You are on page 1of 56

Procurement of Plant

Design, Supply, and Installation


Single-Stage: Two-Envelope
Tender Procedure

TENDER DOCUMENT
for
Procurement
of

Design, Supply, Installation, Testing & Commissioning of 400kV


& 230kV underground XLPE cable Transmission lines on
Chattogram Area.(Package-2)

Issued on: June 10, 2021

Invitation for Tenders No.: 27.21.0000.101.07.311.21.2532


Contract Ref. No.: PGCB/AIIB/0088A-BGD/TL/P-2
Employer: Power Grid Company of Bangladesh Limited (PGCB)
Country: Bangladesh

Volume 3 of 3
Preface
This Tender Document for Procurement of Plant - Design, Supply, and Installation,
has been prepared by Power Grid Company of Bangladesh Ltd (PGCB) and is based on the
MDB Harmonized Standard Tender Document for Procurement of Plant - Design, Supply, and
Installation (STD Plant) issued by the Asian Infrastructure Investment Bank dated May 2019.

AIIB’s STD Plant has the structure and the provisions of the Master Procurement
Document entitled “Procurement of Plant - Design, Supply, and Installation”, prepared
by multilateral development banks and other public international financial institutions
except where AIIB-specific considerations have required a change.
Contents of the Tender Documents

Volume 1

Section I. Instructions to Bidders (ITB)


Section II. Bid Data Sheet (BDS)
Section III. Evaluation and Qualification Criteria
Section IV. Bidding Forms
Section V. Eligible Countries
Section VI. Employer's Requirements
Section VII. General Conditions of Contract (GCC)
Section VIII. Special Conditions of Contract (PCC)
Section IX. Contract Forms

Volume 2

Scope of Works
Technical Specifications
Drawings forming Part of the Specification

Volume 3

Schedule A: Introduction & Preamble to the Price & Technical Schedules


Schedule B: Bid Prices & Schedules
Schedule C: Bar Chart Program of Key Activities-Delivery & Completion Time
Schedule
Schedule D: Manufacturers, Places of Manufacture and Testing
Schedule E: Technical Particulars and Guarantees
Schedule F: Proposed Subcontractors
Volume 3 Page 1

1. Schedule A: Introduction and Preamble to


the Price and Technical Schedules

Please refer to Section-1: Scope of Work under Volume 2 of 3 of the


Tender document.
Volume 3 Page 2

2. ESMP Requirement for Technical Proposal


A. Technical Proposal

1. Environmental and Social Management Plan (ESMP)


The Tenderer shall submit and Tender costs for a comprehensive and concise Environmental and Social
Management Plan (ESMP) as attached. The ESMP prepared as part of the ESIA/ESMPF is attached in
below Section B. The Contractor shall follow the attached ESMP to prepare an Environmental and Social
Management Plan (ESMP) and provide a budget for executing the ESMP.

(Insert the Code of Conduct, GRM, and GBV in the GC where the Contractor’s ESMS is provided)

2. Code of Conduct for Contractor’s Workers


Contractor’s Worker shall:
1) carry out his/her duties competently and diligently;
2) comply with this Code of Conduct and all applicable laws, regulations and other requirements,
including requirements to protect the health, safety and well-being of other Contractor’s Workers
and any other person;
3) maintain a safe working environment including by:
a. ensuring that workplaces, machinery, equipment and processes under each person’s
control are safe and without risk to health;
b. wearing required personal protective equipment;
c. using appropriate measures relating to chemical, physical and biological substances and
agents; and
d. following applicable emergency operating procedures.
4) report work situations that he/she believes are not safe or healthy and remove himself/herself from
a work situation which he/she reasonably believes presents an imminent and serious danger to
his/her life or health;
5) treat other people with respect, and not discriminate against specific groups such as women,
people with disabilities, migrant workers or children;
6) not engage in Sexual Harassment, which means unwelcome sexual advances, requests for sexual
favors, and other verbal or physical conduct of a sexual nature with other Contractor’s or
Employer’s Personnel;
7) not engage in Sexual Exploitation, which means any actual or attempted abuse of position of
vulnerability, differential power or trust, for sexual purposes, including, but not limited to, profiting
monetarily, socially or politically from the sexual exploitation of another;
8) not engage in Sexual Abuse, which means the actual or threatened physical intrusion of a sexual
nature, whether by force or under unequal or coercive conditions;
9) not engage in any form of sexual activity with individuals under the age of 18, except in case of
pre-existing marriage;
10) complete relevant training courses that will be provided related to the environmental and social
aspects of the Contract, including on health and safety matters, Sexual Exploitation and Abuse
(SEA), and Sexual Harassment (SH);
11) report violations of this Code of Conduct; and
12) not retaliate against any person who reports violations of this Code of Conduct, whether to AIIB or
the Employer, or who makes use of the grievance mechanism for Contractor’s Workers or the
project’s Grievance Redress Mechanism.

3. Gender Based Violence


The Contractor shall be intolerant of, and enforce disciplinary measures for gender-based violence,
inhumane treatment, sexual exploitation, rape, sexual abuse, sexual activity with children, and sexual
harassment. Any such case reported in the project area or involving people associated with the project
should be reported to the GRM
Volume 3 Page 3

4. Grievance Redress Mechanism

The Contractor shall have the respective grievance mechanisms for Contractor’s Workers and Project
Affected People to raise workplace concerns and construction related nuisance. The mechanism shall
address concerns promptly, using an understandable and transparent process that provides timely
feedback to those concerned in a language they understand, without any retribution, and shall operate in
an independent and objective manner.

The Contractor’s Workers shall be informed of the grievance mechanisms and its functions at the earliest
convenience. Measures will be put in place to make the grievance mechanisms easily accessible to all
Contractor’s Workers.

The grievance mechanisms shall not impede access to other judicial or administrative remedies that might
be available, or substitute for grievance mechanisms provided through collective agreements.

B. Works Requirements

Minimum Content of ES Requirements


In preparing detailed specifications for E&S requirements, the Contractor should refer to and consider:
i. project reports e.g. Environmental and Social Impact Assessment (ESIA)/ESMP
ii. consent/permit conditions
iii. required standards including national legal and/or regulatory requirements and international and
sectoral recognized standards (e.g., UN agencies, WHO, IFC/WB EHS Guidelines), whichever
stringent
iv. Grievance Redress Mechanism including types of grievances to be recorded and how to protect
confidentiality e.g. of those reporting allegations of SEA
v. SEA prevention and management

The detail specification for E&S should, to the extent possible, describe the intended outcome rather than
the method of working.

The E&S requirements should be prepared in manner that does not conflict with the relevant General
Conditions of Contract (and the corresponding Particular Conditions if any) and other parts of the
specifications.
Volume 3 Page 4

Schedule B: Bid Prices & Schedules

1. General
1. The Price Schedules are divided as follows:

Schedule No. 1: Plant and Mandatory Spare Parts Supplied from Abroad
Schedule No. 2: Plant and Mandatory Spare Parts Supplied from within the Employer's Coun-
try
Schedule No. 3: Design Services
Schedule No. 4: Installation and Other Services
Schedule No. 5: Grand Summary
Schedule No. 6: Recommended Spare Parts

2. The Schedules do not generally give a full description of the plant to be supplied and the ser-
vices to be performed under each item. Bidders shall be deemed to have read the Employer's
Requirements and other sections of the Bidding Document and reviewed the Drawings to ascer-
tain the full scope of the requirements included in each item prior to filling in the rates and pric-
es. The entered rates and prices shall be deemed to cover the full scope as previously men-
tioned, including overheads and profit.

3. If Bidders are unclear or uncertain as to the scope of any item, they shall seek clarification in
accordance with ITB 7 prior to submitting their bid.

2. Pricing
4. The units and rates in figures entered into the price schedules should be type written or if written
by hand, must be in print form. Price schedules not presented accordingly may be considered
nonresponsive. Any alterations necessary due to errors, etc., shall be initialed by the Bidder.

As specified in the bid data sheet and special conditions of contract, prices shall be fixed and
firm for the duration of the contract, or prices shall be subject to adjustment in accordance with
the corresponding appendix (price adjustment) to the contract agreement.

