Professional Documents
Culture Documents
Section 1. Summarize
F3 adopts HVAC housing assy. with the function of ventilation 、refrigeration in summer、heating and
defrosting in winter.
1. Refrigeration theory:
The refrigeration system is composed of compressor 、 evaporater 、 condensor 、 drier 、 expansion
valve、blower、control module and so on as follows:
Illustration 8-1-1
Heat enter
Heat enter evaporator refrigerant
air from Condensor from air
refrigerant
Illustration 8-1-2
The heating system works eith coolant from engine. It’s mainly composed of heat
exchanger、coolant pipe、blower、vent and control module. The housing heating system is integrated
with evaporator housing, the heating system use the same blower and vent together with the
refrigeration system as follows.
Illustration 8-1-3
While the engine is running, the cooling water pumps propell the coolant which is heated through
the high temperature-cylinder into the heat exchangerthrough water pipe. Then the air is heated
through the heat exchanger and blowed into the passenger compartment or the windshield by blower to
keep the compartment warm or defrost on the windshield. Then the collant is propelled back by water
pump and repeat the circulation as follows:
High
temperature
Engine coolant
Heat
ente
Low r air
temperature Heat from
coolant exchanger here
Middle
Water temperature
Radiator pump coolant
Illustration 8-1-4
Pressure switch
Wire connector
Condensor
Stitch Wire
Test port Port illustration Test condition Standard value
code colour
A/C request signal output Compressor runs,All the
1-body AC1 Y/R < 1V
end time
High/low pressure signal Input
Pressure of A/C high
2-body PRS Y/B output end of pressure characteristic
pressure pipe changes
switch curve A
Evaporator temperature Input
3-13 TE B/L
sensor input end Temperature of characteristic
Evaporator temperature evaporator changes resistance table
13—3 SG W/L
sensor grounding end B
5-body GND W/B grounding All the time < 1Ω
Engine permitted signal Compressor runs,All the
7-body ACT R/L < 1V
input end time
Blower runs,press down
8-body A/C Y/B A/Cswitch signal input end 10~14V
A/C switch,All the time
10 - Control end of A/C switch A/C switch indicator light
LED G/Y —
body indicator light works
Middle pressure signal Input
11 - Pressure of A/C high
CFN- G/B output end of pressure characteristic
body pressure pipe changes
switch curve C
12 - Control end of A/C Compressor runs,All the
MGC Y/R < 1V
body electromagnetic clutch time
Wire
Stitch Standard
Test port colou Port illustration Test condition
code value
r
1-body GND W/B grounding All the time < 1Ω
Grounding end for feedback
See the stitch
2-body SGTPM Y/B resistance of blow mode Automatic A/C runs
definitionⅠ
motor
Grounding end for See the stitch
3-body SGTP Br/Y Automatic A/C runs
temperature motor definitionⅠ
feedback resistance end for See the stitch
4-body TPM L/O Automatic A/C runs
blow mode motor definitionⅠ
feedback resistance end for See the stitch
5-body TP W/L Automatic A/C runs
temperature motor definitionⅠ
Connect the feedback
See the stitch
7-body S5TPM G resistance of blow mode Automatic A/C runs
definitionⅠ
motor to +5v end
Connect the feedback
See the stitch
8-body S5TP W/R resistance of temperature Automatic A/C runs
definitionⅠ
motor to +5v end
Control end 1 for blow mode See the stitch
9-body AOF Y/B Automatic A/C runs
motor rotation direction definitionⅠ
10 - Control end 2 for blow mode See the stitch
AOD R/B Automatic A/C runs
body motor rotation direction definitionⅠ
Control end 1 for
11 - See the stitch
AMH L Temperature motor rotation Automatic A/C runs
body definitionⅠ
direction
Control end 2 for
12 - See the stitch
