You are on page 1of 186

Transient Recovery Voltages (TRVs)

for High-Voltage Circuit Breakers


Part 1

Denis Dufournet
Chair CIGRE WG A3.28 & IEEE WG C37.011, Fellow IEEE
San Antonio (USA), 19/09/2013

GRID
Content (1/3)

Page
• Introduction & General Considerations 4 &13
• Capacitive Current Switching TRV 29
• Types of Fault TRVs 45
• TRV Modification 63
• Terminal Fault TRV 72
− First-pole-to-clear factor 73
− TRV rating & testing 88
− TRV & arcing times 120
− TRV for generator circuit breakers 138
• Short-Line Fault TRV 148
• ITRV (Initial TRV) 187

TRV HV Circuit Breakers P 2


Content (2/3)

Page
• Out-of-Phase TRV 194
• Three-Phase Line Faults TRV 199
• Shunt Reactor Switching TRV 217
• Transformer Limited Fault TRV 229
• Series Reactor Limited Fault TRV 264
• Influence of Series Capacitors on TRV 271
• Harmonization of TRVs in IEC & IEEE 282

TRV HV Circuit Breakers P 3


Content (3/3)

Page
• Annexes 306
− A: First-pole-to-clear factor 307
− B: Second-pole-to-clear factor 316
− C: Complement on line faults 321
− D: Equivalent circuit for 3-phase to ground fault 326
− E: Test circuit for kpp = 1.3 329
− F: Bibliography 333

TRV HV Circuit Breakers P 4


Introduction

GRID
Importance of TRV

• The TRV is a decisive parameter that limits the interrupting capability


of a circuit breaker.
• The interrupting capability of a circuit breaker was found to be strongly
dependent on TRV in the 1950’s.
• When developing interrupting chambers, manufacturers must verify
and prove the TRV withstand specified in the standards for different
test duties.
• Users must specify TRVs in accordance with their applications.
• Type tests in high-power laboratories must be performed in
accordance with international standards, in particular with rated values
of TRVs.

TRV HV Circuit Breakers P 6


“Recent” TRV Studies in International Bodies

• TRV Studies by International Working Groups


1993-1996: CIGRE-CIRED WG CC03 “Medium Voltages TRVs“
1994-1998: IEC SC17A WG21 “Revision Circuit Breaker Standard”
1997-2002: IEC SC17A WG23 “Harmonization TRVs Circuit Breakers ≥ 100kV”
2002-2006: IEC SC17A WG35 “”Revision TRVs Circuit Breakers < 100kV”
2001-2009: IEEE C37-04 & 06 ”Harmonization TRVs Circuit Breakers”
2002-2005: IEEE C37-011 “Revision Application Guide HV Circuit Breakers”
2004-2008: CIGRE WG A3-19 ”Implications of Three-phase Line Faults”
2007-2009: CIGRE WG A3-22 ”Technical Requirements for UHV Equipment”
2009-2011: IEC SC17A MT36 TF ”Introduction UHV TRVs in IEC 62271-100”
2008-2011: IEEE C37-011 ”Revision Application Guide HV Circuit Breakers”
2011-2013: CIGRE WG A3-28 ”Switching Phenomena for UHV & EHV Equipment”

TRV HV Circuit Breakers P 7


Main References

• A.Greenwood, Electrical Transients in Power Systems. (book) 2nd


edition, John Wiley & Sons (1991).
• R.Alexander, D.Dufournet, IEEE Tutorial on TRVs (2003-05)
http://www.ewh.ieee.org/soc/pes/switchgear/presentations/trvtutorial/T
utorialTRVAlexander-Dufournet.pdf
• D.Dufournet, TRVs for High-Voltage Circuit Breakers, Presentation at
IEEE Switchgear Committee meeting in Calgary (2008-10)
http://www.ewh.ieee.org/soc/pes/switchgear/presentations/2008cbtutor
ial/Part4_IEEETutorialonTRVHVCircuitBreakers-Dufournet.pdf
• CIGRE Technical Brochure N°134, Transient Recovery Voltages in
Medium Voltage Networks (1998-12)
• CIGRE Technical Brochure N°408, Line fault phenomena and their
implications for 3-phase short and long-line fault clearing, (2010-02)

TRV HV Circuit Breakers P 8


Main References

• A.Janssen, D.Dufournet, “Travelling Waves at Line Fault Clearing and


Other Transient Phenomena”, CIGRE Session 2010, Paper A3-102.
• CIGRE Technical Brochure 456, “Background of Technical
Specifications for Substation Equipment Exceeding 800kV AC”, by
CIGRE WG A3-22 (2011-04).
• D.Dufournet, A.Janssen, “Transformer Limited fault TRV”, Tutorial at
IEEE Switchgear Committee Meeting in San Diego (2012-10)

• Denis Dufournet, Joanne (Jingxuan) Hu, High-Voltage Circuit


Breakers Seminar Part 2 Transient Recovery Voltages, University of
Manitoba, Winnipeg (2012-06)

TRV HV Circuit Breakers P 9


Standards & Guides

• IEC 62271-100, High-Voltage Circuit-Breakers (2012-09)


• IEC 62271-101, Synthetic testing (2012-10)
• IEC 62271-110, Inductive load switching (2012-09)
• IEC 62271-306, Guide to IEC 62271-100, 62271-1 .. (2012-12)
• ANSI/IEEE C37.04, 04a, 04b, IEEE Standard Rating Structure for AC
High-Voltage Circuit Breakers.
• IEEE Std C37.06-2009, Draft AC High-Voltage Circuit Breakers Rated on
a Symmetrical Current Basis-Preferred Ratings and Related Required
Capabilities
• IEEE Std C37.09, 09b-2010, IEEE Standard Test Procedure for AC High-
Voltage Circuit Breakers Rated on a Symmetrical Current Basis.
• IEEE C37.011, Application Guide for TRV for AC High-Voltage Circuit
Breakers” (2011).
• IEEE C37.013, IEEE Standard for AC High-Voltage Generator Circuit
Breakers Rated on a Symmetrical Current Basis.

TRV HV Circuit Breakers P 10


Historical Perspective

• In the second edition of IEC 56 published in 1954, the TRV, defined as


"restriking voltage”, was of single frequency.
The amplitude factor (or crest value) and the TRV frequency (related to
the rate-of-rise) were not specified but had to be evaluated during the
tests.
• In the third edition of IEC 56, published in 1971, IEC introduced for the
first time the term “TRV” and its representation by two or four
parameters. The short-line-fault tests were also introduced in this
edition.
• TRVs requirements were also introduced in 1971 in ANSI C37.072-
1971 (IEEE Std. 327), with TRV ratings in C37.0722-1971 and TRV
Application Guide C37.0721-1971 (IEEE Std. 328).

TRV HV Circuit Breakers P 11


Historical Perspective

• In the fourth edition of IEC 56, published in 1987, a first-pole-to-clear


factor of 1.3 is the only factor specified for rated voltages ≥ 245 kV.
− the rate of rise of recovery voltage (RRRV) is doubled to 2.0 kV/µs
for terminal fault test duty T100.
− ITRV is introduced for rated voltages ≥ 100 kV.
• ITRV is introduced in ANSI C37.04 and C37.09 in 1991 (amendments
04i and 09g).
• ANSI C37-06 (1997) harmonize partly TRV parameters with those in
IEC (e.g. RRRV = 2.0 kV/µs for T100).
• As in IEC, line surge impedance is 450 Ω for all rated voltages in
ANSI/IEEE C37.04-1999 (instead of 450 Ω for Ur ≤ 242 kV and 360 Ω
for Ur ≥ 362 kV).

TRV HV Circuit Breakers P 12


Historical Perspective

• Further Harmonization of TRVs between IEC and IEEE lead


to
− Amendments 1 and 2 of IEC 62271-100 (respectively in 2002 and
2006)
− Amendments of IEEE C37.04b (2008), IEEE C37.06 (2009) and
IEEE C37.09b (2010).
Harmonization of IEC and IEEE standards for high-voltage circuit
breakers is presented in detail in a specific chapter.

TRV HV Circuit Breakers P 13


General considerations on
Transient Recovery Voltages

GRID
General Considerations

• The recovery voltage is the voltage which appears across the


terminals of a pole of circuit breaker after current interruption.

A B
Xs CURRENT

Recovery
voltage
U

TRANSIENT RECOVERY RECOVERY


VOLTAGE VOLTAGE

TRV HV Circuit Breakers P 15


General Considerations

• Current Interruption Process in SF6 Circuit Breakers

Two contacts are


separated in each
interrupting chamber.
An arc is generated, it is
cooled and extinguished
when current passes
through zero.

Simulation arc interruption

TRV HV Circuit Breakers P 16


General Considerations

• During the interruption process, the arc loses rapidly its conductivity as
the instantaneous current approaches zero.

TRV (kV)
I (A) Gas circuit breakers:
Within a few microseconds
after current zero, arc
TRV resistance (RARC) rises to
one million ohm in a few
microseconds and current
stops flowing in the circuit.
Interruption when current passes through zero

• During the first microseconds after current zero, the TRV withstand is
function of the energy balance in the arc: it is the thermal phase of
interruption.
TRV HV Circuit Breakers P 17
General Considerations

• Later, the voltage withstand is function of the dielectric withstand


between contacts: it is the dielectric phase of interruption.

The breaking operation is successful if the circuit breaker is able to


withstand the TRV and the power frequency recovery voltage.
The TRV is the difference between the voltages on the source side
and on the load side of the circuit breaker.
• During type tests, standards require that the recovery voltage is
applied during 300 ms after current interruption.

TRV HV Circuit Breakers P 18


General Considerations

• The nature of the TRV is dependent on the circuit being interrupted,


whether primarily resistive, capacitive or inductive, (or some
combination).
• When interrupting a fault at the circuit breaker terminal (terminal fault)
in an inductive circuit, the supply voltage at current zero is maximum.
The circuit breaker interrupts at current zero (at a time when the power
input is minimum) the voltage on the supply side terminal meets the
supply voltage in a transient process called the TRV.
1
TRV frequency is
2 LC
Fault
with L = short-circuit inductance
C = supply capacitance.