5. Bid prices shall be quoted in the manner indicated and in the currencies specified in the Instruc-
tions to Bidders in the bidding document.

For each item, Bidders shall complete each appropriate column in the respective schedules,
giving the price breakdown as indicated in the schedules.

Prices given in the schedules against each item shall be for the scope covered by that item as
detailed in Volume II (Employer's Requirements) or elsewhere in the bidding document.

6. Payments will be made to the Contractor in the currency or currencies indicated under each re-
spective item.
Volume 3 Page 5

7. When requested by the Employer for the purposes of making payments or part payments, valu-
ing variations or evaluating claims, or for such other purposes as the Employer may reasonably
require, the Contractor shall provide the Employer with a breakdown of any composite or lump
sum items included in the schedules.

3. Schedules of Rates and Prices


Schedule No. 1: Plant and Mandatory Spare Parts Supply from Abroad

Schedule No. 2: Plant and Mandatory Spare Parts Supplied from Within the
Employer's Country

Schedule No. 3: Design Services

Schedule No. 4: Installation and Other Services

Schedule No. 5: Grand Summary

Schedule No. 6: Recommended Spare Parts

Please see the separate EXCEL file for the above.

The Bidder shall fill, sign and stamp the attached price schedules and shall attach them to the bid.

(Price schedules are attached at the end of this document.)


Volume 3 Page 6

Schedule C: Bar Chart Program of Key Activi-


ties - Delivery & Completion Time Schedule
The Bidder shall fill, sign and stamp the attached time schedule and shall attach it to the bid.

Time for completion of the whole facilities shall be Seven Hundred Twenty (720) days from the
effective date as de- scribed in Section 8 - Special Conditions of Contract, Sub-Clause 8.2.

The Bidder shall provide

 filled general time schedule, provided below and as Appendix 4 to the Section 9: Contract Forms,
 a detailed proposal for mobilization schedule, Section 4: Bidding Forms, item 5.3. and
 a detailed proposal for the construction schedule, Section 4: Bidding Forms, item 5.4.

Please find the time schedule attached.


Page 13

Time Schedule (Show Activity in Bar Chart for 720 days.)

Work under this contract shall be completed within Seven Hundred Twenty (720) days from contract effective date.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Design Design, Supply, Duration
Installation, Testing &
Commissioning of 400kV &
230kV underground XLPE
cable Transmission lines
on Chattogram
Area.(Package-2)

Line route survey

Geotechnical investigation

Line route finalization and


XLPE Cable design
Manufacturing of Cable and
Accessories
Testing
Civil works/installation
Scope-1
Scope-2
Scope-3

Scope-4
Testing and
commissioning
Scope-1

Scope-2

Scope-3

Scope-4

N.B. Please insert additional rows as required to define all activities to complete the works.

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)
Page 13
Schedule D: Manufacturers, Places of Manufacture and Testing
The following form shall be filled and attached to the bid. Bidders are free to propose more than one Manufacturer for each item.

Manufacturers

Place of Country of Origin


Place of
Item Description Manufacturer Testing and
Manufacture
Inspection
1. XLPE Cable
1.1 400kV
1.2
230kV
2
Outdoor Cable sealing end
2.1
400kV
2,2
230kV
3.
GIS Cable sealing end
4.
Fiber optic cable
5.
Surge arrester

Name of Bidder:

Signature of Bidder:

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)
Page 15

Schedule E: Technical Particulars and Guaran-


tees

1. General
The technical data schedules hereafter provide more details on the specific technical criteria and
complement the Information given in the bidding document.

They form an essential part of bid submission and will be used in bid evaluation.

They should be fully completed and submitted with the bid.

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable
Transmission lines on Chattogram Area.(Package-2)
Page 27

2. Technical Data Schedules


The technical data schedules hereafter provide more details on the specific technical criteria and
complement the Information given in the bidding documents.

They form an essential part of bid submission and will be used in bid evaluation. They should be fully
completed and submitted with the bid. Fill out 1 form for each manufacturer.

2.1 400kV XLPE Cable

SL. Description Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage
Rated voltage 400kV
Maximum system voltage 420kV
3 Cores
Number of cores 1 (one)
4 Conductor
Cross sectional area 2000mm2
Material Copper
Design Milliken type
5 Conductor Screen
Material
Thickness (approx)
6 Insulation XLPE
Thickness  27mm
Extrusion Process VCV/CCV
Type of curing (dry) Dry Curing
7 Insulation screen
Material Extruded semi
conducting
compound
Thickness approx. 1.0 mm
8 Protection Tapes
Material Semi-conducting
water blocking tapes
under metallic
screen/sheath
Nominal thickness
9 Metallic Screen/Sheath
Type
10 Outer Sheath
Material MDPE
Minimum average thickness 5mm
Type of termite repellent
11 Completed Cable
Overall diameter (approx)
Weight per meter (approx)
Maximum drum length(approx) 350m

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable
Transmission lines on Chattogram Area.(Package-2)
Page 28

12 Cable Drums
Overall diameter (approx)
Width (approx)
Weight loaded (approx)
13 Continuous current carrying
capacity based on the conditions
laid in the ground.
One circuit
Two circuit
Four circuit
Drawn into ducts
One circuit
Two circuit
Four circuit
In air
14 Permissible overload in 2 hrs in a day 100 hrs
service conditions for a period of in a month 500 hrs in
total life
15 Max conductor temperature
Laid direct in ground ºC
Drawn into ducts ºC
Laid in air ºC
16 Conductor short circuit current for 280.0kA for 1 sec.
one second cable loaded as above
prior to short circuit
-do- for three second
Final conductor temperature
17 Sheath earth fault current carrying 50.0 kA for 3 sec.
capacity for three second cable
loaded as above prior to earth fault
Final metallic sheath temperature 250ºC
18 Max. dielectric stress all the
conductor screen (assumed
smooth)
19 Minimum radius of bend around
which
cable can be laid
Laid direct 20 x overall diameter
of cable in meters
In ducts
In air
20 Nominal internal diameter of pipes
on ducts through which cable may
be pulled
21 Maximum DC resistance per km of
cable at 20ºC
Of conductor
Of metallic layer
22 Maximum AC resistance per km of
cable at maximum conductor
temperature
23 Insulation resistance per km of
cable per core
At 20ºC mega ohm. km
At maximum rated temperature mega ohm. km
24 Equivalent star reactance per meter
of 1- phase circuit at nominal
frequency
25 Maximum electrostatic capacitance
per meter of cable
26 Maximum charging current per
core per meter of cable at nominal

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable
Transmission lines on Chattogram Area.(Package-2)
Page 29

voltage Uo
27 Maximum dielectric loss of cable per
3 phase circuit when laid direct in
the ground at nominal voltage Uo,
normal sequence at maximum
conductor temperature.
28 Maximum induced voltage on metal
sheath under fault condition
29 Maximum dielectric dissipation
factor of charging of cable when laid
direct in the ground at nominal
voltage Uo, normal frequency at :
Conductor temperature of 20ºC
Maximum conductor temperature of
90deg. C
30 Sheath loss of cable per meter of 3
phase circuit at nominal voltage
Uo, normal frequency
31 Earth continuity copper conductor (If 400 mm2
required)
32 Condition on which current carrying
capacity are based
Soil thermal resistivity ºC. cm/W
Ground temperature ºC
Air temperature ºC
Burial depth m
Axial spacing between phase cables mm
Axial spacing between circuits mm
Type of earth bonding system of
metallic sheath.

