Professional Documents
Culture Documents
e.g., aircrafts [17], [18], ships [19], and microgrids [20]. The The virtual-impedance-based stabilizers are employed in the
impact of CPL on the system stability is induced by its neg- control diagram of the interface converters in this stage.
ative impedance in the small signal analysis. The negative Meanwhile, droop control is also used to achieve proper power
incremental impedance makes the system poorly damped and sharing among different converters. Meanwhile, the transmis-
can induce instable poles in the frequency domain. Therefore, sion line connected to each local output bus is also included
the system stability is degraded [21], [22]. The above issue in this stage. The third stage is the load stage which includes
induced by CPL has been studied extensively, as shown in the the common load bus. Here, in order to study the impact of
literature review in Section II. Considering that dc microgrid CPL and develop the related damping method, CPLs are con-
is the research focus of this paper, since multiple interface nected at the PCC in the third stage. Among the above three
converters usually co-exist and they are connected in parallel, stages, the first and second stage features distributed configu-
it is necessary to derive a comprehensive system model that ration, which can be regarded as distributed power generation
includes different components of a dc microgrid and extend units, and the third stage includes the common bus where dif-
the research on CPL and its damping method to multiple con- ferent distributed units are collected. In order to study the
verter system. Meanwhile, the commonly used droop control overall system stability, a comprehensive small-signal model
should be taken into account when discussing the stabilization of the whole system comprised of the above three stages is
of the microgrid with CPLs. derived. Based on the derived model, the stability analysis
Virtual impedances have obtained increasing awareness in considering the impacts of CPL and the proposed stabiliz-
the control diagram of the interface converters nowadays. They ers are performed. Based on the derived systematic model
have generally two functionalities. First, virtual impedances of dc microgrids with multiple distributed power generation
can be used to match the grid-side impedance in ac micro- units, virtual-impedance-based stabilizers are implemented in
grids. The sharing of output active and reactive power can Stage II. Virtual impedances at two positions in the output side
be thereby efficiently decoupled [23]. Furthermore, the vir- of the interface converters are realized to tackle the instability
tual impedance can be programmed at the certain frequency issues induced by CPLs. Since the virtual-impedance-based
to form the expected harmonic impedance, which enables the stabilizers are located at two positions, higher control flexi-
function of harmonic sharing and damping [24]. Second, vir- bility can be achieved compared to conventional approaches
tual impedances can be employed to realize the resonance based on single virtual impedance. Impedance criteria is
damping in the LCL filters [25]. By using the additional cur- selected as a tool to evaluate the overall system stability with
rent sensors and multiple control loops, the resonance peaks the virtual-impedance-based stabilizers [27]. In particular, the
imposed by LCL filters can be attenuated. above multistage dc microgrid is divided into two sections,
Diverse types of configurations can be found in the existing that is: 1) the local source section; and 2) common load sec-
dc microgrids. The single bus system in [26] is commonly tion. The local source section is comprised of stages I and II,
used in small-scale dc microgrids, which is comprised of while the common load section is comprised of stage III.
renewable energy sources with stochastic output power, e.g. The output impedance of the local source section, namely Z s ,
photovoltaic (PV), wind turbines, etc., and energy storage as and the input impedance of the common load section includ-
energy buffer to establish the bus voltage. The PVs and wind ing CPL, namely Zl , are calculated. By using the criteria of
turbines commonly operate in power output mode to absorb impedance matching, the overall system stability is evaluated
maximum power, and the energy storage operates in volt- by the dominant poles of (1 + Zs /Zl )−1 . When all the dom-
age output mode to establish the common bus voltage. For inant poles locate in the stable region, the system stability is
larger-scale dc microgrids, the above single bus system can guaranteed. The proposed virtual-impedance-based stabilizers
be extended to a multibus system [14]. In a dc microgrid are employed to move the instable poles into the stable region.