TRV HV Circuit Breakers P 19


General Considerations

TRV during inductive current breaking

CURRENT

Supply voltage

TRANSIENT RECOVERY
Current and TRV waveforms during interruption of inductive current
VOLTAGE

Note: voltage polarity not respected on Figure


TRV HV Circuit Breakers P 20
General Considerations

TRV and recovery voltage in resistive, inductive


and capacitive circuits
2,5

1,5
CAPACITIVE
CIRCUIT
1

0,5

0
0 0,005 0,01 0,015 0,02 0,025 0,03 0,035

-0,5

-1
RESISTIVE
CIRCUIT
-1,5
INDUCTIVE CIRCUIT
(with stray capacitance)
-2

TRV HV Circuit Breakers P 21


General Considerations

• Combination of the former basic cases are possible, for example the
TRV for mainly active load current breaking is a combination of TRVs
associated with inductive and resistive circuits.
• They are specified for high-voltage switches only as circuit-breakers
are able to interrupt with more severe TRVs (in inductive circuits).

TRV HV Circuit Breakers P 22


General Considerations

• Fault interruptions are often considered to produce the most onerous


TRVs. Shunt reactor switching is one of the exceptions.
• TRVs can be oscillatory, triangular, or exponential and can occur as a
combination of these forms.
• The highest peak TRVs are met during capacitive current and out-of-
phase current interruption,
• TRVs associated with the highest short-circuit current are obtained
during terminal fault and short-line-fault interruption.
• In general, a network can be reduced to a simple parallel RLC circuit
for TRV calculations.
This representation is valid for a short-time period until voltage
reflections return from remote buses (see IEEE C37.011-2011)

TRV HV Circuit Breakers P 23


General Considerations

Real network Equivalent circuit


(Vcb)

L
C
R

Z
N Lines, each with surge R
impedance
N
l
Z L: source inductance, lines excepted
c
C: source capacitance, lines excepted

TRV HV Circuit Breakers P 24


General Considerations

(Vcb)

L
C
R

− The TRV in the parallel RLC circuit is oscillatory (under-damped) if


1
R  L/C
2
− The TRV in the parallel RLC circuit is exponential (over-damped) if
1
R  L/C
2
TRV HV Circuit Breakers P 25
General Considerations

TRV (p.u.)
2
0.5
R / (L / C) = 10
1,8
4
1,6
2
1,4
1
1,2
0.75
1
0,8
0,6
0,5
0,4
0,3
0,2
0
t/RC
0 1 2 3 4 5 6 7 8 9

Damping of the oscillatory TRV is provided by R, as R is in parallel


t / RC to L and C
(parallel damping) the damping increases when the resistance decreases (the
TRV peak increases when R increases).
TRV HV Circuit Breakers P 26
General Considerations

• Reflection from end of lines


When longer time frames are
considered, typically several hundreds
of micro-seconds, reflections on lines
must be considered.
VOLTAGE (kV)
Lines or cables must then be
900 treated as components with
800
SYSTEM TRV
distributed elements on
700 TRV CAPABILITY FOR A
STANDARD BREAKER which voltage waves travel
600
after current interruption.
500

These traveling waves are


400

300

200
reflected and refracted when
100 REFLECTED WAVE reaching an open circuit or a
0
0 100 200 300 400 500 600 700 800 900 1000
discontinuity.
TIME (µs)

TRV HV Circuit Breakers P 27


General Considerations

• The most severe TRV occurs across the first pole to clear of a circuit
breaker when it interrupts a three-phase terminal fault with a
symmetrical current and when the system voltage is maximum (see
section on Terminal fault).

• By definition, all TRV values defined in the standards are inherent,


i.e. the values that would be obtained during interruption by an ideal
circuit breaker without arc voltage.
(arc resistance changes from zero to an infinite value at current
zero).

TRV HV Circuit Breakers P 28


Capacitive Current Switching
TRV & Recovery Voltage

GRID
Capacitive Current Switching

U (p.u.)
2,5

2
Recovery voltage
1,5

1
current
interruption
0,5

Supply voltage
0
Example of a single
-0,5
Load voltage phase interruption at
-1 50 Hz
-1,5
0,005 0,01 0,015 0,02 0,025 0,03 0,035

Time (s)

Capacitive current interruption: recovery voltage has a (1 – cos) waveshape

TRV HV Circuit Breakers P 30


Capacitive Current Switching

Supply-side voltage

Load-side voltage

Recovery voltage

Current

Contact separation Final current interruption


Current interruption
Restrike
TRV HV Circuit Breakers P 31
Capacitive Current Switching

U (p.u.)
Overvoltage 3 p.u.
3,5

2,5

2
2 p.u.
Recovery voltage
1,5 instant of current
interruption
1

0,5
2 p.u.
0

-0,5

-1
Reignition Restrike
-1,5
no overvoltage overvoltage
0,005 0,01 0,015 0,02 0,025
Time (s)

TRV HV Circuit Breakers P 32


Capacitive Current Switching

• Two cases can be distinguished, depending on when the restrike


happens:

− When it is less than 1/4 of a cycle after current interruption: it is


called a reignition,
no overvoltage is produced on the circuit during the transient
period when the load voltage tend to reach the supply voltage.
− When it is more than 1/4 of a cycle after current interruption, it is
called a restrike,
there is an overvoltage on the circuit during the transient period
following the restrike.

TRV HV Circuit Breakers P 33


"1-Cos" Waveshape

• Special case of series capacitor switching by by-pass switches

− By-pass switches must be able to withstand the reinsertion voltage


without restrike during the transfer of reinsertion current.

TRV HV Circuit Breakers P 34


"1-Cos" Waveshape

• Special case of series capacitor switching


by by-pass switches

− Several transient reinsertion voltage


waveshapes can be obtained in service.
− The reinsertion voltage waveshape should be determined by
systems studies.
− For standardization purposes, and in order to cover the greatest
number of practical cases, IEC 62271-109 recommends a "1-cos"
waveshape having a preferred first time-to-peak of 5,6 ms.
− A restrike happens if there is a resumption of current 2.8 ms or
later after the initial current interruption.

TRV HV Circuit Breakers P 35


Capacitive Current Switching
Voltage Jump

Circuit with capacitive and inductive A


components.
E
• The recovery voltage is the sum a 1– cos
wave-shape and a high-frequency voltage
oscillation on the supply side due to a
transient across the short-circuit
(inductive) reactance at the time of
interruption (explanation on next slide).
• There is an initial voltage jump.
• It tends to increase the minimum arcing
time and therefore to increase the shortest
duration between contact separation and
the instant of peak recovery voltage.
• Interruption is easier when the voltage
jump is higher
TRV HV Circuit Breakers P 36
Capacitive Current Switching
Voltage Jump

1 1- Supply-side voltage after


current interruption, with
0 voltage jump
2- Load-side voltage after
current interruption
3- Recovery voltage across
circuit-breaker terminals
Voltage before
current interruption

I 1 E E
UA    
C C 1 1  Ls C  2
 Ls 
C
TRV HV Circuit Breakers P 37
Three-Phase Capacitive Current Breaking
Capacitor Bank with Isolated Neutral

CR
A B
ER

CS
ES EN

CT N

ET

TRV HV Circuit Breakers P 38


Three-Phase Capacitive Current Breaking
Capacitor Bank with Isolated Neutral

Recovery voltage for the first pole to interrupt


2,0

VB
1,5

1,0

2.5 p.u.
0,5

VN
0,0
-0 ,0 05 -0,003 -0,00 1 0,00 1 0 ,0 03 0,00 5 0,0 07 0 ,0 09 0,01 1 0,0 13 0 ,0 15

-0,5

-1,0

VA
-1,5

Due to neutral voltage shift (VN) after interruption by the first pole, the peak
recovery voltage is 2.5 p.u. instead of 2 p.u. for single-phase interruption.

TRV HV Circuit Breakers P 39


Three-Phase Capacitive Current Breaking
Capacitor Bank with Isolated Neutral

Recovery voltage (RV) on each pole

uc= 2.5 p.u.


kc= 1.25

RV on first-
pole-to-clear

The recovery voltage is higher on the first pole to clear

TRV HV Circuit Breakers P 40


Three-Phase Capacitive Current Breaking
Capacitor Bank with Isolated Neutral

TRV 3-PHASE CAPACITIVE CURRENT SWITCHING (50Hz)


Capacitor bank with isolated neutral
3
The three-phase
Single-phase test with kc= 1,4
recovery voltage is 2,5
considered to be
covered during a 2
TRV (p.u.)

single phase test Three-phase test


1,5
with a supply
voltage equal to the 1
phase to ground Single-phase test with kc= 1,25

voltage multiplied 0,5


by 1.4
0
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10
T (ms)

TRV HV Circuit Breakers P 41


Three-Phase Line-Charging Current Breaking

In the case of line switching

The recovery voltage is


influenced by phase-to-
ground and phase-to-phase
capacitances

Equivalence during single-


phase test is obtained with a
supply voltage equal to the
phase-to-ground voltage
multiplied by a factor = 1.2
(U is 2.4 p.u.).