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable
Transmission lines on Chattogram Area.(Package-2)
Page 40

2.2 230kV XLPE Cable

SL. Description Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage
Rated voltage 230kV
Maximum system voltage 245kV
3 Cores
Number of cores 1 (one)
4 Conductor
Cross sectional area 2000mm2
Material Copper
Design Milliken type
5 Conductor Screen
Material
Thickness (approx)
6 Insulation XLPE
Thickness  21mm
Extrusion Process VCV/CCV
Type of curing (dry) Dry Curing
7 Insulation screen
Material Extruded semi
conducting
compound
Thickness approx. 1.0 mm
8 Protection Tapes
Material Semi-conducting
water blocking tapes
under metallic
screen/sheath
Nominal thickness
9 Metallic Screen/Sheath
Type
10 Outer Sheath
Material MDPE
Minimum average thickness 5mm
Type of termite repellent
11 Completed Cable
Overall diameter (approx)
Weight per meter (approx)
Maximum drum length(approx) 500m
12 Cable Drums
Overall diameter (approx)
Width (approx)
Weight loaded (approx)
13 Continuous current carrying
capacity based on the conditions
laid in the ground.
One circuit
Two circuit
Four circuit
Drawn into ducts
One circuit
Two circuit
Four circuit

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 41
In air
14 Permissible overload in 2 hrs in a day 100 hrs
service conditions for a period of in a month 500 hrs in
total life
15 Max conductor temperature
Laid direct in ground ºC
Drawn into ducts ºC
Laid in air ºC
16 Conductor short circuit current for 280.0kA for 1 sec.
one second cable loaded as above
prior to short circuit
-do- for three second
Final conductor temperature
17 Sheath earth fault current carrying 40.0 kA for 3 sec.
capacity for three second cable
loaded as above prior to earth fault
Final metallic sheath temperature 250ºC
18 Max. dielectric stress all the
conductor screen (assumed
smooth)
19 Minimum radius of bend around
which
cable can be laid
Laid direct 20 x overall diameter
of cable in meters
In ducts
In air
20 Nominal internal diameter of pipes
on ducts through which cable may
be pulled
21 Maximum DC resistance per km of
cable at 20ºC
Of conductor
Of metallic layer
22 Maximum AC resistance per km of
cable at maximum conductor
temperature
23 Insulation resistance per km of
cable per core
At 20ºC mega ohm. km
At maximum rated temperature mega ohm. km
24 Equivalent star reactance per meter
of 1- phase circuit at nominal
frequency
25 Maximum electrostatic capacitance
per meter of cable
26 Maximum charging current per
core per meter of cable at nominal
voltage Uo
27 Maximum dielectric loss of cable per
3 phase circuit when laid direct in
the ground at nominal voltage Uo,
normal sequence at maximum
conductor temperature.
28 Maximum induced voltage on metal
sheath under fault condition
29 Maximum dielectric dissipation
factor of charging of cable when laid
direct in the ground at nominal
voltage Uo, normal frequency at :
Conductor temperature of 20ºC
Maximum conductor temperature of
90deg. C
30 Sheath loss of cable per meter of 3
phase circuit at nominal voltage
Uo, normal frequency

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 42
31 Earth continuity copper conductor (If 400 mm2
required)
32 Condition on which current carrying
capacity are based
Soil thermal resistivity ºC. cm/W
Ground temperature ºC
Air temperature ºC
Burial depth m
Axial spacing between phase cables mm
Axial spacing between circuits mm
Type of earth bonding system of
metallic sheath.

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 43

2.3 OPTICAL FIBRE CABLE

Manufacturer’s
Description Requirement Particulars
Manufacturer name and address
Optical fibre cable designation & type
Reference standard
No. of fibre 48
Central strength member FRP
Luse tube Material
Diameter Nom. 2.5mm
Filling compound in tube Jelly
Strength element Aramid yarn
Inner sheath Material HDPE
Thickness Nom. 1.0mm
Armouring Material Corrugated steel
tape
Thickness mm
Outer sheath Material HDPE
Thickness mm
Anti-termite layer
Cable diameter mm
Weight of cable kg/km
Mode field diameter at 1310nm 9.0um±0.5um
Mode field concentricity error m
Cladding diameter 125.0±1.0um
Cladding non-circularity Max. 1%
Attenuation at1310nm dB/km
at 1550nm dB/km
Dispersion at range 1285-1300nm ps/nm・km
At1550nm ps/nm・km
Zero dispersion wavelength ≤ 1310 nm
Zero dispersion slope ps/nm・km
Cable cut-off wavelength ≤ 1270 nm

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 44
2.4 CABLE SEALING END

2.4.1 400kV OUTDOOR CABLE SEALING END

Item Description Unit Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage rating kV 400
3 Current rating amp As per cable
4 Type Elastomeric stress
cone with
porcelain/polymeric
insulator.
5 Insulator material Porcelain/Polymeric
bushing
6 Pollution severity levels Heavy
7 Pitch circle diameter mm
8 Overall length of insulator mm
9 Weight of bushing including kg
sealing compound
10 Total creepage distance of outdoor mm
sealing end
11 Total creepage distance of shedding mm
12 Impulse withstand voltage (External)
(a) Positive kV 1425
(b) negative kV 1425
Standards IEC 60840/62067
13 Height of steel mounting structure over mm 2500 (min.)
the finished switchyard level

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 45

2.4.2 230kV OUTDOOR CABLE SEALING END

Item Description Unit Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage rating kV 230
3 Current rating amp As per cable
4 Type Elastomeric stress
cone with
porcelain/polymeric
insulator.
5 Insulator material Porcelain/Polymeric
bushing
6 Pollution severity levels Heavy
7 Pitch circle diameter mm
8 Overall length of insulator mm
9 Weight of bushing including kg
sealing compound
10 Total creepage distance of outdoor mm 6250mm
sealing
end
11 Total creepage distance of shedding mm 450mm (approx)
12 Impulse withstand voltage (External)
(a) Positive kV 1050
(b) negative kV 1050
Standards IEC 60840/62067
13 Height of steel mounting structure over mm 2500 (min.)
the finished switchyard level

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 46
2.4.3 230kV GIS CABLE SEALING END

Item Description Unit Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage rating kV 230
3 Current rating amp As per cable
4 Type .
5 Insulator material Epoxy bushing
6 Pollution severity levels Heavy
7 Pitch circle diameter mm
8 Overall length of insulator mm
9 Weight of bushing including kg
sealing compound
10 Total creepage distance of shedding mm 450mm (approx.)
11 Impulse withstand voltage (External)
12 (a) Positive kV 1050
(b) negative kV 1050
Standards IEC 60840/62067

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

2.5 CABLE JOINT


2.5.1 400 kV Straight Through Joint/Insulated Joint

Item Description Unit Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage rating kV 400
3 Current rating amp As per cable
4 Type Pre-molded
(One piece)
5 Stress relief cone
Material EPDM/EPR/
Silicon Rubber
6 The Interface pressure between cable Min. 0.15MPa
insulation and joint rubber block insulator
7 Conductor connecting method
8 Impulse withstand voltage
(a) Positive kV 1425
(b) negative kV 1425
Standards IEC
60840/62067

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 47

2.5.2 230 kV Straight Through Joint/Insulated Joint

Item Description Unit Requirement Manufacturer’s


Particulars
1 Manufacturer name and address
2 Voltage rating kV 230
3 Current rating amp As per cable
4 Type Pre-molded
(One piece)
5 Stress relief cone
Material EPDM/EPR/
Silicon Rubber
6 The Interface pressure between cable Min. 0.15MPa
insulation and joint rubber block insulator
7 Conductor connecting method
8 DC voltage withstand of the insulation flange kV
9 Impulse withstand voltage
(a) Positive kV 1050
(b) negative kV 1050
Standards IEC
60840/62067

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 48

2.6 230KV SURGE ARRESTER

Minimum Requirements Manufacturer’s


No. Description
Unit Data Particulars

1. Surge Arresters - General


1.1 Manufacturer Insert
1.2 Type insert
1.3 Model designation Insert
1.4 Country of origin Insert
1.5 Standards IEC 60099-4
1.6 Quality control ISO 9001
Metal oxide,
1.7 Design
gapless,outdoor
1.8 Short circuit testing authority Insert authority

2. Surge Arresters - Characteristics


2.1 Nominal system voltage kV rms 230
2.2 Highest voltage for equipment Un kV rms 245
216
2.4 Rated voltage of surge arrester Ur kV rms
196
2.5 Max. continuous operating voltage Uc kV rms
2.8 Rated frequency Hz 50
2.9 Nominal discharge current In (8/20 μs) kA peak 10
2.10 High current impulse of an arrester (4/10 μs) kA peak 100