AMC R/W Temperature motor rotation Automatic A/C runs
body definitionⅠ
direction
Control end 1 for Fresh air
13 - See the stitch
AIR L/W inner circulation motor Automatic A/C runs
body definitionⅠ
rotation direction
Control end 2 for Fresh air
14 - See the stitch
AIF G/Y inner circulation motor Automatic A/C runs
body definitionⅠ
rotation direction
16 - CFN- G/B Connector of Middle A/C is in middle < 1V
Page of chapter 8. Air conditioner
10
pressure、engine ECM and
body pressure, All the time
cooling fan
17 - Compressor clutch control Compressor runs, All the
MGC Y/R < 1V
body connector time
Input
18 - High/low pressure signal Pressure of A/C high
PSW Y/B characteristic
body output end of pressure switch pressure pipe changes
curve A
Ignition
19 - Electric source input of < 1V→10-
IG R/L switch:ACC→ON, All the
body ignition switch in ON position 14V
time
20 -
+B L/Y Constant power input All the time 10-14V
body
Grounding end for
Input
21-24 SGTE W/L Evaporator temperature
Temperature of characteristic
sensor signal
evaporator changes resistance
Input end for Evaporator
24-21 TE B/L table B
temperature sensor signal
Grounding end for outer
22-25 SGTAM Br/Y Input
temperature sensor signal Outer temperature
characteristic
Input end for outer changes
25-22 TAM W/G resistance D
temperature sensor signal
Grounding end for inner
23-26 SGTR Br/Y Input
temperature sensor signal Inner temperature
characteristic
Input end for inner changes
26-23 TR G/R resistance E
temperature sensor signal
Input end for light intensity
27-28 TS W/R Input
sensor signal
Light intensity changes characteristic
Grounding end for light
28-27 S5TS L/W resistance F
intensity sensor signal
Engine water temperature Input
30-31 SGTW W/G
signal grounding end Temperature of Engine characteristic
Engine water temperature coolant changes resistance
31-30 TW Y/G
signal input end table G
32 - Engine permitted signal Compressor runs,All
ACT R/L < 1V
body inputend the time
33 - Compressor runs,All
ACI Y/R A/C request signal ouput < 1V
body the time
Input impulse
signal(see
34 - Vehicle runs,All the
SPD V/W Vehicle speed signal input combination
body time
instrument
A10)
35 - Blower PWM signal output
BLC L/B Blower works —
body end
36 - Control output end of blower Blower works,All the
HR L/O < 1V
body relay time
37 - Control output end of rear Rear windshield heater
RDEF B < 1V
body windshield heater works,All the time
Ignition
39 - Electric source input for night
ILL+ G switch:ON,combination 10~14V
body illumination
switch:Tail,All the time
Electric source input for Ignition
40 - < 1V→10-
ACC W/L Ignition switch in ACC switch:OFF→ACC, All
body 14V
position the time
Section 4 Maintenance of A/C
components
1. Overhauling of the compressor belt:
(1) Remove
The location of the compressor and belt is
showed in the illustration 8-4-1.
Page of chapter 8. Air conditioner11
Illustration 8-4-1
(a) Loosen the nut a showed in the illustration 8- Illustration 8-4-4
4-2.
2. The overhaul of the air filter
(1) Remove the glove box as showed in the
illustration 8-4-5.
Illustration 8-4-2
(b) Loosen the nut B, and remove the compressor belt
Illustration 8-4-5
(2) Installation (2) Remove the filter as showed in the illustration
(a) Install the compressor belt as showed in the 8-4-6.
illustration 8-4-3.
Illustration 8-4-7
Illustration 8-4-11
Illustration 8-4-8
Use the wrenches to remove the nuts on the M16
(2) Remove the lower duct and M8 pipes.
1) Move the seat to the back. 3) Remove the snap rings from the pipe.
2) Open the carpet, remove the floor duct. Remove the snap rings from the heater inlet
(a) Remove the left floor duct as showed in the and outlet pipes
illustration 8-4-9. (showed in the illustration8-4-12).
