HBRC Journal
http://ees.elsevier.com/hbrcj
KEYWORDS Abstract In seismic areas many buildings need to be retrofitted. In some cases, it is possible to
Fiber-reinforcement apply carbon fiber-reinforcement polymer/plastic (CFRP), steel-jackets, and concrete jackets as
polymer/plastic; rehabilitation methods. Several researches have been developed with this technology in the last
Steel-jackets; years. In addition, there are guides for the design of retrofitted systems of existing structures. How-
Concrete-jackets; ever, it is necessary to count with reliable methodologies for structural analysis of these structures
Pushover analysis retrofitted. In some cases, the codes require non-linear analysis for the verification of design pro-
posed as retrofit. In this study, an attempt has been done for investigating the seismic behavior
of a typical existing building in Cairo by performing static pushover analysis before and after ret-
rofitting the columns by either, reinforced concrete, steel sections or carbon fiber reinforced polymer
(CFRP) composite jackets. The selected model building represents nearly all typical construction
deficiencies of buildings constructed before recent earthquake resistant design codes. To investigate
the possibility and effectiveness of the use of these systems, a comparative study was performed. A
comparison was made between a typical framed RC building and the same building after retrofit-
ting with CFRP confinement, steel elements and concrete jackets. By using nonlinear static (push-
over) analysis, the performance levels of structural members were evaluated for all structures.
According to the results of the structural analysis, significantly larger lateral displacement and
slightly higher lateral strength with respect to original performance are possible by jacketing the col-
umns of the building with CFRP sheets. On the other hand, a moderate larger lateral displacement
and higher lateral strength by using steel-jackets was seen. In the case of reinforced concrete jacket-
ing, the lateral strength and stiffness were significantly increased, as well as a remarkable improve-
ment of the lateral displacement capacity.
ª 2013 Production and hosting by Elsevier B.V. on behalf of Housing and Building National Research
Center.
1687-4048 ª 2013 Production and hosting by Elsevier B.V. on behalf of Housing and Building National Research Center.
http://dx.doi.org/10.1016/j.hbrcj.2013.07.002
Analysis of a retrofitted reinforced concrete building 101
without adequate transverse reinforcement may cause a total Purpose of pushover analysis
collapse of this type of structure due to lack of sufficient defor-
mation capacity. Retrofit of this type of column by means of The purpose of the pushover analysis is to evaluate the ex-
forming an additional jacket layer may supply the required pected performance of a structural system by estimating its
transverse reinforcement and enhance the seismic performance strength and deformation demands in designing earthquake
by providing additional ductility, and reducing the seismic resistant buildings by means of a static inelastic analysis, and
force demand. In this study, the seismic behavior of a typical comparing these demands to available capacities at the perfor-
existing building in Cairo is investigated by using pushover mance levels of interest. The evaluation is based on an assess-
analysis before and after retrofitting its columns with CFRP, ment of important performance parameters, including global
reinforced concrete jackets or steel element jackets. The se- drift, inter-story drift, inelastic element deformations (either
lected building contains most of the typical construction defi- absolute or normalized with respect to a yield value), deforma-
ciencies that are common for the buildings constructed tions between elements, and element and connection forces
before recent earthquake resistant design codes. In addition (for elements and connections that cannot sustain inelastic
to the insufficiency observed in the planning of the structural deformations). The inelastic static pushover analysis can be
system, deficiencies such as low quality of concrete (f0 c: viewed as a method for predicting seismic force and deforma-
10 MPa), inadequate transverse reinforcement (12 mm diame- tion demands, which accounts in an approximate manner for
ter bars with 300 mm spacing), and usage of plain bars with the redistribution of internal forces occurring when the struc-
relatively lower yield strength (fy: 240 MPa) also exist. Due ture is subjected to inertia forces that no longer can be resisted
to low concrete strength and relatively smaller column dimen- within the elastic range of structural behavior. The pushover is
sions, level of axial stresses are generally greater than 50% of expected to provide information on many response character-
the axial load capacity of the sections. During the analysis of istics that cannot be obtained from an elastic static or dynamic
the original structure, unconfined concrete stress–strain rela- analysis. The following are examples of such response charac-
tionship was used for determining the contribution of concrete. teristics (Helmut Krawinkler) [7]:-
For the analysis of the structural members retrofitted by
CFRP jacketing, a stress–strain model which was specially The realistic force demands on potentially brittle elements,
proposed for CFRP jacketed low strength concrete, was used. such as axial force demands on columns, force demands on
Finally, analysis of the members retrofitted by reinforced con- brace connections, moment demands on beam-to-column
crete jacketing or steel elements was carried out by using a tri- connections, shear force demands in deep reinforced con-
linear confined concrete stress–strain model. Both for original crete spandrel beams, shear force demands in unreinforced
and retrofitted members, a trilinear stress–strain relationship, masonry wall piers, etc.
that took the effect of strain hardening into account, was used Estimates of the deformation demands for elements that
for reinforcing steel. The analytical results showed that CFRP, have to deform in-elastically in order to dissipate the energy
steel jackets and reinforced concrete jacketing of this type of imparted to the structure by ground motions.
deficient column enhanced the overall structural seismic Consequences of the strength deterioration of individual
performance. elements on the behavior of the structural system.