3. Surge Arresters - Design and Construction


Heavy Duty 3
3.1 Line discharge class Class
3.2 Pressure Relief Class Class insert
3.2 Duty Class Class insert
Energy dissipation capacity (per kV of rated
3.3 kJ/kV ≥ 6.5
voltage)
3.4 Long duration current impulse (2000 μs) A ≥ 850
3.5 Maximum residual voltage Ures
3.5.1 For switching impulse current 30/60 μs at 0,5 kA kV peak ≤ 375
3.5.2 For switching impulse current 30/60 μs at 1 kA kV peak ≤ 385
3.5.3 For switching impulse current 30/60 μs at 2 kA kV peak ≤ 405
3.5.4 For lightning impulse current 8/20 μs at 5 kA kV peak ≤ 435
3.5.5 For lightning impulse current 8/20 μs at 10 kA kV peak ≤ 465
3.5.6 For lightning impulse current 8/20 μs at 20 kA kV peak ≤ 515
3.6 Steep Current residual voltage kV peak Insert
3.7 Dielectric endurance of arrester housing
Lightning impulse withstand voltage of arrester
3.7.1 kV ≥ 925
housing (1.2/50 μs)
Power frequency withstand voltage of arrester
3.7.2 kV ≥ 425
housing (1 min wet)
3.8 Temporary Overvoltage (TOV) kV rms Insert
3.9 Mechanical requirements
3.9.1 Specified short-term load SSL (Fdyn) N ≥ 2250
3.9.2 Specified long-term load SSL (Fstat) N ≥ 1550
3.9.3 Maximum Cantilever Strength Nm Insert
Maximum force due to wind (at maximum
3.9.4 Nm Insert
specified gust speed)
3.10 Minimum creepage distance mm/kV ≥ 25 mm/kV
3.11 Overall creepage distance mm Insert
3.12 Housing insulating material Composite/Silicon
3.13 Insulating basement Yes Insert
3.14 Nominal Diameter of Resistor Blocks Nos Insert
Number of resistor blocks connected electrically
3.15 Nos Insert
parallel
3.16 Number of separately housed units per phase Nos Insert

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
Page 49
Minimum Requirements Manufacturer’s
No. Description
Unit Data Particulars
Overall height of arrester (without supporting
3.17 mm Insert
structure)
Overall height of arrester including grading ring
3.18 Mm Insert
if applicable
Clearances:
3.19 Phase to earth (from central line) mm Insert
Phase to phase (center line to center line) mm Insert
Overall weight of arrester (without supporting
3.20 Kg Insert
structure)
yes / no /
3.21 Voltage distribution ring present / ring diameter Insert
mm
3.22 Type and description of surge monitoring Insert
3.23 Surge Counter Yes Insert
3.24 Leakage current detector Yes Insert
3.25 HV terminal
3.25.1 Shape Flat
3.25.2 Dimension mm x mm Min 100 x 100
3.25.3 Number of holes Min 4
3.25.4 Distance between holes mm x mm 50 x 50
3.25.5 Material suitable for Al terminal
3.26 Type test certificate ref/date Insert
Number of the same type of surge arresters
3.27 Insert
supplied to date
Overall compliance with the requirements &
3.28 Insert
detail specification described in Vol-2

Name & Signature of


Manufacturer`s Representative:

Stamp of Manufacturer

Design, Supply, Installation, Testing & Commissioning of Anowara-Ananda bazar(New Mooring) 400kV
Transmission Lines on turnkey basis (Package-1)
SCHEDULE F

PROPOSED SUBCONTRACTORS

The bidder shall propose a list of the Sub-contractors in the following table as per sub-clause 2.5.2,
Subcontractors, Section-3, Evaluation and Qualification Criteria, Volume 1 of 3 of the Bidding Document.

Sl. No. Name and Address of the Subcontractor

Signature ----------------------------------
Date ----------------------------------
Attachment-Price Schedule
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Unit Price1 Total Price1 Taxes and Duties


2
Item Description Country of origin Unit Quantity
Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
1

400kV XLPE Underground Power Cable with


1.1
Necessary Accessories
400kV single core 2000sqmm copper conductor,
1.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 31.518
outer sheathed cable
Straight Through Joint suitable for above cable
1.1.2 mentioned in item 1.1.1 including all related Set 12
accessories

Insulated Joint suitable for above cable mentioned


1.1.3 Set 72
in item 1.1.1 including all related accessories

Outdoor Cable Sealing End for above cable


1.1.4 mentioned in item 1.1.1 including all related Set 6
accessories(Long rod type polymar)
230kV outdoor Cable Sealing End for above cable
1.1.5 mentioned in item 1.1.1 including all related Set 6
accessories(Long rod type polymar)
Link Box for cross bonding including all related
1.1.6 Set 24
accessories
Link Box for earthing at straight through joint
1.1.7 Set 4
including all related accessories
Link Box for earthing at cable sealing end including
1.1.8 Set 8
all related accessories
Fibre Optic Cable inclusive of joint boxes including
1.2
all related accessories
Fibre Optic Cable including of joint boxes and all
1.2.1 km 5.253
related accessories
Fibre Optic Cable Termination Box inclusive all
1.2.2 set 2
related accessories

BP-1
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1 Taxes and Duties

Item Description Country of origin2 Unit Quantity


Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Scope-1: Anowara-Ananda
Connection of Undergroundbazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
and Overhead
1.3
Transmission Lines
Steel structure for gantry column and beam including
1.3.1 nut&bolts at O/H to U/G Transition compound Lot 1
arrangement
Equipment Support Structures at O/H to U/G
1.3.2 Transition compound arrangement and support Lot 1
structure for CSE at Anandabazar substation

Material(ACSR Conductor, Clamp, Connector etc.)


for AIS Connection from slack span conductor to
1.3.3 Lot 1
Cable sealing end and LA as per drawings
PGCB/400KV/OH-UG/Anow-Ananda/TL

1.3.4 230kV Lightenning Arrester set 6


1.4 Spares
Outdoor Cable sealing end terminations complete
1.4.1 kit with filling compound for above cable set 2
mentioned in item 1.1.1
GIS Cable sealing end terminations complete kit
1.4.2 with filling compound for above cable mentioned in set 0
item 1.1.1(Male Part)

Cable joint (straight through suitable for above


1.4.3 set 3
cable mentioned in item 1.1.1)

Sub-total Columns 7 to be carried forward to Schedule No. 5 - Grand Summary

2 Scope-2: Rampur-Anandabazar 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


2.1
Necessary Accessories
230kV single core 2000sqmm copper conductor,
2.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 22.62
outer sheathed cable

BP-2
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1 Taxes and Duties

Item Description Country of origin2 Unit Quantity


Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Scope-1: Anowara-Ananda
Straight Through bazarfor
Joint suitable (New Mooring)
above cable 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
2.1.2 mentioned in item 2.1.1 including all related Set 18
accessories

Insulated Joint suitable for above cable mentioned


2.1.3 Set 24
in item 2.1.1 including all related accessories

Outdoor Cable Sealing End for above cable


2.1.4 mentioned in item 2.1.1 including all related Set 0
accessories(Long rod type polymar)

GIS Cable Sealing End for above cable mentioned


2.1.5 Set 12
in item 2.1.1 including all related accessories

Link Box for cross bonding including all related


2.1.6 Set 8
accessories
Link Box for earthing at straight through joint
2.1.7 Set 6
including all related accessories
Link Box for earthing at cable sealing end including
2.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
2.2
all related accessories
Fibre Optic Cable including of joint boxes and all
2.2.2 km 3.770
related accessories
Fibre Optic Cable Termination Box inclusive all
2.2.3 set 4
related accessories
2.3 Spares
Outdoor Cable sealing end terminations complete
2.3.1 kit with filling compound for above cable set 0
mentioned in item 2.1.1
GIS Cable sealing end terminations complete kit
2.3.2 with filling compound for above cable mentioned in set 3
item 2.1.1(Male Part only)
Cable joint (straight through suitable for above
2.3.3 set 0
cable mentioned in item 2.1.1)

