Wavelength
FT-H10/H20/H30
655 nm
FT-H50/H40K/H50K
Instruction Output 90 µW
Manual
Laser Class
(IEC60825-1, FDA(CDRH) Part 1040.10*)
sensor head
Handling measurement
through hole
1. Do not drop the FT series products, bang them against something, or
NOTICE
apply excessive force. Handle the product by holding it by the main body.
2. Do not pull heavily on the cable.
3. Do not use a sharply pointed object to press the setting keys. Refer to the table below for the diameter of the measurement hole on the
covering board.
Wiring
Detection distance 200 400 600 800 1000 1200 1400 1600
CAUTION 1. Before wiring the FT series, check the color of the wires. Hole diameter φ 30 60 90 120 150 180 210 240
2. Use the FT series within the rating range. Do not use a load that
exceeds the allowable limit. Unit: mm
NOTICE
1. Use an insulated stabilizing supply for the power supply. Cleaning
2. Do not apply excessive tensile force to the cable.
3. Ensure that the cable tip does not become submerged in water Dirt on the sensor lens may result in errors. Clean the lens as shown in the out-
during wiring work. line below. Make sure to turn off power to the sensor before cleaning the lens.
4. Isolate the cable from power supply lines or power lines.
5. Keep the cable as far as possible from any source of noise.
Other
1. Three seconds after supplying power to the FT series is its power
NOTICE
ON reset time. Do not use outputs from the sensor during this
period.
2. The display value may drift immediately after turning on the
Get rid of dust on the lens by using a blower If the lens is badly soiled, gently wipe it with a
power. In this case, make sure to use the FT Series after warm- made for cleaning camera lenses. Do not at- cotton swab. If the dirt still cannot be removed,
ing up for 15 to 30 minutes. tempt to remove dust by breathing directly on the dip the swab in a small amount of alcohol and
lens. wipe the lens. Do not use an organic solvent oth-
er than alcohol under any circumstances.
When used in an environment with high dust, use the FT-S1 tough box with air
purge function. For details about FT-S1, contact your nearest KEYENCE office.
E FT-IM
1
■ FT-55A/55AP (Types with attached panels)
Checking the Package Contents
Before using the FT Series, check that the following items are all included in
1 Create a panel opening for mounting referring to the dimensions below.
(unit: mm)
the package for each model.
X=24x(A-1)+21
■ Sensor Head When 'A' units are
FT-H10/H20/H30 FT-H50/H40K/H50K X mounted side-by-side
45
83.1
+0.4
21 +0.1
anchoring ring
The sensor head cable and power cable are each equipped with connector
Front protection covers.
Power cable *2
cover*3 x1 Point After the connectors are inserted into the amplifier, attach the connector
(2m) x1
covers over the connectors. Finally, lock the base of the connector covers
with the anchoring rings.
Instruction manual x1
Unit cover sticker (black sheet)*4 x1
Mounting the Sensor Head
Power cable *2
(2m) x1
■ Identifying Names of Parts of the Sensor Head
output 1 operation
output 1 operation output 2 operation
indicator
Instruction manual x1 output 2 operation indicator indicator
Unit cover sticker (black sheet)*4 x1 indicator
power indicator
power indicator
*1 Also sold separately as OP-76877.
*2 Also sold separately as OP-82488.
*3 Also sold separately as OP-51476 (set with the panel mounting bracket and protective front cover).
*4 When using the Infrared Radiation (IR) mode, use this to cover the ”°C” mark.
laser emission
areas
We have thoroughly inspected the package contents before shipment. However, in the case of
defective or broken items, please contact your nearest KEYENCE office.
infrared radiation collector laser emission areas
lens tube
FT-H10/H20/H30 FT-H50/H40K/H50K
Mounting the Amplifier Unit
■ FT-50A/50AP (Types with attached DIN rail)
1 Align the tab at the bottom of the amplifier 3 ■ Connecting the Sensor Head Cable to the Amplifier
with the DIN rail. While pushing the amplifier Connect the sensor head cable to the
in the direction of arrow 1, slant it in the left side of the amplifier.
direction of arrow 2. Insert the connector in the direction as
2 indicated by the diagram showing the
2 To detach the amplifier, raise it in the direc-
1
direction of connector insertion.
tion of arrow 3 while pushing it in the direction of arrow 1.
