You are on page 1of 24

book 1_jan10:Layout 1 15/04/2010 17:30 Page 24

www.gyproc.ie

24
book 1_jan10:Layout 1 15/04/2010 17:31 Page 25

Gyproc Plaster
book 1_jan10:Layout 1 15/04/2010 17:31 Page 26

Some things make


life better!

We’ve just done it!


Introducing New Gyproc Base Coat
A better and easier way to plaster
Gypsum Industries have just made life easier for you, by
introducing a new robust base coat plaster for use on
concrete block backgrounds. Specially formulated for today’s
busy plasterers, New Gyproc Base Coat is convenient,
high-impact resistant with low shrinkage and high
compressive strength. 50% lighter than
traditional plaster, it sets in hours,
allowing up to 40% more
productivity. Guaranteed by Gypsum
SpecSure Warranty. Make life easier
with New Gyproc Base Coat.
Gypsum Industries, Kingscourt, Co. Cavan. Head Office, Unit 14, Park West Industrial Park, Dublin 12. Tel: 01-6298400
E-mail: enquiries@gyproc.ie Web: www.gyproc.ie
book 1_jan10:Layout 1 15/04/2010 17:31 Page 27

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Introdduction
INTRODUCTION CODES OF PRACTICE

Gyproc and Carlite plasters provide a smooth high quality The following should be referred to:
surface to internal walls and ceilings. They also provide a
I.S. EN CEN/TR 15124:2005: Design, Preparation and
durable base for the application of decorative finishes. The
Application of Internal Gypsum Plastering Systems.
range includes two-coat plastering (using basecoat & finish
coat plaster), finish plastering over Gyproc plasterboards I.S. EN 13914-2:2005: Design, Preparation and Application of
and special application plasters*. The plasters can be used External Rendering and Internal Plastering - Part 2: Design
in both new buildings and refurbishment and can be Considerations and Essential Principles for Internal Plastering.
applied to all common background types.
PERFORMANCE
*Specialist applications include:
• X-ray protection
Temperature
• Projection plastering
It is recommended that the background temperature should
• Airtightness
be at least 5ºC and that the plaster should not be subjected
• Salt retarding plastering
to temperatures below 5ºC before it has set. Dry bagged
Gyproc and Carlite plasters are pre-mixed and only require the plaster is not affected by low temperatures.
addition of clean water. They have a controlled setting time
During application of gypsum plaster in hot and/or dry
and are free from inherent shrinkage cracking. All plasters
conditions, care should be taken to ensure that rapid loss of
are predominantly supplied in 25kg bags for ease of
water is avoided. Gypsum plaster requires a proportion of
handling and storage.
the mixing water in order to set and achieve full strength. If
the water is dried off too rapidly, the strength of the set
Limitations
plaster will be impaired.
Gyproc and Carlite plasters should not be used to isolate
dampness and are not suitable for use in continuously Once set and fully dry, Gyproc and Carlite plasters are
damp or humid conditions. suitable for use in situations where the temperature is up to
43°C.
IS EN ISO 9001:2000
Gypsum Industries manufactures its products under the IS Reaction to Fire
EN ISO 9001:2000 quality assurance system. The plasters are non-combustible when tested in
accordance with BS 476: Part 4 1970 (Amended 1984). For
IS EN ISO 14001:1996
the purpose of the Building Regulations 1997, gypsum
Gypsum Industries has an environmental management
plasters are designated non-combustible materials,
system which complies with the requirements of IS EN ISO
(Technical Guidance Document B). Gypsum plasters also
14001:1996.
satisfy the requirements for Class O surfaces.
Handling and Storage
During handling, care should be taken to avoid puncturing DESIGN
the bags or allowing them to come into contact with
dampness. The bags should be stored in a completely dry Planning - key factors
place and never placed directly onto a concrete floor. When When specifying the thickness of plaster, the specifier
storing on concrete the bags should be laid on wooden should have an awareness of other design factors.
pallets or battens. Poor storage or prolonged storage will Examples include:
affect the setting time and ultimate hardness of the product. 1. The finished dimensions of rooms and internal spaces.
Health and Safety 2. The thickness of grounds (these should be less than the
Safety Data Sheets for all Gypsum Industries’ products are specified thickness of plaster to allow for packing out).
available to download from our website 3. The dimensions of joinery and its positioning relative to
www.gypsum.ie, or from our Technical Sales Department. the plaster face.
4. The positioning of installations such as heating
Durability
appliances and other fittings.
Gypsum plasters attain early strength during the drying
process and the plasterwork does not suffer from inherent 5. The accommodation of services.
shrinkage cracks. Whilst the finished surface can be 6. The required fire resistance, sound insulation or
indented by impact, the natural resilience of set plaster radiation control.
prevents more serious damage. Where specified in locations 7. Minimum coverage of plasters.
where there is a risk of repetitive damage, consideration
should be given to the provision of rails or other physical
barriers to protect vulnerable areas.
1.1

12. Tel: 01-6298400


27
book 1_jan10:Layout 1 15/04/2010 17:31 Page 28

www.gyproc.ie
Plaster Selection

Basecoat Plasters Finishing Plasters


Pre-mixed Gyproc and Carlite plasters are frequently used Gyproc Plasterboards
due to the many benefits over site-mixed sand and cement: Following the bedding in of Gyproc Joint Tape into Gyproc
Joint Filler or Gyproc Pro Fill, finishing for subsequent
• Consistency and quality assurance with factory controlled decoration can be one of the following options:
formulation. • 10mm undercoat plastering on grey side with Gyproc
• Gypsum plaster has no appreciable shrinkage once set Bonding, followed by 2mm Gyproc Skimcoat or Carlite Finish
while cement has an extended shrinkage period and • Finish coat plastering with Gyproc Skimcoat,
therefore may suffer from cracking. Carlite Finish or Gyproc Board Finish plaster applied
• Gypsum plaster sets in a matter of hours allowing approximately 2mm thick.
significantly earlier application of the finishing coat • Application of a special primer (Gyproc Drywall Primer
compared to finishing cement-based basecoats. or Drywall Sealer) to the entire surface, following the
complete Gyproc Jointing Method (see section 2.2 )
The range of gypsum basecoats designed for various • Texture coating with Artex.
backgrounds and performances include:
b) Plaster Backgrounds
• Gyproc Floating Coat Where the background is a Gyproc undercoat plaster,
• Gyproc Base Coat finishing is invariably carried out by application of a
• Gyproc Bonding gypsum based finish plaster. Gyproc Skimcoat or Carlite
Finish are applied approximately 2mm thick. Such a finish is
These plasters offer the following benefits: generally problem-free when applied over a gypsum
• Lightweight basecoat. However, cement based undercoats shrink for
• High coverage some weeks while curing. This places shearing forces on the
• Ease of application interface of the cement based basecoats and the gypsum
• Good impact resistance finish, which frequently result in cracking of the finish or
• Early application of finishing plaster even shelling of the finish from the basecoat. See section 1.4
• No scud coat required on blockwork and 1.11 .
• Minimisation of crane usage in high rise buildings.
Gyproc Plaster Beads
Please refer to section 8.2 for information.