BP-3
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1 Taxes and Duties

Item Description Country of origin2 Unit Quantity


Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
Sub-total Columns 7 to be carried forward to Schedule No. 5 - Grand Summary

3 Scope-3: Anandabazar-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


3.1
Necessary Accessories
230kV single core 2000sqmm copper conductor,
3.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 36.60
outer sheathed cable
Straight Through Joint suitable for above cable
3.1.2 mentioned in item 3.1.1 including all related Set 30
accessories

Insulated Joint suitable for above cable mentioned


3.1.3 Set 36
in item 3.1.1 including all related accessories

AIS Cable Sealing End for above cable mentioned


3.1.4 in item 3.1.1 including all related accessories(Long Set 0
rod type polymar)

GIS Cable Sealing End for above cable mentioned


3.1.5 Set 12
in item 3.1.1 including all related accessories

Link Box for cross bonding including all related


3.1.6 Set 12
accessories
Link Box for earthing at straight through joint
3.1.7 Set 10
including all related accessories
Link Box for earthing at cable sealing end including
3.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
3.2
all related accessories
Fibre Optic Cable including of joint boxes and all
3.2.2 km 6.10
related accessories
Fibre Optic Cable Termination Box inclusive all
3.2.3 set 2
related accessories

BP-4
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1 Taxes and Duties

Item Description Country of origin2 Unit Quantity


Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

3.3 Scope-1:
Spares Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
Outdoor Cable sealing end terminations complete
3.3.1 kit with filling compound for above cable set 0
mentioned in item 3.1.1
GIS Cable sealing end terminations complete kit
3.3.2 with filling compound for above cable mentioned in set 3
item 3.1.1(Male Part)

Cable joint (straight through suitable for above


3.3.3 set 3
cable mentioned in item 3.1.1)
Sub-total Columns 7 to be carried forward to Schedule No. 5 - Grand Summary

4 Scope-4: Madunaghat-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


4.1
Necessary Accessories
230kV single core 2000sqmm copper conductor,
4.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 87.48
outer sheathed cable
Straight Through Joint suitable for above cable
4.1.2 mentioned in item 4.1.1 including all related Set 48
accessories

Insulated Joint suitable for above cable mentioned


4.1.3 Set 120
in item 4.1.1 including all related accessories

GIS Cable Sealing End for above cable mentioned


4.1.5 Set 12
in item 4.1.1 including all related accessories

Link Box for cross bonding including all related


4.1.6 Set 40
accessories
Link Box for earthing at straight through joint
4.1.7 Set 16
including all related accessories
Link Box for earthing at cable sealing end including
4.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
4.2
all related accessories

BP-5
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1 Taxes and Duties

Item Description Country of origin2 Unit Quantity


Foreign Currency [xxx] Foreign Currency [xxx]
Local Currency [XXX]
CIP CIP

1 2 3* 4 5 6 7= 5 x 6 8

Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Scope-1:
Fibre Optic Anowara-Ananda
Cable includingbazar (New
of joint Mooring)
boxes and all400 kV double circuit Underground cable line portion (2000 mm² XLPE):
4.2.2 km 14.58
related accessories
Fibre Optic Cable Termination Box inclusive all
4.2.3 set 2
related accessories
4.3 Spares
Outdoor Cable sealing end terminations complete
4.3.1 kit with filling compound for above cable set 3
mentioned in item 4.1.1
GIS Cable sealing end terminations complete kit
4.3.2 with filling compound for above cable mentioned in set 3
item 4.1.1(Male Part only)
Cable joint (straight through suitable for above
4.3.3 set 3
cable mentioned in item 4.1.1)
Sub-total Columns 7 to be carried forward to Schedule No. 5 - Grand Summary

Total Columns 7 to be carried forward to Schedule No. 5 - Grand Summary

Name of Bidder

Signature of Bidder

1  
Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to a maximum of two foreign currencies, if so required.

Bidders shall enter a code representing the country of origin of all imported plant and equipment.

Country of Origin Declaration Form


Item Description Code Country

BP-6
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes
2
Item Description Country of origin Unit Quantity
Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
1

400kV XLPE Underground Power Cable with


1.1
Necessary Accessories
400kV single core 2000sqmm copper conductor,
1.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 31.518
outer sheathed cable
Straight Through Joint suitable for above cable
1.1.2 mentioned in item 1.1.1 including all related Set 12
accessories

Insulated Joint suitable for above cable mentioned


1.1.3 Set 72
in item 1.1.1 including all related accessories

Outdoor Cable Sealing End for above cable


1.1.4 mentioned in item 1.1.1 including all related Set 6
accessories(Long rod type polymar)

230kV Outdoor Cable Sealing End for above cable


1.1.5 mentioned in item 1.1.1 including all related Set 6
accessories (Long rod type polymar)

Link Box for cross bonding including all related


1.1.6 Set 24
accessories
Link Box for earthing at straight through joint
1.1.7 Set 4
including all related accessories
Link Box for earthing at cable sealing end including
1.1.8 Set 8
all related accessories
Fibre Optic Cable inclusive of joint boxes including
1.2
all related accessories
Fibre Optic Cable including of joint boxes and all
1.2.1 km 5.253
related accessories

BP-7
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes

Item Description Country of origin2 Unit Quantity


Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1: Anowara-Ananda
Fibre Optic bazar
Cable Termination (New
Box Mooring)
inclusive all 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
1.2.2 set 2
related accessories
Connection of Underground and Overhead
1.3
Transmission Lines
Gantry Column with signle beam including nut&bolts at
1.3.1 Lot 1
O/H to U/G Transition compound arrangement
Equipment Support Structures at O/H to U/G
1.3.2 Transition compound arrangement and support Lot 1
structure for CSE at Anandabazar substation
Material(ACSR Conductor, Clamp, Connector etc.)
for AIS Connection from slack span conductor to
1.3.3 Lot 1
Cable sealing end and LA as per drawings
PGCB/400KV/OH-UG/Anow-Ananda/TL
1.3.4 230kV Lightenning Arrester set 6

1.4 Spares
Outdoor Cable sealing end terminations complete
1.4.1 kit with filling compound for above cable set 2
mentioned in item 1.1.1
GIS Cable sealing end terminations complete kit
1.4.2 with filling compound for above cable mentioned in set 0
item 1.1.1(Male Part)
Cable joint (straight through suitable for above
1.4.3 set 3
cable mentioned in item 1.1.1)

Sub-total Columns 7 & 9 to be carried forward to Schedule No. 5 - Grand Summary

2 Scope-2: Rampur-Anandabazar 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


2.1
Necessary Accessories

BP-8
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes

Item Description Country of origin2 Unit Quantity


Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1: Anowara-Ananda
230kV single core 2000sqmm bazar (Newconductor,
copper Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
2.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 22.62
outer sheathed cable
Straight Through Joint suitable for above cable
2.1.2 mentioned in item 2.1.1 including all related Set 18
accessories
Insulated Joint suitable for above cable mentioned
2.1.3 Set 24
in item 2.1.1 including all related accessories

Outdoor Cable Sealing End for above cable


2.1.4 mentioned in item 2.1.1 including all related Set 0
accessories(Long rod type polymar)

GIS Cable Sealing End for above cable mentioned


2.1.5 Set 12
in item 2.1.1 including all related accessories

Link Box for cross bonding including all related


2.1.6 Set 8
accessories
Link Box for earthing at straight through joint
2.1.7 Set 6
including all related accessories
Link Box for earthing at cable sealing end including
2.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
2.2
all related accessories
Fibre Optic Cable including of joint boxes and all
2.2.2 km 3.770
related accessories
Fibre Optic Cable Termination Box inclusive all
2.2.3 set 4
related accessories
2.3 Spares
Outdoor Cable sealing end terminations complete
2.3.1 kit with filling compound for above cable set 0
mentioned in item 2.1.1
GIS Cable sealing end terminations complete kit
2.3.2 with filling compound for above cable mentioned in set 3
item 2.1.1(Male Part)