Securely insert the sensor Insert the cable
head cable deep into the con- until you hear a click.
Fitting the Amplifier with a Mounting Bracket Point nector.If not inserted com-
pletely, the connector can connector cover
Fix the amplifier as shown in the diagram using
the included mounting bracket. easily become disconnected. anchoring ring
Amplifier mounting
bracket
E FT-IM
2
● If the cable has been cut to a shorter length, install the connector as follows:
FT-H40K
1 Cut the cable to an appropriate
approx. approx.
26
ø11
26
ø7.5
26
ø6
26
ø4
26
ø11.5
laser pointer distance (typical example)
view width (mm)
connector connector
It is not necessary to remove
cover body
Point the covering from the core
wires.
0 100 150 200 300 detection distance (mm)
connector
2 Insert the cables according to the lock
Measurement View and Sight 0 500 1000 1500 2000 3000 detection distance (mm)
To help fix the sight when measuring, the sensor is equipped with laser point-
ers.
• Fix the sight so that the area you want to detect the temperature of falls in
between the two laser pointers.
• When high accuracy is necessary, use a view width that is 1.5 or more
times smaller than the measurement target.
Switching Displays and Basic Settings
FT-H10 laser pointer distance
21 10.5 0 10.5 (typical example)
ø11 ø6.3 ø1.5 ø8 view width (mm)
laser pointer
measurement
area
target
FT Series C
SELECT BANK
pointer distance
set mode
button button
bank selection
preset value indicator timing
indicator indicator
FT-H20
24.5 13 8 17 laser pointer distance (typical example)
ø11 ø8.5 ø6 ø14.5 view width (mm)
Switching Displays
TIM
press
SELECT BANK
TIM
C Hold Display
FT Series C
press
press SELECT BANK
press
0 200 400 600 detection distance (mm)
TIM
C Hold Display
FT Series C
press
SELECT BANK
TIM
they will appear to rotate clockwise, as shown in the above diagrams. press
SELECT BANK
TIM
SELECT BANK
TIM
See “Detection Mode” on p.6 for “Temperature Mode” and “Infrared Radiation
(IR) Mode”.
0 500 1000 1500 2000 3000 detection distance (mm)
E FT-IM
3
Basic Settings Automatically Setting the Preset Value
● Setting Emissivity (Temperature Mode only) The preset value can automatically be set. This is set from Temperature (Infra-
See option 5 on p. 5 for more about selecting Temperature Mode. red Radiation)/ Preset Value display screen (B).
A Specify the settings from the Temperature/Emissivity display screen. ■ Two-Point Calibration
FT Series C
SELECT BANK
TIM
1 Press once without a target.
“SEt” will begin flashing in the preset
value display.
1 Press to start setting the emissivity.
C
FT Series
TIM
Point display will read "FFFF" when the gap between the target and the ambient
SELECT BANK
temperature is small. In this case, set the temperature with a warmer target TIM
■ Fully-Automatic Calibration
3 After entering all the values, press to complete the setting.
C
When the values are set properly, the set values
FT Series
blink, and the screen returns to the
1 Let the target pass by while pressing
and holding .
Temperature/Emissivity display.
SELECT BANK
TIM
2 Check that is flashing in the
display, and releae .
● Setting the Preset Value Manually FT Series C
(Press and hold
B Change the settings from the Temperature (Infrared Radiation)/Preset Value display screen. SELECT BANK
for 3 or more
FT Series C TIM seconds and the
Press to change the preset value. display will flash.)