1.2

28
book 1_jan10:Layout 1 15/04/2010 17:31 Page 29

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Basecoat Plasters
Introduction Storage
Gyproc Floating Coat and Base Coat Plasters have been The plaster should be stored dry, as the absorption of
developed in response to a demand for a high convenience, moisture by any gypsum plaster shortens the setting time
dependable, hard, gypsum base coat plaster providing a and may reduce the strength of the set plaster. Where
high compressive strength and impact resistance. They are storage areas have concrete floors, timber platforms should
specifically designed for use on concrete block backgrounds be laid and the plaster stored on these. The shelf life of
and should not be applied to plasterboard. Gyproc Floating Coat and Base Coat is 12 weeks.

Gyproc Floating Coat and Base Coat are manufactured Mixing


from retarded hemihydrate gypsum. Gyproc Floating Coat and Base Coat plasters are premixed
with aggregate and only clean water need be added to
Reaction to Fire prepare it for use. No admixtures should be used. Mix to a
The plasters are non-combustible when tested in normal plastering consistency. Cleanliness is essential, set
accordance with BS 476: Part 4 1970 (Amended 1984). For plaster left in a receptacle from a previous mixing will
the purpose of the Building Regulations 1997,(Technical shorten the setting time. This can reduce the strength of
Guidance Document B) gypsum plasters are designated the plaster when set. Mixing trays and buckets must be
non-combustible materials. Gypsum plasters also satisfy the washed thoroughly after each mix. Mechanical mixing may
requirements for Class O surfaces. be used, but care should be taken not to mix through
the set.
Effect of Temperature
It is recommended that the background temperature Application
should be at least 5ºC and that the plaster should not be Dry blockwork should be well brushed down to remove any
subjected to temperatures below 5ºC before it has set. Dry dust or loose particles of mortar etc. from the surface. Any
bagged plaster is not affected by low temperatures. metal objects such as nails etc. should be removed from the
face and blockwork should be well wetted to off-set
The plaster is not suitable for use in situations where the excessive suction in the background. Plaster of the correct
temperature exceeds 43°C. consistency should be applied with very firm pressure and
the Gyproc Floating Coat or Base Coat brought to a true
and level surface by means of a straight edge or darby.

The surface should be closed with a hand float and


thoroughly scratched to provide a key for the finishing
coat. Never attempt to retemper Gyproc Floating Coat or
Base Coat Plaster after the set has commenced.

Sector Guide
ure

ent

Hous ntial -

Apar ntial -

High ntial -
& Leis
ercial

ts
tainm
hcare
ation

tmen
trial

oria

dial

Rise

1.3
ing
es

e
Comm

Retail

Custo

Resid

Resid

Resid
Audit
Sport

Indus
Healt

Enter
Offic

Educ

✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

29
book 1_jan10:Layout 1 15/04/2010 17:31 Page 30

www.gyproc.ie
Basecoat Plasters

Approximate Coverage Party Wall Sound Regulations


Gyproc Floating Coat plaster applied to a nominal thickness Technical Guidance Document E, Sound, 1997, provides
of 10mm will give an approximate coverage of 117m2 per several specifications for solid masonry sound insulating
tonne*. Gyproc Base Coat plaster applied to a nominal walls. Wall specification A is as follows:
thickness of 10mm will give an approximate coverage of
102m2 per tonne*. See Plastering Specifications,
A concrete blockwork or concrete brickwork plastered on
section 1.11 . both faces

*Depending on the straightness of the concrete blockwork. The average mass of the wall (including the
plaster) should be at least 415kg/m2.
Setting Time The thickness of the plaster should be at least
3 to 5 hours, depending on background suction and 12.5mm on each face.
environmental conditions. Use blocks which extend to the full thickness of the
wall, i.e. blocks laid on their flat.
Projection Plaster
Gyproc Floating Coat, subject to suitable conditions and Example
215mm solid concrete block, 112.5mm coursing,
use of appropriate equipment, may be suitable for use as a
lightweight plaster; block density of 1860 kg/m3
basecoat projection plaster. A finish coat plaster of Gyproc
gives the required mass.
Skimcoat or Carlite Finish should be applied.

Finishing
A finishing coat of Gyproc Skimcoat or Carlite Finish can be
applied as soon as the Floating Coat or Base Coat has set. Typically the required mass (415 kg/m2) can be achieved by
The finish plaster should be applied to a nominal thickness a 5N common block (must be confirmed by the block
of 2mm and trowelled to provide a smooth finish. manufacturer).

Finishing coat coverage at 2mm thickness is 375m2 per 11mm Gyproc Floating Coat or Base Coat, finished with
tonne. See Plastering Specifications, section 1.11 . 2mm of Gyproc Skimcoat or Carlite Finish is a suitable
plaster finish to each side of the blockwork wall. The use of
Drying Gyproc Floating Coat or Base Coat instead of the
Adequate ventilation is an essential requirement to aid ‘traditional’ sand and cement allows earlier application of
drying out of all plasters. In accordance with I.S. CEN/TR the finish coat plaster.
15124:2005 ‘when the application is finished Gypsum
plastering should be ventilated until it has dried.’ Site sound test results are shown below:
Result Mean
In addition, I.S. EN13914-2:2005 states that ‘if adequate (dB DnT,w) (dB DnT,w)
ventilation is not provided during the drying of the plaster,
Site A 56, 57, 55, 56 56
then the strength of the plaster may be impaired and the
time at which decoration may start may be delayed.’ Site B 58, 57, 57, 58 57.5

Site C 54, 61, 54, 57 57


Decoration
Follow normal procedures and techniques.
These results are well in excess of the values in Table 1
of Technical Guidance Document E, 1997. Please contact
us if you wish to obtain a copy of the sound insulation
test reports.

Air Permeability
Plastering a blockwork wall with Gyproc Base Coat or
Floating Coat finished with Gyproc Skim Coat or Carlite
Finish will aid compliance with the air permeability
requirements listed in Technical Guidance Document L,
Conservation of Fuel and Energy, Dwellings, 2007
(implemented 1st July 2008).