BP-9
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes

Item Description Country of origin2 Unit Quantity


Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1: Anowara-Ananda
Cable joint bazar
(straight through (Newfor
suitable Mooring)
above 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
2.3.3 set 0
cable mentioned in item 2.1.1)
Sub-total Columns 7 & 9 to be carried forward to Schedule No. 5 - Grand Summary

3 Scope-3: Anandabazar-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


3.1
Necessary Accessories
230kV single core 2000sqmm copper conductor,
3.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 36.60
outer sheathed cable
Straight Through Joint suitable for above cable
3.1.2 mentioned in item 3.1.1 including all related Set 30
accessories
Insulated Joint suitable for above cable mentioned
3.1.3 Set 36
in item 3.1.1 including all related accessories

AIS Cable Sealing End for above cable mentioned


3.1.4 in item 3.1.1 including all related accessories(Long Set 0
rod type polymar)

GIS Cable Sealing End for above cable mentioned


3.1.5 Set 12
in item 3.1.1 including all related accessories

Link Box for cross bonding including all related


3.1.6 Set 12
accessories
Link Box for earthing at straight through joint
3.1.7 Set 10
including all related accessories
Link Box for earthing at cable sealing end including
3.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
3.2
all related accessories
Fibre Optic Cable including of joint boxes and all
3.2.2 km 6.10
related accessories

BP-10
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes

Item Description Country of origin2 Unit Quantity


Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1: Anowara-Ananda
Fibre Optic bazar
Cable Termination (New
Box Mooring)
inclusive all 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
3.2.3 set 2
related accessories
3.3 Spares
Outdoor Cable sealing end terminations complete
3.3.1 kit with filling compound for above cable set 0
mentioned in item 3.1.1
GIS Cable sealing end terminations complete kit
3.3.2 with filling compound for above cable mentioned in set 3
item 3.1.1(Male Part)
Cable joint (straight through suitable for above
3.3.3 set 3
cable mentioned in item 3.1.1)
Sub-total Columns 7 & 9 to be carried forward to Schedule No. 5 - Grand Summary

4 Scope-4: Madunaghat-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

230kV XLPE Underground Power Cable with


4.1
Necessary Accessories

230kV single core 2000sqmm copper conductor,


4.1.1 XLPE insulated, corrugated Al sheathed & MDPE km 87.48
outer sheathed cable
Straight Through Joint suitable for above cable
4.1.2 mentioned in item 4.1.1 including all related Set 48
accessories

Insulated Joint suitable for above cable mentioned


4.1.3 Set 120
in item 4.1.1 including all related accessories

GIS Cable Sealing End for above cable mentioned


4.1.5 Set 12
in item 4.1.1 including all related accessories

Link Box for cross bonding including all related


4.1.6 Set 40
accessories
Link Box for earthing at straight through joint
4.1.7 Set 16
including all related accessories

BP-11
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Local Currency in BDT Foreign Currency in (xxx) Sales and Other Taxes

Item Description Country of origin2 Unit Quantity


Unit EXW Total EXW Unit EXW Total EXW
Local Currency
Price1 Price Price1 Price

1 2 3* 4 5 6 7=5X6 8 9= 5X8 10

Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

Scope-1:
Link Box forAnowara-Ananda bazar
earthing at cable (Newend
sealing Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
including
4.1.8 Set 4
all related accessories
Fibre Optic Cable inclusive of joint boxes including
4.2
all related accessories
Fibre Optic Cable including of joint boxes and all
4.2.2 km 14.58
related accessories
Fibre Optic Cable Termination Box inclusive all
4.2.3 set 2
related accessories
4.3 Spares
Outdoor Cable sealing end terminations complete
4.3.1 kit with filling compound for above cable set 0
mentioned in item 4.1.1
GIS Cable sealing end terminations complete kit
4.3.2 with filling compound for above cable mentioned in set 3
item 4.1.1(Male Part only)
Cable joint (straight through suitable for above
4.3.3 set 3
cable mentioned in item 4.1.1)
Sub-total Columns 7 & 9 to be carried forward to Schedule No. 5 - Grand Summary

Total Columns 7 & 9 to be carried forward to Schedule No. 5 - Grand Summary

Name of Bidder

Signature of Bidder

1 Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to a maximum of two foreign currencies, if so required.
2 Bidders shall enter a code representing the country of origin of all imported plant and equipment.

BP-12
Design, Supply, Installa on, Tes ng & Commissioning of 400kV & 230kV underground XLPE cable Transmission lines on Cha ogram Area.(Package-2)

Schedule No. 3 Design Services

Unit Price1 Total Price1

Item Description Unit Quantity Local Local


Foreign Foreign
Currency Currency
Currency [XXX] Currency [XXX]
[BDT] [BDT]

1 2 3 4 5 6 7=4X5 8= 4 x 6
Schedule No. 3 Design Services
1 Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):

1.1 Design serices for scope-1 Lump sum 1

2 Scope-2: Rampur-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

2.1 Design serices for scope-2 Lump sum 1

3 Scope-3: Anandabazar-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

3.1 Design serices for scope-3 Lump sum 1

4 Scope-4: Madunaghat-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

4,1 Design serices for scope-4 Lump sum 1

5 Inspection Cost

5.1 Costs and Expenses related to third party witness Lump sum 1

5.2 Costs and Expenses related to test witness3(Provisional Sum) Lump sum 1 $50,000.00 $50,000.00

Total
Columns 7

Name of Bidder

Signature of Bidder
1
. Specify currencies in accordance with ITB 19.1 of the BDS.
3
These costs are fixed ceiling and will be included in total price. But the payment shall be at actual upon submission of relevant documents.

BP-13
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Schedule No. 4 Installation and Other Services

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
1

1.1 Installation and Erection of 400kV XLPE cables and Fibre Optic Cable Circuit
Laying of cables (double circuit of single core cables and one fibre optic cable) as per
1.1.1 per km 5.253
the requirements of the technical specification.
Excavation of cable trench as per the requirements of the technical specification (double
1.1,2 per km 4.663
circuit of single core cables and one fibre optic cable)
Excavation of cable trench for road crossing using cable ducts for individual cables as
1.1.3 per the requirements of the technical specification and laying of cables (double circuit of per km 0.140
single core cables and one fibre optic cable)
Making arrangement /installation of cable trench for Road crossing using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
1.1.4 (HDD) method or any other means. One spare cable duct is to be provided in the Road per km 0.10
crossing cable trench. Total cost of making/installing all arrangements including supply
of materials/accessories required for the Road crossing arrangement/installation are
included in this item.
Making arrangement /installation of cable trench for Rail Line crossing using cable ducts
for individual cables as per the requirements of the technical specification (double circuit
of single core cables and one fiber optic cable) through Horizontal Directional Drilling
1.1.5 (HDD) method or any other means. One spare cable duct is to be provided in the Rail Lot 1.00
Line crossing cable trench. Total cost of making/installing all arrangements including
supply of materials/accessories required for the Rail Line crossing
arrangement/installation are included in this item.

Making arrangement /installation including pile foundations or any other type foundations
as required for the crossing of the canal/khal (double circuit of single core cables and
one fiber optic cable) into/within the canal/khal crossing arrangement/installation through
1.1.6
cable bridge. Total cost of making/installing all arrangements including supply of steel
works and other materials/accessories required for the above canal/khal crossing
arrangement/installation are included in this item.
1.1.6.1 Up to 20 meter width per km 0.05
1.1.6.2 Above 20meter width per km 0.05

BP-14
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
Making arrangement /installation for the crossing of the canal/khal using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
1.1.7 per km 0.25
(HDD) method or any other means into/within the canal/khal. Total cost of
making/installing all arrangements including supply of materials/accessories required for
the above canal/khal crossing arrangement/installation are included in this item.

