Professional Documents
Culture Documents
5-H
AALBORG TABLE OF CONTENTS
INDUSTRIES
IMO 9312494
DSIC T3000-8 _ . . - ' .
Table of contents
Heat-exchanger 10
Smoke density equipment 11
Oxygen analyzer 12
Drawings 13
Datasheets 14
Performance curves 15
Table of contents
1 General data
• ProjectNo.: 737695, 737697, 737699, 738154, 738156, 738158
• ProjectNo.: 738160, 739388, 738390
• Hull No.: T3000-8/9/10/11/12/13/14/16/17
• Classification society: LRS
• Pressure gauge calibration: Bar g
• Thermometer calibration: °C
• Language for signs: UK
11 Manuals
Table of contents
Flow diagrams
Steam/water system X01:029851h
List of parts for steam/water flow diagram X01:029851h
Oil system X02:029894c
List of parts for oil system „ X02:029894c
Burner unit 92X02:038042
List of parts for burner unit flow diagram 92X02:0038042
Feed water
pumps
lii
Steam Oato
Water
Chemicals
NOTE: Cust6mer Dalian New Shipyard 2 x MiSSIWJ Wyfe Kdd 550OO+1 x AQ-2 2000 !f# ISk 14.01.2004
- Components specified by item no. are supplied by Al Oils
Air Society LRS LRS LRS LRS LRS LRS LRS LRS LRS Steam/water system KMo 14.01.2004
- Items: see separate list of parts. T3000-8 T3000-9 T3000-10 T3000-11 T3000-12 T3000-13 T3000-14 T3000-16 T3000-17
Blow down/drain lines Newb. No. Feed water regulation modulating / on-off seal*:
External wiring - For electrical connections, see actual electrical wiring diagrams. 1:1 A1
Project No. 737695-96 737697-98 737693-700 738154-55 738156-57 738158-59 738160-61 739388-89 739390-91
Oil - * Instrument air AALBORG Row diagram AitWeJDrawtngNM
Exhaust gas BoilefNo. 14187-88 14190-91 14193-94 14784-85 14787-88 14790-91 14793-94 16231-32 16234-35
INOUSDIES
Boiler No. 14189 14192 14195 14786 14789 14792 14795 16233 16236 XO1 :029851
I
AALBORG
INDUSTRIES
List of Parts for Oil Fired Boiler Type MISSION D-type Rev: g Class.:
"Steam/Water Flow Diagram", Drawing No.: X01:029851g Date: 03.05.2005 LRS
Item Qty Dim Description Applications Data Sheet
No DN or Drawing
1C l Vertical two-drum D-type boiler 50t/h- 05Y:029875
7/20-22 bar g
Cl 2 65/100 Safety valve Boiler 261 1174
C2 1 250 Stop valve with stellited seat & cone Main steam valve 6010 000085
C3 2 100 Stop valve with stellited seat & cone Feed water valve 6010 000092
C4 2 100 Stop-check valve Feed water valve 6030 000032
with stellited seat & cone
C5 1 40 Stop-check valve Scum valve 6030 000016
with stellited seat & cone
C6 1 40 Stop valve Scum valve 6010 000037
with stellited seat & cone
C7 1 50 Stop-check valve Blow-down valve 6030 000035
with stellited seat & cone
C8 1 50 Stop valve Blow-down valve 6010 000130
with stellited seat & cone
C9 1 1/2" Stop valve Sample valve 6220 000002
CIO 1 1/2" Stop valve Air valve 6220 000002
Cll 1 1/2" Stop valve Gauge board valve 6220 000002
C14 1 250 Check valve Main steam check valve 6020 000023
C15 1 25 Stop valve By-pass steam valve 250 1088
C16 2 50 Valve Furnace drain valve 253 1005
C17 1 25 Water level gauge, left Water level indicator 7010 000136
C18 1 25 Water level gauge, right Water level indicator 7010 000135
C23 1 Heating coil
*C24 1 25 Stop valve Heating coil inlet 250 1088
*C25 1 25 Stop valve Heating coil outlet 250 1088
C26 1 15 Safety valve for heating coil 261 1358
C27 2 25 Stop valve for item W16 250 1088
C28 2 25 Stop valve for item W14 250 1088
C30 1 Gauge board (mounted on burner) Boiler
C179 1 1300 Smoke uptake 05K37:032015
C123 1 80 Soot blower stop valve Steam flow 250 1093
C125 2 Soot blower Manual Clyde SR/V/D
C130 1 3/4" Drain valve for soot blower Instrument stop valve 6000 000012
C184 2 Expansion for safety valve 85Y:013427
C186 2 Remote pull for safety valve K03:019136
C187- 2 Remote pull for water level gauge K03:019137
y
'i/8 ' . > • • ' - • '• ••••' ':
AALBORG
INDUSTRIES
List of Parts for Oil Fired Boiler Type MISSION D-type Rev: g Class.:
"Steam/Water Flow Diagram", Drawing No.: X01:029851g Date: 03.05.2005 LRS
Item Qty Dim Description Applications Data Sheet
No DN or Drawing
1C 1 Vertical two-drum D-type boiler 50t/h- 05Y:029875
7/20-22 bar g
C195 1 15 Steam trap 7020 000001
C211 1 Counter flanges incl. gaskets and bolts K16:004096
C212 set (not shown on the flow diagram)
C213
C213
C227 1 80 Control ball valve with micro switch 6050 000152
and solenoid valve (IGS interlock)
L2 1 Boiler control panel
W14 1 25 Water level switch 8100 000008
W16 1 25 DP unit 70Z:019540
:
' • 2 / 8 • "• ••'. * '
AALBORG
INDUSTRIES
List of Parts for Oil Fired Boiler Type MISSION D-type Rev: g Class.:
"Steam/Water Flow Diagram", Drawing No.: X01:029851g Date: 03.05.2005 LRS
Item Qty Dim Description Applications Data Sheet
No DN or Drawing
2C 1 Vertical two-drum D-type boiler 50t/h- 05Y:029875 "
7/20-22 bar g
Cl 2 65/100 Safety valve Boiler 261 1174
C2 1 250 Stop valve with stellited seat & cone Main steam valve 6010 000085
C3 2 100 Stop valve with stellited seat & cone Feed water valve 6010 000092
C4 2 100 Stop-check valve Feed water valve 6030 000032
with stellited seat & cone
C5 1 40 Stop-check valve Scum valve 6030 000016
L with stellited seat & cone
C6 1 40 Stop valve Scum valve 6010 000037
with stellited seat & cone
C7 1 50 Stop-check valve Blow-down valve 6030 000035
with stellited seat & cone
C8 1 50 Stop valve Blow-down valve 6010 000130
with stellited seat & cone
C9 1 1/2" Stop valve Sample valve 6220 000002
CIO 1 1/2" Stop valve Air valve 6220 000002
Cll 1 1/2" Stop valve Gauge board valve 6220 000002
C13 1 25 Stop-check valve Atomising steam valve 6030 000001
C14 1 250 Check valve Main steam check valve 6020 000023
C15 1 25 Stop valve By-pass steam valve 250 1088
C16 2 50 Valve Furnace drain valve 253 1005
C17 1 25 Water level gauge, left Water level indicator 7010 000136
C18 1 25 Water level gauge, right Water level indicator 7010 000135
C23 1 Heating coil
*C24 1 25 Stop valve Heating coil inlet 250 1088
*C25 1 25 Stop valve Heating coil outlet 250 1088
C26 1 15 Safety valve for heating coil 261 1358
C27 2 25 Stop valve for item W16 250 1088
C28 2 25 Stop valve for item W14 250 1088
C30 1 Gauge board (mounted on burner) Boiler
C179 1 1300 Smoke uptake 05K37:032015
C123 1 80 Soot blower stop valve Steam flow 250 1093
C125 2 Soot blower Manual Clyde SR/V/D
C130 1 W Drain valve for soot blower Instrument stop valve 6000 000012
..