1.3

30
book 1_jan10:Layout 1 15/04/2010 17:31 Page 31

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Basecoat Plasters
Introduction Mixing
Gyproc Bonding Plaster is one of the range of lightweight, Mix to normal plastering consistency using clean water
retarded hemihydrate, premixed gypsum plasters, requiring drawn directly from a tap or hydrant. No admixtures
only the addition of clean water to prepare them for use. should be used. Cleanliness is essential. Set plaster left in a
Gyproc Bonding is a base coat for low suction backgrounds. receptacle from a previous mix will shorten the setting time
and may reduce the strength of the plaster when set.
Reaction to Fire Mixing trays and buckets must be washed thoroughly after
The plasters are non-combustible when tested in each mix. Mechanical mixing may be used, but care should
accordance with BS 476: Part 4 1970 (Amended 1984). For be taken not to mix through the set.
the purpose of the Building Regulations 1997, gypsum
plasters are designated non-combustible materials, Application
(Technical Guidance Document B). Gypsum plasters also Gyproc Plasterboards
satisfy the requirements for Class O surfaces. Gyproc Bonding should be applied to the grey face of
Gyproc Wallboards, 4x2’s, 8x2’s, Round Edge Greyboards
Effect of Temperature and Plank at a thickness of 10mm.
It is recommended that the background temperature
should be at least 5ºC and that the plaster should not be In-situ concrete
subjected to temperatures below 5ºC before it has set. Dry Plastering over in-situ concrete has long been regarded as
bagged plaster is not affected by low temperatures. one of the plastering trade’s most complex problems.
Depending on mix, aggregates, chemical additives,
The plaster is not suitable for use in situations where the vibrating and shuttering, the surface of concrete can vary
temperature exceeds 43°C. from one contract to another and cannot, therefore, be
considered a consistent background for plastering. A very
Storage smoothly finished concrete can inhibit good adhesion of
The plaster should be stored dry, as the absorption of the plaster, as can concrete with a very high suction. The
moisture by any gypsum plaster shortens the setting time shearing force set up by the differential expansion
and may reduce the strength of the set plaster. Where between plaster and concrete can cause loss of adhesion of
storage areas have concrete floors, timber platforms should the plaster. The formulation of a plaster capable of dealing
be laid and the plaster stored on these. The shelf life of with all combinations of these factors has so far not been
Gyproc Bonding is 12 weeks. achieved. However, experience over many years has shown
that once the concrete surface is clean and free of all dust,
mold-oil or other release agents the following methods
may be suitable:

Sector Guide
ure

ent

Hous ntial -

Apar ntial -

High ntial -
& Leis
ercial

ts
tainm
hcare
ation

tmen
trial

oria

dial

Rise

1.3
ing
es

e
Comm

Retail

Custo

Resid

Resid

Resid
Audit
Sport

Indus
Healt

Enter
Offic

Educ

✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

31
book 1_jan10:Layout 1 15/04/2010 17:31 Page 32

www.gyproc.ie
Basecoat Plasters

(a) the application of ThistleBond-it in accordance with


section 1.6 or
(b) the application of Gyproc Bonding over a scudcoat
incorporating an S.B.R. bonding agent, applied as per
the bonding agent manufacturer’s instructions*.

*Scud Coat: Tests have indicated that best results are


obtained when a latex modified mortar of sand, cement
and a proprietary bonding agent such as Evo-Fix, or
equivalent, is applied as a scud coat. Such modified mortar
should be prepared strictly in accordance with the
instructions of the bonding agent manufacturer. It is
reiterated that the concrete surface should be cleaned
down and be free of all dust, mould-oil, or other
release agents.

Gyproc Bonding should normally be applied to a thickness


of 10mm. The coat should not be thicker than is necessary
to bring the work to a level surface, particularly on soffits.
The plaster must not be mixed to a softer consistency than
normal in an effort to apply a very thin coat since the
additional water used will reduce the strength of the
plaster. With thin coats there is also a risk of dry out.

Gyproc Bonding should be trowelled tightly with firm


pressure, built out to the required thickness, ruled to an
even surface and properly scratched to form a key for the
finishing coat of Carlite Finish or Gyproc Skimcoat Plaster.

Setting Time
3 to 4 hours, but may be affected by background suction
and environmental conditions.

Drying
Adequate ventilation is an essential requirement to aid
drying out of all plasters. In accordance with I.S. CEN/TR
15124:2005 ‘when the application is finished Gypsum
plastering should be ventilated until it has dried.’

In addition, I.S. EN13914-2:2005 states that ‘if adequate


ventilation is not provided during the drying of the plaster,
then the strength of the plaster may be impaired and the
time at which decoration may start may be delayed.’

Durability
Gyproc Bonding Plaster with a final coat of 2mm Carlite
Finish or Gyproc Skimcoat provides a plastering system
suitable for moderate to high impact/wear areas.

1.3

32
book 1_jan10:Layout 1 15/04/2010 17:31 Page 33

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Background Preparation
SCRATCHING

All base coats must be thoroughly scratched to provide a good mechanical key for the finishing plaster.

YES Note how close and regular the scratch


marks are when a proper scratcher is used. NO Inadequate scratching can result in the finishing
plaster falling away.
Good scratching will not however, in itself
guarantee good adhesion. Materials similar
in appearance can have totally different
rates of absorption or suction. High suction
backgrounds can cause rapid dryout of the
finishing coat with consequent adhesion
failure, even when such backgrounds are
well scratched.

GREEN BACKGROUNDS

Another, and possibly more common problem is the


application of finishing plaster to ‘green’ backgrounds.
These are mortar backgrounds which are set, but are not
cured. The finishing plaster is killed at the interface and
there is no adhesion.

1.4

33
book 1_jan10:Layout 1 15/04/2010 17:31 Page 34

www.gyproc.ie
Finishing Coat Plasters

GENERAL

Carlite Finish, Gyproc Skimcoat and Gyproc Board Finish


can be used for finishing most backgrounds/linings. The
choice will depend on the background or lining (see Table
1) and the personal preference of the plasterer. They
provide a smooth, flat, high quality surface to internal walls
and ceilings, and a durable base for the application of
decorative finishes.

The plasters are retarded hemihydrate, premixed gypsum


plasters, requiring only the addition of clean water to
prepare them for use. They have a controlled, graduated set
and produce surfaces that are free from shrinkage cracks.

PERFORMANCE

TABLE 1: SUITABILITY FOR DIFFERENT BACKGROUNDS

Background/linings Gyproc Skimcoat Carlite Finish Gyproc Board Finish

Gyproc R.E. Greyboard, a a a


4x2’s, 8x2’s, Plank
Front face of all Gyproc* a a a
and Glasroc plasterboards
Gyproc Floating Coat, Base Coat a a
Gyproc Bonding, Thistle X-Ray, Gyproc Dri-Coat
Sand/Cement Basecoats a a

*Gypsum plaster should not be specified as a finish to Moisture Resistant Boards as the board is designed to be suitable for
environments of higher than normal humidity, which no Gypsum plaster is designed to be suitable for. On exposed, untiled, Moisture
Resistant Boards, taping and filling is the recommended approach. However, if a plaster finish is required, the board should first be
treated with ThistleBond-it in accordance with section 1.6 . 6mm Gyproc Multiboards should also first be treated with
ThistleBond-it.

Sector Guide
ure

ent

Hous ntial -

Apar ntial -

High ntial -
& Leis
ercial

ts
tainm
hcare
ation

tmen
trial

oria

dial

Rise

1.5
ing
es

e
Comm

Retail

Custo

Resid

Resid

Resid
Audit
Sport

Indus
Healt

Enter
Offic

Educ

✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

34
book 1_jan10:Layout 1 15/04/2010 17:31 Page 35

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Finishing Coat Plasters


Notes Application
In areas of continuously damp/humid conditions, plastering All undercoats must be well scratched to provide a
specifications are not recommended. satisfactory mechanical key. Particular attention is drawn to
the recommendation on the necessity to allow drying
Where thickness in excess of 2mm is required, shrinkage to occur in sand/cement, sand/cement/lime base
consideration should be given to the use of Gyproc coats before the application of a finishing coat. Over-
Bonding (10mm thickness). trowelling should be avoided.

For full details, refer to Plastering Specifications, section 1.11 Decoration


Finishing Coat Plasters can be decorated with most
Storage proprietary paint finishes, or wall coverings. The
The plaster should be stored dry, as the absorption of manufacturer’s advice on the paint or wallcovering should
moisture by any gypsum plaster shortens the setting time be followed for preparation, priming, suitable adhesives
and may reduce the strength of the set plaster. Where and method of application. With new plaster, decoration
storage areas have concrete floors, plaster should be stored should not commence until the structure and plasterwork
on timber platforms. The shelf life of Carlite Finish, Gyproc have dried out thoroughly.
Skimcoat and Gyproc Board Finish is 12 weeks.
Note: I.S. CEN/TR 15124:2005 contains reference to
Reaction to Fire different levels of smooth finish, depending on the type of
The plasters are non-combustible when tested in paint that will be applied, for example, matt, semi-gloss
accordance with BS 476: Part 4 1970 (Amended 1984). For or gloss.
the purpose of the Building Regulations 1997, gypsum
plasters are designated non-combustible materials, I.S. EN 13914-2:2005 states the following, ‘Whatever the
(Technical Guidance Document B). Gypsum plasters also plastering system and finish and however skilled and
satisfy the requirements for Class O surfaces. conscientious the operative, plastering is a craft and it
should be appreciated that it is not possible to achieve a
Effects of Temperature completely smooth and true surface finish. Painting will
It is recommended that the background temperature tend to reveal any inherent surface irregularities. These
should be at least 5ºC and that the plaster should not be minor imperfections will be highlighted when gloss or semi-
subjected to temperatures below 5ºC before it has set. Dry gloss paints are used, particularly where the plasterwork is
bagged plaster is not affected by low temperatures. subjected to intense or shallow angle lighting. Therefore
these types of paints and lighting require special additional
The plaster is not suitable for use in situations where the measures to be taken. Otherwise, the consequential minor
temperature exceeds 43°C. irregularities will have to be accepted.’

Mixing Mapping
Mix to normal plastering consistency using clean water Finishing coat plaster applied to sand and cement
drawn directly from a tap or hydrant. No admixtures backgrounds may, when dry, exhibit widely varying suction,
should be used. Cleanliness is essential and set plaster left which, if not treated can result in difficulties in achieving
in a receptacle from a previous mix will shorten the setting the required paint finish.
time and may reduce the strength of the plaster when set.
Mixing trays and buckets must be washed thoroughly after Variable suction can easily be identified by brushing on
each mix. Mechanical mixing may be used, but care should water. Irregular patterns indicate variable suction, which
be taken not to mix through the set. will require treatment before painting. The application of a
water-based stablising solution, applied in accordance with
the manufacturer’s instructions, may overcome the problem.

1.5

35
book 1_jan10:Layout 1 15/04/2010 17:31 Page 36

www.gyproc.ie
ThistleBond-it

Introduction ThistleBond-it, stored correctly, has a shelf life of 6 months.


ThistleBond-it is a plaster-bonding agent for use on smooth Tubs are stamped with the date of manufacture.
and/or low suction backgrounds. It provides a mechanical
key by means of coarse aggregate particles. It is used in one Base Preparation
coat only and allowed to dry before plastering. The base must be capable of providing support, be clean,
dust-free, dry and frost-free. Concrete surfaces should also
ThistleBond-it is coloured light green to allow for easy be free of release agents.
identification of backgrounds to which it has been applied.
In addition, if ThistleBond-it is to be applied to a sand and
Typically, once the ThistleBond-it has dried, Gyproc Bonding cement background, the sand and cement must be fully
plaster of 10mm thickness is applied and then finished with dried and cured.
2mm of Gyproc Skimcoat or Carlite Finish.
If unsure about the suitability of the background, Gypsum
If the surface flatness allows it, Carlite Finish or Gyproc Industries strongly recommends the preparation of a test
Skimcoat may be directly applied to ThistleBond-it. area prior to starting the project.

ThistleBond-it is suitable for preparation of a variety of Application


backgrounds before plastering or drylining for interior use. ThistleBond-it is ready to use. Stir thoroughly before use
and apply evenly, preferably by roller. ThistleBond-it does
If a plaster finish is required to a Gyproc Moisture Resistant not require dilution.
Board, or 6mm Gyproc Multiboard, ThistleBond-it should
first be applied. Allow to dry thoroughly (please refer to Effect of
Temperature and Drying time for guidance).
Dabs of Gyproc DryWall Adhesive or Gyproc Compound
may also be used over ThistleBond-it. Apply 10mm of Gyproc Bonding plaster and allow to set
before application of 2mm of Gyproc Skimcoat.
ThistleBond-it should not be used where the plaster
contributes to the designed fire performance or plays and Alternatively, if the surface flatness allows, a 2mm coat of
essential part in fire protection. Carlite Finish or Gyproc Skimcoat can be applied directly to
the ThistleBond-it, once dry.
Effect of Temperature
ThistleBond-it is not suitable for application to frozen Care must be taken not to apply to window frames, door
backgrounds. Site temperature must be maintained above frames or other decorative surfaces. Once hardened
5ºC until thoroughly dry. ThistleBond-it can only be removed mechanically.

Drying Time Coverage


ThistleBond-it should be allowed a minimum of 24 hours Approximately 4.5m2 per litre, depending on background
drying time, however, this can be dependent on both suction. ThistleBond-it is available in 10 litre tubs.
environmental conditions and ventilation.
Cleaning of Tools and Equipment
Storage Tools and equipment should be cleaned with water
ThistleBond-it should be stored in a dry, cool and frost-free immediately after use of ThistleBond-it.
environment. When stored on concrete floors, timber
platforms should be provided. Pallets of tubs should not
1.6 have any other material stacked on top of them.

36
book 1_jan10:Layout 1 15/04/2010 17:31 Page 37

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Thistle X-Ray Plaster


Introduction Radiation Control
Thistle X-Ray is an undercoat plaster for use in suitable The normal way of expressing the resistance of any
backgrounds where protection from X-rays is required e.g. substance to X-rays is by comparison with lead sheet. For
areas within hospitals/dental surgeries. Thistle X-Ray has a example, with an X-ray tube potential of 75kV, an
controlled set, and provides a coating which is free from application of 20mm of Thistle X-Ray gives the same
shrinkage cracks. protection as a lead sheet 2mm thick.