Illustration 8-4-10
9) Remove the beam (see the method of (1) Remove the evaporator inlet and outlet
removing the beam). cover as showed in the illustration 8-4-17.
10) Remove the three nuts showed in the
illustration 8-4-14.
Illustration 8-4-14
Illustration 8-4-17
11) Remove the nut showed in the illustration 8-
(2) Remove the two clips and expansion valve as
4-15.
showed in the illustration 8-4-17.
(3) Remove the evaporator right plate as showed
in the illustration 8-4-17.
(4) Remove the evaporator as showed in the
illustration 8-4-17.
(5) Remove the two O-sharp rings from the
evaporator core as showed in the illustration
8-4-18.
Illustration 8-4-15
Illustration 8-4-21
Illustration 8-4-23
Install the outer cable into the clip, press down
the cable in the shown direction.
NOTE:
①Do not contort the cable.
②If the cable is bent; there will be problem with
the heating controller and accessories assy. Illustration 8-4-25
③Operate the heating control rod, check (1)Remove the A/C pipe
whether the rod can stay in the inner and Seal the opening of the disconnected parts
outer circulation position and not to rebound. using vinyl tape to prevent moisture and
4)Check whether refrigerant leaks after foreign matter from entering.
installation. (2)Remove the compressor belt (showed in
the illustration 8-4-26).
4. Overhaul of compressor assy.
1. Disassembly and installation
Drain the refrigerant before disassemble the
compressor, and fill the refrigerant after
installation, then check the tension of the
compressor belt.
Illustration 8-4-26
Loosen the steering pump held bolt.
Loosen the adjusting bolt, and remove the
Page of chapter 8. Air conditioner
16
driving belt.
Illustration 8-4-30
While install the clutch coil to the house of
compressor, please face the bulge to the house
positioning hole.
Illustration 8-4-27
Connect the battery positive terminal to the
connector of the electromagnetic, negative
terminal to the body of the compressor. If the
compressor is normal, there will be a “kaka”
sound. If there is not this sound, it is indicated
that there is some malfunction.
Illustration 8-4-31
NOTE: Install the snap ring to make sure the
core is at the outside of it.
Illustration 8-4-28
Disassembly tips
Remove the locknut as shown in the illustration
Illustration 8-4-32
Check whether the clearance is in the standard
value; if necessary adjust it using the washer.
Standard value is 0.3-0.5mm.
Check
Illustration 8-4-29 Check the over-heat protecting switch as showed
Installing tips in the illustration 8-4-33.
Installation of clutch coil
Illustration 8-4-34
The compressor over-heat protecting switch
Connected: Less than 105℃
Disconnected: Above 130℃ ( at OFF status, at
least 125℃) Illustration 8-4-36
2) Remove the 3 O-sharp rings from the cap
5. The overhaul of the condenser assy. (showed in the illustration 8-4-36).
with the reservior
1. On-vehicle check-up
1)The check of the condenser assy.
(1)Use the air flow to clean the condenser
radiator.
(2)If the plate of radiator is distortion, please
make it straight.
2)Check whether there is leakage.
(1)Check the gas leakage using the Halogen
checking device.
(2)If there is leakage at the connector, please Illustration 8-4-37
check the tighten torque. 3) Remove the drier using the needle nose pliers
(showed in the illustration 8-4-37)
2. On-vehicle disassembly
NOTE:
1)Seal the pipe connector after remove the
pipes to avoid the entry of moisture and dusts,
don’t use the material which will be corroded
by R134a.
2)Don’t forget to install the pipe clips while
install the pipes as the following illustration.
Illustration 8-4-43
5. Installation is in the reverse order of the
removal.
Illustration 8-4-41
8. The overhaul of the condenser fan:
1. Disconnect the connector of the condenser
fan.
2. Remove the condenser.
3. Loosen the two bolts as showed in the
illustration 8-4-42.