with multiple buses, different local dc buses are collected at The contribution of this paper can be summarized as fol-
point-of-common-coupling (PCC) through transmission lines. lows. A comprehensive system model for dc microgrids is
Meanwhile, the original single bus can be regarded as source derived by considering three stages, that is: 1) source stage;
bus with combined renewable energy sources. 2) interface converter stage; and 3) load stage. The dynam-
In this paper, virtual-impedance-based stabilizers for dc ics involved in each stage and the impact of droop control are
microgrids with CPLs is proposed. Without loss of general- taken into account. The proposed model is specially developed
ity, a multistage configuration of dc microgrid is employed, for dc microgrids with multiple distributed energy genera-
which is comprised of three stages. The first stage is the tion units. Meanwhile, virtual-impedance-based stabilizers are
source stage where combined sources of PV and battery are employed in each distributed power generation unit. In par-
utilized to establish the source bus. Similar to the single ticular, the virtual-impedance-based stabilizers are located at
bus system, the PV works in maximum power point track- two positions. One of them is connected in series with the
ing (MPPT) mode and the battery works in voltage output dc-link capacitor of the interface converter, while the other
mode to build the bus voltage. By considering the stochastic one is connected at the output path of the converter. Both of
output power of PV and load condition, sizing of the battery them are located at the generation side. The combination of
can be properly accomplished to guarantee the stable source the virtual stabilizers at two positions allows higher flexibility
bus voltage. The second stage is the local interface converter of the control diagram.
stage. The input of the interface converter is the source bus The following paper is organized as follows. Section II
with stable voltage, and the output is the local output bus. briefly investigates the impact of CPL on system stability,
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 3
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 5
ĩL1
ṽo1 = [ rC1 (1 − D1 ) 1] · − rC1 IL1 · d̃1 − rC1 · ĩo1 (8)
ṽC1
where the variables showing in capital letter represent the (a)
steady-state values of duty cycle, inductor current, capacitor
voltage, and output current, the variables with “∼” indicate
the small-signal disturbance.
Let (b)
− rLC11 (1 − D1 ) − L11 (1 − D1 )
A1 =
C (1 − D1 )
1
0
1
1
(r C1 I L1 + V C1 − r C1 I o1 )
B11 = L1
− C11 IL1
r 1
L1 (1 − D1 )
C1
B21 = B31 = L1
− C11 0
C1 = [ rC1 (1 − D1 ) 1 ], D11 = −rC1 IL1 , D21 = −rC1 . (9) (c)
Hence, the small-signal model of the state-space function Fig. 6. Control diagram of different interface converters. Control dia-
gram of (a) unidirectional boost converter, (b) bidirectional boost converter,
in (7) and (8) can be simplified as and (c) bidirectional buck converter.
⎡ ⎤
dĩL1
⎢ ⎥
⎢ dt ⎥ = A1 · ĩL1 + B11 · d̃1 + B21 · ĩo1 + B31 · ṽs1 Let
⎣ dṽC1 ⎦ ṽC1
dt G11 = C1 (sI − A1 )−1 B11 + D11 · Gpi1 Gd
(10)
G21 = C1 (sI − A1 )− B31 − C1 (sI − A1 )−1
ĩ
ṽo1 = C1 · L1 + D11 · d̃1 + D21 · ĩo1 . (11) B11 Gpi1 Gd − D11 Gpi1 Gd
ṽC1
Zo1 = −C1 (sI − A1 )−1 B21 − D21 . (15)
By transferring the linear small-signal model in (10)
and (11) into frequency domain and combining the results, Therefore, (14) can be simplified as
it is derived that
ṽo1 (s) = G11 · ṽ∗s1 (s) + G21 · ṽs1 (s) − Zo1 · ĩo1 (s). (16)
ṽo1 (s) = C1 (sI − A1 )−1 B11 + D11 · d̃1 (s) It is seen from (16) that in the small-signal model, the output
+ C1 (sI − A1 )−1 B31 · ṽs1 (s) voltage of the converter can be represented by two parts. The
first part is the controlled voltage source determined by the
− −C1 (sI − A1 )−1 B21 − D21 · ĩo1 (s). (12)
reference and measured value of the input voltage of the con-
Since the interface converter for PV is used to reach MPPT verter, i.e., the output voltage of PV panel; the second part is
and does not need to establish the voltage of source bus, a basic the output impedance. Hence, the dynamics involved by MPPT
control diagram shown in Fig. 6(a) is used. Hence, the small- that is represented by ṽ∗s1 , input voltage and output current are
signal model of the control diagram in frequency domain is all taken into account.