SELECT BANK
or buttons. The preset value will be displayed. The preset value will be the median of
The preset values can be set by bank. the maximum and minimum values measured while was held down.
FT Series C
TIM
SELECT BANK
TIM
Value 2 when Preset Value 2 is selected.
press
When Auto Hold is selected,
the lower display reads " ". ■ Introducing Options
press press
Alternates between displays If the emissivity and temperature of the measurement target are unknown, use the
FT Series C
optional blackbody tape or blackbody spray to take simplified measurements.
Bottom Display
press C
Option Blackbody Tape Blackbody Spray
SELECT BANK FT Series
TIM
•
•
The laser emits.
The laser emissions stop.
3 Measure the temperature of the portion of the target covered in blackbody
tape and take note of the measured value.
• The laser emits only when it receives a timing signal.
(Can be selected when is set for option 7 on p. 5) 4 Measure the temperature of the target on an area that is close to the area
measured in 3, but not covered in blackbody tape.
Laser ON/OFF does not affect detection.Use it as a rough indication of the
measurement view. 5 Choose "Set by temperature" and enter the temperature measured in 3 to
set the emissivity.
E FT-IM
4
Setting Each Mode
FT Series C
7 Switch input 2 (purple line) p.6
C
SELECT BANK
FT Series
Press to select the option.
TIM
• Not used
SELECT BANK
TIM
• Bank input
• Timing input
Press and hold for 3 or more seconds * When IR mode is selected, bank input cannot be chosen.
TIM
H40K/ • Displays temperature in 0.1ºC units
H50K
When USEr
is selected Hysteresis width setting
press
Press to select the option.
C
"Temperature Mode"
3 Switch response time
FT Series
0 to 520 (H10/H20/H30/H50)
C
FT Series
Press to select the option. SELECT BANK 0 to 1400 (H40K/H50K)
• High speed TIM * The setting unit is the one selected at
SELECT BANK option 2.
TIM • 0.03 sec "Infrared Radiation Mode"
• 0.1 sec 0 to 9999
press
• 0.2 sec 0 to 2500 (H50 only)
• 0.5 sec
• 1 sec
press • 5 sec
9 Select hold value display p.7
FT Series C
Press to select the option.
• Peak/bottom
4 Switch output mode SELECT BANK
TIM
• Automatic peak/bottom hold
FT Series C
Press to select the option.
Output 1 Output 2
SELECT BANK
• N.O. N.O.
TIM
press
• N.C. N.O.
• N.O. N.C.
• N.C. N.C.
press 10 Select power save mode p.7
FT Series C
Press to select the option.
• Normal operation
SELECT BANK
C TIM
• Operate in power save mode
FT Series
Select to end/continue the menu
Press to select the option.
SELECT BANK
FT Series C
Analog output upper limit setting 1 While holding down , press five times until FT Series C
Press to select the option. “rSEt/no” appear in the displays. SELECT BANK
TIM
SELECT BANK
Setting range
TIM
-50 to 520 (H10/H20/H30/H50)
press
-50 to 1400 (H40K/H50K)
* The setting unit is the one selected at option 2. 2 Press or to select “YES”. FT Series C
SELECT BANK
E FT-IM
5
■ Selecting the Bank
Settings for Each Mode
Selecting with Operation Keys
If key lock is on, cancel the key lock (p. 7) and follow the steps below.
Operation Mode
1 Switch to Temperature/Emissivity display, as shown in “Switching
■ Upper Limit Detection Mode Displays” (p. 3).
(F-1) P1
Hys 2 While holding down , press or .
This mode detects when the tempera-
P2 Hys C
ture rises above a fixed value. FT Series
limit. TIM
Output 2 OFF ON OFF Switch between the banks in the following manner depending on the input/out-
put 1/2 settings.
Output 1 Turns ON when the temperature (or amount of infrared radiation) rises
above preset value 1 (P1). • Bank input is selected only for input /output 1 (option 6 on p.5)
Turns OFF again when the value falls below the range of hysteresis Bank 0 Bank 1
from preset value 1.
