Project : Outfitting Works for CT3 in Cleantech Park

Schedule of "VMC" Spring Jackup Floating Slab for AHU Room @ Level 3

S/N Item Size, mm Area Unit Weight Weight No of Total Weight Jackup Ope. Ope. Jackup Isolator Rated Rated
Set Isolator Load Defl. Model Load Defl.
Qty
L x B x H m2 kg kg kg mm kg mm

1 AHU-1
1.1 AHU 1,759 kg 1,759
1.2 AHU Plinth 4506 x 2148 x 200 9.7 2,400 kg/m3 4,646
1.3 Concrete Slab 4781 x 2423 x 200 11.6 2,400 kg/m3 5,560
Subtotal 11,965 1 13,162 14 940 47 ASFF-6-553 1000 50

2 AHU-2
2.1 AHU 1,438 kg 1,438
2.2 AHU Plinth 4506 x 2453 x 200 11.1 2,400 kg/m3 5,306
2.3 Concrete Slab 4781 x 2728 x 200 13.0 2,400 kg/m3 6,260
Subtotal 13,004 1 14,304 16 894 45 ASFF-6-553 1000 50

3 AHU-3
3.1 AHU 1,753 kg 1,753
3.2 AHU Plinth 2453 x 4506 x 200 11.1 2,400 kg/m3 5,306
3.3 Concrete Slab 2728 x 4781 x 200 13.0 2,400 kg/m3 6,260
Subtotal 13,319 1 14,651 16 916 46 ASFF-6-553 1000 50

4 AHU-4
4.1 AHU 2,706 kg 2,706
4.2 AHU Plinth 3591 x 4435 x 200 15.9 2,400 kg/m3 7,645
4.3 Concrete Slab 3866 x 4710 x 200 18.2 2,400 kg/m3 8,740
Subtotal 19,091 1 21,000 22 955 48 ASFF-6-553 1000 50

5 AHU-5
5.1 AHU 1,680 kg 1,680
5.2 AHU Plinth 2758 x 3591 x 200 9.9 2,400 kg/m3 4,754
5.3 Concrete Slab 3033 x 3866 x 200 11.7 2,400 kg/m3 5,628
Subtotal 12,062 1 13,268 14 948 47 ASFF-6-553 1000 50

Page 1 CT3 - Floating Floor Loading Calculation - R0 - 020320


Project : Outfitting Works for CT3 in Cleantech Park

Schedule of "VMC" Spring Jackup Floating Slab for AHU Room @ Level 3

S/N Item Size, mm Area Unit Weight Weight No of Total Weight Jackup Ope. Ope. Jackup Isolator Rated Rated
Set Isolator Load Defl. Model Load Defl.
Qty
L x B x H m2 kg kg kg mm kg mm
6 AHU-6
6.1 AHU 2,156 kg 2,156
6.2 AHU Plinth 3368 x 3591 x 200 12.1 2,400 kg/m3 5,805
6.3 Concrete Slab 3643 x 3866 x 200 14.1 2,400 kg/m3 6,760
Subtotal 14,722 1 16,194 18 900 45 ASFF-6-553 1000 50

7 Heat Recovery Pump


7.1 Heat Recovery Pump 900 kg 900
7.2 Plinth 1500 x 2500 x 200 3.8 2,400 kg/m3 1,800
7.3 Concrete Slab 1775 x 2775 x 200 4.9 2,400 kg/m3 2,364
Subtotal 5,064 1 5,571 6 928 46 ASFF-6-553 1000 50

8 Heat Recovery Pump (Standby)


8.1 Heat Recovery Pump 900 kg 900
8.2 Plinth 2500 x 1500 x 200 3.8 2,400 kg/m3 1,800
8.3 Concrete Slab 2775 x 1775 x 200 4.9 2,400 kg/m3 2,364
Subtotal 5,064 1 5,571 6 928 46 ASFF-6-553 1000 50

9 General Area of Floating Slab (43m2)


Total slab Area (182m2)
Equipment Area (92m2)
9.1 Concrete Slab 200 90.0 2,400 kg/m3 43,200
9.2 Live Load 90.0 150 kg/m2 13,500
Subtotal 56,700 1 62,370 63 990 50 ASFF-6-553 1000 50

NETT TOTAL LOAD 166,091 175

Note:
1) Perimeter of Floating Slab approx. 63m.

Page 2 CT3 - Floating Floor Loading Calculation - R0 - 020320


Project : Outfitting Works for CT3 in Cleantech Park

Schedule of "VMC" Spring Jackup Floating Slab for Mech (Air Velocity) Room @ Level 3

S/N Item Size, mm Area Unit Weight Weight No of Total Weight Jackup Ope. Ope. Jackup Isolator Rated Rated
Set Isolator Load Defl. Model Load Defl.
Qty
L x B x H m2 kg kg kg mm kg mm

1 Air Velocity Room


1.1 Equipment 1,500 kg 1,500
1.2 Concrete Slab 200 25.0 2,400 kg/m3 12,000
1.3 Live Load 25.0 150 kg/m2 3,750
Subtotal 17,250 1 18,975 22 863 43 ASFF-6-553 1000 50

NETT TOTAL LOAD 18,975 22

Note:
1) Perimeter of Floating Slab approx. 21m.

Page 3 CT3 - Floating Floor Loading Calculation - R0 - 020320


Project : Outfitting Works for CT3 in Cleantech Park

Schedule of "VMC" Spring Jackup Floating Slab for Mech (Liquid Flow) Room @ Level 3

S/N Item Size, mm Area Unit Weight Weight No of Total Weight Jackup Ope. Ope. Jackup Isolator Rated Rated
Set Isolator Load Defl. Model Load Defl.
Qty
L x B x H m2 kg kg kg mm kg mm

1 Liquid Flow Room


1.1 Equipment 2,000 kg 2,000
1.2 Concrete Slab 200 101.0 2,400 kg/m3 48,480
1.3 Live Load 101.0 150 kg/m2 15,150
Subtotal 65,630 1 72,193 90 802 40 ASFF-6-553 1000 50

NETT TOTAL LOAD 72,193 90

Note:
1) Perimeter of Floating Slab approx. 61m.

Page 4 CT3 - Floating Floor Loading Calculation - R0 - 020320