A2 , y2 + z2 = A2
n+1
FDPS(n) = F x, y (k ) (5) Fig. 5 Step-by-step results obtained during PS analysis for a WSCC
k=n 3-machine, a 9-bus system
a x–y-plane projection of the embedded signal for symmetrical fault during power swing
where F(x, y) is the distance between each point and x–y-plane (160° inception angle, 65% line, and 50 Ω fault resistance)
b x–z-plane projection of the embedded signal for symmetrical fault during power swing
origin [8]. The projections of the embedded signal on the xy-plane (160° inception angle, 65% line, and 50 Ω fault resistance)
and the yz-plane are a circle (for pure sinusoidal signal) whose c x–y–z-plane projection of the embedded signal for symmetrical fault during power
radius is the amplitude of the sinusoidal signal and whose centre is swing (160° inception angle, 65% line, and 50 Ω fault resistance)
the origin of the plane, while the projection on the xz-plane is a
line segment. However, in case of power swing the radius on the x
and y axes are not same due to oscillation in current waveform so Step 6: Calculate FDPS.
projection of the embedded signal on the xy-plane and the yz-plane Step 7: Set threshold.
is an ellipse. The radius of ellipse is constant during power swing Step 8: If FDPS > threshold; then symmetrical fault else power
(as shown in Figs. 5a and 11b), whereas in case of fault occurs swing.
during power swing new ellipse with different radius is formed.
This information is effectively used for developing the fault
detector. Fig. 2 shows the flowchart of the proposed method. The 4 Results and analysis
proposed algorithm in steps is given below:
4.1 Testing and validation in WSCC 3-machine, 9-bus
Step 1: Obtain any one phase current information from relay end. system
Step 2: Consider moving window of half cycle data.
Step 3: Perform PS transformation. To verify the proposed technique for a larger system Western System
Step 4: Evaluate the norm of the eigenvector over the defined Coordinating Council (WSCC) 3-machine, a 9-bus system [21] as
window. shown in Fig. 3 is considered. The system is simulated using
Step 5: Extract time-domain information of disturbance. Dig-silent power factory software. Transmission lines are modelled
x(k ) = A sin vkDt + w A sin v(k + t)Dt + w A sin v(k + 2t)Dt + w
= A sin vkDt + w A cos vkDt + w −A sin vkDt + w (4)
= j1k j2k j3k
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
1950 & The Institution of Engineering and Technology 2016
Fig. 6 PS-based fault detector (FDPS) plot during high resistance fault
a Current waveform
b Symmetrical fault detection signal using FDPS during fast swing
c Current waveform
d Symmetrical fault detection signal using FDPS during slow swing (at different fault instant, 30° inception angle, 75% line, 200 Ω fault resistance)
with distributed parameter in the simulation. Generators are modelled 4.2 Testing and validation in series-compensated WSCC
with one axis flux decay dynamics, and exciters are modelled as an 3-machine, 9-bus system
IEEE type-1 exciter. For this paper, a distance relay is considered at
bus-9 for the line connecting to bus-6. To develop a power swing, a Flexible AC transmission systems devices are used increasingly for
three-phase fault is created in the line connecting buses 5 and 4 at improving steady-state and transient stability improvement. Among
1 s. The fault is cleared after 0.3 s (1.3 s from Figs. 4a and b) by those thyristor controlled series capacitor is used for enhancing
opening the breakers at both the ends of the line. As a result, the power transfer capability by variation of series compensation.
distance relay at bus-9 experiences a power swing. Any fault in the However, variation in series compensation introduces number of
line between buses 9 and 6 during the power swing is to be protection challenges for the distance relay operation. Voltage
detected by the distance relay immediately. Assume that the relay is inversion, current inversion, reach measurement, and relay
present in bus-6 for detecting the symmetrical fault during power coordination are some of the major concerns in series-compensated
swing. Figs. 4c and d show the voltage and current waveforms for lines [25, 26]. Overreaching of distance elements is the most
symmetrical fault during power swing. To test the proposed critical problem with series-compensated lines. Also the distance
method, three-phase faults are simulated in the line at different function may fail to pick up for low-current faults [27]. The
swing conditions. Data are collected at a sampling frequency of 1 evaluation and performance assessment of different power swing
kHz. Figs. 5a–c show the step- by-step results obtained during PS detectors for a series-compensated line has been discussed in [28–30].