TRV HV Circuit Breakers P 42


Three-Phase Cable-Charging Current Breaking

• Types of cables & equivalent circuits

Similar case as
Same case as overhead lines
capacitor bank
with grounded C1/C0=3 Ur ≤ 52kV
neutral
C1/C0=2 Ur > 52kV

Screened cable Belted cable

TRV HV Circuit Breakers P 43


Three-Phase Capacitive Current Breaking
Single-phase tests to simulate three-phase conditions

Ur
• Test voltage for single-phase tests: U test  k c
3
• Voltage factors in case of effectively grounded neutral systems
− Line-charging current kc = 1.2
− Cable-charging current kc = 1.0 (screened cable)
= 1.4/ 1.2 (belted cable ≤52kV / >52kV)
− Capacitor-bank current kc = 1.0/1.4 grounded/isolated neutral
• Voltage factors in case of non-effectively grounded neutral systems
− Line-charging current kc = 1.4
− Cable-charging current kc = 1.4
− Capacitor-bank current kc = 1.4
• Voltage factors in the case of fault on another line(s)
− Effectively grounded neutral systems kc = 1.4
− Non-effectively grounded neutral systems kc = 1.7

TRV HV Circuit Breakers P 44


Types of Fault TRVs

GRID
Types of Fault TRVs / Reminder

Real network Equivalent circuit


(Vcb)

L
C
R

Z
N Lines, each with surge R
impedance
N
l
Z L: source inductance, lines excepted
c
C: source capacitance, lines excepted

TRV HV Circuit Breakers P 46


Types of Fault TRVs / Overdamped TRV

Exponential (overdamped) TRV


• The exponential part of a TRV occurs when the equivalent resistance
of the circuit with N connected lines in parallel
Z
R = Zeq =  1 is lower or equal to 0.5 Leq / Ceq
N
where Z1 = positive sequence surge impedance of a line
Z0 = zero sequence surge impedance of a line
3 Z0
N = number of lines,  
Z1  2 Z 0
Leq = equivalent inductance, Ceq = equivalent capacitance.
• It typically occurs when one or several lines are on the unfaulted side
of the circuit breaker and when the fault is cleared at the circuit
breaker terminals.
• The rate of rise of recovery voltage is RRRV = Zeq x (di/dt)
TRV HV Circuit Breakers P 47
Types of Fault TRVs / Overdamped TRV

Three-phase to ground fault


(Vcb)
• Equivalent inductance
3 L 0 L1
L eq 
L1  2 L 0 LLeq
ZReq Ceq
C

when L0  3 L1
9 L1
Leq   1.3 L1
7
• Equivalent capacitance see Annex D: 3-phase
network representation
2 (C1  C0 ) C0  2 C1
Ceq  C0  
3 3

TRV HV Circuit Breakers P 48


Types of Fault TRVs / Overdamped TRV

Three-phase to ground fault


• Equivalent surge impedance (first pole to clear)

3 Z 0Z1
Z eq  
N Z1  2Z 0

Z0  ZS  2 ZM
Z1  Z S  Z M 3 Z0

Z 0  Z1 Z1  2 Z 0
ZM 
3 see Annex D: 3-phase network
representation
ZS: self value
See section on SLF for the calculation of line
ZM: mutual value surge impedance

TRV HV Circuit Breakers P 49


Types of Fault TRVs / Overdamped TRV

• TRV for parallel RLC circuit

 t 
ucb  u1 (1  e (cosh  t  sinh  t ))

with
ucb is the voltage across the open circuit-breaker
u1 = 2 I ω Leq
 = 2  f = 377 rad/s at 60 Hz and 314 rad/s at 50 Hz
I is the short-circuit current (rms)
1
 =
2 Z eq Ceq

 =  2  1 /( Leq Ceq )

TRV HV Circuit Breakers P 50


Types of Fault TRVs / Overdamped TRV

• TRV when Ceq can be neglected

ucb  u1 (1  e t /  )

where
Leq

Z eq

• RRRV
ducb dI
 2 I ω Z eq  Z eq 
dt dt

TRV HV Circuit Breakers P 51


Types of Fault TRVs / Overdamped TRV

• Special case of three-phase ungrounded faults


3 L1
− Equivalent inductance L eq   1 . 5 L1
2

− Equivalent capacitance

2 C1 C1
Ceq  
3 1.5

with C1= C0

TRV HV Circuit Breakers P 52


Types of Fault TRVs / Overdamped TRV

• This exponential part of TRV is transmitted as traveling waves on


each of the transmission lines. Reflected wave(s) returning from open
lines or discontinuities contribute also to the TRV.

TRV HV Circuit Breakers P 53


Types of Fault TRVs / Overdamped TRV

• As an example, the following figure shows the one line diagram of a


550 kV substation. The TRV seen by circuit breaker (A) when clearing
the three-phase fault is shown in the next slide. Circuit breaker (B) is
open.

TRV HV Circuit Breakers P 54


Types of Fault TRVs / Overdamped TRV

System TRV with reflected wave


VOLTAGE (kV)

900

800
SYSTEM TRV
700 TRV CAPABILITY FOR A
STANDARD BREAKER
600

500

400

300

200

100 REFLECTED WAVE

0
0 100 200 300 400 500 600 700 800 900 1000

TIME (µs)

A reflection occurs from the end of the shortest


line after 2 x 81 / 0.3 = 540 µs
TRV HV Circuit Breakers P 55
Types of Fault TRVs / Reflected Waves

• The exponential part of TRV is transmitted as traveling waves on each


of the transmission lines.
• When a wave reaches a discontinuity on the line (another bus or a
transformer termination) a reflected wave is produced, which travels
back towards the faulted bus.
• It takes 6.67 µs for a wave to go out and back to a discontinuity 1km
away as the wave travels at 300 000 km/s (speed of light).
• At a discontinuity transmitted and reflected waves can be described by
the following equations:
2 Zb
et  ei
Za  Zb
Zb  Za
er  ei
Za Zb Za  Zb

TRV HV Circuit Breakers P 56


Types of Fault TRVs / Reflected Waves

Za Zb

• A wave that reaches a short-


circuit point (Zb= 0) is reflected
with an opposite sign 2 Zb
et  ei
Za  Zb
• A wave that reaches an open
point (Zb is infinite) is reflected
with the same sign. Zb  Za
The voltage at this point is then er  ei
Za  Zb
doubled.

TRV HV Circuit Breakers P 57


Types of Fault TRVs / Reflected Waves

• Example of TRV resulting from several traveling waves

From CIGRE WG A3-


22/28 tutorial in Rio
de Janeiro (2012-02)
Times in µs and not in
ms

TRV HV Circuit Breakers P 58


Types of Fault TRVs / Underdamped TRV

Oscillatory (underdamped) TRV


• An oscillatory TRV occurs generally when a fault is limited by a
transformer or a series reactor and no transmission line (or cable) surge
impedance is present to provide damping.

TRV HV Circuit Breakers P 59


Types of Fault TRVs / Underdamped TRV

• To be oscillatory, the equivalent resistance of the source side has to


be such that
Z Leq
Req    0.5
N Ceq
Leq = equivalent source inductance
Ceq = equivalent source capacitance.
• To meet this requirement, only a low number of lines (N) must be
connected on the source side.
Therefore oscillatory TRVs are specified for
− terminal fault test duties T10 and T30 for circuit breakers in
transmission systems (Ur  100 kV),
− all terminal fault test duties in the case of circuit breakers in
distribution or sub-transmission systems (Ur < 100 kV).

TRV HV Circuit Breakers P 60


Types of Fault TRVs / Underdamped TRV

• Transmission systems (Ur  100 kV)


In the large majority of cases, TRV characteristics (peak value and
rate-of-rise) for faults with 10% or 30% of rated short-circuit current
are covered by the rated values defined in the standards for test
duties T10 and T30.

TRV HV Circuit Breakers P 61


Types of Fault TRVs / Triangular wave-shape

• Triangular-shaped TRVs are associated with short-line faults (see


separate chapter on SLF).
• After current interruption, the line-side voltage exhibits a characteristic
triangular waveshape.
• The rate-of-rise of the saw-tooth shaped TRV is function of the line
surge impedance and current. The rate-of rise is usually higher than
that experienced with exponential or oscillatory TRVs (with the same
current), however the TRV peak is generally low.

line

Circuit breaker
TRV HV Circuit Breakers P 62
TRV Modification

GRID
Current Asymmetry and Circuit
Breaker Influence on TRV

TRV HV Circuit Breakers P 64


TRV Modification / Current Asymmetry

• When interrupting asymmetrical currents, TRV is less severe (lower


RRRV and TRV peak) than when interrupting the related
symmetrical current because the instantaneous value of the supply
voltage at the time of interruption is less than the peak value.

SUPPLY VOLTAGE

CURRENT

TIME

TRV HV Circuit Breakers P 65


TRV Modification / Current Asymmetry

• Correction factors of the TRV peak and rate of rise of recovery voltage
(RRRV) when interrupting asymmetrical currents are given in

− IEEE C37.081 “IEEE Guide for Synthetic Fault Testing of AC High-


Voltage Circuit Breakers Rated on a Symmetrical Current Basis”.

− IEEE C37.081a “Supplement to IEEE Guide for Synthetic Fault


Testing 8.3.2: Recovery Voltage for Terminal Faults; Asymmetrical
Short-Circuit Current”.

− IEC 62271-100 “High-Voltage Circuit-Breakers” (2012-09).

− IEC 62271-101 “Synthetic testing” (2012-10): Annex I

TRV HV Circuit Breakers P 66


TRV Modification / Current Asymmetry

• The RRRV is proportional to the slope of current before interruption


(di/dt). Factor F1 gives the correction due to current asymmetry:
D
F1  1  D  2

X /R
with D degree of asymmetry (p.u.)
-D interruption after a major loop of current
+D interruption after a minor loop of current
X/R short-circuit reactance divided by resistance
• When time to peak TRV is relatively short (< 500 µs), the correction
factor for the TRV peak is also F1.

TRV HV Circuit Breakers P 67


TRV Modification / Current Asymmetry

• Correction factor for the TRV peak in case of long time to peak TRV
(> 500 µs) :

TRV HV Circuit Breakers P 68


TRV Modification / Circuit Breaker Influence

• During current interruption, the circuit TRV can be modified by a


circuit breaker:
− by arc resistance,
− by the circuit breaker capacitance or opening resistor (if any).
• The TRV measured across the terminals of two different types of
circuit breakers under identical conditions can be different.
• To simplify both rating and application, the power system TRV is
calculated ignoring the influence of the circuit breaker.
The circuit breaker is considered to be ideal i.e. without modifying
effects on the electrical characteristics of a system,
− when conducting its impedance is zero,
− at current zero its impedance changes from zero to infinity.