Illustration 8-4-44
2)Remove the lower duct in the driver side:
Illustration 8-4-45
3)Remove the heater、screw of pressing plate
Illustration 8-4-47
and screw of fix clip:
2 . Installation is in the reverse order of the
removal.
Hint: if the refrigerant is enough, the environment temperature is high than the normal, and there is
some bubble in the inspecting hole is normal.
Test conditions:
1) Engine speed is 1500r/min
2) The blower speed control switch is at “HI” position
3) The A/C switch is on.
4) Temperature control lever is at MAX cold position.
5) All of the doors are opened.
1) Temperature at the air inlet with the switch set at RECIRC is 33~35℃.
2) Engine speed is 1500r/min.
3) The blower speed control switch is at “HI” position.
4) Temperature control level is at “COLD” position.
5) The A/C switch is on.
6) All of the doors are opened.
Illustration 8-5-2
Illustration 8-5-5
Illustration 8-5-3
Illustration 8-5-6
Sympto Reason Diagnosis Remedy
m
(1) (1)Ill effect (1) (1)Clean Illustration 8-5-8
Pressure of Ill effect of condenser Symptom Reason Diagnosis Remedy
too high refrigerating refrigeratin (2)Check (1) Trouble in (1) Check
on both performance -g cooling Pressure expansion Excessive expansion
low and (2)Insufficien performan- fan with too high valve refrigerant valve,
high t cooling of ce cooling on both in low replace if
pressure condenser (2)Supply fan motor low and pressure necessary
sides too much operation high piping
refrigerant (3)If (1) pressure (2)
and (2) sides Expansion
are in (1) Frost valve
normal or large opened
state, amount too wide
check of dew on
amount of piping on
refrigerant low
and pressure
supply side
proper Table 8-5-7
amount of
refrigerant
Page of chapter 8. Air conditioner
24
(i) Defective compression compressor. It is Illustration 8-5-10
showed in the illustration 8-5-9 and table 8-5-8.
(1) Discharge the refrigerant
1 Open the A/C switch.
2 The A/C is running about
5~6min while the engine is running about 1000
r/min.
3 Stop the engine.
Illustration 8-5-9 4 Discharge the refrigerant.
(2) Refill the refrigerant
Symptom Reason Diagnosis Remedy
1 Evacuate air
(1) (1) (1) Repair or
2 Refill the HFC-134a(R134a). Standard
Pressure Leakage of Damage of replace the
value: 580g.
too high the the compressor
3) Run the engine at idle speed
on low compresso compresso
4) Check the leakage of the refrigerant.
and high r r
4. Refrigerant pipe (showed in the illustration 8-
pressure (2) (2)
5-11)
sides Damage of Leakage
(2) the from valve
Refrigerant pipeline layout:
Pressure compresso damaged
too low r or broken
on high sliding
pressure parts
side
`Table 8-5-8
Illustration 8-5-11
●Turn the ignition switch to the “ON” position, and at same time press down the AUTO and OFF
switches for about 5s(all of the indicators will be flashing 4 times), will enter into the checking status of
the indicator. Notice: If do not press down the AUTO and OFF switch at same time, will cancel the
checking status and enter into the A/C control status.
●After the check of the indicator, will enter into the check of the malfunction code automatically, and at
this time can read the malfunction code through the display on the control panel.
●Under the check of the malfunction code, press down the FRONT switch, will enter into the check of
the adjuster, and at this time can read the malfunction code through the display on the control panel.
Press down the OFF switch, will cancel the checking status and enter into the A/C control.
●Under the check of the adjuster, press down the AUTO switch, will enter into the check of the
malfunction code. Press down the OFF switch, will cancel the checking status and enter into the A/C
control.
●After the display, the malfunction code will be cancelled without saved automatically.
NOTE:
(1). If the outer or inner temperature is -40℃ or more less, although the A/C system is normal, some
malfunction codes (10, 11,,20,21) will appear
(2). If the vehicle is under dark, the malfunction codes (40) will appear.