Thistle X-Ray is a retarded hemihydrate, pre-mixed gypsum The table below lists three typical plaster thicknesses
plaster incorporating barytes aggregate, requiring only the against lead equivalence for six tube voltages from 50kV
addition of clean water to prepare it for use. With a final to 200kV.
coat of Gyproc Skimcoat or Carlite Finish, Thistle X-Ray
provides a smooth, inert, high quality surface to internal Where plastering over rib-lath, the thickness of plaster
walls and ceilings and a durable base for the application of required should be measured from the face of the lath.
decorative finishes.
Thistle X-Ray
Plaster
Reaction to Fire
Thickness X-ray Tube Potential
The plasters are non-combustible when tested in
50kV 75kV 100kV 125kV 150kV 200kV
accordance with BS 476: Part 4 1970 (Amended 1984). For
15mm 0.55 1.41 1.33 0.96 0.70 0.56
the purpose of the Building Regulations 1997, gypsum
20mm 0.88 2.00 1.92 1.33 1.02 0.79
plasters are designated non-combustible materials,
25mm 1.08 2.41 2.33 1.53 1.24 1.03
(Technical Guidance Document B). Gypsum plasters also
satisfy the requirements for Class O surfaces.
Note: The lead equivalence required should be
Effect of Temperature specified by the Radiological Protection Institute of
It is recommended that the background temperature Ireland, or the local hospital physicist. From the lead
should be at least 5ºC and that the plaster should not be equivalence the thickness of Thistle X-Ray plaster can
subjected to temperatures below 5ºC before it has set. Dry be determined. It is imperative that the specified
bagged plaster is not affected by low temperatures. thickness of plasterwork is achieved, in order to
provide the required degree of protection.
The plaster is not suitable for use in situations where the
temperature exceeds 43°C. Radiological Protection Institute of Ireland,
3 Clonskeagh Square, Clonskeagh Road, Dublin 14.
Storage Phone 01-269 7766 Fax 01-269 7437.
The plaster should be stored dry, as the absorption of
moisture by any gypsum plaster shortens the setting time Durability
and may reduce the strength of the set plaster. Where Thistle X-Ray with a final coat of 2mm Gyproc Skimcoat or
storage areas have concrete floors, timber platforms should Carlite Finish provides a plastering system suitable for
be laid and the plaster stored on these. The shelf life of
Thistle X-Ray is 16 weeks.
moderate to high impact/wear areas. 1.7

37
book 1_jan10:Layout 1 15/04/2010 17:31 Page 38

www.gyproc.ie
Thistle X-Ray Plaster

Background preparation should be applied at a thickness of 8mm up to the


Surfaces should be reasonably dry, clean, protected from thickness required and wire scratched between each coat.
the weather and suitable for the chosen specification. The final floating coat should be ruled to an even surface
Special precautions are often necessary due to the weight and lightly scratched to form a key for 2mm Gyproc
of the system. Skimcoat or Carlite Finish.

Walls To give full protection, it is essential that the finished


Thistle X-Ray can be applied directly to open textured plasterwork is completely crack-free. Thistle X-Ray should
dense concrete blocks. Other blocks and bricks (typically be therefore be applied with considerable care. Gyproc
lightweight or with poor mechanical key) require Skimcoat or Carlite Finish should be applied as soon as the
reinforcement with a suitable rib-lath, fixed in accordance basecoat has set.
with the manufacturer’s recommendations. Concrete lintels
within wall structures should be reinforced with expanded Setting Time
metal lath of a suitable type and gauge, again fixed in Thistle X-Ray has a setting time of 1.5 to 2 hours after
accordance with the manufacturer’s recommendations. mixing. The exact set time is largely dependent on
background suction.
Soffits
Soffits of solid construction (i.e. concrete or pot and
beam) or timber joists require reinforcement with a
suitable rib-lath. Thickness, weight & coverage
Coat Approx. Approx
Mixing Backgrounds Thickness wt.set & dry Cov.

Thistle X-Ray is pre-mixed and only clean water needs to (mm) (kg/m2) (m2/1000kg)

be added to prepare it for use. Mixing should be carried


Walls of open textured dense 25 50 19
out in a clean tray or bath. Tools and water used in
concrete blocks or keyed
mixing must be clean. Contamination from previous mixes
surface bricks (fletton type)
can shorten the setting time and reduce the strength of
the plaster when set. Mix by mechanical whisk to a lump-
Other block/brick walls with 25 65 14
free consistency. If required, small quantities can be
rib-lath
mixed by hand.

Concrete lintels reinforced 25 65 14


Application
with expanded metal lath
Thistle X-Ray plaster should not be applied to plasterboards.
of suitable gauge

When plastering directly to suitable walls a total plaster


Soffits of solid construction 15 40 23
thickness of up to 25mm can be applied using the following or timber joist floors - both
method. Floating coats should be applied with firm reinforced with rib-lath
pressure at a thickness 8mm, wire scratched and allowed to
set but not dry between coats. The final floating coat
should be ruled to an even surface and lightly scratched to
form a key for Gyproc Skimcoat or Carlite Finish.

Thistle X-Ray can be applied to suitable rib-lath to a total


thickness of 15mm from the face of the lath in soffits, or
to a total thickness of 25mm from the face of the lath in
wall applications. Plastering of Thistle X-Ray to metal lath
involves first a pricking up coat, which should be forced
through the metal lath in order to provide a good key to
the lath. The surface of the pricking up coat must be wire
scratched to provide a good key and allowed to set but
not dry before the floating coat is applied. Floating coats