C184 1 Expansion for safely valve 85Y:013427
C186 1 Remote pull for safety valve K03:019136
V:\Marine\Order\737xxx\737695~700\0800 Documentation\0810 Flow diagrams - steam water\737695.doc737695.doc
:: ;:
3/8 •- , , ' '
AALBORG
INDUSTRIES
List of Parts for Oil Fired Boiler Type MISSION D-type Rev: g Class.:
"Steam/Water Flow Diagram", Drawing No.: X01:029851g Date: 03.05.2005 LRS
Item Qty Dim Description Applications Data Sheet
No DN or Drawing
2C 1 Vertical two-drum D-type boiler 50t/h- 05Y:029875
7/20-22 bar g
C187 1 . Remote pull for water level gauge K03:019137
C195 1 15 Steam trap 7020 000001
C211 1 Counter flanges incl. gaskets and bolts K16:004096
C212 set (not shown on the flow diagram)
C213
C213
C227 1 80 Control ball valve with micro switch 6050 000152
and solenoid valve (IGS interlock)
L2 1 Boiler control panel
W14 1 25 Water level switch 8100 000008
W16 1 25 DP unit 70Z:019540
:
5/8 - - ' -• -
AALBORG
INDUSTRIES
6/8 .
AALBORG
INDUSTRIES
7/8 . • , , ; *
AALBORG
INDUSTRIES
8/8
G47 data sheet changed
Revised according to order
Instrument air
max. 10 bar
min. 5 bar
JL fl G114
J I
Steam
max. 16 bar
min. 6 bar
Water
- All heavy fuel oil piping to be steam traced piping and insulated
Chemicals
- Components specified by Tag No. are supplied by Al.
Dalian New Shipyard Flow diagram, oil system
Air
For 2 x steam atomising burner size 4150
Blow down/drain lln - Components: see separate list of parts.
External wiring - Electrical wiring connections shown is our standard.
Oil For actual plant we refer to electrical wiring drawings. AALBORG
Exhaust gas Article/Drawing No:
INDUSTRIES
THtS DRAWING AND DESIGN SHOWN HERON IS THE PROPERTY OF AALBORG INDUSTRIES
AND MUST HOT 8E USED BY OR REPRODUCED FOR THIRD PAHTY X02:029894
Tag No./
Item PCS. Designation Dimension Article No.
1F 1 Burner unit, chosen by project
1F.1 1 Burner front plate incl. lance 4800000029
2F 1 Burner unit, chosen by project
2F.1 1 Burner front plate incl. lance 4800000029
G19 1 Filter for steam DN50 PN40 7040000046
G20 1 Temperature control valve DN50 PN25 6050000064
1G22 1 Fuel oil heater L=1400 8640000121
2G22 1 Fuel oil heater L=1400 8640000121
1G23 1 Safety valve 1/271/2" 87S0041
2G23 1 Safety valve 1/271/2" 87S0041
1G24 1 Heater drain valve oil side 1/2" 30 bar 87D3062
2G24 1 Heater drain valve oil side 1/2" 30 bar 87D3062
G28 1 Temp, transmitter PT100 G1/2"-m 0-160 Deg.C. 8060000007
1G40 1 Air vent valve for heater 1/2" PN100 87N6003
2G40 1 Air vent valve for heater 1/2" PN100 87N6003
G41 1 Temperature gauge 88T0003
G42 1 Temp, gauge HFO heated 0-200 Deg.C. 1/2"-m 88T0003
G47 1 Pressure gauge 0-40 bar 6633122
G48 1 Instrument stop valve 87D3050
G78 1 Pressure relief valve DO 3/8" 87D3059
G97 1 Ball stop valve - FO return DN32 87D3066
G99 1 Pressure transmitter FO press. 0-40 Bar G1/2"-m 6638234
G99.1 1 Gasket for G99, not shown 018/06.51=2 2911602
G100 1 Control valve - FO press. DN32 PN40 6050000165
G101 1 Stop valve - FO press, control DN32 87D3066
G102 1 Ball stop valve - FO by-pass DN32 87D3066
G105 1 Instrument stop valve 1/2" PN400 2541002
G111 1 Three way ball valve FO return DN32 6070000029
G114 1 Air filter/regulator for G111 0-10 bar 2915101
G115 1 Three way ball valve HFO/DO DN80 6070000042
1G145 1 Ignition oil pump 0-25 kg/cm2 6638141
2G145 1 Ignition oil pump 0-25 kg/cm2 6638141
G147 1 Fuel oil supply pump
G148 1 Fuel oil pressure control unit DN32 4800000023
G224 1 Remote start/stop box 8001002002
G279 1 Counter flanges (not shown)
G354 1 Check valve 6020 000028
L1 1 Boiler power panel
1R 1 Fan unit chosen by project
Title Drawn Date
• ISk 15.01.2004
• • #
Flow diagram, oil system Appr. Date
Page 1 04/01-2006
This drawing and design shown herein is the property of Aalborg Industries
and must not bs used by or reproduced for third party
X02 :029894 c
Tag No./
Item Pcs. Designation Dimension Article No.
2R Fan unit chosen by project
Page 2 04/01-2006
This drawing and design shown herein is the property of Aalborg Industries
and must not be used by or reproduced for third party
X02: 029894
Description Index Date Drawn Appr.
NOTE:
- The Indicated tag numbers are AI supply
- Components: see separate list of parts
• For electrical connections, see actual electrical wiring diagrams
- All heavy fuel oil piping to be steam traced piping and Insulated
- Steam tracing to be temperature controlled
- For connections: [g]- see burner arrangement drawing 3
ll -1
Signatures:
M E E
to .£
It
Title: Date
Steam
Water
1 x KBSD Appr.
STh 21.05.2002
Date
Chemicals Standard JMN 21.05.2002
Air
Weight Scale: Size
Blow down/drain lines
Burner unit
1:1 A3R
External wiring
AALBORG Flow diagram Article/Drawing No: Index
Oil INDUSTRIES
THIS DRAWING AND DESIGN SHOWN HEREIN IS THE PROPERTY OF AALBORG INDUSTRIES
Exhaust gas
AND MUST NOT BE USED BY OR REPRODUCED FOR THIRD PARTY 92X02:038042
Tag No./
Item Pcs. Designation Dimension Article No.
C31 1 Instrument stop valve
C33 1 Pressure gauge
C35 1 Pressure switch max. steam
C48 1 Pressure transmitter
C50 1 Drain valve
C431 1 Instrument stop valve
C331 1 Instrument stop valve
F1 1 Steam atomising burner
F17 1 Stop valve, ball - oil ign burner
F18 1 Solenoid valve - oil ign burner
F19 1 Solenoid valve - oil ign burner
F31 1 Ignition burner
F33 2 Flame scanner auto/man
F36 1 Temp, switch - fire in windbox
F41 1 Stop valve, ball atom, steam
F42 1 Stop valve, ball - atom, steam
F43 1 Water separator atom, steam
F44 1 Shut off valve - purge steam
F45 1 Non return valve - purge steam
F50 1 Instrument stop valve
F51 1 Press, transm. atom, steam
F56 1 Solenoid valve, air for F57
F57 1 Pneumatic actuator for F42
F58 1 Pneumatic actuator for F44
F59 1 Solenoid valve, air for F58
F60 1 Pneumatic actuator for F75
F61 1 Solenoid valve, air for F60
F62.1 1 Manometer
F62.2 1 Filter regulator, for F148
F63.1 1 Filter regulate for valve actuator
F63.2 1 Manometer
F64 1 Stop valve, ball FO to burner
F65 1 Solenoid valve for F66
F66 1 Pneumatic actuator for F67
F67 1 Ball stop valve, FO to burner
F68 1 Pressure gauge FO nozz. pr.
F69 1 Instrument stop valve
F73 1 Stop valve
F74 1 Position switch, lance in position
Title Drawn Date
• •• STh 21.05.2002
1 x KBSD Appr. Date
iiiiiilii
AALBC)RG
Standard
Burner unit
Weight Scale
1:1
Size
A3R
INDUST R 1E S Article / Drawing No: Affix
Flow diagram
Page 1 04/01-2006
This drawing and design shown herein is the property of Aaiborg Industries
and must not be used by or reproduced for third party
92X02 :038042
Tag No./
Item PCS. Designation Dimension Article No.