analysis for a WSCC 3-machine, a 9-bus system. Figs. 6a–d present For evaluation of the proposed PS-based symmetrical fault
the PS-based fault detector (FDPS) plot during high resistance detection method’s performance in a multi-machine power system
fault; this shows the effectiveness of FDPS. with series compensation WSCC 3-machine, a 9-bus is considered
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
& The Institution of Engineering and Technology 2016 1951
Fig. 7 Testing and validation in series-compensated WSCC 3-machine, 9-bus system
a WSCC 3-machine, 9-bus system with series compensation (SC)
b Voltage
c Current waveform during power swing
d Impedance trajectory during unstable power swing
(Fig. 7a) for the study where a modification has been incorporated by power swing enters zone-1 of the relay, as shown in Fig. 7d. This
providing 70% compensation at the beginning of line T7–T8 and corresponds to an unstable swing as the impedance trajectories
developed using Dig-silent power factory software package. The enter zone-1. It gives an indication of the existence of the
distance relay R1 for bus-7 is considered for the paper. A electrical centre in the studied line. However, for stable or unstable
three-phase fault is created in line T5–T7 at 0.2 s. The fault is swings, relays should not operate, as they result in no optimal
cleared at 0.45 s by opening breaker B3 (bus-T5) and B4 (bus-T7). islanding of the system. Hence, this paper derives a PS-based fault
The removal of the line causes a swing condition for relay R1. detector based on which trip/block command can be given to the
The phase-a voltage and current waveforms at relay R1 during the distance relay, as shown in Figs. 8a and b.
power swing are shown in Figs. 7b and c, respectively. Different
faults are simulated on line T7–T8 to test the algorithm. The 4.3 Testing and validation in IEEE-39 New England
results of only two representative test cases are included below. system
For power swing study, the relay R1 at bus-7 is considered and its
zone-3 is set at 240% of line 7–8, in order to provide backup The proposed detector is studied on the IEEE-39-bus test system by
protection to the adjacent line. The impedance trajectory during using the commercial Dig-silent power factory software. The test
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
1952 & The Institution of Engineering and Technology 2016
Fig. 8 PS-based fault detector based on which trip/block command
a Current waveform
b Symmetrical fault detection signal using FDPS during power swing for SC-line
Fig. 10 Current and voltage waveform for terminal T-27 and T-19
a Terminal-27 phase-a voltage
b Terminal-27 current
c Terminal-29 phase-a voltage
d Terminal-29 current waveforms during power swing
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
& The Institution of Engineering and Technology 2016 1953
Table 1 Fault situation during power swing tested using FDPS
Number Faults type Fault δ0 Rf (fault Response
of test during distance, resistance in time, cycle
power % Ω)
swing
1 AG 15 90 10 1
2 AG 15 160 100 1
3 BG 15 90 20 1
4 CG 80 90 300 1
5 ABG 35 140 10 1
6 ABG 35 90 100 1
7 BCG 20 45 10 1
8 ACG 50 45 250 1
9 ABCG 75 60 100 1
10 ABC 65 90 20 1
11 AB 50 135 150 1
12 AB 50 60 200 1
Fig. 13 Fault detection signals for the load change at 2 s (phase-a increase
in load)
when the system goes to power swing mode, then different kinds of
faults (mentioned in Table 1) with different fault location, different
fault inception angle and different fault resistance on line
T26-T28, have been tested with the proposed algorithm.
According to the results, the proposed method demonstrates its
ability to unblock distance relay in different relevant conditions. It
is found that, for each fault situation, the fault detection index
during power swing, i.e. FDPS is always greater than set
threshold, which clearly identifies the fault situation during stress
condition such as power swing. Table 1 shows the results of
the proposed algorithm in different operating conditions. So the
response time for fault detection does not affect by varying the
operating condition. The set threshold is also found immune to
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
1954 & The Institution of Engineering and Technology 2016
Fig. 15 Fault detection signals for different swing cycle frequencies
a 1 Hz
b 5 Hz
c 10 Hz
Table 2 Symmetrical fault detection during power swing with different 30 dB noise [19] and detect the high-impedance symmetrical faults
swing cycle frequencies 1–10 Hz tested using FDPS effectively.