In recent years, nonlinear static analyses have received a Identification of the critical regions in which the deforma-
great deal of research attention within the earthquake engi- tion demands are expected to be high and that have become
neering community. Their main goal is to describe the non- the focus of thorough detailing.
linear capacity of a structure when subject to horizontal Identification of the strength discontinuities in plan or ele-
loading with a reduced computational effort with respect vation that will lead to changes in the dynamic characteris-
to nonlinear dynamic analysis. Pushover methods are partic- tics in the inelastic range.
ularly indicated for assessing existing structures (Ferracuti Estimates of the inter-story drifts that account for strength
et al.) [1]. or stiffness discontinuities and that may be used to control
Sonia et al. [2] checked common software SAP2000 in non- damage and to evaluate P-delta effects.
linear analysis of retrofitting flat slab building. To analyze the Verification of the completeness and adequacy of load path,
retrofitting buildings methods, it is necessary to have software considering all the elements of the structural system, all the
where the analysis of these structures can be made. Research in connections, the stiff nonstructural elements of significant
this area is necessary to develop and to check the accuracy of strength, and the foundation systems.
these programs.
Spoelstra and Monti [3] studied the effects of the confine-
ment introduced by the FRP wrapping for the reinforced con-
Background to pushover analysis
crete with FRP.
Marco Savoia et al. [4] compared the results obtained from
the test program and finite element analyses using two pro- The static pushover analysis has no rigorous theoretical foun-
grams SAP2000 [5] and SeismoStruct [6]. The results on com- dation. It is based on the assumption that the response of the
parison showed that it is possible to get a good accuracy of the structure can be related to the response of an equivalent single
highest load that a RC frame can reach through the pushover degree-of-freedom (SDOF) system. This implies that the re-
analysis in SAP2000 or in Seismo Struct. sponse is controlled by a single mode, and that the shape of
So, in this study, analyses have been performed using this mode remains constant throughout the time history re-
SAP2000 Version 15 which is a general purpose structural sponse. Clearly, both assumptions are incorrect, but pilot stud-
analysis program for static and dynamic analyses of ies carried out by several investigators (Lawson [8], Fajfar [9],
structures. Saiidi [10]) have indicated that these assumptions lead to
102 A. Ismail
Ground th th th th th th
model st nd Third 4 +5 6 +7 8 +9
+1 +2
Dimensions 25x110 25x90 25x85 25x75 25x65
C1
Reinforcement 16φ16 12φ16 10φ16 8φ12 8φ12
Dimensions 25x130 25x110 25x90 25x80 25x70
Fig. 3a Typical residential building (reinforced concrete frame). C2
Reinforcement 18φ16 16φ16 12φ16 8φ12 8φ12
Dimensions 30x90 25x75 25x70 25x60 25x60
C3
Reinforcement 12φ16 10φ16 8φ16 8φ12 8φ12
Dimensions 30x80 25x65 25x60 25x60 25x60
C4
Reinforcement 10φ16 10φ16 8φ16 8φ12 8φ12
Steel jacket has been utilized; (Fig. 5a) using welded steel plates
with a thickness of 8 mm. The yield strength for steel plates is
considered as 240 MPa.
Fig. 8 Deformation and distribution of plastic hinges for original and retrofitted structures.
Fig. 9 Normalized base shear-top displacement for original and retrofitted structures.
Results and discussions plastic deformation due to very low strength and ductility of
columns. This is a clear demonstration of weak column-strong
The deformed shapes and plastic hinges of the frame indicated beam configuration. However, as seen in Fig. 8b and c, as the
in Fig. 4 are presented in Fig. 8. From Fig. 8a, it can be seen ductility of the columns was increased by the CFRP jackets or
that in the original structure, none of the beams experienced partial steel jackets, the structure exhibited larger
106 A. Ismail
displacements without strength loss and there were plastic cross-sections and additional longitudinal reinforcement. Dy-
hinges on a few sections of the beams. As seen in Fig. 8d namic characteristics of the retrofitted structure were signifi-
and e, when the columns were retrofitted with reinforced con- cantly reduced specially for the reinforced concrete jacketing
crete jackets, and full steel jackets (using steel plate around due to the increase in lateral stiffness. Consequently, rein-
concrete sections) due to the increase in ductility and particu- forced concrete jacketing may be more preferable when lateral
larly strength of the columns, many beam sections experienced drifts are needed to be limited, which in turn limits the damage
plastic deformations and the structure resisted relatively higher as well. However, when fewer disturbances are required and a
lateral loads. relatively higher level of damage is acceptable against severe
The normalized base shear-top displacement relationships earthquakes, CFRP jacketing may be more preferable. In this
obtained by pushover analysis for original and retrofitted technique, since the dimensions of the columns are not chan-
structures are presented in Fig. 9 for partial steel jacketing, ged, the seismic demand is not increased either. Using partial
full steel jacketing, CFRP jacketing and reinforced concrete steel jackets is not the best technique for retrofitting the low
jacketing cases. In this figure, the normalized base shear strength of concrete even though it enhances the ductility of
forces calculated according to Egyptian loading code the building and it does not significantly increase the total flex-
(EC203-2012) are also plotted. In comparison with the origi- ure of the elements.