2.3. Check the malfunction code and circuit of heating electronic control system
2.3.1. Check the malfunction codes 10, 11
●Check the circuit
●Check-up process
Page of chapter 8. Air conditioner
26
1. Check the inner temperature sensor
Remove the inner temperature sensor; test the resistance between 1 and 2. At 20℃, the
resistance is 12.37-12.67kΩ. At 40℃, the resistance is 5.225-5.397 kΩ.
If normal, please to next step If abnormal, replace the inner temperature
sensor.
2. Check the wire harness or connector between the A/C controller and the inner
temperature sensor
(1)Disconnect the inner temperature sensor connector A19
(2)Disconnect the A/C controller connector C11
(3)Test the resistance between the port 1-A19 of the inner temperature sensor and the port A26-
C11 of A/C controller. And the resistance should be less than 1Ω.
(4)Test the resistance between the port 2-A19 of the inner temperature sensor and the port 23-
C11 of A/C controller. And the resistance should be less than 1Ω.
( 5 ) Test the resistance between the port 23-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
( 6 ) Test the resistance between the port 26-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
If normal, replace the A/C controller. If abnormal, overhaul or replace the wire
harness or the connector.
●Check-up process
●Check-up process
1. Check the evaporator temperature sensor
Disconnect the evaporator temperature sensor connector, test the resistance between the port 1 an d
port 2. At 10℃, the resistance is 3.101~3.359kΩ. At 20℃, the resistance is 1.964~2.106kΩ.
If normal, go to next step If abnormal, replace the evaporator temperature
sensor.
2. Check the wire harness or connector between the evaporator temperature sensor and A/C
controller.
(1)Disconnect the evaporator temperature sensor connector A18
(2)Disconnect the A/C controller connector C11
(3)Test the resistance between the port 1-A18 of the inner temperature sensor and the port 21-C11 of
A/C controller. And the resistance should be less than 1Ω.
(4)Test the resistance between the port 2-A18 of the inner temperature sensor and the port 24-C11 of
A/C controller. And the resistance should be less than 1Ω.
(5)Test the resistance between the port 21-C11 of A/C controller and the body. And the resistance
should be more than 100KΩ.
(6)Test the resistance between the port 24-C11 of A/C controller and the body. And the resistance
should be more than 100KΩ.
If normal, replace the A/C controller. If abnormal, overhaul or replace the wire harness
or the connector.
●Check-up process
1. Check the A/C controller
(1)Remove A/C controller but the connector also be connected. Turn the ignition switch to the
ON position
(2)Test the voltage between the port 2-C11 and the port 7-C11 of A/C controller, the voltage is
about 5V.
(3)Test the voltage between the port 2-C11 and the port 4-C11 of A/C controller, the voltage is
3.5-4.5V while the wind outlet port is at FACE position. The voltage is 0.5-1.5V while the wind
outlet port is at DEF position.
If normal, to next step If abnormal, overhaul or replace the wire harness or the
connector.
2. Check the blow mode control motor
(1)Disconnect the blow mode control motor connector.
(2)Connect the battery positive pole to the port 5-A24, connect the battery negative pole to the
port 7-A24. The lever is turned to the DEF position.
(3)Connect the battery positive pole to the port 7-A24, connect the battery negative pole to the
port 5-A24. The lever is turned to the FACE position.
(4)Test the resistance between the port 2-A24 and the port 3-A24 of blow mode control
motor,it should be about 10kΩ. The resistance between the port 6-A24 and the port 2-A24 of that
should be 0.5~2kΩ while the wind outlet duct is in FACE position, and the resistance should be 7
~9kΩ while the duct is in DEF position.
If normal, to next step If abnormal, replace the blow mode control motor
3. Check the wire harness and connector between the blow mode control motor and A/C
controller.
(1)Disconnect the blow mode control motor connector
(2)Disconnect the A/C controller connector
(3)Test the resistance between the port 2-A24 of the blow mode control motor and the port 7-
C11 of A/C controller. And the resistance should be less than 1Ω.