achieved The above discussion is for the modeling of unidirectional
boost converter that is used for PV. For the bidirectional boost
∗
ṽs1 (s) − ṽs1 (s) · Gpi1 Gd = d̃1 (s) (13) converter used for battery, the analysis is the same as that
for PV converter. The basic topology of bidirectional boost
where Gd represents the unit pulse width modulation delay. converter is shown in Fig. 5(b). In order to avoid repetition,
It should be noted that the impact of MPPT on PV is rep- no detailed procedures are shown below. It can be finally
resented by the perturbation in the reference value of the PV derived that
output voltage ṽ∗s1 .
By analyzing the simultaneous equations of (12) and (13), ṽo2 (s) = C2 (sI − A2 )−1 B12 + D12 · d̃2 (s)
it yields + C2 (sI − A2 )−1 B32 · ṽs2 (s)
ṽo1 (s) = C1 (sI − A1 )−1 B11 + D11 · Gpi1 Gd · ṽ∗s1 (s) − −C2 (sI − A2 )−1 B22 − D22 · ĩo2 (s) (17)
+ C1 (sI − A1 )−1 B31 − C1 (sI − A1 )−1 B11 + D11 where A2 , B12 , B22 , B32 , C2 , D12 , and D22 follow the similar
expressions compared to A1 , B11 , B21 , B31 , C1 , D11 , and D21 .
× Gpi1 Gd · ṽs1 (s) Only the subscriptions should be changed.
The battery converter is used for establishing the source bus,
− −C1 (sI − A1 )−1 B21 − D21 · ĩo1 (s). (14) so its basic control diagram is shown in Fig. 6(b). Based on
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 7
this control diagram, the small-signal model is achieved , and R are the virtual inductance and
where Ldc , Rdc , Ldc dc
resistance, respectively.
− ṽo2 (s) · Gpi2 Gd = d̃2 (s). (18)
For the output power, it satisfies the expression below
Since the battery converter is used to establish the stable
po3 = vo3 · io3 . (24)
source bus voltage, its reference value is set to the constant
value of 380 V. Therefore, no dynamics of the reference value Hence, the small-signal expression of (24) can be shown as
is considered in (18).
By solving the simultaneous equations of (17) and (18), p̃o3 = Vo3 · ĩo3 + Io3 · ṽo3 . (25)
it yields
By transferring (25) into frequency domain and substituting
ṽo2 (s) = G12 · ṽs (s) − Zo2 · ĩo (s) (19) the result into (21), it is obtained
where d̃3 (s) = − 1 + mGlpf Io3 Gpi3 + Gdc Zdc Gd · ṽo3 (s)
−1
G12 = 1 + Gpi2 Gd C2 (sI − A2 )−1 B12 + Gpi2 Gd D12 − mGlpf Vo3 Gpi3 + Zdc Gd · ĩo3 (s). (26)
It can be seen from (19) that, similar to the unidirectional G13 = {1 + C3 Gd (sI − A3 )−1 B13 [(1 + mGlpf Io3 )Gpi3 + Gdc Zdc ]}−1
boost converter for PV, the small-signal model of the bidirec- × C3 (sI − A3 )−1 B33
tional boost converter can also be represented by the Thevenin −1
Zo3 = 1 + C3 Gd (sI − A3 )−1 B13 1 + mGlpf Io3 Gpi3 + Gdc Zdc
equivalent model with the voltage source of G12 · ṽs (s) and
output impedance of Z o2 . The dynamics involved by both of × C3 Gd (sI − A3 )−1 B13 mGlpf Vo3 Gpi3 + Zdc
0 − 0
C3 RL CL LL · s3 + LL · s2 + RL 1 + KpL VinL · s + RL KiL VinL
ZL = .