TRV HV Circuit Breakers P 69


TRV Modification / Circuit Breaker Influence

• When a circuit breaker is fitted with grading capacitors or with line-to-


ground capacitors, these capacitors can reduce significantly the rate-
of-rise of TRV during short-line faults.
• Opening resistors (R) are used to assist interruption by air blast circuit
breakers, they are used on some SF6 circuit breakers (Japanese
550kV 1 break & 1100 kV 2 breaks).
The RRRV (rate of rise of
recovery voltage) is reduced
as follows
du Z  R di Z  R
  I 2
dt Z  R dt Z  R
The resistor (R) is in parallel
with the surge impedance of Air blast Generator Circuit Breaker
the system (Z). with opening resistor

TRV HV Circuit Breakers P 70


TRV Modification / Circuit Breaker Influence

Interruption with Opening Resistance

Arc extinction is facilitated by reducing the voltage stress (RRRV) after


current interruption, a parallel resistance is used for this purpose

TRV HV Circuit Breakers P 71


Terminal Fault TRV

GRID
Terminal fault TRV
First pole to clear factor

TRV HV Circuit Breakers P 73


Terminal Fault TRV

CURRENT

TRANSIENT RECOVERY
RECOVERY
VOLTAGE Current - TRV - Recovery Voltage VOLTAGE

TRV HV Circuit Breakers P 74


Terminal Fault TRV

• First Pole to Clear Factor (kpp)


− During 3-phase faults interruption, the recovery voltage is higher on
the first pole to clear.
− The first-pole-to clear factor is the ratio of the power frequency
voltage across the first interrupting pole, before current interruption
in the other poles, to the power frequency voltage occurring across
the pole after interruption in all three poles.
− It is the ratio between the recovery voltage (RV) across the first
pole to clear and the phase to ground voltage of the system.

Recovery Voltage
kpp 
Ur
3

TRV HV Circuit Breakers P 75


Terminal Fault TRV

• First Pole to Clear Factor (kpp)


Ur
Ur kpp 
3
3
A B
ER

ES

ET

TRV HV Circuit Breakers P 76


Terminal Fault TRV

• When tests are performed on one pole (single-phase tests), the supply
voltage must be multiplied by kpp in order to have the recovery voltage
that would be met on the first pole during a three-phase interruption.
• The first–pole–to-clear factor (kpp) is a function of the grounding
arrangements of the system and of the type of fault.

For systems with non-effectively grounded neutral, kpp is 1.5.


For three-phase to ground faults in systems with effectively grounded
neutral, kpp is 1.3 (see Annex A).

Note: for UHV systems (rated voltages 1100 & 1200kV) the ratio X0/X1
is close to 2 and the standardized value of kpp is 1.2.
• For three-phase ungrounded faults, kpp is 1.5.

TRV HV Circuit Breakers P 77


Terminal Fault TRV

Three-phase faults in non-effectively grounded systems


or three-phase ungrounded faults

In these cases, kpp is 1.5

TRV HV Circuit Breakers P 78


Terminal Fault TRV
Example of First-Pole-To-Clear Factor (kpp)

di
3-phase L eB  2 L  eC  0
dt
ungrounded fault L di e  eC
L  B
in effectively- i dt 2
grounded neutral L di e  eC
eP  eB  L  eB  B
i dt 2
e  eC
eP  B   0.5
When pole A 2
interrupts. e A  eP   1  (0.5)  1.5

voltage eA is
maximum = 1 p.u. First-pole-to-clear
eB = eC = - 0.5 p.u. factor is 1.5

TRV HV Circuit Breakers P 79


Terminal Fault TRV
Example of First-Pole-To-Clear Factor (kpp)

3-phase to ground fault in non-effectively grounded system


When the first pole interrupts:
A B
Voltage at neutral point N: ER
EN + ES = Xsc I 1 p.u. Xsc kpp= 1.5
ES
EN + ET = - Xsc I N
Xsc
EN = – (ES + ET)/2
ER is maximum = Emax cos(0°) = 1 p.u.
ET Xsc
ES = Emax cos (120°) = -0.5 p.u.
ET = Emax cos (240°) = -0.5 p.u.
then EN = 0.5 p.u.
Voltage EA = EN + ER = 1.5 p.u.

First-pole-to-clear factor is 1.5

TRV HV Circuit Breakers P 80


Terminal Fault TRV
First-Pole-To-Clear Factor (kpp)

Single-phase fault in an effectively grounded system

• In this case, kpp is 1.0 as the circuit breaker interrupts under the phase-
to-ground voltage.

I3 V3
E

I2 V2

I1 V1

TRV HV Circuit Breakers P 81


Terminal Fault TRV
First-Pole-To-Clear Factor (kpp)

Three-phase to ground fault in effectively


grounded neutral systems
• The value of kpp is dependent upon the sequence impedances from the
location of the fault to the various system neutral points (ratio X0/X1).

3X 0
k pp 
X1  2X 0
where X0 is the zero sequence reactance of the system,
X1 the positive sequence reactance of the system.
For systems up to 800 kV, the ratio X0/X1 is taken to be  3.0.
Hence, for systems with effectively grounded systems kpp is 1.3.

TRV HV Circuit Breakers P 82


Terminal Fault TRV
Pole-To-Clear Factor

Equations for the other clearing poles


• In systems with non-effectively grounded neutral, after interruption of
the first phase (R), the current is interrupted by the last two poles in
series under the phase-to-phase voltage (ES – ET) equal to 3 times
the phase voltage
ER

ES

ES - ET I

ET
I

TRV HV Circuit Breakers P 83


Terminal Fault TRV
Pole-To-Clear Factor

It follows that, in systems with non-effectively grounded neutrals,


for the second and third pole to clear:
After interruption of the
3 3 poles, the recovery
k pp   0.87 voltage is 1 p.u.
2

Current in each phase TRV in each phase

TRV HV Circuit Breakers P 84


Terminal Fault TRV
Pole-To-Clear Factor

In systems with effectively grounded neutrals, the second pole clears


a three-phase to ground fault
with a factor 3 X 02  X 0 X 1  X 12
k pp  See Annex B
X 0  2X1
If X0 / X1 = 3.0 the second pole to clear factor is 1.25.

Currents TRVs

TRV HV Circuit Breakers P 85


Terminal Fault TRV
Pole-To-Clear Factor

In systems with effectively grounded neutral, for the third pole-to-


clear:
k pp  1
I3 V3
E

I2 V2

I1 V1

TRV HV Circuit Breakers P 86


Terminal Fault TRV
Pole-To-Clear Factor

Pole-to-clear factors (kp) for each clearing pole


3-phase to ground case
Neutral X0/X1 Pole to clear factor

first pole 2nd pole 3rd pole

isolated infinite 1.5 0.87 0.87

effectively
3.0 1.3 1.27 1.0
grounded
see note 1.0 1.0 1.0 1.0

Note: values of the pole-to-clear factor are given for X0/X1 = 1.0 to
indicate the trend in the special case of networks with a ratio X0/X1 of
less than 3.0.
kpp= 1.5 is taken for all systems that are not effectively grounded, it
includes (but is not limited to) systems with isolated neutral (it is also
taken for three-phase ungrounded faults).
TRV HV Circuit Breakers P 87
Terminal fault TRV
Rating & Testing

TRV HV Circuit Breakers P 88


Terminal Fault TRV Rating

Current
CURRENT

SupplySupply
voltage
voltage

Transient recovery
TRANSIENT RECOVERY
voltage
VOLTAGE

TRV HV Circuit Breakers P 89


Terminal Fault TRV Rating

• The TRV ratings for circuit breakers are applicable for interruption
of three-phase faults with
− a rated symmetrical short circuit current
− at the rated voltage of the circuit breaker.
• In IEC
− While three-phase ungrounded faults produce the highest TRV
peaks, the probability of their occurrence is very low.
Therefore, in IEC 62271-100 the TRV ratings are based on
three-phase to ground faults.
− TRV parameters are given in subclause 4.102 of IEC 62271-
100.
− For values of fault current other than rated and for line faults,
related TRV capabilities are given in subclause 6.104.5 of IEC
62271-100.

TRV HV Circuit Breakers P 90


Terminal Fault TRV Rating

• In ANSI/IEEE
− TRV withstand capabilities are given in ANSI/IEEE C37.04 and
IEEE C37.06.
− In the case of terminal faults, for circuit-breakers of rated
voltages equal or higher than 100 kV, separate Tables give
TRVs for three-phase to ground and three-phase ungrounded
faults.

TRV HV Circuit Breakers P 91


Terminal Fault TRV Rating

• ANSI/IEEE C37.06 – Table 10

TRV HV Circuit Breakers P 92


Terminal Fault TRV Rating

• ANSI/IEEE C37.06 – Table 11

TRV HV Circuit Breakers P 93


Terminal Fault TRV Rating

• For circuit breakers applied on systems 72.5 kV and below, the TRV
ratings assume that the system neutrals can be non-effectively
grounded.
• For circuit breakers applied on systems 245 kV and above, the TRV
ratings assume that the system neutrals are effectively grounded.

• Standard TRV are defined by two-parameter and four-parameter


envelopes.
• These envelopes are used to compare
− System TRVs
− Standard TRVs
− Test TRVs

TRV HV Circuit Breakers P 94


Terminal Fault TRV Rating

• A two-parameter envelope is used for oscillatory (underdamped)


TRVs specified in standards for:
− circuit breakers rated less than 100 kV, at all values of breaking
current,
− circuit breakers rated 100 kV and above if the short-circuit
current is equal or less than 30% of the rated breaking current.

Ur
uc   2  k pp  k af
3
u '  uc / 3

t d  0.15 t3 (Class S1, cable  systems)


t d  0.05 t3 (Class S 2, line  systems)

The test TRV must not cross the


delay segment defined by (td , 0)
and (t’, u’)

TRV HV Circuit Breakers P 95


Terminal Fault TRV Rating

• A four-parameter envelope is specified for circuit breakers rated 100 kV


and above if the short-circuit current is more than 30% of the rated
breaking current (cases with over-damped TRVs).

Ur Ur
u1   2  k pp  0.75 uc   2  k pp  k af u '  u1 / 2 t 2  4 t1
3 3
TRV HV Circuit Breakers P 96
Terminal Fault TRV Rating

The peak value of TRV is defined as follows:

Ur
U c  k af  k pp  2 
3
where
kpp is the first pole to clear factor

kaf is the amplitude factor (ratio between the peak value of TRV and
the peak value of the recovery voltage at power frequency).
In IEC 62271-100 and IEEE C37.04, kaf is 1.4 at 100% rated breaking
current.