(4)Test the resistance between the port 3-A24 of the blow mode control motor and the port 2-
C11 of A/C controller. And the resistance should be less than 1Ω.
(5)Test the resistance between the port 5-A24 of the blow mode control motor and the port 9-
C11 of A/C controller. And the resistance should be less than 1Ω.
(6)Test the resistance between the port 6-A24 of the blow mode control motor and the port 4-
C11 of A/C controller. And the resistance should be less than 1Ω.
(7)Test the resistance between the port 7-A24 of the blow mode control motor and the port 10-
C11 of A/C controller. And the resistance should be less than 1Ω.
(8)Test the resistance between the port 7-C11 of A/C controller and the body. And the resistance
should be more than 100KΩ.
(9)Test the resistance between the port 24-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
(10)Test the resistance between the port 9-C11 of A/C controller and the body. And the
Page of chapter 8. Air conditioner
29
resistance should be more than 100KΩ.(11)Test the resistance between the port 4-C11 of A/C
controller and the body. And the resistance should be more than 100KΩ.
(12)Test the resistance between the port 10-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
If normal, replace the A/C controller. If abnormal, overhaul or replace the wire harness or the
connector.
●Check-up process
1. Check the A/C controller
(1)Remove the A/C controller, but the connector is connected. Turn the ignition switch to the
“ON” position
(2)Test the voltage between the port 8-C11 and port 3-C11 of the A/C controller, it should be
about 5V
(3)Test the voltage between the port 5-C11 and port 3-C11 of the A/C controller, while the
temperature selector is at coldest position, it should be 3.5~4.5V, while the temperature selector is
at hottest position, it should be 0.5~1.5V
If normal, to next step If abnormal, overhaul or replace the wire harness or the
connector.
2. Check the temperature control motor
(1)Disconnect the temperature control motor connector.
(2)Connect the port 5-A23 of the temperature control motor connector and the battery positive
terminal, port 7-A23 to the battery negative terminal,and the lever should be turned to the cold
position.
(3)Connect the port 7-A23 of the temperature control motor connector and the battery positive
terminal, port 5-A23 to the battery negative terminal,and the lever should be turned to the hot
position.
(4)Test the resistance between the port 2-A23 and the port 3-A23 of temperature control
motor,it should be about 10kΩ. The resistance between the port 6-A23 and the port 2-A23 of that
should be 0.5~2kΩ while the wind outlet duct is in cold position, and the resistance should be 7~
9kΩ while the duct is in hot position.
If normal, to next step If abnormal, replace the temperature control motor
3. Check the wire harness and connector between the temperature control motor and A/C
Page of chapter 8. Air conditioner
30
controller.
(1)Disconnect the temperature control motor connector
(2)Disconnect the A/C controller connector
(3)Test the resistance between the port 2-A23 of the temperature control motor and the port 3-
C11 of A/C controller. And the resistance should be less than 1Ω.
(4)Test the resistance between the port 3-A23 of the temperature control motor and the port 8-
C11 of A/C controller. And the resistance should be less than 1Ω.
(5)Test the resistance between the port 5-A23 of the temperature control motor and the port 12-
C11 of A/C controller. And the resistance should be less than 1Ω.
(6)Test the resistance between the port 6-A23 of the temperature control motor and the port 5-
C11 of A/C controller. And the resistance should be less than 1Ω.
(7)Test the resistance between the port 7-A23 of the temperature control motor and the port 11-
C11 of A/C controller. And the resistance should be less than 1Ω.
(8)Test the resistance between the port 3-C11 of A/C controller and the body. And the resistance
should be more than 100KΩ.
(9)Test the resistance between the port 8-C11 of A/C controller and the body. And the resistance
should be more than 100KΩ.
(10)Test the resistance between the port 12-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
(11)Test the resistance between the port 5-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
(12)Test the resistance between the port 11-C11 of A/C controller and the body. And the
resistance should be more than 100KΩ.