C3 = [ rC3 1 ], D23 = −rC3 . RL CL D2L · s2 + D2L − KpL D2L VinL · s − KiL D2L VinL
(28)
Considering the control diagram in Fig. 6(c), it is reached
where ZL and RL are the closed-loop input impedance and
d3 (s) = [v∗o3 (s) − vo3 (s) − m · Glpf · po3 (s)] · Gpi3
load resistance of the POL converter, CL and LL are the capaci-
−vo3 (s) · Gdc Zdc − io3 (s) · Zdc · Gd (21) tance and inductance of the output filter, VinL is the steady-state
where m is the droop coefficient, Glpf is the transfer function input voltage of the POL converter, KpL and KiL are the pro-
of low-pass filter, po3 is the output power. portional and integral terms of the PI controller, DL is the duty
Droop control is considered in the control diagram. cycle in steady state.
Meanwhile, the virtual-impedance-based stabilizers are By summarizing the results in (16), (19), (27), and (28),
employed, which are shown as Zdc and Zdc in (21). Here, the small-signal models of the multistage configuration of
Zdc and Zdc are expressed as dc microgrids is obtained, as shown in Fig. 7. Meanwhile,
the transmission line that is connected to the common load
Zdc = s · Ldc + Rdc (22) bus with aggregated CPLs is also taken into account in the
Zdc = s · Ldc + Rdc (23) derived model.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Zs −1 Fig. 8. Dominant poles of polynomial p w/o virtual-impedance-based
p= 1+ (29) stabilizers.
ZL
where Zs is the small-signal output impedance of the source. By taking the transmission lines into account, the source-
For each distributed power unit, it can be derived from the side impedance is obtained
detailed small-signal model in Fig. 7 that
Zs = (Zs1 + Zline1 )//(Zs2 + Zline2 )// · · · //(Zsn + Zlinen ).
G13 G11 Zo2 ṽ∗s1 (s) + G21 Zo2 ṽs1 (s) + G12 Zo1 ṽs2 (s)
ṽo3 (s) = (32)
Zo1 + Zo2
Zo1 Zo2 G213 + Zo1 Zo + Zo2 Zo Meanwhile, the load-side input impedance can be rep-
− · ĩo3 (s). (30)
Zo1 + Zo2 resented by using the impedance calculated in (28). By
substituting (28) and (32) into (29), the system stability can
Hence, the equivalent output impedance for each local be evaluated by testing the positions of the dominant poles of
power stage is derived as polynomial p.
Zo1 Zo2 G213 + Zo1 Zo + Zo2 Zo As shown in Fig. 8, when the virtual-impedance-based stabi-
Zsi = (31) lizers are not activated, instable dominant poles can be found
Zo1 + Zo2
in z domain. They are −1.04, 0.98 ± j 0.34, and 0.96 ± j
where Zsi is the source-side output impedance for distributed 0.28, respectively. When the virtual stabilizers are activated,
power unit #i. the original instable dominant poles are forced to move into
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 9
Imag Part
Imag Part
v
Real Part
Real Part
(a)
Fig. 10. Dominant poles of polynomial p with parameter deviation.
TABLE I
S YSTEM PARAMETERS
Time (s)
Time (s)
Solar Power
Fig. 14. Voltage of local output bus.
PV Output Power in
Power (kW)
Time (s)
Unit #1
PV Output Voltage in
Initial Period
Time (s)
Time (s)
Fig. 12. Output voltage of PV panel.
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 11
2 kW
Unit #1 Unit #1 1 kW
0.67 kW
1 kW
1 kW Unit #2
Unit #1 0.67 kW
Time (s)
Time (s)
0.67 kW
Unit #1
Unit #3 0
Time (s)
Time (s)
Unit #1 and 1.2 kW, which are all one-third of the related load power.
Meanwhile, stable operation is guaranteed in the whole process
by using virtual-impedance-based stabilizer.