F75 1 Three way valve, FO return
F76 1 D.P. transmitter, airflow
F77 1 Non return valve
F78 1 Solenoid valve
F80 1 Non return valve
F85 1 Micro switch on F67
F86 1 Micro switch on F75
F87 1 Stop valve, ball
3
F91 1 ressure control valve
F92 1 Stop valve, globe
F93 1 Stop valve, ball
F94 1 Control valve
F95 1 I/P converter
F96.1 1 Filter regulator
F96.2 1 Manometer
F97.1 1 Filter regulator
F97.2 1 Manometer
F99 1 Three-way valve
F100.1 1 Flow meter, oil
F100.2 1 Pick-up for flow meter
F106 1 Flame scanner - ign. burner
F108 1 Non return valve
F135 1 Pressure gauge
F148 1 Actuator
F149 1 Position switch
F150 1 Solenoid valve
F151 1 Solenoid valve
F152 1 Throttle valve
F153 1 Solenoid valve
F157 1 Temperature indicator
F166 1 Transformer for Ignition Burner
L2 1 Boiler control panel
iii Standard
Burner unit
Weight Scale Size
AALBC)RG 1:1 A3R
INDUST Article / Drawing No: Affix
R 1E S Flow diagram
Page 2 04/01-2006
This drawing and design shown herein is the property of Aalborg Industries
and must not be used by or reproduced for third party
92X02:038042
AALBORG TABLE OF CONTENTS
INDUSTRIES
Table of contents
Descriptions
MISSION™ boiler 1
Boiler mountings 2
Water level control 3
Gauge board _
. 4
Inspection of the burner flame is possible through the two inspection holes arranged
at two different levels on the furnace panel wall.
Access door.
Smoke outlet/
Steam drum
Burner
Manhole -
I ^^^- Buckstay
Manual soot blower
Inspection hole
Access door
Supports
Furnace
Generating tube bank
Membrane walls
Screen vail
Down comer
Water drum
Heating coil
Boiler mountings
1 Mountings
The following is a brief description of the most important items of the boiler
mountings. The components mentioned in this section are referring to the general
arrangement drawing of the boiler.
Safety valves
Two safety valves are fitted to the pressure vessel of the boiler. They are installed
for security reasons, and designed to prevent the boiler pressure from rising above
the design value.
The safety valves must be supplied with waste steam pipes and either expansion
devices, or bellows.
Main steam valve
The main steam valve is a shut off valve. When closed, it isolates the boiler from the
main steam line. A check valve is mounted after the main steam valve which
prevents steam from flowing backwards into the boiler.
The steam piping up to the main steam valve must be flexible in order to minimise
external loads on the main steam valve and associated branch. The flexibility can be
achieved with loops build into the main steam line to take up heat expansion from
the boiler and steam piping or with an expansion joint next to or close to the main
steam valve.
By-pass valve
The by-pass valve is a shut-off valve. The purpose of the valve is to equalise the
pressure between the boiler and the steam system when the main steam valve is
closed.
Atomising steam valve
The atomising steam valve is a shut-off/non-return valve. The shut-off function is
for security and the non-return function prevents steam/water from flowing into an
empty boiler by mistake.
Feed water valve / feed water valve (sdnr)
Two groups of feed water valves are provided in the boiler. Each group comprises a
shut-off valve and a non-return valve.
The shut-off valve in the ordinary group must be open when the boiler is in
operation, or if the boiler is used as a steam drum.
The shut-off valves should be closed when the boiler is not in use.
Water level gauges
Two local water level gauges are connected to the front of the boiler, each gauge
being provided with two shut-off valves and a drain valve.
The shut-off valves, fitted at the top and bottom of the sight glass, have a quick-
closing mechanism to be used in case of broken glass.
The pipes from the drain cocks on the water level gauge must lead to an open drain,
visible for inspection.
Blow-down valve
Two blow-down valves of the shut-off/non-return type are mounted at the bottom of
the boiler body.
The shut-off function is for security and the non-return function prevents
steam/water from flowing into an empty boiler by mistake.
Air valve
The air/ventilation valve located on top of the boiler is a shut-off valve. It is
normally closed except when the boiler is being filled or completely drained. The
end of the drain pipe from the air valve must be visible in order to determine when
water or steam is coming out.
Gauge board valve(s)
The gauge board valve(s) are located on the top of the boiler and is of the shut-off
type. The valve(s) must always be opened during boiler operation.
Scum valve
Two scum valves of the shut-off/non-return type are mounted of the boiler body.
The shut-off function is for security and the non-return function prevents
steam/water from flowing into an empty boiler by mistake.
In the event of scum in the boiler, this scum can be blown off from the water surface
by opening this valve.
Valves for heating coil
The boiler is provided with two shut-off valves for inlet and outlet connection of the
heating coil. The valves should only be opened when the water drum is filled with
water.
Valves for soot blower
The boiler is provided with a shut-off valve and two ball valves for the soot blower
arrangement. Furthermore, a drain valve is fitted in the system.
Sample valve
A sample valve is installed enabling connection to a sample cooler for taking test
samples to perform boiler water analyses.
Inspection hole
Two small inspection holes are provided in the furnace wall to enable inspection of
the burner flame. A proportion of the air supply is bled off from the burner fan to
cool the window of the inspection hole, and prevent soot deposits.
Inspection door
The boiler is provided with an inspection door to enable inspection of the generating
tube bank.
Manhole
Two manholes placed at the boiler top and boiler bottom allow inside inspection of
the steam/water drum.
Access door
Access to the furnace is possible through the access door placed at the bottom of the
furnace.
Drain for furnace
The furnace bottom is provided with a socket for drain of the washing water.
Instrument air
Main steam line
Regulating feed water valve
i
Dp-transmitter for / £ 3^
flow measurementV T
Reference leg
Variable leg
Valve
manifold
dp-transmitter
Figure 1 dp_l_mod_flowl.cdr
The first control element is the dp water level transmitter unit, which includes
external reference and variable legs, and a dp-transmitter. The second control
element is the steam flow measuring equipment, which consists of a measuring
probe, pressure transmitter, and flow computer.
Finally the third control element is the feed water flow, which is measured by means
of the boiler pressure transmitter and feed water pressure transmitter. The
differential pressure of the transmitters together with the opening signal of the
regulation valve is calculated into feed water flow.
When the boiler is stopped, in starting/stopping mode, or operating at low loads only
the dp water level transmitter unit is active. At higher loads and especially if large
load variation occurs all three control elements are active. Thus the feed water
regulation becomes more rapid in this condition.
Gauge board
1 Description
The function of the gauge board is to control the burner and to give alarm and shut
down for low and high steam pressure.
• A pressure gauge is fitted for analogous reading of the actual steam pressure in
the boiler. The pressure gauge is located on the local control panel.
• A pressure switch "high steam pressure" gives shut down and cut-off the burner
when the steam pressure rises above the pre-adjusted set point (one set point in
high pressure mode). Furthermore, the pressure switch locks the burner in stop
mode. Operation of the burner is only possible when the steam pressure falls
below the differential set point of the pressure switch and the shut down
function is reset.
• A pressure transmitter connected directly on the boiler converts the actual steam
pressure of the boiler into corresponding electric signals. The signals are used to
give alarms for low/high steam pressure and shut down/burner cut-off for high
steam pressure.
• A pressure transmitter is located in the main steam line. The transmitter is
common for both boilers and converts the actual steam pressure in the common
steam line into corresponding electric signals. The signals are used to give
alarms for low/high steam pressure and shut down/burner cut-off for high steam
pressure. Furthermore, the signals are used to control start/stop and modulation
set point of the burners both in low and high pressure mode. The signals from
the transmitter are also used to control the master/slave operation.
Table of contents
General .1
Start-up , ..2
Boiler stop ..3
Boiler maintenance
Boiler maintenance ,1
Inspection of the boiler. ,2
Boiling out
Boiling out
Water washing
Description
Soot blowing
Description .1
Cleaning procedure. ,.2
Preservation
Preservation of boiler..
Plugging of tubes
Refractory repair
Maintenance of repair. \i
Language UK Pag
AALBORG TABLE OF CONTENTS
INDUSTRIES
Lighting-up curve
Lighting-up curve.
1 General
The following chapters of the instruction manual describe the operation and
maintenance of the pressure part. As this is only a part of the complete boiler plant,
it is important to study the remaining chapters in this manual very thoroughly. It is
especially important that the operator of the boiler plant becomes familiar with the
operation instructions of the burner and the control panel.
Important: To ensure a safe and reliable operation of the boiler plant, all
operation and/or maintenance of the boiler should be carried out
only by skilled personnel.
Start-up
When the boiler is started, the lighten-up rate of the boiler must not be accelerated
too much as this might cause an unnecessary overstrain of the boiler material by
quick and uneven temperature rises. It might be necessary to perform a number of
start/stop sequences to reduce the lighten-up rate.
