SI.No.

Defect Department Notification


1 Data Concentrator not working EMD
2 Bus Voltage/Current not available in OWS EMD
3 220 V DC Battery Charger parameters not available in OWS EMD/C&I
4 EERM 1A1 not available EMD/AHD
5 Offsite bus scheme not available in OWS EMD
6 24V battery bank charger/UPS scheme not available in OWS EMD/C&I
7 All buses breaker nomenclature not available in OWS EMD/C&I
8 Module lock of breakers/panels broken EMD
9 ESP hopper heaters taking less current and all are not on EMD
10 220 V DCDB earth fault EMD
11 ESP hopper transformer earthing key removal (Locking) not av EMD
12 ST oil temp high faulty alarm appearing EMD
13 3.3 kv/415v Staion service transformer-2 marshling box supply is not available EMD
14 Oil Lkg in CT transformer-3, UAT-1, GT RY EMD
15 ID Fan-A channel-1 PRV (limit switch) defective EMD
16 ID Fan-B channel-1/2 PRV (limit switch) defective EMD
17 GRAVEL is not available in ID FAN-B channel-1/2 EMD
18 Breather Sillica gel colour is pink in MISC AUX TRF-1 (fire water) EMD
19 LED not working in CT#6DB MCC Module- 1F1, 31F1, 16F1, EMD
20 LED not working in RODM MCC Module- 1F1 EMD
21 LED not working in ODD( fire water) MCC Module- 7R3 EMD
22 LED not working in MISC. 0 QA MCC Module- 1F1 EMD
23 LED not working in UES 6DG MCC Module- 27F1, 15F1, 2F1 EMD
24 LED not working in Station Service ODA MCC Module- 15F1, 12F2 EMD
25 LED not working in Unit Service 6DA MCC Module- 16F1, 16F2, 13F2, 12F1, 10F1, 1F1 EMD
26 LED not working in TURBINE 6KA MCC Module- 17F1 EMD
27 LED not working in 6QA MCC Module- 1F4, 13F4 EMD
28 LED not working in BOILER 6HC MCC Module- 1F4, 6F1 EMD
29 LED not working in BOILER 6HA MCC Module- 1F1, 8F1 EMD
30 LED not working in AC OTA MCC Module- 9F1 EMD
31 ACMCC # OTA Module no- 2F1 is not available EMD
32 AC EMERGENCY MCC # OTB Module no- 1F1 is not available EMD
33 MISC. Service # 0QA module 16F1 is not available EMD
34 UNIT SERVICE ACDB # 6QA Module 7F1 is not available EMD
35 220 DCDB Battery Charger-1 volt meter defective EMD
36 LTMCC Pass-D module 13F1 breaker shutter defective EMD
37 ESP PASS-D TRF-1 WTI reading error EMD
38 TDBFP –A one LOP should be at TMCC EMD
39 TDBFP –B one LOP should be at TMCC EMD
40 One BCW Emergency Fill pump supply should be at DG Board EMD
Coal feeder-A,C,E,G,J three phase supply from section-1 and feeder –B,D,F,H Supply from
41 section-2 of 6HC Board EMD
Coal feeder-A,C,E,G,J single phase supply from section-1 and feeder –B,D,F,H Supply from
42 section-2 of 6HC Board EMD
43 IAC lube oil pump supply to be provided with 6DG Bus EMD
44 DCS to be commissioned for auto logic( Stage -4 service building DCS) ID Fan EMD
Total 03 no. and 02 no. ERVs supply coming from single module of 220V DCDV
45
Board. Each ERV should be supplied from separate EMD
46 PAPH -A and PAPH -B main motor drive should be from 6DG Board EMD
Contactor auto logic to be commissioned, if one fail other will pick, Both isolator will
47
be made on EMD
All breaker mimic to be provided in DCS, Remote (CCR-6) operation to be provided of
48
Station auxiliary board (Fire MCC) EMD
49 AC plant Incommer-1 (OTA) not avaialble. To be made available at the earliest EMD
50 AC PLANT (OTB), RODM and PT PLANT on single source EMD
51 ESP 415 V Breaker inoperative from remote EMD
GT MB supply-1, 2 from section-2 of 6DA and section-2 of ODA bus. ONE source
52
should be from any section of 6DG board. EMD
53 ALL ERV and MS , CRH, HRH releving valve module cable to be provided EMD
54 MVAR transducer to be changed EMD
55 400 KV BUS-1 Voltage tx-1 EMD
56
Offsite and ash handling switch gear breaker remote and auto operation not available EMD
57 H2 drier i/l o/l due point measurement to be provided. EMD/C&I
58 Generator slot temp 13 to 19 erratic EMD/C&I
59 H2 purity meter to be commissioned. Line leakage to be attended EMD/C&I
60 Bus duct pressurization unit not working EMD
61 GCB LA showing zero leakage current EMD
62 Primary Water conical filter choking EMD
63 CT Fan-A7 module not available EMD
64 Generator End winding Vibrations running on higher side EMD
65 Generator Field Voltage and Current value not availble in OWS EMD
66 415V Fuel Oil MCC (0DB) Incomer-1 &2 are crossed EMD
67 415V Service Building MCC (0DC) Incomer -1 & 2 are crossed EMD
68 415V Make Up Water MCC (0DE) Incomer -1 & 2 are crossed EMD
69 3.3KV Miscelleneous MCC (0CA) Incomer-1 & 2 are crossed EMD
70 415V Fire Water MCC (0DD) Incomer -1 & 2 are crossed EMD
71 415V ESP LT MCC-C (6DE) Incomer -1 & 2 are crossed EMD
72 415V CT MCC (6DB) Incomer -2 & 3 are crossed EMD