Excavation of cable joint bay as per the requirements of the technical specification
1.1.8 Set 14
including all related works
Installation and jointing of 400kV insulated/straight through joints as per the
requirements of the technical specification including installation of link box and
1.1.9 Set 84
associated earthing works with provision for link pit as per the requirements and all
related works
Installation and terminating of 400kV AIS Cable sealing end termination as per the
1.1.10 requirements of the technical specification including installation of link box and Set 6
associated earthing works as per the requirements and all related works
Installation and terminating of 230kV outdoor cable sealing end termination as per the
1.1.11 requirements of the technical specification including installation of link box and Set 6
associated earthing works as per the requirements and all related works
1.1.12 Installation and jointing of Fibre optic cable joint inclusive all related accessories Lot 1
Installation and terminating of Fibre optic cable terminal box inclusive all related
1.1.13 Set 2
accessories
1.1.14 Installation of Gantry column and beam at O/H to U/G Transition compound. Lot 1
1.1.15 Installation of 230kV Lighting Arrester including earthing & all related accessories Set 6
1.2 Route Survey & Clearance
Check Survey in accordance with the requirements of the technical specification, incl. full
1.2.1 ground survey with change of route, if any, preparation and submission of route maps, per km 5.253
SIMM document, etc.
Route clearance in accordance with requirements of the technical specification including
1.2.2 Lump sum 1.00 2,801,000.00 2,801,000.00
payment of damage compensation
1.3 Testing and Commisioning
Testing and commissioning of 400kV cable circuit and fibre optic cable with provision of
1.3.1 Lot 1
all test equipment as per the requirements of technical specification
1.4 MISCELLANEOUS
AIS termination/connection from slack span conductor to Cable sealing end and LA as
1.4.1 Lot 1
per drawings PGCB/400KV/OH-UG/Anow-Ananda/TL

BP-15
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
Complete civil works including but not limited to surface finishing of termination area,
1.4.2 gravel laying, earthing, foundation (Gantry, CSE and LA), fencing, drainage etc as Lot 1
indicated on tender drawings PGCB/400KV/OH-UG/Anow-Ananda/TL

Complete civil works including foundation for outdoor cable sealing end at Anandabar
1.4.3 Lot 1
substation.

Sub-total Columns 7 & 8 to be carried forward to Schedule No. 5 - Grand Summary

Scope-2: Rampur-Anandabazar 230 kV double circuit underground cable line (XLPE 2000 mm²):
2

2.1 Installation and Erection of 230kV XLPE cables and Fibre Optic Cable Circuit
Laying of cables (double circuit of single core cables and one fibre optic cable) as per
2.1.1 per km 3.770
the requirements of the technical specification.
Excavation of cable trench as per the requirements of the technical specification (double
2.1.2 per km 3.510
circuit of single core cables and one fibre optic cable)
Excavation of cable trench for road crossing using cable ducts for individual cables as
2.1.3 per the requirements of the technical specification and laying of cables (double circuit of per km 0.100
single core cables and one fibre optic cable)
Making arrangement /installation of cable trench for Road crossing using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
2.1.4 (HDD) method or any other means. One spare cable duct is to be provided in the Road per km 0.04
crossing cable trench. Total cost of making/installing all arrangements including supply
of materials/accessories required for the Road crossing arrangement/installation are
included in this item.
Making arrangement /installation of cable trench for Rail Line crossing using cable ducts
for individual cables as per the requirements of the technical specification (double circuit
of single core cables and one fiber optic cable) through Horizontal Directional Drilling
2.1.5 (HDD) method or any other means. One spare cable duct is to be provided in the Rail Lot 1.00
Line crossing cable trench. Total cost of making/installing all arrangements including
supply of materials/accessories required for the Rail Line crossing
arrangement/installation are included in this item.

BP-16
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line portion (2000 mm² XLPE):
Making arrangement /installation including pile foundations or any other type foundations
as required for the crossing of the canal/khal (double circuit of single core cables and
one fiber optic cable) into/within the canal/khal crossing arrangement/installation through
2.1.6
cable bridge. Total cost of making/installing all arrangements including supply of steel
works and other materials/accessories required for the above canal/khal crossing
arrangement/installation are included in this item.
2.1.6.1 Up to 20 meter width per km 0.04
2,1.6.2 Above 20meter width per km 0.04

Making arrangement /installation for the crossing of the canal/khal using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
2.1.7 per km 0.040
(HDD) method or any other means into/within the canal/khal. Total cost of
making/installing all arrangements including supply of materials/accessories required for
the above canal/khal crossing arrangement/installation are included in this item.

Excavation of cable joint bay as per the requirements of the technical specification
2.1.8 Set 7
including all related works

Installation and jointing of 230kV insulated/straight through joints as per the


requirements of the technical specification including installation of link box and
2.1.9 Set 42
associated earthing works with provision for link pit as per the requirements and all
related works
Installation and terminating of 230kV GIS sealing end termination as per the
2.1.10 requirements of the technical specification including installation of link box and Set 12
associated earthing works as per the requirements and all related works
2.1.11 Installation and jointing of Fibre optic cable joint inclusive all related accessories Lot 1
Installation and terminating of Fibre optic cable terminal box inclusive all related
2.1.12 Set 2
accessories
2.2 Route Survey & Clearance
Check Survey in accordance with the requirements of the technical specification, incl. full
2.2.1 ground survey with change of route, if any, preparation and submission of route maps, per km 3.770
SIMM document, etc.
Route clearance in accordance with requirements of the technical specification including
2.2.2 Lump sum 1.00 1,271,000.00 1,271,000.00
payment of damage compensation
2.3 Testing and Commisioning

BP-17
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1:and
Testing Anowara-Ananda
commissioning bazar (New
of 230kV Mooring)
cable circuit400
andkV double
fibre opticcircuit
cable Underground
with provisioncable
of line portion (2000 mm² XLPE):
2.3.1 Lot 1
all test equipment as per the requirements of technical specification
2.4 MISCELLANEOUS
2.4.1 Miscellaneous works at Anandabazar(New mooring) and Rampur GIS S/S: Lot 1

Sub-total Columns 7 & 8 to be carried forward to Schedule No. 5 - Grand Summary

Scope-3: Anandabazar-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):
3

3.1 Installation and Erection of 230kV XLPE cables and Fibre Optic Cable Circuit
Laying of cables (double circuit of single core cables and one fibre optic cable) as per
3.1.1 per km 6.10
the requirements of the technical specification.
Excavation of cable trench as per the requirements of the technical specification (double
3.1.2 5.40
circuit of single core cables and one fibre optic cable)
Excavation of cable trench for road crossing using cable ducts for individual cables as
3.1.3 per the requirements of the technical specification and laying of cables (double circuit of per km 0.370
single core cables and one fibre optic cable)
Making arrangement /installation of cable trench for Road crossing using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
3.1.4 (HDD) method or any other means. One spare cable duct is to be provided in the Road per km 0.125
crossing cable trench. Total cost of making/installing all arrangements including supply
of materials/accessories required for the Road crossing arrangement/installation are
included in this item.
Making arrangement /installation of cable trench for Rail Line crossing using cable ducts
for individual cables as per the requirements of the technical specification (double circuit
of single core cables and one fiber optic cable) through Horizontal Directional Drilling
3.1.5 (HDD) method or any other means. One spare cable duct is to be provided in the Rail Lot 1.00
Line crossing cable trench. Total cost of making/installing all arrangements including
supply of materials/accessories required for the Rail Line crossing
arrangement/installation are included in this item.

Making arrangement /installation including pile foundations or any other type foundations
as required for the crossing of the canal/khal (double circuit of single core cables and
one fiber optic cable) into/within the canal/khal crossing arrangement/installation through
3.1.6
cable bridge. Total cost of making/installing all arrangements including supply of steel
works and other materials/accessories required for the above canal/khal crossing
arrangement/installation are included in this item.

BP-18
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
3.1.6.1 Scope-1:
Up Anowara-Ananda
to 20 meter width bazar (New Mooring) 400 kV double circuit Underground cable line
per portion
km (2000
0.02 mm² XLPE):
3.1.6.2 Above 20meter width per km 0.03

Making arrangement /installation for the crossing of the canal/khal using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
3.1.7 per km 0.03
(HDD) method or any other means into/within the canal/khal. Total cost of
making/installing all arrangements including supply of materials/accessories required for
the above canal/khal crossing arrangement/installation are included in this item.