TRV HV Circuit Breakers P 97


Terminal Fault TRV Rating - Ur < 100 kV

TRV envelopes for terminal fault (Ur < 100 kV)


VOLTAGE

0.1 I
0.3 I
0.6 I 1.0 I

TIME
I is the rated short-circuit current

TRV HV Circuit Breakers P 98


Terminal Fault TRV Rating - Ur < 100 kV

• Cable systems and line systems


In order to cover all types of networks (distribution, industrial and sub-
transmission) and for standardization purposes, two types of systems
are introduced:
− Cable systems
Cable systems have a TRV during breaking of terminal fault at
100% of short-circuit breaking current that does not exceed the
envelope derived from Table 24 in Edition 1.2 of IEC 62271-100.
TRV values are those defined in the former editions of IEC
standard for high-voltage circuit breakers.
− Line systems
Line systems have a TRV during breaking of terminal fault at 100%
of short-circuit breaking current defined by the envelope derived
from Table 25 in Edition 1.2 of IEC 62271-100. Standard values of
TRVs for line systems are those defined in ANSI/IEEE C37.06 for
outdoor circuit-breakers.
TRV HV Circuit Breakers P 99
Terminal Fault TRV Rating - Ur < 100 kV

• Comparison of TRVs for cable systems and line-systems

Envelope of Envelope of
Line system TRV Cable system TRV
Uc

t3

The rate of rise of recovery voltage (RRRV) for line


systems is approximately twice the value for cable systems

TRV HV Circuit Breakers P 100


Terminal Fault TRV Rating - Ur < 100 kV

• Classes of Circuit breakers


Circuit breaker Ur < 100 kV

ClassCS
Class S1 SLF ?
Cable-system No

Class
Class S2
LS Direct connection
Line-system to OH line Yes

Direct connection
Cable-system
to OH line Yes
Class S2
Class LS
Short-line fault breaking performance is required only for class S2

TRV HV Circuit Breakers P 101


Terminal Fault TRV Rating - Ur < 100 kV

Amplitude factor for terminal fault (Ur < 100 kV)


Class S2 circuit breakers
1,9

1,8

1,7
Amplitude factor (p.u.)

1,6

1,5

1,4

1,3

1,2
T10 T30 T60 T100

10% I 30% I 60% I 100% I


TRV HV Circuit Breakers P 102
Terminal Fault TRV Rating - Ur < 100 kV

RRRV for terminal fault T100 (Ur < 100 kV)


Class S2 circuit breakers
1,6

RRRV 1.47 72.5kV

(kV/µs) 1,4
1.33

1.21 52kV
1,2

1.05 38kV
1
0.91 24kV
15kV
0,8

0,6

Ur
0,4
12,5 22,5 32,5 42,5 52,5 62,5 72,5
(kV)

TRV HV Circuit Breakers P 103


Terminal Fault TRV Rating - Ur < 100 kV

• Calculation of standard RRRV: circuit breaker 72.5 kV class S2


− Time to peak TRV was taken from ANSI C37.06: T2  106 µs

− Time t3 is 88% of T2 (1-COS waveshape): t3 = 93 µs

− TRV peak uc is calculated from Ur, kpp and kaf

72.5 2
uc  1.5  1.54   137 kV
3
137
− RRRV is the ratio of uc and t3 : VATR   1.47 kV / µs
93
it is the present value in IEC and IEEE standards.

TRV HV Circuit Breakers P 104


Terminal Fault TRV Rating - Ur < 100 kV

RRRV for terminal fault T100 (Ur < 100 kV)


Class S2 circuit breakers
1,6

RRRV 1.47 72.5kV

(kV/µs) 1,4
1.33

1.21 52kV
1,2

1.05 38kV
1kV/µs 1
0.91 24kV
15kV
0,8

RRRV  0.4  U r0.305


0,6

20kV Ur
0,4
12,5 22,5 32,5 42,5 52,5 62,5 72,5
(kV)

TRV HV Circuit Breakers P 105


Terminal Fault TRV Rating - Ur < 100 kV

• RRRV at reduced short-circuit current (Class S2)


− Time t3 for T100 is multiplied by the following factors
0.67 for T60
0.40 for T30 and T10
− Compared with the standard value for T100, the RRRV at
reduced short-circuit current is divided by the multiplier for time
t3 and multiplied by the increase of amplitude factor.
− Example: T60 72.5 kV
1.47 1.65
RRRV    2.35 kV / µs
0.67 1.54

TRV HV Circuit Breakers P 106


Terminal Fault TRV Rating - Ur ≥ 100 kV

TRV envelopes for terminal fault (Ur  100 kV)

I is the rated short-circuit current


Note: time to peak for T60 is shown here according to IEEE, it is half the IEC value
TRV HV Circuit Breakers P 107
Terminal Fault TRV Rating - Ur ≥ 100 kV

Amplitude factor for terminal fault (Ur  100 kV)


according to IEC and IEEE C37.06
1,8
kaf (p.u.) IEC & IEEE k pp=1.3
1,7

1,6

1,5
IEEE k pp=1.5
1,4

1,3

1,2

1,1

1
10 20 30 40 50 60 70 80 90 100 % Isc
Case 10 % Isc: kpp x kaf = 2.46 (IEEE kpp=1.5) and 2.29 (IEC & IEEE kpp=1.3)

TRV HV Circuit Breakers P 108


Terminal Fault TRV Rating - Ur ≥ 100 kV

Rate-of-rise-of-recovery-voltage for terminal fault


(Ur  100 kV)
8

6
RRRV (kV/µs)

1
T10 T30 T60 T100

TRV HV Circuit Breakers P 109


Terminal Fault TRV
Application

• A circuit breaker TRV capability is considered to be sufficient if the two


or four parameter envelope drawn with rated parameters is equal or
higher than the two or four parameter envelope of the system TRV.

Voltage

System TRV envelope

Circuit breaker rated TRV envelope

time

TRV HV Circuit Breakers P 110


Terminal Fault TRV
Application

• The parameters that define the circuit breaker TRV capabilities vary
with the circuit breaker voltage rating and short-circuit current
interrupting level.
• The circuit breaker TRV capabilities at 10%, 30%, 60% and 100% of
rated short-circuit interrupting current (Isc), corresponding to terminal
fault test duties T10, T30, T60 and T100, are given in IEEE Std
C37.06.
• The circuit breaker TRV withstand capability envelope at any other
short-circuit interrupting current below rated can be derived using the
multipliers given in Table 1 of IEEE C37.011-011.
• TRV studies are sometimes carried out to determine if a system TRV
is covered by the circuit breaker TRV capability demonstrated by type
tests, either when new circuit breakers are to be installed or following
a system change.

TRV HV Circuit Breakers P 111


Terminal Fault TRV
Application

• It is not uncommon that the maximum short-circuit current falls in


between 30% and 60% of the circuit breaker rated short-circuit current.
• To allow comparison of system TRV and circuit breaker TRV withstand
capability and to avoid additional testing, a method of interpolation of
TRV capabilities demonstrated by type tests was introduced in the
former editions of IEEE C37.011.
• Following the introduction of the two-parameter and four-parameter
description of TRVs, this method of interpolation in the current range
between T30 and T60 (terminal faults with respectively 30% and 60%
of Isc) was not clearly stated in the 2005 edition of IEEE C37.011.
• Thus, the method of interpolation has been further developed in IEEE
C37.011-2011 to define the circuit breaker TRV withstand capability for
short-circuit currents in this range between T30 and T60.

TRV HV Circuit Breakers P 112


Terminal Fault TRV
Application

• In standards, it is considered that 30 % of Isc is the maximum short-


circuit current for which a two parameter TRV is applicable for circuit
breakers rated 100 kV and above.

• The related TRV capability for short-circuit currents between 30 % of Isc


and 60 % of Isc is then necessarily a four parameter TRV.

• The Working Group in charge of IEEE Guide C37.011 has defined that
the TRV capability between T30 and T60 can be considered to have a
rate-of-rise (u1/t1) and a first reference voltage (u1) that have
intermediate values between those of T30 and T60.

TRV HV Circuit Breakers P 113


Terminal Fault TRV
Application

• TRV parameters (u1, t1, uc, t2) for any terminal fault current between
30 % and 60 % of Isc can be obtained as follows:

− u1 and t1 are linearly interpolated between u1 and t1 of T60 and uc


and t3 of T30

− uc and t2 are linearly interpolated between uc and t2 of T60 and uc


and t3 of T30

• The method of interpolation is illustrated by the Figure shown on the


next slide.

TRV HV Circuit Breakers P 114


Terminal Fault TRV
Application

245kV Breaker TRV Envelope
500

450 T100

T75
400
T60
350 T55

T50
300
T45
kV

250 T40
T35
200
T30

150 T10
u1,t1
100

50

0
0 50 100 150 200 250

Time (µs)

Example of TRV interpolation for a 245kV circuit breaker


TRV HV Circuit Breakers P 115
Terminal Fault TRV
Application
* When the system TRV has an initial slope that is higher than the value
specified for terminal fault type tests, Guide IEEE C37.011 authorizes
to combine the TRV withstands demonstrated during terminal fault and
short-line-fault (same range of currents).

Voltage withstand by a 550kV circuit breaker at 75% rated breaking capability

TRV HV Circuit Breakers P 116


Terminal Fault TRV
Testing

• Tests are required at 100% (T100), 60% (T60), 30% (T30) and 10%
(T10) of rated short-circuit current with the corresponding rated TRVs
and recovery voltages.
• In IEC 62271-100, 3 tests are required with a symmetrical current for
each test duty, except T100 that is performed as follows
− 3 tests with symmetrical current and
− 3 tests with asymmetrical current (when interrupting asymmetrical
currents, the rate-of-rise and peak value of TRV are reduced but the
energy in the arc is higher).
• In IEEE Std C37.09
− for each test duty T10, T30, T60: 2 tests are required with
symmetrical current and 1 test with asymmetrical current.
− test duty T100 is performed as in IEC

TRV HV Circuit Breakers P 117


Terminal Fault TRV
Testing

• During testing, the envelope of the test TRV (in red) must be equal or
higher than the specified TRV envelope (in blue).
U
(kV) A C
Envelope of prospective test TRV
uc
Prospective test TRV

B
u1
Reference line of specified TRV

u'

Delay line of specified TRV

0 td t' t1 t2 t (µs)

This procedure is justified as it allows to compare TRVs in the two


regions where a restrike is likely: during the initial part of the TRV where
the RRRV is maximum and in the vicinity of the peak voltage (uc).

TRV HV Circuit Breakers P 118


Terminal Fault TRV
Initial TRV

• In a network, the initial part of the TRV may have a high-frequency


oscillation of small amplitude.
• This ITRV (Initial Transient Recovery Voltage) is due to reflections
from the first major discontinuity along the busbar.
• It may influence the thermal phase of interruption.
• In most cases the ITRV withstand capability is proven during short-line-
fault tests.

More information is given in the chapter dedicated to ITRV

TRV HV Circuit Breakers P 119


Terminal fault
TRV & Arcing Times

TRV HV Circuit Breakers P 120


Terminal Fault TRV & Arcing Time

Arcing time
1,5

Contacts separation
1

Current Interruption at 2nd


passage through zero
0,5

Arcing time = 13 ms

0 0,005 0,01 0,015 0,02 0,025 0,03 0,035 0,04 0,045 0,05

Time
-0,5

1st passage
through zero
-1

-1,5

TRV HV Circuit Breakers P 121


Terminal Fault TRV & Arcing Times

In the case of periodic 1,5

phenomena, durations
can be expressed in 1

milliseconds or in
electrical degrees. 0,5 10 ms
For a system frequency
of 50 Hz, the duration of 0

0 0,002 0,004 0,006 0,008 0,01 0,012 0,014 0,016 0,018 0,02
one half loop is 10 ms, it
corresponds to 180° el., it -0,5

follows that 18° el. = 1ms


For a system frequency -1

of 60 Hz the duration of
one half loop is 8.33 ms -1,5

so 18° el. = 0.83 ms One period at 50 Hz

TRV HV Circuit Breakers P 122


Terminal Fault TRV & Arcing Times

Current

Arcing time
1st pole

Arcing time
last poles

One period (360°) at 60Hz is 16.7 ms last poles


Contacts 1st pole
One period (360°) at 50Hz is 20 ms separation clears clear
TRV HV Circuit Breakers P 123
Minimum & Maximum Arcing Times

• Case 1: Reference case with contact separation at 29.67ms

Example
three-phase
fault
interruption
Fr = 50 Hz

Pole 3
interrupts first

Arcing time
pole 3 = 8.4ms
(minimum arcing
time)

System with non-effectively grounded neutral


TRV HV Circuit Breakers P 124
Minimum & Maximum Arcing Times

• Case 2: Contact separation advanced by 3.33ms (60°) = 26.34ms

Arcing time
pole 1 = 8.4ms

Pole 1 interrupts
first with the same
arcing time as in
Case 1 by pole 3
i.e. same breaking
conditions in
terms of arcing
times

TRV HV Circuit Breakers P 125


Minimum & Maximum Arcing Times

• Case 3: Contact separation advanced by 2.33ms (42°) = 27.34ms


Arcing time pole 1
= 15.7ms
= 8.4ms + 7.3ms
= 8.4ms + 132°
maximum arcing
time
Pole 3 interrupts
first with the
longest arcing
time for a first
pole to clear
Arcing time
pole 3 = 10.7ms
= 8.4ms + 42°
The range of arcing times for the first pole to clear is 42°
TRV HV Circuit Breakers P 126
Minimum & Maximum Arcing Times

Three-phase faults in non-effectively


grounded systems or three-phase Example with fr = 50 Hz
ungrounded faults
20000
tarc min = 12 ms

10000

Iarc
0

Contact separation
Current (A)

-10000

18°
-20000

Iarc
-30000

Contact separation
-40000

tarc max = 19,33 ms


-50000

0 5 10 15 20 25 30 35 40
Time (ms)

TRV HV Circuit Breakers P 127


Minimum & Maximum Arcing Times (50Hz)

time [ms] Three-phase faults in non-


effectively grounded systems or
0 5 10 15 20 25 30 35 40
20000

Tmin = 12 ms
15000 three-phase ungrounded faults
10000
Minimum arcing time (blue
5000
Iarc phase) Tmin = 12 ms
current [A]

-5000 Contact Contact separation delayed


separation
-10000 by 18° el.
-15000 18° el. (or 1 ms)
-20000

0 5 10 15
time [ms]
20 25 30 35 40
Arcing time 1st phase (red
20000
phase) = 14.33 ms
15000
(Tmin + 60° - 18°
10000
= Tmin + 42°)
5000
Iarc Maximum arcing time (blue
current [A]

-5000
phase) = 19.33 ms
Contact
-10000 separation (14.33 ms + 90°
-15000
= Tmin + 132°)
T max = 19.33 ms
-20000

TRV HV Circuit Breakers P 128


Minimum & Maximum Arcing Times (60Hz)

Three-phase faults in non-


time [ms]
0 5 10 15 20 25 30 35 40

effectively grounded systems or


20000

Tmin = 12 ms
15000
three-phase ungrounded faults
10000

5000 Minimum arcing time (blue


Iarc
current [A]

0 phase) Tmin = 12 ms
-5000 Contact
-10000
separation Contact separation delayed
by 18° el.
-15000
18° el.
-20000
(or 0.83 ms)
0 5 10 15
time [ms]
20 25 30 35 40
Arcing time 1st phase (red
20000
phase) = 13.94 ms
15000
(Tmin + 60° - 18°
10000
= Tmin + 42°)
5000
Iarc
current [A]

0 Maximum arcing time


-5000 (blue phase) = 18.1 ms
Contact
-10000 separation (13.94 ms + 90°
-15000
T max = 18.1 ms
= Tmin + 132°)
-20000

TRV HV Circuit Breakers P 129


Terminal Fault Arcing times
Three-Phase Short-Circuit Current Interruption

Three-phase fault in network with isolated neutral (Ur < 245kV)

Current
A B
ER

ES

ET
Contact
separation
Time
Interruption of current in a first pole, followed ¼ cycle later by
interruption of the two other poles in series

Breaking Tests HV Circuit-Breakers – Denis Dufournet


Terminal Fault Arcing Times
Three-Phase Short-Circuit Current Interruption
Three-phase fault in network with effectively grounded
neutral (Ur ≥ 245kV)
Voltages Currents

A B
ER

ES

ET

Contact
separation

The three poles interrupt at separate current zeros with


different arcing times

Breaking Tests HV Circuit-Breakers – Denis Dufournet


Arcing Times and TRVs / Fr = 60 Hz

Three-phase faults in
0.87 non-effectively grounded
systems or three-phase
90° ungrounded faults

Maximum arcing time


0.87 = Tmin + 132°
1.5 = Tmin + 6.1 ms

Currents TRVs (pole factor)


Three-phase faults in
1.27 effectively grounded
systems
120°
Maximum arcing time
= Tmin + 162°
= Tmin + 7.5 ms
1.3 1.0
TRV HV Circuit Breakers P 132
Arcing Times and TRVs / Fr = 50 Hz

Three-phase faults in
0.87 non-effectively grounded
systems or three-phase
90° ungrounded faults

Maximum arcing time


0.87 = Tmin + 132°
1.5 = Tmin + 7.3 ms

Currents TRVs (pole factor)


Three-phase faults in
1.27 effectively grounded
systems
120°
Maximum arcing time
= Tmin + 162°
= Tmin + 9 ms
1.3 1.0
TRV HV Circuit Breakers P 133
Terminal Fault TRV & Arcing Times

Pole to clear factor

Arcing time
° el.

Reference = Minimum arcing time first pole Minimum arcing time + 180° -18°
TRV HV Circuit Breakers P 134
Terminal Fault TRV & Arcing Times at 60Hz

Pole to clear factor Arcing times in ms FR = 60 Hz

Arcing time
° el.
0 1.95 3.55 4.15 5.5 6.1 7.5 ms
5.55
Reference = Minimum arcing time first pole to clear
TRV HV Circuit Breakers P 135
Terminal Fault TRV & Arcing Times

Single-phase "umbrella" test with


Pole to clear factor kpp=1.3

Increased
stress

° el.

Reference = Minimum arcing time first pole Minimum arcing time + 180° -18°
TRV HV Circuit Breakers P 136
Terminal Fault TRV & Arcing Times

1,5

Contacts separation

Current
0,5

Single-phase tests
Minimum arcing time
= 13 ms

with minimum &


0

0 0,005 0,01 0,015 0,02 0,025 0,03 0,035 0,04 0,045 0,05

Time

maximum arcing time


-0,5

-1

-1,5
1,5

Contacts separation

Current
Mximum arcing time = 22 ms
0,5
= 13 ms + 10 ms - 1 ms
= 13ms + 180° el. - 18° el.

0 0,005 0,01 0,015 0,02 0,025 0,03 0,035 0,04 0,045 0,05

Example with F=50Hz -0,5


Time

restrike with arcing


time 12 ms

-1

-1,5

TRV HV Circuit Breakers P 137


Terminal Fault TRV
Generator Circuit Breakers

TRV HV Circuit Breakers P 138


Generator Circuit Breakers TRV

• Special TRV requirements are applicable for generator circuit breakers


installed between a generator and a transformer.

• Two types of faults need to be considered


A1 System-source fault B1 Generator-source fault

TRV HV Circuit Breakers P 139


Generator Circuit Breakers TRV

• For the two types of fault, the TRV has an oscillatory waveshape and
the first-pole-to-clear factor is 1.5 in order to cover three-phase
ungrounded faults.
• TRV parameters, i.e. peak voltage uc, rate-of-rise (RRRV) and time
delay, are listed in ANSI/IEEE C37.013.
TRV for system-source faults
• RRRV for system-source faults is 3 to 5 times higher than the value
specified for distribution or sub-transmission circuit breakers ANSI/IEEE
C37.04.
This is due to the fact that the TRV frequency is dominated by the
natural frequency of the step-up transformer.
• IEEE has defined TRV parameters in several ranges of transformer
rated power.