1.7

38
book 1_jan10:Layout 1 16/04/2010 15:59 Page 39

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Airtightness Plaster
Introduction Cleanliness is essential, set plaster left in a receptacle from
Gyproc Airtite Plaster has been developed specifically to a previous mixing will shorten the setting time. This can
achieve very high levels of airtightness in modern reduce the strength of the plaster when set. Mixing trays
dwellings. Gyproc Airtite is specially formulated to reduce and buckets must be washed thoroughly after each mix.
air permeability and specifically designed for use on Mechanical mixing maybe used, but care should be taken
concrete block backgrounds and should not be applied to not to mix through the set.
plasterboard. It is envisaged that air permeability
performance levels are going to reduce further over the Application
next few years, driven through regulation. Dry blockwork should be well brushed down to remove any
dust or loose particles of mortar, debris, etc. from the
Reaction to Fire surface. Any metal objects such as nails, etc. should be
The plasters are non-combustible when tested in removed from the face and blockwork should be well
accordance with BS 476: Part 4 1970 (Amended 1984). For wetted to off-set excessive suction in the background.
the purpose of the Building Regulations 1997, (Technical Gyproc Airtite can be applied directly to open textured
Guidance Document B) gypsum plasters are designated medium or dense concrete blocks. Plaster of the correct
non-cobustible materials. Gypsum plasters also satisfy the consistency should be applied with firm pressure and the
requirements for Class O surfaces. Gyproc Airtite brought to a true and level surface by means
of a metal straight edge or darby.
Effect of temperature
It is recommended that the background temperature The surface should be adequately flattened with a hand
should be at least 5°C and that the plaster should not be float. The most common applications over Gyproc Airtite
subjected to temperatures below 5°C before it has set. Dry are either the Gyproc GypLyner systems or the Gyproc
bagged plasters is not affected by low temperature. DriLyner systems in which case the surface is not scratched.
When using the Gyproc DriLyner system, one can apply
The plaster is not suitable for use in situations where the Gyproc Compound to Gyproc Airtite plaster when the
temperature exceeds 43°C. plaster is set but it is good practice to let it dry out before
applying. Gyproc Finishing Coat Plasters such as Gyproc
Storage Skimcoat or Carlite Finish must not be applied directly to
The plaster should be stored dry, as the absorption of the Gyproc Airtite parge coat.
moisture by any gypsum plaster shortens the setting time
and may reduce the strength of the set plaster. Where Gyproc Airtite should normally be applied to a thickness of
storage areas have concrete floors, timber platforms should 6mm but to a maximum of 11mm in one application.
be laid and the plaster stored on these. The shelf life of
Gyproc Airtite is 12 weeks. Smooth or low suction background areas such as concrete
lintels or smooth faced engineered brick, particularly
Mixing window or door heads need to be firstly treated with
Gyproc Airtite is premixed with aggregate and only clean Gyproc Thistlebond-it, and allowed to fully dry for at least
water need be added to prepare it for use. No admixtures 24 hours prior to applying Gyproc Airtite to the said area.
should be used. Mix to a normal plastering consistency.
1.8

39
book 1_jan10:Layout 1 15/04/2010 17:31 Page 40

www.gyproc.ie
Airtightness Plaster

Gyproc Airtite can also be applied over expanded metal, Airtightness Test Results
but where specific air permeability is required, it is prudent The following masonry walls were constructed and a 6mm
to allow for the thickness of the expanded metal to ensure application of Gyproc Airtite was applied to one side of
a continuous 6mm parge coat is applied throughout. same. The air permeability tests were carried out in BSRIA,
a UKAS accredited laboratory. Test results on each of the 3
Approximate Coverage constructions are shown below.
Gyproc Airtite plaster applied to a nominal thickness of
6mm will give an approximate coverage of approximately The current Technical Guidance Document L, Conservation
180m2 per tonne*. See plastering Specifications, of Fuel and Energy, Dwellings 2007 (implemented 1st July
section 1.11 . 2008) require buildings to be constructed to have an upper
air permeability performance level of 10 m3/h.m2. It should
*Depending on the straightness of the concrete blockwork.
be noted that plastering a blockwork wall with Gyproc
Base Coat or Floating Coat finished with Gyproc Skim Coat
Setting Time
or Carlite Finish will also aid compliance with these air
4 to 5 hours, but may be affected by background suction
permeability requirements. Air permeability levels are
and environmental conditions.
expected to reduce further in future revisions to Technical
Guidance Document L.
Drying
Adequate ventilation is an essential requirement to aid
drying out of all plasters. In accordance with I.S. CEN/TR
15124:2005 ‘when the application is finished with Gypsum
plastering should be ventilated until it has dried.’

In additon, I.S. EN 13914-2:2005 states that ‘if adequate


ventilation is not provided during the drying of the plaster,
then the strength of the plaster may be impaired and the
time at which decoration may start may be delayed.’

Type of Blockwork Construction Air Permeability Air Changes Test Report


Performance Level
m3/h.m2 (50Pa)
215mm wide Block Wall on Flat House Room
(440mm x 215mm x 100mm)
Blockwall with 6mm Gyproc Airtite parge coat 0.11 0.047819 0.103289 24611d01

100mm wide Block Wall on Edge


(440mm x 215mm x 100mm)
Blockwall with 6mm Gyproc Airtite parge coat 0.12 0.050575 0.109241 24611d02

215mm wide Cavity Block Wall


(440mm x 215mm x 215mm)
Blockwall with 6mm Gyproc Airtite parge coat 0.27 0.112642 0.243307 24611d03

Notes: Assumption that the building has an Volume (m3)


impermeable floor & roof. House 576
Room 60
Envelope of house 240
Envelope of room 54

1.8

40
book 1_jan10:Layout 1 15/04/2010 17:31 Page 41

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Gyproc Dri-Coat Plaster


Introduction Once fully set and dry, Gyproc Dri-Coat should not be
Gyproc Dri-Coat is a cement-based renovating plaster exposed to situations where the temperature exceeds 49°C
formulated for re-plastering after the successful installation due to potential detrimental effects on the finishing plaster.
of a new damp proof course. Gyproc Dri-Coat can also be
used to prevent the migration of hydroscopic salts on Dry, bagged plaster is not affected by low temperatures.
blockwork walls which have suffered excessive exposure to During application in hot and/or dry conditions, care
moisture i.e. flood damage or similar. For other re- should be taken to ensure that rapid loss of water is
plastering operations, Gypsum Industries recommends the avoided. The plaster requires a proportion of the mixing
use of the appropriate plaster for the appropriate water in order to set and achieve full strength. If the water
background - usually Gyproc Base Coat, Bonding, or is dried off too rapidly, the strength of the plaster will
Floating Coat. be impaired.

Gyproc Dri-Coat should only be used for re-plastering after Effect of Condensation and Other Moisture
the successful installation of a new damp proof course, or Gyproc Dri-Coat is unaffected by exposure to moisture
elimination of the source of dampness. encountered in most building situations, however any
applied finishes, including finishing plasters may be
Walls which have had defective damp proof courses (or none unsuitable for such conditions. Gyproc Dri-Coat must not
at all) are likely to contain hydroscopic salts, which can be used to resist water under hydrostatic pressure.
continue to be a source of dampness, even after rising damp
is prevented, because they absorb atmospheric moisture. Background Preparation
Gyproc Dri-Coat is cement-based with waterproofing The source of the rising dampness must be identified and
additives, which restrict the migration of these salts from the eliminated. The existing plasterwork should be removed to
background through the plaster and thereby limit their a height at least 0.5m above either the new damp proof
detrimental effect on internal decoration. course or the last detectable sign of dampness. Where the
old plaster is gypsum based, it must be completely
Fire Resistance removed. Following chemical damp-proof injection, old
It should be assumed that Gyproc Dri-Coat makes a mortar joints, which are the site of the higher salt
negligible contribution to fire resistance or fire protection concentrations, should be thoroughly raked out and the
of building elements. face of the brickwork brushed with a wire brush.