nal structure, all retrofit techniques enhanced the strength It should be noted that for reaching results that are more
and ductility characteristics of the building. The occupant general, more detailed retrofit schemes with many load condi-
friendly CFRP jacketing retrofit technique supplied good dis- tions should be examined.
placement capacity but less lateral strength than other jacket-
ing techniques. On the other hand, the structure retrofitted by References
reinforced concrete jacketing exhibited a more rigid behavior
so that structural and non-structural elements could suffer [1] B. Ferracuti, R. Pinho, M. Savoia, R. Francia, Verification of
less damage. Because of increased lateral stiffness, the natural displacement-based adaptative pushover through multi-ground
periods of the retrofitted structure were reduced significantly motion incremental dynamic analyses, Engineering Structures
as shown in Table 1. 31 (2009) 1789–1799.
Refering to the calculated response modification factor, as [2] K. Soni Priya, T. Durgabhavani, K. Mounika, M. Nageswari, P.
shown in Table 1, all retrofitting techniques improved the duc- Poluraju, Non-linear pushover analysis of flatslab building by
using SAP2000, University Annals ‘‘Eftimie Murgu’’ resil Year 1
tility characteristics of the structure. For this structure, either
(2012) 256–266.
CFRP jacket or partial steel section jacket retrofitted structure [3] M. Spoelstra, G. Monti, FRP-confined concrete model, Journal
could not maintain a lateral strength as much as the base shear of Composites For Construction, ASCE 3 (1999) 143–150.
defined by the Egyptian code of loading (ECP201-2012) while [4] Marco Savoia, Nicola Buratti, Barbara Ferracuti, Pablo Martı́n,
reinforced concrete jacket retrofitted could do so. Even though Gustavo Palazzo, Considerations about non linear static
the structural members of the building were flexure critical, the analysis of a reinforced concrete frame retrofitted with FRP,
applied retrofitting techniques increased shear strengths of the Mechanical Computational XXIX (2010) 10173–10182.
members significantly, as well. [5] SAP2000, Integrated software for Structural analysis & design,
Computers & structures, Inc., Berkeley, California, USA, V.
14.0.0.
Conclusion
[6] Seismostruct, Software applications for analysis of structures
subjected to seismic actions, Seismosoft Ltd., Pavia, Italy, V.
The following conclusions are obtained after making an at- 4.1.0.
tempt in analyzing the inelastic behavior of a typical existing [7] Helmut Krawinkler, G.D.P.K. Seneviratna, Pros and cons
reinforced concrete structure with various deficiencies before analysis of seismic evaluation, Engineering Structure 20 (1998)
and after retrofitting it. All retrofitting techniques improved 452–464.
the ductility characteristics of the structure. In the case of [8] R. S. Lawson, V. Vance, H. Krawinkler, Nonlinear static push
over analysis – why, when and how? In: Proceedings of 5th US
CFRP jacketing in addition to significant enhancement in duc-
Conference Earthquake Engineering, vol. I, Earthquake
tility, flexural strength also increased slightly due to the contri- Research Institute, 1994, pp. 283–292.
bution of CFRP jacketing with tensile strength of the [9] P. Fajfar, M. Fischinger, N2 – a method for non-linear seismic
reinforcement. The columns retrofitted with reinforced con- analysis of regular structures, In: Proceedings of 9th World
crete jacketing or full steel jackets using steel plates developed Conference Earthquake Engineering, Tokyo-Kyoto, Japan, vol.
the overall structural performance in terms of ductility and 5, Japan Association for Earthquake Disaster Prevention, 1988,
lateral strength, strength being more pronounced due to larger pp. 111 – 116.
Analysis of a retrofitted reinforced concrete building 107
[10] M. Saiidi, M.A. Sozen, Simple nonlinear seismic analysis of R/C [13] A. Murat Turk, M. Mustafa Comert, Gokhan Kest, Increasing
structures, Journal of Structural Division, ASCE 107 (ST5) seismic capacity of existing reinforced concrete buildings by the
(1981) 937–951. use of frp and steel fuse elements, 3rd fib International Congress,
[11] The Egyptian Loading Code, ECP-201, 2012, pp. 108 – 158. 2010, pp. 2–13.
[12] Egyptian code for design and construction of concrete [14] ATC, Seismic Evaluation and Retrofit of Concrete Building,
structures, Ecp 203–2007. ATC 40, 1996.