TRV HV Circuit Breakers P 140


Generator Circuit Breakers TRV

• TRV parameters for System-Source Faults


Table 5a– TRV parameters for system - source faults

Inherent TRV
Transformer
Rating T2 -Time to - Peak E2 -Peak Voltage TRV Rate
(MVA) (µs) (kV) (kV / µs)
Line Column 1 Column 2 Column 3 Column 4
1 10 - 50 0.68 V 1.84 V 3.2
2 51 - 100 0.62 V 1.84 V 3.5
3 101 - 200 0.54 V 1.84 V 4.0
4 201 - 400 0.48 V 1.84 V 4.5
5 401 - 600 0.43 V 1.84 V 5.0
6 601 - 1000 0.39 V 1.84 V 5.5
7 1001 or more 0.36 V 1.84 V 6.0

TRV HV Circuit Breakers P 141


Generator Circuit Breakers TRV

• TRV for system-source faults (Cont’d)


In IEEE C37.013-1993, the WG introduced time t3 (coming from IEC) to
define precisely the determination of the TRV rate.

E2 is equal to 1.84 V where V is


the rms value of the rated
maximum voltage and the value
1.84 is equal to
2 x 1.5 (= first-pole-to-clear-
3
factor) x 1.5 (= amplitude factor)

t3 E2
T2  
0.85 0.85  TRV rate

TRV HV Circuit Breakers P 142


Generator Circuit Breakers TRV

TRV for system-source faults (Cont’d)


• The RRRV can be significantly reduced if a capacitor is installed
between the circuit breaker and the transformer. It is also reduced in
the special cases where the connection between the circuit breaker
and the transformer(s) is made by cable(s) [29].
TRV RATE FOR SYSTEM FED FAULTS TRANSFORMER 50MVA<<=100MVA

3,6

3,4

3,2
TRV RATE (kV/µs)

81MVA
100MVA
2,8

2,6

65,5MVA
2,4

2,2

2
0 2000 4000 6000 8000 10000 12000

CABLE CAPACITANCE (pF)

TRV HV Circuit Breakers P 143


Generator Circuit Breakers TRV

TRV for system-source faults (Cont’d)


• When a capacitance is added between the circuit breaker and the
step-up transformer, the TRV peak is increased (explanation: see
general considerations).
E2 MULTIPLIER FOR SYSTEM FED FAULTS TRANSFORMER 50MVA<<=100MVA

TRV peak 1,3

increase (p.u.)
1,25
65.5 MVA
E2 MULTIPLIER (p.u.)

1,2
81 MVA

1,15

100 MVA

1,1

1,05
Capacitance
1 (pF)
0 2000 4000 6000 8000 10000 12000
CABLE CAPACITANCE (pF)

TRV HV Circuit Breakers P 144


Generator Circuit Breakers TRV

• TRV for generator-source faults


RRRV for generator-source faults is roughly 2 times the values
specified for distribution or sub-transmission circuit breakers.
“Table 6a – TRV parameters for generator - source faults

Inherent TRV
Generator
Rating T2 -Time - to – Peak E2 -Peak Voltage TRV Rate
(MVA) (µs) (kV) (kV / µs)
Line Column 1 Column 2 Column 3 Column 4
1 10 - 50 1.44 V 1.84 V 1.5
2 51 - 100 1.35 V 1.84 V 1.6
3 101 - 400 1.20 V 1.84 V 1.8
4 401 - 800 1.08 V 1.84 V 2.0
5 801 or more 0.98 V 1.84 V 2.2

TRV HV Circuit Breakers P 145


Generator Circuit Breakers TRV

• TRV in case of asymmetrical currents


− Due to the large time constants of generators and transformers
(high X/R), generator circuit breakers are required to interrupt
currents with a high percentage of dc component (high asymmetry).
− The rate-of rise and peak value of TRV during interruption of
currents with large asymmetry are significantly reduced.
− In this case, the stress is mainly due to the current amplitude and
the energy in the arc (mechanical and thermal stresses), and to a
lesser extent to the TRV.
− The more severe TRV stress is obtained during interruption of
symmetrical currents.

TRV HV Circuit Breakers P 146


Terminal Fault TRV / Summary

• First-pole-to-clear factor
− Effectively earthed systems kpp = 1.3 (1.2 for UHV)
− Non-effectively earthed systems kpp = 1.5
• Rating
− TRV with 2 or 4 parameters
− Classes S1 and S2 for rated voltages < 100 kV
• Testing circuit breakers ≥ 100 kV
− RRRV: 7 – 5 – 3 – 2 kV/µs for resp. T10, T30, T60, T100s
− Interrupting window: 162° (kpp = 1.3) or 132° (kpp = 1.5)
• Generator circuit breakers higher RRRV for T100s

TRV HV Circuit Breakers P 147


Short-Line-Fault (SLF)

TRV HV Circuit Breakers P 148


Introduction

• The severity of SLF with its associated very fast rate-of-rise-of-


recovery-voltage (RRRV) was identified at the end of the 1950’s.
• First SLF tests were performed in 1956-1958 in the USA (G.E.), also
at Mettlen substation (CH), Fontenay (EDF High Power Laboratories)
and CESI. The aim was to compare theoretical studies and
experiments.
• The first published paper on SLF is considered to be by W.F. Skeats,
C.H. Titus, W.R. Wilson (G.E.) in Transactions AIEE, submitted in
April 1957 and published in February 1958.
• In Europe, a paper by Michel Pouard (EDF) was published in the
Bulletin de la Société Française des Electriciens in Nov. 1958.

TRV HV Circuit Breakers P 149


Introduction

Paper in Power Apparatus and Test laboratory line used by General


Systems, Part III, Transactions of Electric in 1957 to test air-blast
the American Institute of circuit-breakers. It was 1.6km long,
Electrical Engineers. Publication short-circuit power of the source was
in February 1958 50kA under 31kV.

TRV HV Circuit Breakers P 150


Introduction

• During the general meetings of CIGRE, SLF was first mentioned


during the session of 1958.
Two reports were presented during the CIGRE session of 1960 (by
France and Switzerland).
• IEC introduced for the first time short-line-fault (SLF) requirements
in 1971.
• SLF TRVs were introduced also in ANSI/IEEE C37.072 in 1971.

TRV HV Circuit Breakers P 151


Introduction

• The requirement of a SLF interrupting capability had and still has a


great influence on the design of high-voltage circuit breakers.
It was already the case with air blast type that had to be fitted with
opening resistors for SLF interruption.
• SLF is also a critical test duty for SF6 type circuit breakers.
Sufficient pressure build-up and mass flow rate are necessary for SF6
circuit breakers to interrupt at current zero.

TRV HV Circuit Breakers P 152


Short-Line-Fault (SLF)

• Short-line faults occur from a few hundred meters up to several


kilometers down the line.
− L90: short-line fault with 90% of rated short-circuit current
− L75: short-line fault with 75% of rated short-circuit current
• After current interruption, the line-side voltage exhibits a characteristic
triangular waveshape.

line

Circuit breaker
TRV, neglecting the contribution from
the supply-side
TRV HV Circuit Breakers P 153
Short-Line-Fault (SLF)

• The circuit-breaker interrupts the current, at a passage through zero,


the supply voltage and the di/dt are both maximum (in amplitude). The
voltage on the circuit-breaker terminals (U0) is a fraction of the supply
voltage Us0.
LS At the time of interruption
LL
Us0 = (LS + LL ) di/dt
line U0 = LL di/dt
Us0 U0
where di/dt is the current
derivative at current zero
Supply side
Voltage (point B) Example Ur = 245kV
Ur 2
U s0   200 kV
3
U0  90 
L90 : U 0  U s 0 1    20 kV
Line side  100 
Voltage (point C)
TRV HV Circuit Breakers P 154
Short-Line-Fault (SLF)

• As the TRV is at high frequency, the line must be treated as a


transmission line with distributed elements.
• The line side voltage oscillates as travelling waves are transmitted with
positive and negative reflections at the open breaker and at the fault,
respectively.

After current interruption


The supply voltage varies
much more slowly than the
line-side voltage Supply side
voltage (point B)
The TRV is mainly due to the
voltage variation on the line
side.
Line-side
voltage (point C)
TRV HV Circuit Breakers P 155
Short-Line-Fault (SLF)

• Supply-side and line-side voltages

Current

Supply-side voltage

Um

t
U=0 Uo
UL Line-side voltage

Um: supply voltage at the time of interruption


Uo: voltage on circuit breaker terminals at the time of interruption
Example L75: Ur = 245kV : Um= 200 kV, Uo= 50 kV, UL= 80 kV

TRV HV Circuit Breakers P 156


SLF / Evolution of Line Voltage

Voltage profile at current zero (t=0),


Voltage decreases linearly towards 0 at the fault point
It is considered to be sum of two voltage waves moving in opposite directions.
TL = Travel time for wave to travel from one end of line to the other and back.

TRV HV Circuit Breakers P 157


SLF / Evolution of Line Voltage

Traveling waves that


reach the fault point are
reflected with an opposite
polarity.

Traveling waves that


reach the open point, at
the circuit breaker
terminal, are reflected
with the same polarity.

Voltage at any location


on the line is the sum of
each component.

TRV HV Circuit Breakers P 158


SLF / Evolution of Line Voltage

TRV HV Circuit Breakers P 159


SLF / Evolution of Line Voltage

Voltage on the line after current interruption


VOLTAGE (p.u.)
2

tL/4 0.5 tL 3 tL/4 tL 1.5 tL


0
TIME

Voltage at x = 0.75 L

Voltage half-way
to the fault x = 0.5 L Voltage at circuit-breaker
-2 Terminal x = 0

TRV HV Circuit Breakers P 160


SLF / Evolution of Line Voltage

Voltage on Circuit Breaker line-side terminal


Line side Voltage
(p.u.)
1,5

0,5

0
0 0,25 0,5 0,75 1 1,25 1,5 1,75 2

-0,5

-1

-1,5

Time / TL

Damping is neglected, in practice at time TL voltage is -0.6 to -0.8 p.u.