Output 2 Turns ON when the temperature (or amount of infrared radiation) rises • Bank input is selected only for input /output 2 (option 7 on p.5)
above preset value 2 (P2).
Turns OFF again when the value falls below the range of hysteresis Bank 0 Bank 2
from preset value 2.
• Bank input is selected for both input /output 1/2 (option 6, 7 on p.5)
Bank 0 Bank 1 Bank 2 Bank 3
■ Lower Limit Detection Mode
Hys
(F-2) P2 Selecting from External Inputs
This mode detects when the tempera-
P1
Hys 1 Turn on key lock (p. 7).
ture falls below a fixed value.
• Two points can be set for the lower 2 Short-circuit the pink (or purple) line for 20 ms or longer in the following manner.
limit. FT-50A/55A FT-50AP/55AP
Output 1 OFF ON OFF brown brown
Output 2 OFF ON OFF +V +V
Output 1 Turns ON when the temperature (or amount of infrared radiation) falls pink
blue (purple)
below preset value 1 (P1). 0V
Turns OFF again when the value rises above the range of hysteresis pink
from preset value 1. (purple) blue
0V
Output 2 Turns ON when the temperature (or amount of infrared radiation) falls
below preset value 2 (P2).
Turns OFF again when the value rises above the range of hysteresis Bank No. Pink Line Purple Line
from preset value 2.
0
1
■ Upper/Lower Limit Detec-
P1 2
tion Mode (F-3) Hys
This mode detects when the tempera- 3
ture falls outside of a fixed range. Hys
P2
• One point each can be set for the It will take 20 ms to reflect the bank selection.Until the selection is reflected,
upper and lower limits. the sensor retains the same condition as before the bank change.
Output 1 OFF ON OFF
After selecting the bank, the display and output assessment will contain the
Output 2 ON ON
OFF following time lag.
Output 1 Turns ON when the temperature (or amount of infrared radiation) rises - Display (digital numbers) : about 0.1 sec
above preset value 1 (P1). - Output Assessment : 20 ms plus response time
Turns OFF again when the value falls below the range of hysteresis
from preset value 1.
[Ex.] When output is OFF before bank change and ON after bank change
Output 2 Turns ON when the temperature (or amount of infrared radiation) falls
below preset value 2 (P2).
Turns OFF again when the value rises above the range of hysteresis
from preset value 2. bank input
OFF ON
control output
Detection Mode 20ms + response time
■ Temperature Mode
This mode uses the set emissivity to convert the amount of received infrared Analog Output
radiation into temperature, and displays this number in degrees. See “Setting
Emissivity” on p. 4 for more about setting the emissivity.
■ Temperature Mode
The output changes from 4mA to 20mA depending on the lower limit (A-Lo)
■ Infrared Radiation (IR) Mode and the upper limit (A-Hi).
• See option 5 on p.5 for the setting of A-Lo and A-Hi.
This mode displays the amount of received infrared radiation in the range of 0
to 9999 (0 to 2500 for the FT-H50).
For 0 °C (A-Lo) and 500 °C (A-Hi) For 200 °C (A-Lo) and 400 °C (A-Hi)
Analog output Analog output
Bank Function (Temperature Mode) (mA) (mA)
E FT-IM
6
Timing Input Upper Limit Range Error • Return the sensor
FT Series C Reading exceeds the within the rated
This option can be used when you want to assess the control output or display
upper limit of the detection temperature range.
the temperature for only a limited period of time. SELECT BANK
range. • Set the emissivity to
To use timing input, set “Switch input (purple line)” (option 7 on p. 5) to timing
TIM
an appropriate value.
input. Lower Limit Range Error • Return the sensor
• The temperature (infrared radiation) display and output is assessed only FT Series C Reading exceeds the within the rated
when the sensor receives the timing signal. lower limit of the detection temperature range.