The performance assessments of symmetrical fault detection
Numberof Swing cycle Fault Fault Response
test frequency, Hz inception distance, time, cycle during noisy condition for WSCC 3-machine 9-bus are shown in
angle, deg % Figs. 12a and b. Figs. 13 and 14 show the fault detection signals
for load change instances at 2 s for increasing and decreasing
1 1 30 75 1 loads, respectively. It is observed that in the case of load change
2 2 45 55 1 FDPS perform satisfactorily. Fault detection signals in both cases
3 3 60 30 1
4 4 75 70 1
remain steady at base value and do not grow to achieve the
5 5 90 20 1 threshold for fault detection, avoiding false detection. Furthermore,
6 6 105 80 1 the performance evaluation with the variation of swing cycle
7 7 120 35 1 frequency (from 1 to 10 Hz) are shown in Fig. 15a–c and
8 8 135 45 1
9 9 150 15 1 presented in Table 2.
10 10 175 60 1
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
& The Institution of Engineering and Technology 2016 1955
power swing are considered for comparison. These are proposed in 6 Rockefeller, G.D.: ‘Fault protection with a digital computer’, IEEETrans. Power
[11] (method 1), in [12] (method 2), in [13] (method 3), in [17] Appl. Syst., 1969, PAS-88, (4), pp. 438–461
7 Phadke, A.G., Thorp, J.S.: ‘Computer relaying for power systems’ (Wiley,
(method 4), in [18] (method 5), and in [19] (method 6). The Hoboken, NJ, 2009, 2nd edn.)
methods 1, 2, 3, 4, 5, and 6 and the proposed method are applied 8 Samantaray, S.R.: ‘Phase-space-based fault detection in distance relaying’, IEEE
to WSCC 3-machine 9-bus system and the results are presented in Trans. Power Deliv., 2011, 26, (1), pp. 33–41
Fig. 16. From Fig. 16, it is observed that the proposed method 9 Paudyal, S., Gokaraju, R., Sachdev, M.S.: ‘Application of equal area criterion
conditions in the time domain for out-of step protection’, IEEE Trans. Power
provides least response time for fault detection during power Deliv., 2010, 25, (4), pp. 600–609
swing compared with existing method. Again, according to 10 Samantaray, S.R., Dubey, R.K., Chitti Babu, B.: ‘A novel time-frequency
Table 4, the proposed method provides the least threshold value transform based spectral energy function for fault detection during power
and lowest value of dead-band, so it is the most reliable method swing’, Electr. Power Compon. Syst., 2012, 40, (8), pp. 881–897
11 Brahma, S.M.: ‘Distance relay with out-of-step blocking function using wavelet
compared with existing method. transform’, IEEE Trans. Power. Deliv., 2007, 22, (3), pp. 1360–1366
12 Lotfifard, S., Faiz, J., Kezunovic, M.: ‘Detection of symmetrical faults by distance
relays during power swings’, IEEE Trans. Power Deliv., 2010, 25, (1), pp. 81–87
13 Dubey, R., Samantaray, S.R.: ‘Wavelet singular entropy based symmetrical
5 Conclusions fault-detection and out-of-step protection during power swing’, IET Gener.
Transm. Distrib., 2013, 7, (10), pp. 1123–1134
A new technique based on phase-space based fault detector is 14 Dubey, R.K., Samantaray, S.R., Panigrahi, B.K.: ‘Adaptive distance relaying
proposed for symmetrical fault detection and out-of-step blocking scheme for transmission network connecting wind farms’, Electr. Power
Compon. Syst., 2014, 42, (11), pp. 1181–1193
protection during power swing. This is based on an embedding 15 Dubey, R., Samantaray, S.R., Panigrahi, B.K.: ‘Simultaneous impact of unified
theorem which shows that a time series can be mapped to a power flow controller and off-shore wind penetration on distance relay
higher-dimensional space called PS through embedding, and thus a characteristics’, IET Gener. Transm. Distrib., 2014, 8, (11), pp. 1869–1880
sampled signal can be transformed into the PS so that its features 16 Nayak, P.K., Pradhan, A.K., Bajpai, P.: ‘Wide-area measurement-based backup
protection for power network with series compensation’, IEEE Trans. Power
can be more clearly viewed. As the original signal is decoupled Deliv., 2014, 29, (4), pp. 1970–1977
into power swing and symmetrical fault, the symmetrical fault 17 Apostolov, A., Tholomier, D., Richard, S.: ‘Superimposed components based