Attention: At the commissioning start-up of the boiler and after any repair
work of the refractory, it is very important to further reduce the
lighting-up rate. This is because the new refractory still contains a
small amount of water. When heated the water vaporises and
expands which might cause fissures and cracks in the refractory.
The burner must therefore only be operated at minimum load and
in intervals of 1-2 minutes for the first hours. Between each
operation interval the burner should remain stopped for
approximately 8-10 minutes.
Before start-up of the boiler plant, some general work and check procedures must be
considered.
Step A: Check that the main steam valve, by-pass valve and circulation valves if
provided, scum valve, and blow-down valves are closed.
Step B: Open the feed water valves and the air valve. Fill the boiler with feed water
to approximately 50 mm below normal water level. The water level rises
due to expansion when the boiler is heated. If the temperature difference
between the boiler and feed water exceeds approximately 50°C, the boiler
must be filled very slowly.
Note: When filling a pressure less boiler, the shut-off valve after the feed water
pump must be throttled. Otherwise the pump motor will be overloaded.
Step C: Check the water level in the water level gauges. Check frequently during
the complete start-up. The water level gauges should be blown down
several times to ensure a correct indication.
Step D: Check that the water level control system is connected and operational.
Step E: Check the oil system and start the fuel oil supply pump. Pre-heat the fuel oil
if the burner should operate on heavy fuel oil.
Step F: Check the burner and the safety functions according to the separate
instruction.
The following work procedures must be followed during start-up of the boiler.
Step A: Check that the gauge board valve and pressure gauge valves are opened.
Step B: Check that the air valve is open if the boiler pressure is below 1.0 barg.
Step C: Start the burner on manual control and on low load. Check that the water
level does not rise too high during the pressure rising period.
Step D: Drain via the blow down valves if the water level is too high.
Step E: If the air valve was opened close it when only steam blows out. A pressure
reading should be indicated on the boiler pressure gauge before the air
valve is closed.
Step F: Tighten all covers such as manholes, hand holes, inspection doors, etc.
during the pressure rising period. If required, check all flange joints on the
plant.
Step G: Change to automatic control of the burner when the boiler pressure is 0.5
barg lower than the working pressure of the boiler.
Step H: Open the by-pass valve slowly to heat-up and pressurise the steam system.
If the boiler is not provided with a by-pass valve, the main steam valve
should be used to heat-up and pressurise the steam system.
Step I: Open the main steam valve and close the by-pass valve.
Step J: Open the valves to the steam consumers carefully in order to avoid water
chocks.
Step K: When the boiler is in normal operation, check that the water level control
system and the gauge board functions are fully operational.
Note: After 3-4 weeks in operation, mud and deposits in the piping system may
have accumulated in the boiler water. This may cause level variations
which disturb the steam generation, and it is therefore recommended to
blow down the boiler. It should then be inspected, cleaned, and refilled
with boiler water.
Boiler stop
Note: When the boiler is stopped, sudden temperature and pressure drops
should be avoided as they might expose mountings, pipe lines, and the
boiler plant to inadmissible temperature gradients.
Step B: Keep the water level at normal level until the boiler stops producing steam.
Step C: Stop the feed water pump and close the feed water valves.
The following describes the measures to be taken when the boiler is shut down for
repair or inspection.
Step A: Clean the boiler from soot with water.
Step B: Operate the burner for at least 15 minutes after the soot removal to dry out
the remaining water.
Step D: Check the furnace and the pin tubes with regard to cleanliness.
Step E: Empty the boiler from water and clean it. Check if lime stone appears.
Step F: Check and clean the outer fittings. Change gaskets where required.
Step G: Clean the feed water tank and feed water pipes.
Step H: Clean and grease the bearings of motor, pump, and fan.
Step J: If the boiler is shut down for a long period of time, the pin tubes must be
thoroughly cleaned.
Step K: Check that the necessary spare parts are available. Order complementary
parts in time.
Boiler maintenance
1 Boiler maintenance
The boiler maintenance should always be executed with skill and in accordance with
valid rules and regulations from the authorities, and below are given some
recommendations for periodical inspections and maintenance.
During normal operation of the boiler some work and check procedures have to be
considered every day.
Step A: Check the boiler steam pressure and the water level.
Step B: Check that the feed water control system is operational, see separate
instructions.
Step C: Check the boiler water condition and make necessary countermeasures with
regard to the feed and boiler water treatment. If necessary blow-down the
boiler.
Step D: Check the function of the oil burner at different capacities through the
inspection holes on the boiler.
Step E: Check the flue gas temperature after and/or the draft loss across the boiler.
If either the temperature or the draft loss is too high, the pin-tube section
must be cleaned.
Step A: Drain each water level glass for about 10-15 seconds.
In case of contaminated boiler water or insufficient water treatment, the draining of
the water level glasses must be done more often.
Step B: Check the safety water level device.
Step C: Depending on the boiler water tests blown-down the boiler. Open the blow-
down valves quickly for a few seconds, and then close and open again for
about 5-10 seconds.
Repeat this operation when required according to the boiler water tests.
Step D: Perform scum blow out by means of the scum valve when required. The
scum blow out must be carried out until the drained water is clean.
Step B: Check all boiler mountings for damage or leaks and repair/replace if
necessary.
Step C: Check the function of the high steam pressure switch by lowering the set
point or by raising the steam pressure, e.g. by closing the main steam valve
slowly.
The burner must stop automatically.
In case of boilers with refractory in the burner opening the throat should be
inspected at least once a year. During this inspection the following issues should be
taken into consideration:
• Check for wear and cracks at the refractory area.
• Check for wear on ceramic felts, if fitted.
• Check for wear and cracks on burner stones, if fitted.
The boiler water side (interior) must be carefully inspected at least twice a year. This
inspection of great importance and without a doubt the most important of all the
maintenance measures, since it has a direct influence on the boiler longevity and on
the security.
At these inspections, hard deposits, corrosion and circulation disturbances can be
found at an early stage, and preventive measures must be taken to avoid unexpected
material damage and boiler breakdown.
Presence of hard deposits at the furnace wall and the pin-tubes reduces their heat
transfer properties and decrease the capacity of the boiler.
Further, it is possible to make out if the feed water treatment has been satisfactory
and if the blow-down has been carried out sufficiently.
Incorrect feed water treatment is commonly causing hard deposits or corrosion.
Insufficient blow-down will cause sludge deposits in the tubes and accumulation of
sludge in the bottom of the boiler.
If hard deposits are not removed, it may lead to overheating in the boiler plate
material which is exposed to the flame in the furnace wall area. This may cause
material damages.
Incorrect feed water treatment does not always lead to hard deposits. For example, a
too low or too high a pH-value may give an electrolytic reaction, causing corrosion
in the boiler.
When the boiler interior is inspected, examine all parts carefully and be attentive to
deposits, corrosion and cracks. It is advisable to pay special attention to this
inspection. If any unusual signs are found, contact Aalborg Industries at once for
advice.
Step A: Shut off the boiler and allow it to cool (below 100°C).
Note: The boiler should NOT be depressurised by lifting the safety valves and
then filled with cold feed water since the stress induced by too rapid
cooling may cause damage.
Note: After chemical treatment the boiler should be blown-down at least twice
a day for approximately one week. This will ensure that excessive sludge
deposits due to chemical treatment do not collect in the bottom of
pressure vessel.
2.5 Contamination
If the boiler is contaminated with foreign substances like oil, chemicals, corrosion
products etc., it is very important to act immediately to avoid damages to the boiler.
Layers of thin oil films, mud, etc. exposed to the heating surfaces causes a bad heat
transfer in the boiler, leading to overheating followed by burned out pressure parts.
In order to remove such contamination, a boiling out or acid cleaning have to be
performed immediately.
Note: Corrosion products from the pipe system or insufficient boiler water
treatment may result in corrosion in the boiler itself. It is therefore
important to observe that such circumstances do not occur in the system.
Boiling out
1 Boiling out
Before putting the boiler into operation for the first time, it should be boiled out to
remove all protecting remedies and impurities on the boiler waterside.
The boiling out procedure is recommended to be carried out as described below:
Caution: Extreme care should be taken while handling the chemicals. The
person handling the chemicals/solution should be properly
dressed/protected.
Step B: Add feed water until the solution is visible in the water gauges above
"lower water level".
Caution: Do never fill feed water into the boiler if the temperature difference
between boiler and feed water exceeds 50°C.