If normal, replace the A/C controller. If abnormal, overhaul or replace the wire harness or the
connector.
●Check-up process
1. Check the light intensity sensor
Remove the light intensity sensor, and connect the resistance 36 kΩ in series, and then connect to
the 5V source. Illuminate the sensor with sunlight(the light intensity is 30000~50000 lux),test
the voltage between the port 1 and port 2 of the light intensity sensor with digital multimeter, the
voltage should be 0.7~1.5V。
If normal, please to next step If abnormal, replace the light intensity sensor.
2. Check the wire harness or connector between the light intensity sensor and A/C
controller.
(1)Disconnect the light intensity sensor connector
●Check-up process
1. Check the 15A fuse of inner light.
Remove the 15A fuse of inner light, and check whether it has been broken off.
If normal, to next step If abnormal, replace the fuse
2. Check the A/C controller.
Remove the A/C controller but also connected, test the voltage between port A20 of the A/C
controller and the body. The voltage is 10-14V.
If normal, make next check following the if abnormal, overhaul or replace the wire
malfunction table. harness or connector.
●Check-up process
●Check-up process
1. Chcek the cigar lighter fuse
Remove the 15A fuse of cigar lighter; check whether it has been broken off.
If normal, to next step If abnormal, replace the cigar lighter fuse
2. Check the A/C controller
Remove the A/C controller but also connected, and the ignition switch in ACC position, test the
voltage between port 40-C11 of the A/C controller and the body. The voltage is 10-14V.
If normal, make next check following the if abnormal, overhaul or replace the wire harness or
malfunction table. connector.
●Check-up process
1. Check the A/C controller
(1)Remove the A/C controller(for automatic A/C), turn the ignition switch to the OFF position, test the
voltage between port 37-C11 of the A/C controller and the body. The voltage is below 1V. Turn the
ignition switch to the ON position, The voltage between port 37-C11 of the A/C controller and the body, it
is 10-14V.
(2)Remove the A/C controller(for manual A/C), turn the ignition switch to the OFF position, test the
voltage between port 1-H5、2-H5 and the body. The voltage is below 1V. Turn the ignition switch to the
ON position, The voltage between port 1-H5、2-H5 and the body, it is 10-14V.
If normal, overhaul or replace the A/C controller、rear If abnormal, to next step
windshield heater switch
2. Check the heater replay
If normal, overhaul or replace the wire harness or If abnormal, replace the relay
connector.
2.3.12. Check the blower speed adjusting resistance (for manual A/C)
Checkthe resistances between the ports of blower speed adjusting resistance, the resistance between
Page of chapter 8. Air conditioner
35
the port 1-B5 and the port 2-B5 should be 1.2~1.6Ω,the resistance between the port 1-B5 and the
port 2-B5 should be 0.35~0.45Ω,the resistance between the port 1-B5 and the port 2-B5 should be
2.2~3.0Ω, or replace the blower speed adjusting resistance.
●Check-up process
1. Check blower motor
Disconnect the B4 connector of blower motor, connect the port 2-B4 of blower motor and the battery
positive pole. Connect the port 1-B4 of blower motor and the battery negative pole. And the blower
should run normally.
If normal, to next step If abnormal, overhaul or replace the blower
motor
2.Check the A/C servo
If normal, to next step If abnormal, overhaul or replace the A/C servo
3.Check the noise filter
If normal, to next step If abnormal, overhaul or replace the noise
filter
4. Check the wire harness and connector between blower speed adjusting module and battery.
If normal, make next check following the malfunction If abnormal, overhaul or replace the wire
table. harness or connector.
●Check-up process
1.Check the A/C controller
Remove the A/C controller but also connected, start the engine and press down the AUTO button, test
the voltage between port 17-C11 of the A/C controller and the body. The voltage is less than 1V while
the A/C is running, and it is 10-14V while the A/C is closed.