Furthermore, the performance of the system with continuous
voltage reference step-up change is also tested. In particular, the
rated voltage of the local output bus is set to change following
Time (s)
the sequence of 200, 220, 240, 260, and 280 V. It is seen in
Fig. 16(b) that with the proposed stabilizer, stable operation is
Fig. 16. Changing of operating point. Output power of unit #1 with (a) load maintained in the whole process. It should be noted that the
power step-up, (b) voltage reference step-up, (c) load power step-down, output voltage of the local bus is slightly lower than its rated
and (d) voltage reference step-down.
value. It is because that droop control is used in the control.
droop control, the load power is equally shared by three power Similar to the above conditions, the results of load power
stages. and voltage step-down change are shown in Fig. 16(c) and (d).
As shown in Fig. 15(b), at t = 40 s, the stabilizer is deac- In particular, in Fig. 16(c), the load power decreases following
tivated. Due to the influence of CPL, the system becomes the sequence of 3.6, 3, 2.4, 1.8, and 1.2 kW. Hence, consid-
instable. ering equal load power sharing among three units, the output
power of unit #1 follows the sequence of 1.2, 1, 0.8, 0.6, and
C. Case III: Changing of Operating Points 0.4 kW. In Fig. 16(d), the voltage reference changes following
The stability analysis is performed based on small-signal the sequence of 280, 260, 240, 220, and 200 V.
model in Section III. In order to test the proposed stabilizers, it
is necessary to verify the performance with different operating D. Case IV: Plug-and-Play of Distributed Power
points. Generation Units
Continuous load step-up change occurs at the common load In order to further test the dynamic performance of the sys-
bus. In particular, the CPL changes following the sequence of tem with the proposed stabilizer, plug-and-play of distributed
1.2, 1.8, 2.4, 3, and 3.6 kW. By using the proposed stabilizer power generation units is studied.
and droop control, as shown in Fig. 16(a), the output power As shown in Fig. 17(a)–(c), three distributed power units
of unit #1 changes following the sequence of 0.4, 0.6, 0.8, 1, are connected to the load bus sequentially. Before t = 20 s,
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
2 kW
Unit #1
Unit #1 1 kW
Unit #2
0.67 kW
Unit #3
Fig. 19. Output power of three units with parameter deviation in the output
0.67 kW
filter and different droop coefficients.
0
E. Case V: Testing of Parameter Deviation
-
In order to test the performance of the stabilizer with param-
Time (s) eter deviation, the inductance and capacitance of the output
filter in the interface converters between local source bus and
local output bus is changed. In particular, the inductance and
Fig. 18. Dynamic disconnection of each unit with virtual-impedance-based
stabilizer activated. Output power of (a) unit #1, (b) unit #2, and (c) unit #3. capacitance for the converter in unit #2 are changed to have
a −20% error, while the inductance and capacitance for the
only power unit #1 is started. Hence, all the CPL of 2 kW is converter in unit #3 are changed to have a +20% error. The
supplied by unit #1. At t = 20 s, unit #2 is started. Hence, parameters of the filter for unit #1 keep the original value.
the load power is shared between these two power stages. The Meanwhile, in order to further test the parameter devia-
output power of each unit, i.e., unit #1 and #2, is 1 kW. At tion induced by the control diagram, the droop coefficients for
t = 40 s, unit #3 is started. Therefore, the load power of 2 kW unit #1–#3 are changed from equal values to those following
is shared among three modules. Each of them delivers 0.67 kW the relationship of 1:2:3. Previously, the droop coefficients for
output power. During the whole process of dynamic connec- each unit are the same.
tion, the system stability is ensured by using the proposed The above parameter differences are activated at t = 30 s.
stabilizer. By involving the above differences in the main power circuit
As shown in Fig. 18(a)–(c), three distributed power units and control diagram, the output power of each power module is
are disconnected sequentially. Before t = 20 s, three units shown in Fig. 19. It is seen that stable operation is also ensured
work together to feed the CPL of 2 kW. Each one delivers with different parameters. Meanwhile, by using proportional
0.67 kW output power. At t = 20 s, unit #2 is disconnected. droop coefficients, the output power of each module follows
Hence, each of unit #1 and #3 delivers 1 kW. At t = 40 s, unit the inverse proportion of droop coefficients, which is 3:2:1.