detection technique during power swing is easily achieved as the sub-cycle protection of transmission lines’. Proc. IEEE Power Engineering
symmetrical fault part of the signal produces an irregular shape Society General Meeting Power Systems Conf. Exposition, 2004, pp. 592–597
18 Lin, X., Gao, Y., Liu, P.: ‘A novel scheme to identify symmetrical fault occurring
compared with the shape produced from the power swing part of during power swings’, IEEE Trans. Power Deliv., 2008, 21, (1), pp. 73–78
the signal. The proposed FDPS has been found highly effective for 19 Khodaparast, J., Khederzadeh, M.: ‘Three-phase fault detection during power
symmetrical fault detection during power swing in the swing by transient monitor’, IEEE Trans. Power Syst., 2015, 30, (5),
transmission line with wide variations in operating conditions pp. 2558–2565
20 Takens, F.: ‘Detecting strange attractors in turbulence’. in (Eds.): ‘Lecture notes in
while meeting the speed criteria of one cycle from the event of mathematics’ (Springer Berlin/Heidelberg, Berlin, Germany, 1981), pp. 366–381
inception. 21 Ji, T.Y., Lu, Z., Tang, W.H., et al.: ‘Disturbance detection in the phase-space
through GK clustering’. Proc. Third Int. Conf. Electric Utility Deregulation and
Restructuring and Power Technologies, Nanjing, China, 6–9 April 2008,
pp. 2328–2332
6 Acknowledgments 22 Baker, G.L., Gollub, J.P.: ‘Chaotic dynamics: an introduction’ (Cambridge
University Press, Cambridge, UK, 1990)
This research work was supported by the Prime Minister’s 23 Sauer, T., Yorke, J.A., Casdagli, M.: ‘Embedology’, J. Stat. Phys., 1991, 65, (3–4),
Fellowship for Doctoral Research and being implemented jointly pp. 579–616
24 Grassberger, P., Procaccia, I.: ‘Estimation of the Kolmogorov entropy from a
by Science & Engineering Research Board (SERB) and the chaotic signal’, Phys. Rev. A, 1983, 28, (4), pp. 2591–2593
Confederation of Indian Industry (CII), with industry partner 25 Novosel, D., Phadke, A.G., Saha, M.M., Lindahl, S.: ‘Problems and solutions for
Robert Bosch. microprocessor protection of series compensated lines’, Proceedings of Sixth
International Conference on Developments in Power System Protection, IEE
Conference Publication No. 434, Nottingham, UK, 1997, pp. 18–23
26 Altuve, H.J., Mooney, J.B., Alexander, G.E.: ‘Advances in series compensated line
7 References protection’. Proc. 35th Annual Western Protective Relay Conf., Spokane, WA,
October 2008
1 Kundu, P., Pradhan, K.: ‘Synchrophasor-assisted zone 3 operation’, IEEE Trans. 27 Bogdan, K.: ‘Distance protection of series compensated lines – problems and
Power Deliv., 2014, 29, (2), pp. 660–667 solutions’. Proc. 27th Annual Western Protective Relay Conf., 2001, pp. 22–25
2 Blumschein, J., Yelgin, Y., Kereit, M.: ‘Blackout prevention by power swing 28 Ghaderi, E.A., Tasdighi, M., Rouhani, A.: ‘Evaluation and performance
detection and out-of-step protection’, J. Power Energy Eng., 2014, 2, pp. 694–703 comparison of power swing detection algorithms in presence of series
3 Power grid: ‘Report on the grid disturbance on 30th and 31th July 2012’. CERC compensation on transmission lines’. Proc. 10th Int. Conf. Environment
Order in Petition, 1 August 2012, no. 167 Electrical Engineering, 8–11 May 2011, pp. 1842–1848
4 Lim, S., Liu, C., Lee, J., et al.: ‘Blocking of zone 3 relays to prevent cascaded 29 Rao, J.G., Pradhan, A.K.: ‘Differential power based symmetrical fault detection
events’, IEEE Trans. Power Syst., 2008, 23, (2), pp. 747–753 during power swing’, IEEE Trans. Power Deliv., 2012, 27, (3), pp. 1557–1564
5 IEEE PSRC WG D6: ‘Power swing and out of step considerations on transmission 30 Nayak, P.K., Pradhan, A.K., Bajpai, P.: ‘A fault detection technique for a series
lines’, A Report to Power System Relaying Committee of The IEEE Power compensated line during power swing’, IEEE Trans. Power Deliv., 2013, 28,
Engineering Society, 2005 (2), pp. 714–722
IET Gener. Transm. Distrib., 2016, Vol. 10, Iss. 8, pp. 1947–1956
1956 & The Institution of Engineering and Technology 2016