Professional Documents
Culture Documents
PAGE OF
PTD-DGS-122 1 11
PREPARED BY DATE
PROCESS TECHNOLOGY PROCEDURES Edited from existing April 30, 2000
doc by H Andrawis
APPROVED BY
DEPARTMENT: PROCESS ENGINEERING JRB
SUBJECT: REBOILER CALCULATIONS DESIGN GUIDE REVISION DATE REV.
1/11/2006 21
TABLE OF CONTENTS
Section
1.0 SCOPE.............................................................................................................
2.0 RESPONSIBILITIES........................................................................................
4.0 CALCULATIONS.............................................................................................
LIST OF ILLUSTRATIONS
Figure
PTD-DGS-122 21 1/11/2006 2 12
REBOILER CALCULATIONS DESIGN GUIDE
1.0 SCOPE
This design guide1 covers the calculation of vessel skirt heights, pressure drops, line
sizes, and calculation of driving head to determine required drawoff nozzle elevations for
reboiler circuits.
2.0 RESPONSIBILITIES
The process engineer is responsible for determining vessel skirt heights, pressure drops,
line sizes, and driving heads for reboiler circuits.
Lines carrying liquid to the reboiler shall be sized using a maximum liquid velocity of 4 to
5 feet per second. For lines drawing liquid from the side of a column, a velocity of 2 feet
per second shall be used for a minimum length of 5 feet.
For a reboiler vapor outlet, ρ V2 should generally not exceed 500. The mixed-phase
reboiler return line shall be sized using a minimum vapor velocity of 15 feet per second,
even if this produces unstable flow in the vertical up. In cases where the density is low,
higher velocities will occur, but these should not exceed 100 feet per second.
The horizontal portion of the mixed-phase line may be larger (vapor velocity may be
lower) than the vertical up portion of the line, if necessary to maintain stable flow in both
the horizontal and vertical run of lines.
4.0 CALCULATIONS
1
Rev. 0 of the Design Guide was adapted with minimal changes from a Pasadena document, DSG-MP8, 1/93
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 3 12
REBOILER CALCULATIONS DESIGN GUIDE
Horizontal reboilers, with natural circulation, have a simple circulation system. Liquid
flows from a tower side-drawoff nozzle, tower bottom, or an elevated drum through a
downcomer pipe to the bottom of the reboiler shell. The liquid is heated, partially
vaporized, and leaves the reboiler in the return piping as vapor-liquid mixture, then
flowing back to the tower or drum. The circulation is forced by the static head difference
between the two fluid columns.
where:
H1 = height of downcomer, in ft
H2 = height of riser, in ft
P1 = downcomer static pressure at reboiler center line, in pounds per square inch
atmosphere (psia)
P2 = riser static pressure at reboiler center line, in psia
∆ P = pressure drop, in pounds per square inch (psi)
ρ 1 = hot liquid density, in lb/cu ft
ρ 2 = liquid/vapor density, in lb/cu ft
This ∆ P is the driving force necessary for natural circulation. This is also the pressure
available to overcome exchanger and piping friction losses.
PTD-DGS-122 21 1/11/2006 4 12
REBOILER CALCULATIONS DESIGN GUIDE
∆ Pdowncomer and ∆ Priser should be calculated using the Parsons Line Sizing and
Optimization program and the design criteria in section 3.0. These ∆ Ps should include
pipe inlet and outlet losses and acceleration losses.
The riser pipe diameter is generally one or two sizes larger than the downcomer pipe
diameter.
The minimum downcomer nozzle elevation above the horizontal reboiler centerline (H 1)
may be found from the available DP Equation 4-3.
The minimum (H1 - H2) is usually 3 feet. Insert H 2 = H1 - 3 into the available ∆ P
equation and solve for H1:
144∆P − 3 ρ 2
H1 = (Eq. 4-6)
ρ1 − ρ 2
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 5 12
REBOILER CALCULATIONS DESIGN GUIDE
where:
The value of H1 is useful when elevation adjustments are made to vessel heights during
plant layout or when the vessel can be located at a minimum elevation.
Many towers have a bottom drawoff pump. Pump net positive suction head (NPSH)
requirements generally elevate the process vessel and the reboiler drawoff nozzle higher
than that of the reboiler's minimum. This increases the static head in the vertical legs and
also the driving force in the circuit. With the increased tower height, it is worthwhile to
check the reboiler circuit for a possible reduction of liquid and return line sizes, especially
where large diameter lines are required.
At horizontal reboilers, whether the drawoff nozzle is elevated or located in the bottom of
the tower, the hydraulic conditions are the same. To find the available energy, the ∆ P
Equation 4-3 can be used.
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 6 12
REBOILER CALCULATIONS DESIGN GUIDE
For the minimum downcomer length (H 1), the return line nozzle elevation (H 3) must be
known. Insert H2 = H1 + H3 into DP Equation 4-3 and solve for H 1, as shown in Equation
4-7:
144∆P + ρ 2H3
H1 = (Eq. 4-7)
ρ1 − ρ 2
There are two general types of kettle reboilers: the pressured flow and the gravity flow.