Excavation of cable joint bay as per the requirements of the technical specification
3.1.8 Set 11
including all related works
Installation and jointing of 230kV insulated/straight through joints as per the
requirements of the technical specification including installation of link box and
3.1.9 Set 66
associated earthing works with provision for link pit as per the requirements and all
related works
Installation and terminating of 230kV GIS sealing end termination as per the
3.1.10 requirements of the technical specification including installation of link box and Set 12
associated earthing works as per the requirements and all related works
3.1.11 Installation and jointing of Fibre optic cable joint inclusive all related accessories Lot 1
Installation and terminating of Fibre optic cable terminal box inclusive all related
3.1.12 Set 2
accessories
3.2 Route Survey & Clearance
Check Survey in accordance with the requirements of the technical specification, incl. full
3.2.1 ground survey with change of route, if any, preparation and submission of route maps, per km 6.10
SIMM document, etc.
Route clearance in accordance with requirements of the technical specification including
3.2.2 Lump sum 1.00 2,057,000.00 2,057,000.00
payment of damage compensation
3.3 Testing and Commisioning
Testing and commissioning of 230kV cable circuit and fibre optic cable with provision of
3.3.1 Lot 1
all test equipment as per the requirements of technical specification
3.4 MISCELLANEOUS
3.4.1 Miscellaneous works at Khulshi and Anandabazar GIS S/S: Lot 1

Sub-total Columns 7 & 8 to be carried forward to Schedule No. 5 - Grand Summary

Scope-4: Khulshi-Madhunaghat 230 kV double circuit underground cable line (XLPE 2000 mm²):
4

BP-19
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
4.1 Scope-1: Anowara-Ananda
Installation bazar (New
and Erection of 230kV XLPEMooring) 400Fibre
cables and kV double circuit Circuit
Optic Cable Underground cable line portion (2000 mm² XLPE):
Laying of cables (double circuit of single core cables and one fibre optic cable) as per
4.1.1 per km 14.58
the requirements of the technical specification.
Excavation of cable trench as per the requirements of the technical specification (double
4.1.2 13.69
circuit of single core cables and one fibre optic cable)
Excavation of cable trench for road crossing using cable ducts for individual cables as
4.1.3 per the requirements of the technical specification and laying of cables (double circuit of per km 0.50
single core cables and one fibre optic cable)
Making arrangement /installation of cable trench for Road crossing using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
4.1.4 (HDD) method or any other means. One spare cable duct is to be provided in the Road per km 0.15
crossing cable trench. Total cost of making/installing all arrangements including supply
of materials/accessories required for the Road crossing arrangement/installation are
included in this item.
Making arrangement /installation of cable trench for Rail Line crossing using cable ducts
for individual cables as per the requirements of the technical specification (double circuit
of single core cables and one fiber optic cable) through Horizontal Directional Drilling
4.1.5 (HDD) method or any other means. One spare cable duct is to be provided in the Rail Lot 1.00
Line crossing cable trench. Total cost of making/installing all arrangements including
supply of materials/accessories required for the Rail Line crossing
arrangement/installation are included in this item.

Making arrangement /installation including pile foundations or any other type foundations
as required for the crossing of the canal/khal (double circuit of single core cables and
one fiber optic cable) into/within the canal/khal crossing arrangement/installation through
4.1.6
cable bridge. Total cost of making/installing all arrangements including supply of steel
works and other materials/accessories required for the above canal/khal crossing
arrangement/installation are included in this item.
4.1.6.1 Up to 20 meter width per km 0.060
4.1.6.2 Above 20meter width per km 0.060

Making arrangement /installation for the crossing of the canal/khal using cable ducts for
individual cables as per the requirements of the technical specification (double circuit of
single core cables and one fiber optic cable) through Horizontal Directional Drilling
4.1.7 per km 0.12
(HDD) method or any other means into/within the canal/khal. Total cost of
making/installing all arrangements including supply of materials/accessories required for
the above canal/khal crossing arrangement/installation are included in this item.

BP-20
Design, Supply, Installation, Testing Commissioning of 400kV 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Unit Price1 Total Price1


Item Description Unit Quantity
Foreign Currency Local Currency Foreign Currency
Local Currency [BDT]
[xxx] [BDT] [xxx]
1 2 3 4 5 6 7=4x5 8=4x6
Schedule No. 4 Installation and Other Services
Scope-1:
ExcavationAnowara-Ananda
of cable joint baybazar (New
as per the Mooring) 400 kV
requirements double
of the circuitspecification
technical Underground cable line portion (2000 mm² XLPE):
4.1.8 Set 28
including all related works
Installation and jointing of 230kV insulated/straight through joints as per the
requirements of the technical specification including installation of link box and
4.1,9 Set 168
associated earthing works with provision for link pit as per the requirements and all
related works
Installation and terminating of 230kV GIS sealing end termination as per the
4.1.10 requirements of the technical specification including installation of link box and Set 12
associated earthing works as per the requirements and all related works
4.1.11 Installation and jointing of Fibre optic cable joint inclusive all related accessories Lot 1
Installation and terminating of Fibre optic cable terminal box inclusive all related
4.1.12 Set 2
accessories
4.2 Route Survey & Clearance
Check Survey in accordance with the requirements of the technical specification, incl. full
4.2.1 ground survey with change of route, if any, preparation and submission of route maps, per km 14.58
SIMM document, etc.
Route clearance in accordance with requirements of the technical specification including
4.2.2 Lump sum 1.00 4,918,000.00 4,918,000.00
payment of damage compensation
4.3 Testing and Commisioning
Testing and commissioning of 230kV cable circuit and fibre optic cable with provision of
4.3.1 Lot 1
all test equipment as per the requirements of technical specification
4.4 MISCELLANEOUS
4.4.1 Miscellaneous works at Khulshi and Madhunaghat GIS S/S: Lot 1

Sub-total Columns 7 & 8 to be carried forward to Schedule No. 5 - Grand Summary


Total Columns 7 & 8 to be carried forward to Schedule No. 5 - Grand Summary

Name of Bidder

Signature of Bidder

1
Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to a maximum of three foreign currencies, if so required.

BP-21
Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable Transmission lines on Chattogram Area.(Package-2)

Schedule No. 5. Grand Summary


Total Price1
Item Description
Local Currency Portion [BDT] Foreign Currency Portion [xxx]
Scope-1: Anowara-Ananda bazar (New Mooring) 400 kV double circuit Underground cable line
portion (2000 mm² XLPE):

1 Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

2 Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

3 Schedule No. 3 Design Services

4 Schedule No. 4 Installation and Other Services -

Scope-2: Rampur-Anandabazar 230 kV double circuit underground cable line (XLPE 2000 mm²):

1 Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

2 Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

3 Schedule No. 3 Design Services

4 Schedule No. 4 Installation and Other Services -

Scope-3: Anandabazar-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

1 Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

2 Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

3 Schedule No. 3 Design Services

BP-22
4 Schedule No. 4 Installation and Other Services -

Scope-4: Madunaghat-Khulshi 230 kV double circuit underground cable line (XLPE 2000 mm²):

1 Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

2 Schedule No. 2 Plant and Mandatory Spare Parts Supplied from Within the Employer's Country

3 Schedule No. 3 Design Services

4 Schedule No. 4 Installation and Other Services -

GRAND TOTAL

Name of Bidder

Signature of Bidder

1. Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to a maximum of three foreign currencies, if so required.

BP-23
6A-24

Design, Supply, Installation, Testing & Commissioning of 400kV & 230kV underground XLPE cable
Transmission lines on Chattogram Area.(Package-2)

Schedule No. 6. Recommended Spare Parts


Unit
Total Price1
Price1
Item Description Unit Quantity
Local Foreign
Local
Currency Currency Foreign Currency
Currency
Portion Portion Portion [xxx]
Portion [BDT]
[BDT] [xxxxx]
1 2 3 4 5 6 7=4x5 8=4x6

Name of Bidder

Signature of Bidder

1. Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to
a maximum of three foreign currencies, if so required.

BP-24