When the timing signal is not received, the temperature (infrared radiation) SELECT BANK
TIM
range. • Set the emissivity to
display lights one segment at a time in order. (When analog output is being an appropriate value.
used, the analog output operates normally no matter what timing input is
used.)
The temparature (infrared radiation) display normally flashes one segment
at a time in order. Input/Output Circuit Schematic
• After receiving the input signal, the display and output assessment will ■ FT-50A/55A
contain the following time lag.
– Display (digital numbers) : about 0.1 sec Input/output circuit schimatic
– Output Assessment : 2 ms plus response time Brown
12 to 24V DC
Black
Main circuit
Hold Display White
Load 5 to 40V DC
(Control output 2)
Load 5 to 40V DC
■ Peak/Bottom Hold
Blue
0V
The peak/bottom hold values will be displayed after turning the power ON or Analog output/Bank input1/
after the hold values are reset (see p. 4 C). Input/output circuit1
Pink selectable
Timing input/Bank input2/
Purple selectable
■ Auto Peak/Bottom Hold Input circuit 2
The peak value updates when the temperature rises above the P1 preset External input circuit
value. Likewise, the bottom value updates when the temperature drops below Analog output circuit (Bank input 1 & 2, Timing input)
the P1 preset value. Pink Analog
5V
output
Main circuit
[Ex.] Peak Hold Value Update [Ex.] Bottom Hold Value Update (4 to 20 mA)
Main circuit
Pink/
peak hold Blue Purple
0V
temperature display value temperature
Blue
preset value preset value
■ FT-50AP/55AP
bottom hold
display value
Input/output circuit schematic
Peak Hold updates when the temperature Bottom Hold updates when the temperature Brown
climbs above the reset value and holds until falls below the reset value and holds until 12 to 24V DC
Black
Overcurrent protection circuit
the next time the temperature peaks. the next time the temperature falls.
(Control output 1)
Main circuit
White
(Control output 2)
Power Save Mode Load
Load
When Power Save Mode is turned ON (option 10 on p. 5), the power save dis- Blue
0V
play will turn on after three minutes of inactivity. Pink Bank input 1/analog output:
Input/output circuit1
• When the power save display is on, only one segment C FT Series
Selectable
will blink in the preset value display. Input circuit 2
Purple Bank input 2/timing input:
Selectable
The output indicator, bank indicator, and timing indi- SELECT BANK
TIM
(4 to 20 mA)
Main circuit
TIM
Emissivity
The following chart shows examples of emissivity.
To release key lock, press and hold + (or + ) for about three
seconds in key lock mode. Substance Emissivity Substance Emissivity
• When “unL” flashes in the preset value display, key FT Series C Asphalt 0.90 to 0.98 Leather 0.75 to 0.80
lock has been released. Concrete 0.94 Charcoal (powder) 0.96
SELECT BANK
Cement 0.96 Lacquer 0.80 to 0.95
TIM
TIM
range. substance. It can also differ according to the surface condition (bumps and
irregularities) or thickness of the same substance.
E FT-IM
7
Specifications
■ Sensor Head
Low / Medium Temperature High Temperature
Type
Small Spot Mid Range Long Range Ultralong Range Mid Range Ultralong Range
Model FT-H10 FT-H20 FT-H30 FT-H50 FT-H40K FT-H50K
Rated temperature range *1 0 to 500°C 0 to 1350°C
Display temperature range -50 to 520°C -50 to 1400°C
Detection distance No limits*2
17.5 / φ 6.3 mm 60 / φ 8.5 mm 200 / φ 15 mm 500 / φ 18 mm 100 / φ 7.5 mm 500 / φ 18 mm
view width/Measuring distance (typical examples) 35 / φ 1.5 mm 120 / φ 6 mm 400 / φ 18 mm 1500 / φ 30 mm 200 / φ 4 mm 1500 / φ 30 mm
52.5 / φ 8 mm 180 / φ 14.5 mm 600 / φ 33 mm 3000 / φ 75 mm 300 / φ 11.5 mm 3000 / φ 75 mm
Sight*3 Two visible light lasers
Detection components Thermopile
Detection wavelength 8 to 14 μm
Reproducibility ±0.5°C ±3°C
Emissivity (ε) correction 0.10 to 1.99 (0.01 steps)
Operating ambient
-10 to +55°C (no freezing)
temperature
Environmental Operating ambient
35 to 85% RH (no condensation)
resistance humidity
Vibration resistance 10 to 55 Hz, 1.5 mm double amplitude, 2 hours in each XYZ axis
Shock resistance 500 m/s2, 10 times in each direction of each axis XYZ, total 60 times
Case: glass-reinforced polyetherimide
Infrared radiation collector lens: germanium
Material Laser emission areas: polyarylate
Lens tube*4: aluminum, Cable: vinyl chloride
Mounting bracket: SUS304
Weight Approx. 120 g Approx. 150 g
* 1: The specifications are guaranteed within the rated temperature range.
* 2: Use a distance where the detection target is at least 1.5 times as large as the view width.
* 3: Semiconductor laser, Wavelength 655nm, Class 1 Laser Product (IEC60825-1, FDA (CDRH) Part 1040.10)
The laser classification for FDA(CDRH) is implemented based on IEC60825-1 in accordance with the requirements of Laser Notice No.50.
* 4: The FT-H10/H20/H30 does not have the lens tube.
■ Amplifier
Type DIN rail mounted type Panel mounted type
NPN output FT-50A FT-55A
Model
PNP output FT-50AP FT-55AP
Power voltage*1 12 to 24 VDC*3, Ripple (P-P): 10% max, Class2 or LPS
Normal mode 1400 mW (12 V), 1600 mW (24 V)
Current consumption
Power Save Mode 1150 mW (12 V), 1350 mW (24 V)
4 + half digit 7-segment LED
Display method
Red and green dual display (Uppercase letter height: Upper display: 8 mm (red), Lower display: 5.7 mm (green))
Operation indicators Red LED x 3 (corresponding to Control Output 1, Control Output 2, and Timing Input)
Display resolution (when using H10/H20/H30) 0.1 or 1°C, (when using H50 / H40 / H50K) 1°C
Hysteresis (hys) Variable
Responsiveness Select HSP, 30 ms, 100 ms, 200 ms, 500 ms, 1000 ms, 5000 ms (HSP: representative example is 10 ms, 15 ms max.)
Switch bank Switch between timing input line and analog output line to set bank input / up to 4 banks can be set
Bank specifications Emissivity (temperature mode only) and preset value x 2 can be set for each bank
Timing input Input time: 2 ms or more
External input
Bank input Input time: 20 ms or more
NPN (PNP) open collector x 2 ch
Control output
(N.O./N.C. selectable), 40VDC (30VDC) or less,Max 100 mA (50mA), Residual voltage: 1 V or less
4 to 20mA, maximum load resistance 260Ω
Analog output
(Upper/lower limit range for analog output can be set optionally)
Operating ambient
-10 to +50 °C (no freezing)
temperature*2
Environmental
resistance Operating ambient 35 to 85% RH (no condensation)
humidity
Vibration resistance 10 Hz to 55 Hz, 1.5 mm double amplitude, 2 hours in each XYZ axis
Main unit and cover: polycarbonate
Main unit Keycaps: polyester elastomer
Material Cable: vinyl chloride
Mounting bracket Mounting bracket: SPCC Mounting bracket: polyacetal
Front protection cover: polycarbonate
Weight Approx. 85 g
* 1: Use with the over current protection device which is rated 24V or more and not more than 1A.
* 2: When using analog output: -10 to +45°C.
* 3: When using this product as an UL recognized product, use the power supply with Class 2 output defined in NFPA70 (NEC: National Electrical Code).