In this type of kettle reboiler, the liquid level in the reboiler is generally controlled by a
level controller. Excess liquid flows from the reboiler to a lower pressure destination
through a level control valve. These reboilers are generally mounted at grade, and the
hydraulics involved is the same as for any pressured flow from a vessel.
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 7 12
REBOILER CALCULATIONS DESIGN GUIDE
In this type of kettle reboiler, the liquid flows by gravity from a tower side drawoff nozzle
into the reboiler. In the reboiler, the liquid overflows a weir, which maintains the liquid
level. The overflow is returned to the bottom of the tower by gravity.
As in thermosyphon reboilers, the static head between the tower drawoff nozzle and the
top of the reboiler weir must be large enough to overcome the reboiler and piping
pressure drops.
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 8 12
REBOILER CALCULATIONS DESIGN GUIDE
(Ho-Hw) specific gravity x 0.4331 psi > ∆ Preboiler + ∆ Pdowncomer + ∆ Priser (Eq. 4-
8)
where:
∆ Pdowncomer and ∆ Priser should be calculated using the Parsons Line Sizing and
Optimization program and the design criteria in Section 3.0. These ∆ Ps should include
pipe inlet and outlet losses.
A kettle-type reboiler produces high evaporation rates and a large diameter return line
might be necessary. The process flow diagram, of course, should indicate flowrates and
the physical properties of the flowing fluid.
The static head between the top of the weir in the reboiler and the tower high liquid level
must be great enough to overcome the liquid return line pressure drops, including the pipe
inlet and outlet losses.
(Hw - HHLL) x specific gravity x 0.433 psi > ∆ P liquid return line (Eq. 4-9)
where:
Liquid flows from a tower side drawoff nozzle, tower bottom, or an elevated drum through
a downcomer to the bottom of the vertical reboiler shell. The liquid is heated and leaves
the reboiler in the return piping as vapor or vapor-liquid mixture. It then flows back to the
tower or drum. A simplified, conservative, and convenient assumption is made that
density varies along the vertical reboiler length in a straight-line proportion.
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 9 12
REBOILER CALCULATIONS DESIGN GUIDE
Assuming that the fluid density in the reboiler will be an average of the liquid downcomer
and return line densities we have
ρ1 + ρ2
ρ3 = (Eq. 4-10)
2
where:
H'1 = relative elevation between the tower bottom tangent and bottom of the reboiler
H2 = height of riser, in ft
H3 = elevation between the tower bottom tangent and vapor return nozzles, in ft
H4 = height of the vertical reboiler, in ft
ρ 1 = density of the liquid, in lb/cu ft
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 10 12
REBOILER CALCULATIONS DESIGN GUIDE
This ∆ P is the driving force for vertical reboilers. Friction losses should be smaller than
this.
The relative position between the tower bottom tangent and the bottom of the reboiler
must be a minimum of H'1 feet. Expressing H'1 from the above equation and inserting
H2 = H '1 + H3 − H4 or H '1 + H3 = H2 + H4
144∆P + ρ 2 ( H3 − H 4 ) + ρ3H4
H '1 = (Eq. 4-12)
( ρ1 − ρ2 )
Assuming that the tower bottom tangent line and the top tubesheet are on the same
elevation, the above Equations 4-11 and 4-12 can be simplified, because H' 1 = H4 and
H3 = H2. Consequently:
and
144∆P + ρ 2H3
H '1 =
( ρ1 − ρ3 ) , no safety factor has been included (Eq. 4-14)
The H2 dimension can be greater than H 3. The minimum liquid level static head above
the bottom tangent line can also be taken into account as an additional driving force.
PROCEDURE NO. REV. DATE PAGE OF
PTD-DGS-122 21 1/11/2006 11 12
REBOILER CALCULATIONS DESIGN GUIDE
For a vertical reboiler with a high drawoff nozzle, the driving force is:
where:
H"1 = relative elevation between the tower drawoff nozzle and the bottom of the
reboiler, in ft
This ∆ P is the driving force for vertical reboilers. Friction losses should be smaller than
this.
The minimum height between the liquid drawoff nozzle and the vapor return nozzle is 3
feet. Therefore, the minimum drawoff nozzle elevation will be as shown in Equation 4-16:
Once more the total system loss ( ∆ P), known densities, and exchanger length (H 4) will
give the distance between the drawoff nozzle and the reboiler bottom tubesheet (H" 1).
PTD-DGS-122 21 1/11/2006 12 12
REBOILER CALCULATIONS DESIGN GUIDE
The process engineer is responsible for selecting the type of Reboiler required for the
service. The process specification shall include the type, either by indication the type on
the data sheet or better include a sketch, examples figure 1 through 6 , depicting the type
of boiler specified.