TRV HV Circuit Breakers P 161
SLF TRV

Voltage (kV)

TRV Supply voltage

Line voltage

Time (µs)

TRV HV Circuit Breakers P 162


SLF / RRRV

• The rate-of-rise of recovery voltage (RRRV) on the line side is function


of the slope of current before interruption and of the surge impedance
of the line:
du di
RRRV  Z ZI 2sI
dt dt

L
Z Z is the surge impedance of the line (450 ohm)
C

L and C are respectively the self inductance and the capacitance of the
line per unit length
I fault current (kA)
at 50 Hz Z  2  0.2 10 6
ω pulsation
s multiplier = 0.20 (f = 50Hz) or 0.24 (f = 60 Hz), du/dt in kV/µs

TRV HV Circuit Breakers P 163


SLF / Line Surge Impedance

• Assumptions: conductors of infinite length, the electrical field and magnetic field
do not penetrate the ground.
• Self surge impedance
D = 2 h with h = height of line r = radius of conductor
Ln = natural logarithm µ0 = magnetic constant = 4π×10−7 H/m

= electric constant = 8.854×10−12 F/m

L D  2h
with
Z  60 Ln    60 Ln   (1)
C  
r  r 
• Mutual surge impedance (ZM) between 2 conductors is given by (1) where D is
the distance between one conductor and the image of the other conductor, and r
represents the distance between the two conductors (see next slide).
• A matrix equation is done in case of multi-conductors circuits with self and
mutual couplings. Modal analysis done by digital calculations gives the relevant
modes of travelling waves (see Annex C in [39] and [47]).
TRV HV Circuit Breakers P 164
SLF / Line Surge Impedance

• Distances to consider for mutual surge impedance calculation

d12 Bundle 2

Bundle 1 Bundle 3

D12

Ground

D 
Z M 12  60 Ln  12 
 d12 
Image of bundle of conductors 2

TRV HV Circuit Breakers P 165


SLF / Line Surge Impedance

• Factors that influence the surge impedance


− Geometry of a conductor
− Arrangement of the conductors in relation to the towers and the ground
(single or double circuits..)
− Frequency of the TRV: Z decreases by 4% when the frequency increases
from 1 to 100 kHz.
− In case of bundled conductors, they can clash if the current is high enough.
The surge impedance is higher after conductor clashing and reach the
value for a single conductor: 450 Ω.
− Line height: the surge impedance of lines increases with the conductor
height above ground.
− Earth resistivity: the surge impedance increases by 5.7% at 1kHz and
3.2% at 100 kHz when earth resistivity changes from 10 to 1000 Ω-m.
− Tower footing resistance: if it rises from 0 to 10 Ω the surge impedance
increases by about 2%.
TRV HV Circuit Breakers P 166
Short-line-fault

• Percentage of SLF (or M)

V VLG
I S  LG IL 
XS XS  XL

TRV HV Circuit Breakers P 167


Short-line-fault

• The transmission line parameters are given in terms of the effective


surge impedance ( Zeff) of the faulted line and a peak factor (d)

uL
d
uO
uO
uL

u L  Z eff  di / dt  2  / v Z eff
d  2
uo    X L  I L 2 XL v
XL is the line reactance per unit length
v is the velocity of light (0.3 km/µs),  is the line length
 is 2   system power frequency (314 or 377 rad/s for 50 or 60 Hz)

TRV HV Circuit Breakers P 168


SLF / Voltage at Current Zero

U0  X L  IL
US  X S  IS
U0 IL  M  IS
US XS
M
XS  XL
or M  X L  X S  M  X S
U0  X L  M  IS
U0  X S  M  X S   IS
U 0  1  M   X S  I S  1  M   U S

U 0  1  M   U S

TRV HV Circuit Breakers P 169


SLF / Line-side Contribution to TRV

• The rated values for the line surge impedance Z and the peak factor
d are defined in standards as follows:
Z  450  d  U L / U 0  1.6
• The line side voltage contribution to TRV is defined as a triangular
wave as follows (where IS is the rated short-circuit current) :
2 du di
U L  1.6 (1  M ) Ur Z  Z  M IS 2
3 dt dt
the first peak UL decreases when M increases
the rate-of-rise of recovery voltage increases with M
• There is a critical value of the short-line-fault current for which the
circuit breaker has more difficulty to interrupt.
• The critical value of M is close to 90% for SF6 circuit breakers
(generally in the range 90%-95%). it is between 75% and 80% for
air blast circuit breakers.
TRV HV Circuit Breakers P 170
Short-line-fault

• The following Table gives the comparison of current and voltage


stresses during test duties L90 and L75, respectively at 90% and 75%
of rated short-circuit current, for a circuit-breaker 245kV 40kA 50Hz.
• The current and RRRV are higher during L90, but the (first) peak
voltage is higher during L75.
• In practice, L90 is usually the most severe test duty.
L90 L75

Current (kA) 36 30

RRRV (kV/µs) 7.2 6

UL (kV) 32 80

RRRV: rate of rise of recovery voltage UL= first peak voltage


Voltage on the line side only is considered

TRV HV Circuit Breakers P 171


SLF / Comparison of Test Duties

140

120
L60
Ur = 245kV
4.8 kV/µs
100 Isc = 40kA
80
fr = 50Hz
U (kV)

L75
6 kV/µs
60

40
L90
7.2 kV/µs
20

0
0 5 10 15 20 25 30 35

T (µs)

When current decreases (longer line), the slope decreases but the peak
value increases. It is generally considered that for SF6 circuit breakers
interruption is more influenced by the voltage slope (RRRV).

TRV HV Circuit Breakers P 172


Short-line-fault

• The TRV seen by the circuit breaker is the sum of a contribution


from the line side (eL) and a contribution from the supply side (eS):

e  e L  eS
with (in a first approximation)

eS  2 M (TL  t d )
where

2M = RRRV (T100) x M = 2 kV/µs x M

TL is the time to peak of the line side TRV

td is the time delay of TRV on the source side

TRV HV Circuit Breakers P 173


Short-line-fault

• Example of calculation of SLF TRV : L90 245 kV 50 kA 50 Hz


Fault current = 0.9 x 50 = 45 kA (assuming time delay tdL= 0 µs)

TRV HV Circuit Breakers P 174


Short-line-fault

• This rate-of-rise of TRV during SLF is much higher than the values
that are met during terminal fault interruption:
RRRV I F
Test duty
(kV/µs) (kA) (Hz)

SLF
10.8 45 60
L90 50 kA

SLF
9 45 50
L90 50 kA

SLF
8.64 36 60
L90 40 kA

Terminal fault
3 30 50/60
T60

Terminal fault
2 50 50/60
T100

For SLF, this table gives the RRRV of the line side voltage

TRV HV Circuit Breakers P 175


SLF / Line Characteristics

• Standard values of lines characteristics for SLF

IEC values are shown, ANSI/IEEE values cover rated voltages up to 800kV
TRV HV Circuit Breakers P 176
Short-Line-Fault
Influence of an Additional Capacitor

TRV HV Circuit Breakers P 177


SLF / Influence of an Additional Capacitor

• The SLF performance can be increased by adding a capacitor, either


between terminals or phase to ground (see figure).
• A capacitor has two effects:
− it decreases the oscillation frequency and the RRRV of the line
side contribution to TRV;
− it increases the time delay of the line side contribution to TRV.

XS XL
C.B.

VLG

TRV HV Circuit Breakers P 178


SLF / Influence of an Additional Capacitor

60

[ kV ]

50

40

30

1 2 3
20

10

0
0 4 8 12 16 [ u s] 20
(file t r v 2 .pl4 ; x - v ar t ) v :P 0 0 v :P 1 v :P 4 v :P 1 0

TRV without TRV with capacitor


capacitor (capacitance increase from 1 to 3)

TRV HV Circuit Breakers P 179


SLF / Influence of an Additional Capacitor

− Equation of the line-side contribution to TRV up to the first peak:


e(t )  Z (di / dt ) t  Z C  Z C e  t / Z C 
− If the capacitor is connected phase to ground on the line side, the
reduction of the line side RRRV can be estimated by a simple
calculation, as detailed in the next slide, with
Cadd additional line-to-ground capacitance;
L line inductance;
Z line surge impedance;
CL total line capacitance = L/Z2;
Ce equivalent line capacitance: capacitance which, together
with the inductance L, gives the line frequency of oscillation

TRV HV Circuit Breakers P 180


SLF / Influence of an Additional Capacitor

1
− By definition of Ce fL 
2 LCe
2u *L
− The period of oscillation is equal to with u *L  2 X L  I L 2
 du 
 du   
and    Z    I L 2  dt  L
 dt  L
Z 
− It follows that fL 
4X L
and 4L 4 CL
Ce  2  2  0.4 CL
 Z 2

If an additional capacitance is added at the line entrance, the RRRV on
the line side is reduced in the same manner as the line frequency of
oscillation.

TRV HV Circuit Breakers P 181


SLF / Influence of an Additional Capacitor

− The RRRV on the line side is then

du 2 LCe
 Z   IL
dt 2 L(Ce  Cadd )

du Ce
 Z   IL
dt Ce  Cadd

du CL
 Z   IL 2
dt C L  2.5 Cadd

TRV HV Circuit Breakers P 182


Short-Line-Fault
Influence of an Opening Resistor

TRV HV Circuit Breakers P 183


SLF / Breaking with Opening Resistor

• Some circuit breakers, mainly air-blast, have an opening resistor to


assist a short-circuit interruption.
• It was introduced to improve the SLF breaking capability of air-blast
circuit breakers, but it has been used also to facilitate the interruption
of fast TRVs by some SF6 circuit breakers.

TRV HV Circuit Breakers P 184


SLF / Breaking with Opening Resistor

• In case of SLF, the RRRV (or du/dt) is modified as follows:

du Z  R di Z  R
  I 2
dt Z  R dt Z  R

where R = value of opening resistor


Z = line surge impedance
I = short-circuit current

TRV HV Circuit Breakers P 185


Short-Line--Fault TRV / Summary

• Very fast RRRV (rate-of-rise of recovery voltage)


− Product of fault current derivative by surge impedance
− Standard value of surge impedance = 450 Ω
• Triangular waveshape due to travelling waves
• Test duties L90 and L75 (+ L60 is some cases)
− Single-phase tests that cover all SLF conditions
• SLF performance improved by
− additional capacitor (or opening resistor)

TRV HV Circuit Breakers P 186

You might also like