#3 is disconnected. The load power of 2 kW is only supplied Although parameter deviations are involved for the passive
by unit #1. As same as the results for dynamic connection, components in the output filter, the output power of each unit
during the whole process of dynamic disconnection, the system also follows the desired value that is inversely proportional to
stability is guaranteed by using the proposed stabilizer. the droop coefficients.
It should be noticed that some over-shoots/under-shoots in
the output power waveforms can be found during connection, V. C ONCLUSION
while the over-shoots/under-shoots cannot be observed obvi- In this paper, virtual-impedance-based stabilizers are pro-
ously in the waveforms for disconnection process. The reason posed to enhance the stability of dc microgrids with CPLs.
for this can be summarized below. Since the output voltage A comprehensive small-signal model of multistage dc micro-
of each distributed power generation unit is controlled, each grid is derived. Based on this model, the system stability
unit behaves as a voltage source. This is the nature of the considering the impact of CPL and the proposed stabilizer
difference of dynamic process when connecting or discon- is studied. By using the criteria of impedance matching, it
necting each unit. It is known that for a voltage source, the is demonstrated that the instable poles induced CPLs are
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
LU et al.: STABILITY ENHANCEMENT BASED ON VIRTUAL IMPEDANCE FOR DC MICROGRIDS WITH CPLs 13
forced to move into the stable region with properly designed [20] N. Bottrell, M. Prodanovic, and T. C. Green, “Dynamic stability of
stabilizers. Hence, the system stability can be guaranteed. a microgrid with an active load,” IEEE Trans. Power Electron., vol. 28,
no. 11, pp. 5107–5119, Nov. 2013.
[21] A. Emadi, A. Khaligh, C. H. Rivetta, and G. A. Williamson, “Constant
R EFERENCES power loads and negative impedance instability in automotive systems:
Definition, modeling, stability, and control of power electronic con-
[1] R. Lasseter et al., The Certs Microgrid Concept—White Paper on verters and motor drives,” IEEE Trans. Veh. Technol., vol. 55, no. 4,
Integration of Distributed Energy Resources, U.S. Dept. Energy, pp. 1112–1125, Jul. 2006.
Washington, DC, USA, Tech. Rep. LBNL-50829, Apr. 2002. [22] D. Marx, P. Magne, B. Nahid-Mobarakeh, S. Pierfederici, and B. Davat,
[2] A. A. A. Radwan and Y. A.-R. I. Mohamed, “Modeling, analysis, and “Large signal stability analysis tools in DC power systems with constant
stabilization of converter-fed AC microgrids with high penetration of power loads and variable power loads—A review,” IEEE Trans. Power
converter-interfaced loads,” IEEE Trans. Smart Grid, vol. 3, no. 3, Electron., vol. 27, no. 4, pp. 1773–1787, Apr. 2012.
pp. 1213–1225, Sep. 2012. [23] J. M. Guerrero, L. G. de Vicuña, J. Matas, M. Castilla, and J. Miret,
[3] D. Dong et al., “Modes of operation and system-level control of single- “Output impedance design of parallel-connected UPS inverters with
phase bidirectional PWM converter for microgrid systems,” IEEE Trans. wireless load-sharing control,” IEEE Trans. Ind. Electron., vol. 52, no. 4,
Smart Grid, vol. 3, no. 1, pp. 93–104, Mar. 2012. pp. 1126–1135, Aug. 2005.
[4] Y. W. Li and C. N. Kao, “An accurate power control strategy for [24] J. He, Y. W. Li, and M. S. Munir, “A flexible harmonic control approach
power-electronics-interfaced distributed generation units operating in through voltage-controlled DG-grid interfacing converters,” IEEE Trans.
a low-voltage multibus microgrid,” IEEE Trans. Power Electron., vol. 24, Ind. Electron., vol. 59, no. 1, pp. 444–455, Jan. 2012.
no. 12, pp. 2977–2988, Dec. 2009. [25] A. A. Rockhill, M. Liserre, R. Teodorescu, and P. Rodriguez,
[5] Q. C. Zhong, “Robust droop controller for accurate proportional load “Grid-filter design for a multimegawatt medium-voltage voltage-source
sharing among inverters operated in parallel,” IEEE Trans. Ind. Electron., inverter,” IEEE Trans. Ind. Electron., vol. 58, no. 4, pp. 1205–1217,
vol. 60, no. 4, pp. 1281–1290, Apr. 2013. Apr. 2011.
