Coldroom

Cold room type

industrial room
Insulation thickness: 100 mm
Floor insulation: yes
Length (inner): 10.00 m
Width (inner): 11.00 m
Height (inner): 5.00 m
Inner volume: 550.00 m³

Application
Room temperature: 10.0 ºC
pre-cold room

Product type
Storage temperature: -1.0 ºC
beef on rails
Storage humidity: 90 % Freezing point: -2.0 ºC
Water content: 69 % Specific heat capacity: 3.2 kJ/kg·K
Respiration heat: 0.0 kJ/kg Specific heat below freezing point: 1.7 kJ/kg·K

Product loading
Load rate: 250 kg/m³ Total load: 137500 kg
Daily turnover rate: 12 %/24h Daily turnover: 16000 kg/24h
Inlet temperature: 35.0 ºC

Product cooling
Product shape: Weight per piece: 200.00 kg
cylinder
Product length: 100 mm Product thickness: 10 mm
Mass density: 876 kg/m³ Thermal conductivity: 0.4 W/m·K
Air speed: 1.0 m/s Final inner temperature: 0.0 ºC
Cooling time: 0.25 h Air temperature: -6.3 ºC

Location
Altitude: 9m
within a building
Ambient temperature: 34.0 ºC Ambient relative humidity: 50 %

Thermal insulation
Walls: area: 216.2 m² thickness: 100 mm
Injected polyurethane
Roof: Injected polyurethane area: 112.1 m² thickness: 100 mm
Floor: Injected polyurethane area: 112.1 m² thickness: 100 mm

Door: Injected polyurethane area: 8.0 m² thickness: 75 mm

Ventilation through
Door openings per day: 8.5 /24h Air volume renewal rate: 8.5 /24h
doors

Defrost
Defrost type:
electrical

Fans
Airflow rate: 11000 m³/h Input power: 1.330 kW

https://intarcon.calcooling.com/#coldroom 1/2
11/24/21, 9:11 AM Cooling calculator

Cooling needs
Calculation time period: 24.0 h
Products
Refrigeration of goods: 1769600 kJ
H. Transfer
Heat transfer: 206049 kJ
Air renewal
Air renewal: 287014 kJ
Loads
Thermal loads: 233077 kJ
TOTAL: 2495740 kJ
Working hours: 18.0 h

Necessary cooling
Necessary capacity for 11206 W Total cooling capacity: 38514 W
capacity preservation of goods: