Professional Documents
Culture Documents
Introduction
Abstract
The domestic refrigeration test rig ensures taking test on a set up having domestic
refrigeration its power consumption and exhaust unit is on separate location.Power
consumption unit incorporate compressor and exhaust unit condenser.The evaporator
is having bulb fitted inside which takes care of heat load.The heat load added can be
removed as time passes and EER is to be calculated.
Construction
The domestic refrigerator is having a vertical cabinet. The inside of which is
made-up of PVC material. The outside construction is of CRCA sheet metal duly
powder coated or epoxy coated paint. These two portions are separated by
polyurethane foam insulation.
The compressor ( a hermetically sealed one ) is located at the rear end bottom
portion. The condenser, which is made up of 5 mm dia MS tubes made in zig-zag
pattern. It is a natural convection type condenser. Small wire-like rods ( which are
called “fins”) are fixed to the tubes in order to enhance the heat transfer rate to the
surroundings. At the end of the condenser, there is filter /drier.
Inside the cabinet, at the upper portion, there is location of evaporator. The
evaporator tubes are made up of aluminum through which cold refrigerant
circulates. A suction line accumulator is fixed at the end of evaporator.
Suitable shelves, racks and compartments are provided inside the cabinet for the
required items to be stored and preserved.
Working
The refrigerator works on vapour compression cycle. The refrigerant vapour is
compressed by means of compressor to a pressure at which temperature obtained
at the end of compression will be more than the atmospheric so that, at this high
temperature, it will reject heat to the atmosphere and will then get condensed. The
condensate is then allowed to pass through a capillary so that the pressure and
temperature are lowered. Capillary tube acts as a throttling device. The low
temperature refrigerant enters the evaporator, where it absorbs heat from the
surrounding space and consequently, the refrigerant evaporates. This saturated or
superheated vapour is sucked by the compressor and the cycle is repeated.
Along with these major components, there will strainer/ drier and accumulator.
The strainer/drier will absorb residual moisture if at all present in the refrigerant
to avoid freezing in the capillary. The accumulator will not allow the liquid
refrigerant to enter into the compressor.
Defrosting
Frost is collected on the evaporator coil as the temperature of the coil is lower
than the freezing temperature of water. Frost thickness increases due to frequent
door opening. As Frost (ice) is poor conductor of heat, the accumulation of frost
on the coils adversely affects the heat transfer between the cabinet air and the
refrigerant. it increases the running time of refrigerator and hence power
consumption. Therefore regular de-frosting must be done when frost thickness
increases above 6 mm.
In the present case, the manual defrosting is done by pushing the red button,
which stops the compressor on pushing it. When the ice is melted, the compressor
will restart.
Equipments
Set of Experiments
Operation Instruction
= V1 x I1 4 1
Pressure
in
Where, kg/cm2
3. C.O.P ( Act ) :
Power Cosumed By Heater
= Power Consumed By Compressor
Nact
=
Wact.
Heo – Hei
4. Theoretical C.O.P =
Hci – Heo
Where,
Heo = Enthalpy of gas at evaporator outlet
Where,
TH = Saturated Temperature of Condenser Pressure in ° K.
6. COP Relative :
Actual C.O.P
Theoretical C.O.P
Observation table
S r. HP LP Tci Tco Tei Teo Tbath V1 I1 V2 I2
No oc oc oc oc oc
1. 12.5 0.5 45 42 -10 35 6 224 0.5 215 0.7
= V1 x I1
= 224 x 0.5
= 112 Watt.
= V1 x I1
= 215 x 0.7
= 150.5 Watt.
Nact 150.5
= =
Wact 112.0
= 1.34
4. Carnot C.O.P :
TL
=
TH - TL
Where
TL = Saturated Temp. of Evaporator
Pressure in 0 K
Where
LP = 0.5 Kg/Cm2
= 0.5 + 1.0133
= 1.5133 Kg/cm2
HP = 12.5 Kg/Cm2
= 12.5 + 1.0133
= 13.6133 Kg/cm2
256
Carnot C. O. P.=
( 324 – 256 )
= 3.76
Actual C.O.P.
=
Carnot C.O.P
1.34
= X 100
3.76
= 35.63 %
6. Theoretical C. O. P.
Heo - Hei
=
Hci - Heo
430 - 398
=
445 - 430
= 2.46
7. Ton of Refrigeration ( T )
= 150.5 x 60
210
112 x 10-3
=
0.043
= 2.06 Kwatt/Ton
Conclusion
The actual C.O.P. is less than the theoretical due to the losses at different
points also the temperature are measured at somewhat different positions.
Precautions
Questions :
1) Write some precautions to be ensured for domestic refrigerator.
2) Which type of compressor is used in domestic refrigeration ? Explain.
PROPERTIES OF R 134a
Procedure
1) Make sure that the electric connection and the system is to be closed for
precaution .
2) Initially,by starting the mains on take the readings for no load condition
when temperatures in equilibrium state.
3) Then a rotameter is used for measuring the flow rate of refrigerant and
pressure gauges P1 & P2 at inlet of compressor and at outlet of
compressor to be measured.
4) In the same way,increases the load on system by giving input to heater
using dimmerstat,so that the digital value of work input is to be taken.
5) Repeat the same procedure for various readings,hence to know the
performance of the VCR CYCLE SYSTEM.
Obervation Table :
Mass
Sr. T1 T2 T3 T4 T5 Compr. Heater P1 in P2 in of
No ℃ ℃ ℃ ℃ ℃ i/p (w) i/p (w) PSI PSI Refrig.
(LPH)
Calculations :
𝑇1
1) C.O.P carnot cycle = 𝑇2−𝑇1
ℎ1−ℎ4
2) C.O.P theoretical = ℎ2−ℎ1
Observations
1) Density of refrigerant ( ) = kg/m3
Result :
It is seen that for no load condition
COP Carnot =
COP Theoretical =
COP Actual =
Refrigerating Effect =
Conclusion :
Questions:
1)What would be the replacement for VCR Cycle and Why?
2)What is said to be the Heart of VCR System and Why?
Introduction
1. Plate Type.
2. Can Type.
Abstract
The Ice Plant Test Rig ensures taking test on ice plant which includes
making of an ice in 7 cans filled with water.The cooling effect is be given
with the aid of secondary refrigerant i.e glycol.It takes care for the
formation and retention of ice.
Reading for this test has to be taken from the start of test till the ice forms
in half an hour interval.
The sec ref temp. is first lowered down in minus degree celcius which then
gives the cooling effect to the ice cans further.
Description
The compressor is mounted at one side of base with a condenser & fan. A
liquid receiver is adopted in the circuit. The evaporator coil is held at one
side in the brine tank.
2. Condenser : Air cooled condenser size 14” x 14” with cooling fan.
3. Brine Tank : Brine tank insulated from all sides with provision to hold
cans, evaporator coil at one side & an arrangement to drain the brine
solution. A door is provided at the top of this tank.
i. High & Low pressure gauge : These gauges indicate, High & Low
pressure respectively in the circuit.
Empty before starting the Refrigeration Cycle please checks the following.
The pressure gauges should indicate equal pressure, that indicates HP &
LP side are balanced. Proper earthing is provided to unit. See that the
motor shaft along with fan is free in its bearing. This can be confirmed by
rotating the shaft manually cans concentration of brine.
Put water in the brine tank approximately up to mark. Add 100 Kgs. of
common salt into the tank without splashing the water. Then stir this
water by using the stirrer for sometime. If the strength is proper then close
door of the tank. Also confirm that there is no leakage at the drain of the
tank.
Test procedure
Now the unit is ready for the experiment. Start the condenser fan & after
2 - 3 minutes start the compressor. When the refrigeration circuit starts
functioning put the stirrer fan on. Note down the brine solution
temperature at certain interval of time say 1/2 Hr or so. The temperature
of the brine drops slowly. The stirrer may be put off for some time if
necessary. Now when the temperature of brine reaches 3 0 - 40 stop the
stirrer open the door of tank. Load the Ice cans on the frame of brine tank.
See that the cans contain water up to slightly below the level mark. Close
the door properly.
Note down the exact time when the cans are loaded. Now let the
Refrigeration system run for some time. The dial thermometer
temperature will rise. Then start the stirrer motor. The temperature of dial
thermometer will start dropping. The system runs continuously & the
observations are entered in the table. Now at the end of 24 Hrs period
from the loading the cans stop the stirrer motor. Open the door & see the
condition of water in the cans. The Ice should have formed. Take out the
cans properly. Deep the cans one by one in water tank so that the Ice slab
will come out. Weight the slab & confirm that weight of all slabs is 8 Kg.
If another test is to be repeated then load the cans properly filled with
water. And confirm formation of Ice at the end of 24 Hrs.
Observations
1. Date of Trial :
4. HP: LP:
Specimen calculations
From the pressure & temperature plot cycle on P-H chart, find out the heat
at four points. Now the theoretical COP can be calculated by :
heo - hei
hci - heo
Where,
3600 x Nc
=
Tc x EMC
Where,
Nc = 10 = No of Revolutions on energymeter.
EMC = Energy constant.
Tc = Time Required for Nc Revolution in Sec.
= W x ( Tw – T5 ) x cp
Where,
Precautions
1. The water used for Ice should be free of salt & other impurities etc.
Observations
0
1. Temp. of water in the can at the time of loading ( T w) = C
3. Starting time =
4. Date =
0
5. Refrigerant inlet Temp. to Evaporator ( T3 ) = C
0
6. Refrigerant Outlet Temp. from Evaporator ( T4 ) = C
0
7. Refrigerant Inlet Temp. to Condenser (T1 ) = C
0
8. Refrigerant Outlet Temp. from Condenser ( T2 ) = C
0
9. Brine solution Temp. ( Temp. of Ice ) T5 = C
Calculations
= m x ( Tw - T5 ) x Cp x Time
= KJ/hr
=
KJ/Sec.
2) Work Input :
= Voltmeter Reading x Ammeter Reading
= x
= Watt.
3) Actual C. O.P. :
4) Carnot C.O.P. :
TL
=
TH - TL
Where,
TL = Saturated Temp. of ,
Refrigerant at Evap. pressure
LP = PSI
=( x 0.0731 ) + 1.0133
= Kg/cm2
0
= K
HP = PSI
=( x 0.07031 ) + 1.0133
= Kg/cm2
0
= K
Carnot C. O. P.=
( – )
= X 100
= %
6. Theoretical C. O. P.
Heo - Hei
=
Hci - Heo
-
=
-
7. Relative C.O.P.
Actual C.O.P.
=
Theoretical c.O.P.
8. Ton of Refrigeration ( T )
Refrigeration Effect Produced in K J/Min
=
210
N act X 60
=
210
X 60
=
210
= ton of refrigerant
Conclusion :
Questions :
1) Classify refrigerants.
2) Note down ideal properties of refrigerants.
3) Which is the best suited primary refrigerant for domestic use ?
PROPERTIES OF R 134a
Temp Pressure Enthalpy of Enthalpy of
Liquid Vapour
[0C] [bar] [kj/kg] [kj/kg]
-50 0.2945 135.7 367.7
-49 0.3121 136.9 368.3
-48 0.3305 138.2 368.9
-47 0.3498 139.4 369.6
-46 0.37 140.6 370.2
-45 0.3912 141.9 370.8
-44 0.4133 143.1 371.5
-43 0.4364 144.4 372.1
-42 0.4606 145.6 372.7
-41 0.4858 146.9 373.4
-40 0.5121 148.1 374
-39 0.5395 149.4 374.6
-38 0.5682 150.7 375.3
-37 0.598 151.9 375.9
-36 0.6291 153.2 376.5
-35 0.6614 154.4 377.2
-34 0.6951 155.7 377.8
-33 0.7302 157 378.4
-32 0.7666 158.2 379.1
-31 0.8044 159.5 379.7
-30 0.8438 160.8 380.3
-29 0.8846 162.1 380.9
-28 0.927 163.3 381.6
-27 0.971 164.6 382.2
-26 1.017 165.9 382.8
-25 1.064 167.2 383.4
-24 1.113 168.5 384.1
-23 1.164 169.8 384.7
-22 1.216 171.1 385.3
-21 1.271 172.3 385.9
-20 1.327 173.6 386.6
-19 1.386 174.9 387.2
-18 1.446 176.2 387.8
-17 1.508 177.5 388.4
-16 1.573 178.8 389
-15 1.639 180.1 389.6
-14 1.708 181.4 390.2
-13 1.779 182.8 390.8
-12 1.852 184.1 391.5
-11 1.928 185.4 392.1
-10 2.006 186.7 392.7
-9 2.086 188 393.3
-8 2.169 189.3 393.9
Precautions :
1) Work in a clean,well ventilated and dry area.
2) Wear gloves,goggles,apron or clothing which covers the body when working.
3) Ensure the appliance is disconnected from the main electric supply before
carrying out any work on it.
4) Take care while opening the system as the pressure inside the system is
generally higher than atmospheric pressure.
5) Keep systems & components sealed.Repair & replace components as necessary.
6) Change the filter drier whenever the system is opened for maintenance or if it is
contaminated.
7) Liquid refrigerant causes frostbite if it comes into contact with human skin.for
protection wear personal protective equipement (PPE)
8) The refrigerant in the air conditioner may be contaminated with acids.Ensure it
does not come into contact with the skin.
9) The compressor oil may also be acidic,so wear gloves and goggles when
removing or repairing faulty compressor.
10) Always use a two stage pressure regulator ( upto 50 bar ) when using nitrogen.
11) Ensure that all hoses are free from cracks and have adequate strength to
withstand high pressures.
12) Charge the system with correct quantity of good quality refrigerant.
13) Seal the charging point by brazing and then test for leakage.
14) Do not modify cylinder/can or valves.
15) Do not refill disposable cylinders / cans.
Conclusion :
By doing this, We can able to install,uninstall & repair / servicing of split air
conditioner at home.