[6] N. Pogaku, M. Prodanović, and T. C. Green, “Modeling, analysis and [26] G. AlLee and W. Tschudi, “Edison redux: 380 Vdc brings reliability
testing of autonomous operation of an inverter-based microgrid,” IEEE and efficiency to sustainable data centers,” IEEE Power Energy Mag.,
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007. vol. 10, no. 6, pp. 50–59, Nov./Dec. 2012.
[7] J. M. Guerrero, M. Chandorkar, T. L. Lee, and P. C. Loh, “Advanced [27] C. M. Wildrick, F. C. Lee, B. H. Cho, and B. Choi, “A method of
control architectures for intelligent microgrids—Part I: Decentralized defining the load impedance specification for a stable distributed power
and hierarchical control,” IEEE Trans. Ind. Electron., vol. 60, no. 4, system,” IEEE Trans. Power Electron., vol. 10, no. 3, pp. 280–285,
pp. 1254–1262, Apr. 2013. May 1995.
[8] H. Valderrama-Blavi, J. M. Bosque, F. Guinjoan, L. Marroyo, and [28] M. Cespedes, L. Xing, and J. Sun, “Constant-power load system sta-
L. Martínez-Salamero, “Power adaptor device for domestic DC micro- bilization by passive damping,” IEEE Trans. Power Electron., vol. 26,
grids based on commercial MPPT inverter,” IEEE Trans. Ind. Electron., no. 7, pp. 1832–1836, Jul. 2011.
vol. 60, no. 3, pp. 1191–1203, Mar. 2013. [29] M. Cupelli, L. Zhu, and A. Monti, “Why ideal constant power loads are
[9] A. Pratt, P. Kumar, and T. V. Aldridge, “Evaluation of 400V DC distri- not the worst case condition from a control standpoint,” IEEE Trans.
bution in Telco and data centers to improve energy efficiency,” in Proc. Smart Grid, to be published.
INTELEC, Rome, Italy, 2007, pp. 32–39. [30] A. Kwasinski and C. N. Onwuchekwa, “Dynamic behavior and stabiliza-
[10] H. Kakigano, M. Nomura, and T. Ise, “Loss evaluation of DC distribu- tion of DC microgrids with instantaneous constant-power loads,” IEEE
tion for residential houses compared with AC system,” in Proc. IPEC, Trans. Power Electron., vol. 26, no. 3, pp. 822–834, Mar. 2011.
Sapporo, Japan, Jun. 2010, pp. 480–486. [31] W.-J. Lee and S.-K. Sul, “DC-link voltage stabilization for reduced
[11] T. F. Wu, K. H. Sun, C. L. Kuo, and C. H. Chang, “Predictive current DC-link capacitor inverter,” in Proc. IEEE ECCE, San Jose, CA, USA,
controlled 5-kW single-phase bidirectional inverter with wide inductance 2009, pp. 1740–1744.
variation for DC-microgrid applications,” IEEE Trans. Power Electron., [32] P. Magne, B. Nahid-Mobarakeh, and S. Pierfederici, “DC-link voltage
vol. 25, no. 12, pp. 3076–3084, Dec. 2010. large signal stabilization and transient control using a virtual capacitor,”
[12] D. Dong et al., “Grid-interface bi-directional converter for residential in Proc. IEEE IAS, Houston, TX, USA, 2010, pp. 1–8.
DC distribution systems—Part one: High-density two-stage topology,” [33] D. Bosich, G. Giadrossi, and G. Sulligoi, “Voltage control solutions to
IEEE Trans. Power Electron., vol. 28, no. 4, pp. 1655–1666, Apr. 2013. face the CPL instability in MVDC shipboard power systems,” in Proc.