Effect of Temperature Ideally, re-plastering with Gyproc Dri-Coat should be


Gyproc Dri-Coat is not suitable for plastering onto frozen delayed as long as possible to allow the background to dry
backgrounds. Use in ambient conditions below 5°C may out. Before re-plastering, any salts brought to the surface
reduce the strength of the set plasterwork and should of the background during drying should be carefully
be avoided. removed. Heavy salt contamination in the background can
cause persistent damp problems. Buildings such as old
farmhouses, stables and barns not originally built with a
damp-proof course, or buildings that have been exposed to
1.9

41
book 1_jan10:Layout 1 16/04/2010 14:19 Page 42

www.gyproc.ie
Gyproc Dri-Coat Plaster

storage of chemicals, are particularly at risk from this


problem. Gyproc Dri-Coat should not be used in these
situations unless a proper survey shows that the risk from
salts is minimal. An independent wall lining may be a
better solution. Chimney breasts are another area where
salt deposits may be heavy.

Storage
Bags should be stored dry, as absorption of water causes
set lumps to form in the bags and may reduce the strength
of the set plasterwork. If storing on a concrete floor, dry
timber platforms should be provided. Gyproc Dri-Coat
stored correctly has a shelf life of 6 months and bags are
printed with the use by date.

Mixing
Gyproc Dri-Coat plaster is pre-mixed with aggregate and
only clean water needs to be added to prepare it for use.
Hand mixing should be carried out in a clean tray or bath.
Excessive mechanical mixing should be avoided. Tools and
water used in mixing must be clean. Contamination from
previous mixes can reduce the strength of the plaster
when set.

Application
Application of Gyproc Dri-Coat can proceed once the
background is clean, sound, free from dust and
efflorescence, and where only residual moisture is present.
Low suction or smooth backgrounds, such as engineering
bricks, should be treated prior to plastering with a water
resisting bonding agent (by others) which should be applied
in accordance with the manufacturers' recommendations.

Where the background is dry, it is important to control


suction with the application of water. This prevents rapid
drying of the plaster which would impair its strength.
Angle beads must not be fixed with gypsum-based
materials. The use of Gyproc Bead Adhesive is
recommended. If the floor is solid, a 50mm gap should be
left between the plasterwork and the floor level. Under no
circumstances should the damp proof course be bridged.
Smooth or low suction background areas such as concrete
lintels or smooth faced engineering brick, particularly in
older buildings or indeed areas such as window or door
heads should be firstly treated with a styrene butadiene
resin (S.B.R.) or equivalent.

Finishing
Initial curing and shrinkage of the scratched undercoat
must be allowed to take place prior to application of finish
plaster. In cold/damp conditions, or where background
suction is low, a longer delay will be necessary. If sufficient
delay is not allowed, cracking or shelling of the finish coat
may result. Finish using Gyproc Skim Coat or Carlite Finish.

1.9 Tiling
Tiles up to 20kg/m² can be applied directly to the Gyproc
Dri-Coat. If applying Dri-Coat to provide a background for
tiles, avoid polishing the surface. Polished plaster surfaces
should be roughened and a suitable primer used.

42
book 1_jan10:Layout 1 15/04/2010 17:31 Page 43

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Casting Plasters
Gypsum Industries distributes a comprehensive range of specialist casting plasters. For additional information, please
contact our Customer Services Department at 01 629 8400.

Plaster/Water
Product Typical Applications Ratio Guide

Fine Casting Plaster An off white plaster suitable for fibrous plaster 100/70
work. i.e. decorative cornices, ceiling roses. General
casting, modelling applications also suitable for
carving.

Superfine Casting Plaster A white plaster suitable for fibrous plasterwork, 100/70
general casting, modelling applications, also
suitable for carving.

Helix Plaster A Hard White Plaster for use where colour, high 100/50
strength and surface durability are required in
Fibrous Plasterwork, GRG, Giftware and Modelling
Applications.

Herculite No 2. Plaster A Hard White Plaster for use where colour, high 100/42
strength and surface durability are required in
Fibrous Plasterwork, GRG, Giftware and Modelling
Applications.

Crystacal R Plaster An extra hard white plaster for use where high 100/35
strength and surface hardness are important
in GRG, Giftware and Modelling Applications.

Herculite Stone Plaster A white, longer, setting high strength plaster 100/33
suitable for Giftware and Modelling
Applications.

Crystacast An exceptionally hard plaster for use in giftware 100/28


and modelling applications where surface hardness
and exceptional details are important.

Crystacal Alpha K A new ultra high strength casting plaster developed 100/21
to replace resin in the production of fine detailed
giftware. Can also be used in other applications
including industrial modelling.

All packed in 25kg bags.

PLASTER TO WATER RATIO

A basic property of plaster is its natural water demand. reduced and the setting time lengthened. Conversely with
This is the amount of water required to combine with a less water, the setting time and thus working time of the
fixed quantity of plaster to obtain a standard ‘pourable’ mix are shorter but the hardness and compressive strength
mix. Both the plaster and water are measured by weight greater. It is important, therefore, to consider the ultimate
and the required amounts expressed as a numerical ratio. use of plaster mix, selecting not only the type of plaster to
Therefore, a plaster to water ratio of 100:70 is equivalent use but also the optimum plaster water ratio. It must be
to a mix of 100 parts of plaster to 70 parts of water. decided whether workability or strength is more
Generally, if a greater amount of water is used per 100 important. The precise consistency to use will depend on
parts of plaster, the mix will be more fluid, the strength the individual application.
1.10

43
book 1_jan10:Layout 1 15/04/2010 17:31 Page 44

www.gyproc.ie
Plastering Specifications

BACKGROUND GRADE OF APPROXIMATE APPLICATIONS


BASECOAT SET-TIME

Concrete Blockwork Gyproc Floating Coat 3/5hrs Ruled to an even surface and
or Gyproc Base Coat properly scratched to form a key for the finish plaster.

Concrete Blockwork Gyproc Airtite 4/5hrs Ruled to an even surface as a parge coat only.

Concrete Blockwork Gyproc Dri-Coat 4/6hrs Replastering of walls following damp-proof course
treatment, delayed as long as possible to allow the
background to dry out.

Concrete Surfaces, suitably Gyproc Bonding 3/4hrs Bonding Coat applied with firm pressure, built out to
treated (see section 1.3) or required thickness ruled to an even surface and
Dense Concrete Blocks properly scratched to form a key for finish coat plaster.

Mortar (Sand/Cement) Matured mortar background, properly scratched


and prepared.

4x2’s Gyproc Bonding 3/4hrs Caulk joints with Gyproc Skimcoat, Carlite Finish
Gyproc Round Edge Greyboard or Gyproc Board Finish. Allow to set before
skimming commences.

4x2’s Bedding in of Gyproc Paper Joint Tape into Gyproc


Gyproc Round Edge Greyboard Joint Filler or Gyproc Pro Fill Filler. Bonding Coat
(applied when plaster used for treating joints and
angles has set) ruled to an even surface and properly
scratched to form a key for finish coat plaster.

Grey face of all square or Gyproc Bonding 3/4hrs Bedding in of Gyproc Paper Joint Tape into Gyproc
tapered edge Gyproc Joint Filler or Gyproc Pro Fill Filler.
Plasterboards

Front face (the side without the


paper overlap) of all Gyproc
Plasterboards* and Gyproc
Thermal laminates, and the
smooth face of MultiBoard and
FireCase s

Mortar (Sand/Cement/Lime) Matured mortar background, properly scratched


and prepared.