Step D: Raise steam pressure slowly to working pressure, and keep the pressure for
approx. 3-4 hours with closed main steam valve.
Step E: Scum until water level is between "Normal water level" and "High water
level".
By this procedure grease and other impurities are removed from the internal surfaces
of the boiler.
Step F: Start skimming by opening the scum valve, and lower the water level to
lower edge of "Normal water level" mark.
Step H: Refill the boiler with feed water and start skimming again in intervals of 30
minutes for a period of two hours.
Step I: Stop the boiling out procedure by switching off the burner.
Step J: Let the boiler water rest for about five minutes.
Step L: Blow off the boiler water by opening the blow down valves.
Step M: Remember to open the air escape valve, to avoid a vacuum in the boiler
when the boiler pressure decreases to approx. depressurised/atmospheric
pressure.
Step N: Open the manhole and let the boiler cool down to approx. 100°C.
Step O: The boiler is to be flushed with clean water on the boiler waterside, when
the temperature has decreased. The flushing removes remaining impurities.
Step P: Dismantle the bottom blow down valves, for cleaning and inspection
because deposits/foreign substances will usually be accumulated in these
valves and cause leaking if not cleaned.
Step Q: Inspect the boiler and remove any remaining deposits and foreign
substances.
Step R: Finally, new gaskets to be fitted in all hand- and manholes before refilling
the boiler with water to upper edge of "Low water level".
The boiler is now ready to be taken into service.
Note: During the first two weeks in operation we recommend to carry out
frequently skimming and bottom blow down to remove impurities
entering the boiler from the pipe system.
Water washing
1 Description
In order to keep the heat transfer area sufficiently clean the boiler is designed with a
high flue gas velocity through the generating tube bank. Therefore fouling will be
minimised, under normal circumstances, with a correct combustion. However, after
long term operation, e.g. during combustion of poor quality oil or with reduced
combustion quality, deposits can be formed on the heating surface.
The most effective way of soot cleaning is water washing, as most of the deposits
consist mainly of non-soluble particles held together by a water soluble bonding
material. Water washing will have the following benefits:
• Dissolves the bonding material.
• Washes the loosened insoluble deposits away.
Smoke outlet'
r^q< LJ_
Figure 1 Miss D03.cdr
The MISSION™ D-type boiler is easily cleaned from the smoke outlet box with a
water hose. Water washing must be carried out when the oil burner is stopped and
the boiler has been cooled down to a temperature below 100°C. The boiler should,
however, be warm enough for the water to evaporate so that the generating tube
bank and furnace will not remain moist after washing.
Both fresh and sea water can be used. If sea water is used, the boiler must be
thoroughly washed afterwards with fresh water in order to remove all salt deposits.
Where deposits are highly corrosive or bonded, a soaking spray with a 10% soda ash
solution is advisable before washing.
At the beginning of the water washing procedure the water supply should only be
slightly opened, until it is ensured that the drain and soot collecting system are
working properly.
Warning: When the generating tube bank is water washed, there is a risk of
generating steam. It is therefore very important that all of your body
is outside the smoke outlet box in order not to get your skin burned
by the steam.
When the water washing has begun, it must be completed until the generating tube
bank is thoroughly washed and all deposits are removed. This is because some types
of coatings hardens and accordingly get very difficult to loosen when they first have
been saturated and then dry out.
After the water washing procedure is completed the refractory at the furnace bottom
must be cleaned with alkaline water because the washing water is very corrosive. It
must be observed that all the washing water and loosened deposits are removed from
the boiler.
The boiler must be dried out immediately after the water washing has been
completed in order to avoid damage on refractory and heating surfaces. The boiler
must be lightened-up and pressurised as described in the chapter "Start/stop of the
boiler".
Soot blowing
1 Description
Generally, there will be a self cleaning effect of the generating tube bank due to the
high flue gas velocity. However, deposits are formed on the heating surfaces, e.g.
due to combustion of poor quality oil or reduced combustion quality. These deposits
will accumulate on the heating surface of the generating tube bank if not removed by
cleaning.
The MISSION™ boiler is equipped with soot blowers for cleaning of the generating
tube bank. The soot blowers are manually operated and are arranged for direct
connection to the steam system of the ship. In order to obtain an efficient soot
cleaning, the steam pressure must be at normal working pressure. Furthermore, the
boiler load should not be lower than 50%. This ensures a sufficiently high velocity
of the flue gas, which is necessary to carry loosened soot deposits out of the boiler.
Figure 1 shows a soot blowing arrangement.
Because of the varying combustion parameters, it is impossible to specify exact time
intervals between soot blowing. In general soot blowing is recommended every 24
hours.
Note: Excessive soot blowing by means of steam might cause erosion damage
on the generating tube bank.
During operation of the boiler plant, the operating personnel should determine the
necessity with regard to time intervals for soot blowing. This interval should then be
increased or decreased to fit the specified plant.
Cleaning procedure
Step B: Check that the main valve for soot blower and the two manually operated
ball valves are closed.
Step C: Open the drain valve to drain water from the main tube for a few seconds
and close it again.
Step E: Open the lower manually operated ball valve and soot blow for
approximately five seconds.
Step G: Open the upper manually operated ball valve and soot blow for
approximately five seconds.
On special request
Main valve
Manual
valve
Steam trap
Drain valve
o o o o o o o o o o o o o o o o o o o o o o o o o
Figure 1 sootblowla.cdr
Preservation
Step B: Manhole doors and hand hole covers should be opened when the boiler is
still hot. If there is water left in the bottom of the boiler it must be removed,
e.g., by using a vacuum cleaner.
Step C: If the boiler is cold, drying of the boiler can be done by either circulating
dried air from a fan or by placing bags of silicagel inside the boiler.
Step D: Before the manhole doors and hand hole covers are closed, place a tray with
burning charcoal to remove oxygen. As soon as the tray with charcoal is in
position, close the manhole doors and hand hole covers using new gaskets.
Step E: Alternatively, a small steam phase inhibitor can be added to the boiler after
cooling and careful draining. Afterwards the boiler should be closed
completely.
Step A: The boiler is filled with treated boiler water and hydrazine is added until an
excess of 100-200 ppm is obtained.
Step B: The water should be circulated continuously or at least once per week to
avoid corrosion from any penetration of oxygen, and it is necessary to
check the hydrazine concentration and add the necessary amount to have an
excess of 100-200 ppm. Other oxygen binding agents can also be used.
The pH-value should be 9.5-10.5.
Note: If there is any risk of the temperature falling back below 0°C, this
method should not be used to avoid frost damages.
As this preservation method involves applying hydrazine to the water inside the
boiler, the boiler must be completely drained and refilled with fresh water before
taken into service again.
The boiler should be drained, dried and sealed in the same way as mentioned in
section "1.1, Dry preservation".
Step A: Make a connection point to the bottom of the boiler and open the air escape
valve on top of the boiler.
Step B: Connect cylinders with nitrogen to the bottom connection point via a
reduction valve and purge the boiler until there is no oxygen left.
Step D: Leave a cylinder with nitrogen connected to the boiler via a reduction valve
and keep an overpressure of approximately 0.2 bar inside the boiler.
An alternative to the above mentioned preservation methods may be the use of a so-
called volatile corrosion inhibitor (VCI).
The VCI is a water soluble chemical which partly evaporates and protects both the
water and steam spaces of the boiler. It should be able to eliminate the need for
complete drainage and/or application of nitrogen, and may in particular be
interesting when a forced circulation type exhaust gas boiler is installed in the steam
system. The boiler must be effectively sealed from the atmosphere to maintain the
corrosion protection.
The VCI is offered by various chemical companies and must be used in accordance
with their recommendations.
Step B: When the damaged tube is located it must be plugged with a conical or an
external tube plug. Before the tube plug is mounted clean the inside of the
tube ends with a steel brush, so that no deposits are present in the tube.
Attention: The classification society should be notified about the repair work
and a schedule must be made for exchange of the damaged tubes.
Header
Furnace
Header
As shown in Figure 1 approximately 110 - 120 mm of the tube is left for inserting
the external plug.
It is possible to replace the furnace panel wall tubes from the outside of the boiler.
After location of the damaged tube or tubes, those must be replaced according to the
following procedure:
Step A: Adequate amount of insulation around the damaged panel wall tubes should
be removed.