[13] J. M. Guerrero, J. C. Vasquez, J. Matas, G. G. De Vicuña, and AEIT, Trieste, Italy, 2014, pp. 1–6.
M. Castilla, “Hierarchical control of droop-controlled AC and DC [34] A.-B. Awan, B. Nahid-Mobarakeh, S. Pierfederici, and
microgrids—A general approach toward standardization,” IEEE Trans. F. Meibody-Tabar, “Nonlinear stabilization of a DC-bus supply-
Ind. Electron., vol. 58, no. 1, pp. 158–172, Jan. 2011. ing a constant power load,” in Proc. IEEE IAS, Houston, TX, USA,
[14] X. Lu, J. M. Guerrero, K. Sun, and J. C. Vasquez, “An improved con- 2009, pp.1–8.
trol method for DC microgrids based on low bandwidth communication [35] P. Liutanakul, A.-B. Awan, S. Pierfederici, B. Nahid-Mobarakeh, and
with DC bus voltage restoration and enhanced current sharing accuracy,” F. Meibody-Tabar, “Linear stabilization of a DC bus supplying a constant
IEEE Trans. Power Electron., vol. 29, no. 4, pp. 1800–1812, Apr. 2014. power load: A general design approach,” IEEE Trans. Power Electron.,
[15] X. Lu, K. Sun, J. M. Guerrero, J. C. Vasquez, and L. Huang, “State- vol. 25, no. 2, pp. 475–488, Feb. 2010.
of-charge balance using adaptive droop control for distributed energy [36] V. Arcidiacono, A. Monti, and G. Sulligoi, “An innovative generation
storage systems in DC microgrid applications,” IEEE Trans. Ind. control system for improving design and stability of shipboard medium-
Electron., vol. 61, no. 6, pp. 2804–2815, Jun. 2014. voltage DC integrated power system,” in Proc. IEEE ESTS, Baltimore,
[16] X. Lu, K. Sun, J. M. Guerrero, J. C. Vasquez, and L. Huang, “Double- MD, USA, Apr. 2009, pp.152–156.
quadrant state-of-charge-based droop control method for distributed [37] P. Magne, B. Nahid-Mobarakeh, and S. Pierfederici, “A design method
energy storage systems in autonomous DC microgrids,” IEEE Trans. for a fault-tolerant multi-agent stabilizing system for DC microgrids with
Smart Grid, vol. 6, no. 1, pp. 147–157, Jan. 2015. constant power loads,” in Proc. IEEE ITEC, Dearborn, MI, USA, 2012,
[17] A. Emadi, B. Fahimi, and M. Ehsani, “On the concept of negative pp. 1–6.
impedance instability in advanced aircraft power systems with con- [38] P. Magne, “Contribution a l’etude de la stabilite et a la stabilisation
stant power loads,” Soc. Automot. Eng. J., vol. 1, no. 1, Aug. 1999, des reseaux DC a recuperation d’energie,” Ph.D. dissertation, Dept.
Art. ID 1999-01-2545. Formation Doctorale, Univ. Lorraine, Nancy, France, 2012. [Online].
[18] M. Gries, O. Wasynczuk, B. Selby, and P. T. Lamm, “Designing for Available: http://docnum.univ-lorraine.fr/public/DDOC_T_2012_
large-displacement stability in aircraft power systems,” Soc. Automot. 0119_MAGNE.pdf
Eng. J., vol. 1, no. 1, pp. 894–902, 2009. [39] A. Khaligh and A. Emadi, “Mixed DCM/CCM pulse adjustment with
[19] G. Sulligoi et al., “Multiconverter medium voltage DC power systems constant power loads,” IEEE Trans. Aerosp. Electron. Syst., vol. 44,
on ships: Constant-power loads instability solution using linearization no. 2, pp. 766–782, Apr. 2008.
via state feedback control,” IEEE Trans. Smart Grid, vol. 5, no. 5, [40] D. W. Hart, Power Electronics, New York, NY, USA: McGraw-Hill,
pp. 2543–2552, Sep. 2014. 2010.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.