If normal, to next step If abnormal, to step 5
2. Check the relay of the electromagnetic clutch
Remove the electromagnetic clutch relay in the engine compartment relay case, the resistance
betweenthe port B34 and B35 should be 50~95Ω, it shouldn’t be conducted between the port B62
and B36; connect the battery to the port B34 and B35, it should be conducted between the port B62
and B36.
If normal, to next step If abnormal, replace the relay of the
electromagnetic clutch
3.Check the electromagnetic clutch
Disconnect the A2 connector of electromagnetic clutch; connect the port A2 to the battery positive pole.
Connect the battery negative pole to the body. And the clutch should mesh with noise.
If normal, to next step If abnormal, replace the electromagnetic clutch
4. Check the wire harnesse and connector between compressor and relay, the wire harness and
connector between the compressor and the body.
If normal, make next check following the malfunction If abnormal, overhaul or replace the wire
table. harness or connector.
5. Check the A/C controller
Remove the connector 33-C11 of the A/C controller, turn the ignition switch to ON position, test the
voltage between port 33-C11 of the A/C controller and the body. The voltage should be 10-14V.
If normal, to next step If abnormal, overhaul or replace the A/C
controller
6.Check the engine ECM
Connect the connector 33-C11 of the A/C controller, start the engine and press down the AUTO button,
test the voltage between port 33-C11 of the A/C controller and the body. The voltage is less than 1V
while the clutch is connected, and it is 10-14V while the A/C is disconnected.
If normal, to next step If abnormal, overhaul and replace the engine ECM
7. Check the A/C controller
Start the engine and press down the AUTO button, test the voltage between port 32-C11 of the A/C
controller and the body. The voltage is less than 1V while the A/C is closed, and it is 10-14V while the
A/C is running.
If normal, to next step If abnormal, overhaul or replace the wire harness
or connector.
8. Check the wire harness and connector between A/C controller and engine ECM
If normal, replace the A/C controller If abnormal, overhaul or replace the wire harness
or connector.
1. Technical parameters:
Positon Torque/N·m
compressor 35N·m
Item Capacity
condensor 35ml
evaporator 30ml
piprline 10ml
drier 10ml
NOTE:
1. The maintenance for A/C system must be operated by professional technicians.
2. The maintenance area must be ventilated, don’t use the refrigerant in the close room or close
to fire. Wear the protection glass while maintenance.
3. Don’t get the refrigerant into eyes or skins. If it gets into eyes or skins, clean it with cold water,
don’t scrape it, coat Vaseline unguent on the skin. If it is serious, see the doctor as soon as
possible.
4. Don’t run the compressor if the refrigerant is not enough, avoid the compressor being burnt for
lack of refrigerant.
5. Don’t open the high pressure valve of the pressure gauge while the compressor is running, you
can only open or close the low pressure valve.
6. The refrigerant must be exclusive type for F3, mustn’t be replace or mixed with other type.
7. Total refrigerant capacity in the F3 AC system is 120ml, while the refrigerant is less than 110ml
because of leakage, it will cause excessive wear of compressor, so the service station should
refill the refrigerant according the situation.
8. The O-ring in the opened pipe must be replaced while maintenance, coat refrigerant on the seal
ring, then install it as stated torque.
9. Do the maintenance according to the technical requirement(capacity、refrigerant
type、torque )strictly, to ensure its normal working and usage period
10. The refrigerant is easy to absorb the water, jam the nozzle at once while remove the pipe, to
avoid the entry of moisture or dust.
11. While drain the excessive refrigerant in the outlet system, don’t drain too fast,or it will drain the
compressor oil in the system.
12. Clean the air filter periodically to maintain good ventilation.
13. Check whether the surface of condenser is dirty, don’t use steam or high pressure squirt gun
to clean it, or it will be damaged, you should use fur brush to clean it.
14. Don’t fill the excessive refrigerant. If the refrigerant is excessive, it will cause bad
refrigeration、bad fuel consumption、engine overheating and such problems.