Step B: The damage tubes must be cut right below and above the headers or drums.
Step C: Afterwards the tubes are removed by cutting out in the fins.
Step D: Scraps of metal or welding in the tube holes and the header/drum must be
grind off.
Step E: The new furnace panel wall tubes must be welded on or expanded into the
header/drum and afterwards gas tight welded.
Steam Drum
Plugging of tube
Water Drum
Refractory Swallowtail
(filled in with Plistix 14)
Figure 1 swaltail.cdr
The surface to which the temporary repair is performed, must always be clean, dry
and rugged.
Mixing instructions for the castable refractory appears from the instruction on the
plastic bucket.
The boiler can be lightened-up approx. 1 hour after the refractory has been applied.
The refractory needs no further time for hardening.
If the boiler is pressurized, the lighting-up should be started with the burner in "on"
position for one (1) minute and then in "off' for two (2) minutes, during the first
half Q/z) hour. Then it can be started up according to the ordinary lighting-up
procedure.
Note: Observe the safety rules regarding the refractory which can be seen on
the plastic bucket.
Major repairs and renewal of temporary repairs shall always be carried out and
supervised by maker's specialists, among other things securing that correct drying-
out time and lighting-up is observed.
Furnace tube.
Failed tube
Plicast 31
Figure 2 plugrefrac.cdr
Maintenance of refractory
Note: The refractory should be inspected once a year for shape and wear. It is
recommended to carry out an inspection in due time prior to long repair
periods such as dry docking, etc. Should a repair be required castable
refractors and bricklayers can then be ordered on short notice.
If the refractory has been exposed to water, the refractory should be dried out as
soon as possible. The drying out can be done by hot air (approx. 50°C) or by
operating the oil burner.
Warning: However, if the burner is being used, the burner should be operated
with great care.
Table 1
Lighting-up curve
1 Lighting-up curve for MISSION™ D-type
Figure 1 shows the lighting-up curve for the MISSION™ D-type boiler. When the
burner is started the firing capacity must be adjusted to match the lighting-up curve.
Further start/stop instructions are described in the chapter "Start/stop of the boiler".
//
/ / / /
/
175
7- / /
6 I / / / -
5-
4y
/ -
4- ' /
150
3-
-
2- / /
A
125
1-
/ / /
-
100
/ / / /
-
75
-
/
50
A -
25
Figure 1 startcur2.cdr
Table of contents
Note: The recommended feed and boiler water characteristics are only valid
for boilers with a working pressure below 20 barg.
There is a number of ways to produce good quality feed water for boiler plants.
Methods such as e.g. reverse osmosis plants or ion exchange plants produce good
quality distillate. Also evaporators generally produce good distillate. The important
thing is that the distillate used should be clean and without foreign salt
contamination.
In practice most distillates used contain minor parts of various salt combinations
which can and must be chemically treated away. Furthermore, the distillate may
contain dissolved gases like for example oxygen (O2) and carbon dioxide (CO2)
which may lead to corrosion in the boiler, steam, and condensate system.
Important: Boiler and feed water must be chemically treated in order to avoid
corrosion and scaling in the boiler.
Concentrations are usually expressed in "ppm" i.e. parts solute per million.
Concentrations for parts solution by weight are the same as "mg/litre".
3.1.1 Specific gravity
As guidance the following conversion can be used:
• 1 Be° = 10.000 mg/1 total dissolved solids (TDS)
• 1 mg/1 total dissolved solids = 2 |j.S/cm
• 1 jxS/cm = 1
4.1.1 Daily
4.1.2 Weekly
Step A: Skimming (surface blow down) according to analyses, but at least once per
week (2 minutes with fully open valve).
Step B: Blow down (bottom blow down) according to analyses, but at least once per
week (each blow down valve 1 minute in low load condition).
4.1.3 Monthly
Step A: Check the functions for salinity and oil detection systems.
Step A: The boiler water side (interior) must be carefully inspected at least twice a
year.
4.1.5 Yearly
Step A: Check of the water side of the boiler and hotwell/deaerator for corrosion
and scaling.
Step B: Use the name of the manufacturer and type of chemicals to select which
tables that can be used.
Step C: Check the flow diagrams (Figure 1, Figure 2, or Figure 3) to find a diagram
that matches the actual boiler plant.
Step D: Find in the selected tables the table which includes the matching diagram.
Step E: If more than one table is found to match the actual boiler plant in question it
is recommended to use the method/table which includes note No. 1.
Table No. 1
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
iiliiiilliiw^^
Table No. 6
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
I Table No. 7
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
I Table No. 8
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
iiji|^j:;;;i||i!;|5:.B!i;:;j||i;|Ji
litiiiiiiittiii
Table No. 11
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
I Table No. 12
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
BpBiSp
I Table No. 16
Manufacturer / supplier: Marichem
I Table No. 17
Manufacturer / supplier: Marichem
I Table No. 18
Manufacturer / supplier: Marichem
I Table No. 19
Manufacturer / supplier: Unitor Chemicals
ifflHMW
Table No. 21
Manufacturer / supplier: Unitor Chemicals
iliiiiiiiiiiii
mmmmmmmmum
Manufacturer / supplier:
loints
Uniservice Group Table No. 31
Figure 1 flowdiag_l.cdr
Condensate
Figure 2 flowdiag_2.cdr
Figure 3 flowdiag_3.cdr
Table of contents
1-Nut
2 - Box heads
3 - Joint rings
4 - Box heads
5 - Tubes
6 - Screws
7 - Screws
8 - Cock plug
D - Drain cocks
G - Gauge body
S - Cocks
W-Cocks
1.1 Maintenance
The item nos. mentioned in the following maintenance instructions refer to Figure 1.
When out of service with the gauge body in cool and depressurised condition the
hexagon screws (6) can be re-tightened.
Step A: Start at the centre, working to opposite sides alternately. Max torque: 26
Nm in cold and under working conditions.
The item nos. mentioned in this following blowing down procedures refer to Figure
1.
Step A: The gauge should be blown down before lighting up the boiler and just
before closing down the boiler.
Step B: Open the drain cock D for a short time. This sucks the water out of the glass
without, however, totally depressurising the gauge body.
Step C: Shut the cock D and then water is forced upwards into the glass again.
Step D: Repeat this procedure several times, opening and shutting the cock D. The
water level in glass rises and falls.
Step C: Blow through the steam side and gauge body by opening the drain cock D
for 1-2 seconds.
Step D: A steam blowing of longer duration is not advisable considering the service
life of glass.
1.3 Dismantling
6 - Screws
9 - Wedge piece
10-Centre piece
11 - Reflex
12 - Sealing gasket
13-Cushion gasket
14 - Cover plate
©
Figure 2 kli 05e.cdr
Step B: The drain cock D to be opened until the glass is completely emptied.
Step C: Remove nuts (1) and lift off stuffing box heads (2) together with the gauge
body from the cocks S and W.
Step D: Slacken the union nuts (4) and pull off the stuffing box head (2).
Step E: Place the gauge body (G) horizontally with the screws (6) turning upwards
and loosen the screws.
Step F: Move the wedge piece (9) length wise and lift upwards.
Step G: Lift off centre piece (10) reflex glass (11) and gaskets (12 and 13).
Step H: Clean sealing surface of cover plate (14) and centre piece (10) and examine
for through going scars.
1.4 Assembling
The following assembling instructions refer to Figure 2.
Step A: Insert following items into the centre piece (10): sealing gasket (12) reflex
glass (11) cushion gasket (13).
aiiiiiu
AALBORG
WATER LEVEL GAUGE OM7010#01.1
INDUSTRIES
Step C: Insert wedge piece (9) and move length wise for correct position.
Step D: Tighten screws (6) evenly starting at the centre, working to opposite
alternately. Max torque: 26 Nm in cold and under working conditions.
15-Screw
16-Split ring
17-Packing sleeve
18-Plug
19-Bottom screw
The cylindrical plug (18) is sealed with a resilient packing sleeve (17).
Should leakage arise during service the packing sleeve must be further compressed
by tightening the bottom screw (19) until the leakage is stopped. This must only be
done with the cock in open position.
1.5.2 Dismantling
Step C: Knock the plug (18) together with split ring (16) and packing sleeve (3) out
of the cock body by means of a soft mandrel.
Step D: Remove split ring and knock plug out of the packing sleeve.
Step E: Clean all sealing surfaces carefully and lubricate threads with a high
temperature grease before installation.