*Gypsum plaster should not be specified as a finish to Moisture Resistant Boards as the board is designed to be suitable for environ-
1.11 Boards, taping and filling is the recommended approach. However, if a plaster finish is required, the board should first be treated with

**Carlite Finish or Gyproc Skimcoat plaster must not be applied directly to Gyproc Airtite. Either a Gyproc DriLyner,
Gyproc Skimcoat plaster can be applied.

44
book 1_jan10:Layout 1 15/04/2010 17:31 Page 45

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Plastering Specifications
COVERAGE PER GRADE OF FINISH APPROXIMATE SET THICKNESS OF
TONNE/THICKNESS OF TIME FINISH/COVERAGE PER TONNE
BASECOAT

117m2 at 10mm thickness Carlite Finish or 2/3 hrs 375m2 at 2mm thickness
key for the finish plaster. 102m2 at 10mm thickness Gyproc Skimcoat

parge coat only. 180m2 at 6mm thickness Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness
NOT applied directly**

g damp-proof course 125m2 at 11mm thickness Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness
possible to allow the

m pressure, built out to 121m2 at 10mm thickness Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness
even surface and
ey for finish coat plaster.

properly scratched Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness

coat, Carlite Finish 120m2 at 10mm thickness Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness
to set before

oint Tape into Gyproc Carlite Finish, Gyproc Skimcoat or 2/3hrs 300m2 at 2mm thickness
ller. Bonding Coat Gyproc Board Finish
r treating joints and
en surface and properly
nish coat plaster.

oint Tape into Gyproc 120m2 at 10mm thickness Carlite Finish or Gyproc Skimcoat 2/3hrs 375m2 at 2mm thickness
ller.

Carlite Finish, Gyproc Skimcoat or 2/3hrs 450m2 at 2mm thickness


Gyproc Board Finish

properly scratched Carlite Finish or Gyproc Skimcoat 2/3 hrs 375m2 at 2mm thickness

ments of higher than normal humidity, which no Gypsum plaster is designed to be suitable for. On exposed, untiled, Moisture Resistant
ThistleBond-it in accordance with section 1.6 . 6mm Gyproc Multiboards should also first be treated with ThistleBond-it. 1.11
Gyproc GypLyner or Gyproc GypLyner IWL system may be used in conjunction with Gyproc Airtite where either Carlite Finish or

45
book 1_jan10:Layout 1 15/04/2010 17:31 Page 46

www.gyproc.ie
Plastering Defects and Remedies

Maintenance and Remedial Work defective DPC, cracking as a result of background movement,
Many plasterwork problems result from factors independent and surface dampness due to hygroscopic salts. Whatever the
of the materials used or the techniques employed in defect, it is essential that the primary cause is identified and
plastering operations. Examples include dampness of rectified before the plasterwork is replaced. The main types
plasterwork due to rain penetration or a of defect together with recommended remedial treatments
are listed below.

Plastering Defects Remedies

Bond failure between plasterwork and background When movement has ceased or the residual moisture has
This is often the result of background movement or deflection. However, been removed, the affected plasterwork including any
it can also be due to a weak bond caused by poor keying of the suspect areas should be removed. The background should
background, inadequate control of suction, use of the wrong grade of be prepared and a coat of ThistleBond-it applied prior to
plaster or the presence of residual moisture in the structure. the application of a suitable grade of plaster
(refer to section 1.6 ).

Bond failure between finish plaster and sand/cement undercoat The affected plasterwork should be stripped off.
This takes the form of flaking, blistering, curling or shelling of the Re-plastering can take place once the background is
plaster finish. It normally results from applying plaster over a ‘green’ thoroughly dry after first applying ThistleBond-it in
undercoat (i.e. insufficient time allowed for the sand/cement undercoat accordance with section 1.6 .
to complete its drying shrinkage) and/or inadequate scratching of the
undercoat surface to provide a mechanical key. It can also be caused by
local exposure to excessive heat.

Cracking Localised cracks due to movement can be ‘cut out’


This is usually due to movement in the background/surrounding and filled once movement has ceased.
structure or to drying shrinkage in sand/cement undercoats. When the Otherwise, the recommendations given for bond failures
cracking is due to movement, it takes the form of localised cracks taking should be followed.
a definite line. On walls, they commonly appear around lintels and
window sills due to settlement and/or thermal movement. When
cracking results from drying shrinkage, it takes the form of hair-line
cracks on the surface of the finish plaster.

Crazing/dry-out of finish plaster The plasterwork should be stripped off and any dust
In hot weather conditions, or in situations where the finish plaster has removed from the undercoat surface prior to re-plastering.
been applied exceptionally thin, rapid drying out of the plaster can occur Apply ThistleBond-it (see section 1.6 )
before it has properly set. This can result in a soft and powdery surface.
The problems can also be caused by excessive suction, working the
plaster past its setting point or excessive draught during setting.

Dampness within the plaster The source of the problem must be identified and corrected
This can result from rain penetration, moisture ingress, defective and the plasterwork allowed to dry out. If the plasterwork
defective DPC or poor drying conditions preventing the plaster from fails to develop adequate strength, it will need to be
drying out. removed, followed by suitable background preparation
and re-plastering.

Surface dampness Condensation: The cause of the dampness must be


This is usually due to condensation which can form on new plasterwork eliminated and the plasterwork and the background
due to problems caused by inadequate heating and ventilation. allowed to dry out completely. If due to poor heating and
ventilation, these will need to be addressed accordingly.

Hygroscopic salts: If dampness is persistent, consideration


should be given to an effective treatment followed by
isolating the background from the room surface by
installing an independent plasterboard lining such as
Gyproc GypLyner or Gyplyner IWL.

1.12

46
book 1_jan10:Layout 1 15/04/2010 17:31 Page 47

T 00353 1 629 8400 F 00353 1 623 7054 E enquiries@gyproc.ie

Critical Lighting
I.S. EN 13914-2:2005

I.S. EN 13914-2:2005 states the following, ‘Whatever the


plastering system and finish and however skilled and
conscientious the operative, plastering is a craft and it
should be appreciated that it is not possible to achieve a
completely smooth and true surface finish. Painting will
tend to reveal any inherent surface irregularities. These
minor imperfections will be highlighted when gloss or
semi-gloss paints are used, particularly where the
plasterwork is subjected to intense or shallow angle
lighting. Therefore these types of paints and lighting
require special additional measures to be taken. Otherwise,
the consequential minor irregularities will have to be
accepted. See also Annex A.’

Annex A states the following:


‘As the general level of lighting can have a critical effect on
the appearance of a finished plaster surface, a higher level
of lighting is often needed for such work. The temporary
lighting conditions on site for the plasterer shall simulate
the same or higher lighting conditions produced by the
final permanent installation.’

‘When inspecting plasterwork for acceptance, surfaces shall be


viewed from positions normally used in the adjacent area.’

1.13

47

You might also like