1.5.3 Assembly
Step A: Place the split ring (16) in the recess of the plug (18).
Note: Turn the packing sleeve until the ridge fits with the groove in the cock
body. The eyelets of the packing sleeve must neither protrude nor be
tilted.
Step E: Place the handle and washer on the plug and fit screw (15).
Step F: Tighten the bottom screw (19) and check if the plug can be turned.
Table of contents
Safety valves
General 1
Maintenance and start-up of boiler 2
Adjustment and dismantling 3
Safety valves
1 General
In the following the measures required to achieve a safe and reliable operation as
well as maintenance of the safety valves will be described, together with adjustment
and dismantling instructions. An installation example of the safety valve is shown in
Figure 1.
Expansion joint
with sealing ring
Drain
Drain
Warning: Prior to any handling and dismantling of the safety valve ensure that
the system is depressurised.
Before lighting-up the boiler, pipe connections must be thoroughly cleaned for dirt
and foreign bodies. If the valve is not completely tight, which often is the case after
start up of the plant, this is usually caused by impurities between the seat and the
cone. In order to remove these impurities the valve must be heavily blown out by
means of the lifting device. If the valve is not tight after several blows, it may be due
to the fact that a hard foreign body has got stuck between the cone and the seat, and
it will then be necessary to dismount the valve for overhaul.
Warning: In case of a leaking safety valve the valve must be inspected and
over-hauled as soon as possible. It must be ensured that the boiler is
totally depressurised before dismounting the valve.
Note: Before dismantling the safety valve in the workshop the position of the
adjusting screw must be measured and noted which will facilitate the
adjustment later when the valve is to be adjusted when in service.
In case the facings between the cone and the seat have been damaged, they must be
grinded.
Step A: The cone can be grinded against a cast iron plate, using a fine grained
carborundom stirred in kerosene.
Step B: The seat in the valve body can be grinded in the same way by using a cast
iron punch of suitable size.
Note: Never use the cone itself when grinding the seat.
Warning: The spindle and the valve cone must always be secured against
turning as the seat and the cone may thus be damaged.
Step C: Before assembly the valve must be thoroughly cleaned, and all traces of
grinding material and impurities must be removed.
Step D: When the valve has been mounted and the boiler is commissioned, the
valve must be checked for leakage and adjusted to the set pressure.
Step E: The adjustment screw is secured by means of its lock nut, and the valve is
sealed.
Step A: Examine the safety valves for any leaking, such as:
— Is the escape pipe hot due to seeping steam from the valve seat?
Step B: Examine the drain and expansion device at the escape pipe.
Step C: Examine the lifting gear device, i.e. clean up and grease all sliding parts.
Yearly
Step A: The safety valve should be tested in operation by raising the boiler pressure.
Step B: Expansion and exhaust pipe should be examined at the same time.
Step C: Turn the adjusting screw (17) clockwise for higher and anticlockwise for
low set pressures.
Step D: Secure the new setting with the lock nut (21) and reassemble lifting device.
Step B: Loosen lock nut (21) and turn adjusting screw (17) anticlockwise, then the
spring (37) is not under tension.
Step C: Loosen the nuts (8) and remove the bonnet (42).
Step D: Remove the upper spring plate (26), spring (37), spindle (14) with disc (12),
guide plate (4), and lower spring plate (26).
Step F: Remount the spindle unit with the new spring and upper spring plate.
Assemble bonnet (42) and adjust to the spring range.
Step G: Secure the spring setting through the lock nut (21) and remount lifting
device.
47 Ball
42 Bonnet
41 Lifting lever
40 Split pin
39 Bolt
38 Screw
37 Spring
29 Cap
27 Gasket
26 Spn'ngplate
23 Lead seal
22 Drain screw
21 Lock nut
18 Ball
17 Adjusting screw
16 Slotted pin
15 Gasket
14 Spindle
13 Lift aid
12 Disc
10/25 Split cotters
9 Lift limitation ring
8 Hex, nut
7 Gasket
4 Spindle guide
3 Stud
2 Seat
1 Body
Step A: Remove the bolt (39) and split pin (40), see Figure 1.
Step C: Unscrew the screw (38) and break the lead seal (23), if provided.
Step E: Place one or two bolts (48) on top of the spindle. The height of the bolts
should be approximately 1-2 mm higher than the normal distance between
the top of the spindle and the inside top of the cap (29).
Step F: Carefully screw on the cap until the spindle and bolts are locked. The safety
valve will be completely locked when the bolts cannot be moved anymore.
Step G: The other safety valve can now be tested without any interference from the
locked safety valve.
Warning: As soon as the test procedure for the safety valve has been carried
out the locked safety valve must be unlocked.
Step A: Unscrew the cap (29) and remove the bolts (48).
Step B: Mount the cap (29) again and screw in the screw (38).
Step C: Mount the lifting lever (41), bolt (39), and split pin (40).
Step D: Provide the safety valve with a lead seal (23), if necessary. This depends on
the local rules of the classification society.
Table of contents
Instrument air
Main steam line
Regulating feed water valve
Reference leg
Variable leg
Valve
manifold
dp-transmitter
Figure 1 dp_l_mod_flowl.cdr
The first control element is the dp water level transmitter unit, which includes
external reference and variable legs, and a dp-transmitter. The second control
element is the steam flow measuring equipment, which consists of a measuring
probe, pressure transmitter, and flow computer.
Finally the third control element is the feed water flow, which is measured by means
of the boiler pressure transmitter and feed water pressure transmitter. The
differential pressure of the transmitters together with the opening signal of the
regulation valve is calculated into feed water flow.
When the boiler is stopped, in starting/stopping mode, or operating at low loads only
the dp water level transmitter unit is active. At higher loads and especially if large
load variation occurs all three control elements are active. Thus the feed water
regulation becomes more rapid in this condition.
Shut-off valves
Boiler
Steam drum
Drain valve
Figure 1 rba24.cdr
Commissioning
When installing the level float switch use acetic acid-free silicon cable in the
internal part of the switch housing.
Step A: Unscrew the switch housing and check for correct assembly and wiring.
Step B: Open the feed water valves and the air valve. Fill the boiler with evaporated
water until the "Too low water level" mark has been reached and adjust the
magnet switch to the switch point. It should be moved in upwards direction
until the switch is trigged and secured in this position. The magnet switch
must rest against the transmitting tube.
Note: If the temperature difference between the boiler and feed water exceeds
approximately 50°C, the boiler must be filled very slowly. When filling a
pressure less boiler, the shut-off valve after the feed water pump must be
throttled. Otherwise the pump motor will be overloaded.
Step B: Note that both the shut down and cut out function is delayed via a timer in
the control panel.
Step D: After completion of the function test open the feed water valves fully and
raise the water level to the normal level.
Attention: Both shut-off valves must always be fully open during normal
operation of the boiler.
To ensure a safe and reliable operation of the boiler plant check the level float
switch whenever an opportunity occurs by comparing the magnetic switch function
with the level indicated in the water level gauges.
A great difference in the water levels may indicate either blocked connections to the
float chamber or a water filled level float. Therefore it is recommended to blow-
through the level float switch and connection pipes frequently (see below). The
blow-through procedures can be performed, e.g. in connection with stopping the
boiler plant, in order to get rid of dissolved particles that could settle during the stop
periods. In case of prolonged standstill the level float switch should be checked for
the correct function before the boiler plant is restarted.
Step B: Slowly open the drain valve to fully open position, and allow the chamber
to blow-through for a few seconds.
Step C: Then close the drain valve and open the upper shut-off valve again.
Step E: Slowly open the drain valve to fully open position, and allow the chamber
to blow-through for a few seconds. As the water level falls inside the float
chamber check that the shut down function is activated and the burner cuts
out. Please note that both the shut down and cut out function is delayed via
a timer in the control panel.
Step F: After performing the blow-through and test procedure close the drain valve
and open the lower shut-off valve again.
In case of contaminated boiler water, e.g. sludge, mud, etc., the blow-through
procedure of the level float switch must be done more often.
3.3 Cleaning
The float chamber, transmitting tube, and transmitting magnet must be opened,
checked, and cleaned from dirt at least once a year. Carry out the following work
procedures:
Step B: Close the two shut-off valves and slowly open the drain valve.
Step D: Loosen the float and float rod with transmitting magnet from the top flange.
Step G: Check the condition of the float and that it is not water filled.
Step H: Check the condition of the electrical wiring. Exchange damaged wires if
necessary.
When the cleaning procedure is completed the level float switch must be assembled
as follows:
Step I: Assemble the transmitting magnet in the top flange.
Drain valve
Boiler
Equalising valve
dp-transmitter—
Figure 1 dpunit.cdr
The differential pressure transmitter is installed with the process connections upward
to prevent trapping of air. The pipes are mounted with continuous fall (at least 5°)
from the boiler connections to the transmitter also to prevent trapping of air.
The reference impulse leg (upper connection point) is connected to the high pressure
connection (+), and the variable impulse leg (lower connection point) to the low
pressure connection (-).
Note: The dp water level transmitter unit or any part of it must not be
insulated to ensure the correct function.
Commissioning
Before the boiler is pressurised and started for the first time some initial
commissioning procedures can be performed with regard to the valves of the dp
water level transmitter unit. The shut-off valves, transmitter connection valves, and
equalising valve should be operated in the following sequence during the initial
commissioning:
Step A: Initial setting; all valves of the dp water level transmitter unit closed (see
Figure 1).
Step C: Unscrew the filling plugs for the reference leg and variable leg. Fill the legs
with feed water.
Step D: Open the transmitter connection valve and venting facility on the reference
leg side of the transmitter.
Step E: Close the venting facility on the reference leg side of the transmitter when
no more air escapes.
Step F: Open the venting facility on the variable leg side of the transmitter.
Step G: Close the transmitter connection valve on the reference leg side of the
transmitter when no more air escapes.
Step H: Open the transmitter connection valve on the variable leg side of the
transmitter.
Step I: Close the venting facility on the variable leg side of the transmitter when no
more air escapes.
Step J: Close the transmitter connection valve on the variable leg side of the
transmitter.
Step L: Refill the legs with feed water and screw on the filling plugs for the
reference leg and variable leg.
Step B: Use the "M" key to select modes on the differential pressure transmitter.
When a mode is selected, the keys T and 4 are used to change the mode
value.
Step C: Set the values in mode 4 (electrical damping), 9 (output in error situation),
10 (pushbuttons functions), 11 (characteristic), 13 (value displayed), and 14
(engineering units). In mode 14 select e.g. "mm H2O" as engineering units.
Step E: Use the t or •!• key to set the start of scale in the selected engineering unit. If
mm H2O is selected as engineering units, then set the start of scale to the
calculated value in mm H2O (differential pressure at 4 mA).
Step F: Press both the t and 4- keys simultaneously for about 2 seconds, and the
start of scale is set to zero (in the selected engineering unit).
Step H: Use the t or i key to set the full scale in the selected engineering unit. If
mm H2O is selected as engineering units, then set the full scale to the
calculated value in mm H2O (differential pressure at 20 mA).
Step I: Press both the t and I keys simultaneously for about 2 seconds, and the full
scale is set to the upper limit (in the selected engineering unit).
Step J: Mount the protective cover of the differential pressure transmitter again.
Table 1
t, = not existing
Differential pressure
between connections:
Height between
525 X 0.9922 =
connections, e.g.:
525 mm
521 mmH2O(at4mA)
, Water level
\
= 170°Cat7barg,
204°Cat16barg
Water level
Differential pressure
between connections
(at 7 barg):
525 X (0.9922 - 0.8970) =
Height between
50.0 mm H2O (at 20 mA) connections, e.g.:
525 mm
Differential pressure
between connections
(at 16 barg):
525 X (0.9922 - 0.8596) =
69.6 mm H2O (at 20 mA)
\
= 170°Cat7barg,
density 897.0 kg/m3
204°Cat16barg,
density 859.6 kg/m3
Figure 2 dpunit_calil.cdr
minimum indicated "Too low water level" on the control system not is lower than
the actual "Too low water level" mark. Because of the density difference in the
boiler water at different working pressures/temperatures the indicated water levels
will not be identical. This means that the differential pressure transmitter should be
calibrated when the boiler plant operates in high pressure mode.
When the boiler operates at normal working pressure carry out the following work
steps (please also see the specific instruction for the differential pressure
transmitter):
Step A: Unscrew the screws that hold the protective cover of the differential
pressure transmitter for access to the push buttons.
Step B: Use the "M" key to select modes on the differential pressure transmitter.
When a mode is selected, the keys t and •I are used to change the mode
value.
Step C: Set the values in mode 4 (electrical damping), 9 (output in error situation),
10 (pushbuttons functions), 11 (characteristic), 13 (value displayed), and 14
(engineering units). In mode 14 select "raA" as engineering units.
Step D: Ensure that the boiler cannot be filled with feed water by closing the feed
water valves or stopping the feed water pumps.
Step E: Slowly decrease the water level in the boiler until the lower connection
point is reached (socket centre line of the variable leg). The water level can
be decreased by means of the blow down valves.
Step F: The upper and lower connection points will normally be beyond the visual
indication area of the water level gauges. It is therefore impossible to see
when the water level is at these points. However, the rising/falling rate of
the water level can be controlled, by throttling the feed water valves/blow
down valves. By clocking the rate it can be calculated when the water level
has reached the connection points.
Step H: Set the output current corresponding to the start of scale using the T and -I
keys. Or set the output current to 4 mA by pressing the t and -I keys
simultaneously for about 2 seconds.
Step I: Slowly increase the water level in the boiler until the upper connection point
is reached (socket centre line of the reference leg). The water level can be
increased by means of the feed water pumps.
Step J: When the water level is increased operate the burner so that the boiler
pressure is kept at normal working pressure.
Step L: Set the output current corresponding to the full scale using the t and 4-
keys. Or set the output current to 20 mA by pressing the T and 4- keys
simultaneously for about 2 seconds.
Step M: Mount the protective cover of the differential pressure transmitter again.
During final commissioning a function test of the dp water level transmitter unit
must be performed before the boiler plant is put into normal operation. The purpose
of the function test is to check that the output signals from the differential pressure
transmitter are correct. Furthermore, it should be checked that the connected
alarms/shut downs and control functions are operational. The boiler should be
operated at normal working pressure during the test to provide for correct
indications. When the boiler is at normal water level and the burner is in operation,
carry out the following work steps:
Step A: Slowly increase the water level in the boiler by forcing operation of the feed
water pump until the water level has risen to the "High water level" level.
The control system should indicate an alarm, (if provided).
Note: Note that shut downs, alarms, and cut out functions can be delayed via
timers in the control system.
Step B: Increase the water level somewhat until the "Too high water level" mark is
reached. The burner should stop, and a shut down should be indicated on
the control system, (if provided).
Step C: Increase the water level somewhat until the upper connection point is
reached (socket centre line of the reference leg). Check that the output
signal from the differential pressure transmitter is at 20 mA or the full scale
value in the selected engineering units.
Step D: The upper and lower connection points will normally be beyond the visual
indication area of the water level gauges. It is therefore impossible to see
when the water level is at these points. However, the rising/falling rate of
the water level can be controlled, by throttling the feed water valves/blow
down valves. By clocking the rate it can be calculated when the water level
has reached the connection points.
Step E: Ensure that the boiler cannot be filled with feed water by closing the feed
water valves or stopping the feed water pumps.
Step F: Decrease the water level in the boiler by means of the blow down valves
until the water level has fallen to the " Low water level " level. The control
system should indicate an alarm.
Step G: Decrease the water level somewhat until the "Too low water level" mark is
reached. The burner should stop, and a shut down should be indicated on
the control system.
Step H: Decrease the water level somewhat until the lower connection point is
reached (socket centre line of the variable leg). Check that the output signal
Step I: After completion of the function test open the feed water valves or start the
feed water pumps.
Attention: Both shut-off valves between the boiler and impulse legs must
always be fully open and the reference leg must be totally filled with
water during normal operation of the boiler.
To ensure a safe and reliable operation of the boiler plant check the dp water level
transmitter unit whenever an opportunity occurs by comparing the water level
indicated by the control system with the level indicated in the water level gauges.
A great difference in the water levels may indicate blocked connections to the
differential pressure transmitter. Therefore it is recommended to blow-through the
impulse legs and connection pipes frequently. The blow-through procedures can be
performed, e.g. in connection with stopping the boiler plant, in order to get rid of
dissolved particles that could settle during the stop periods. In case of prolonged
standstill the dp water level transmitter unit should be checked for the correct
function before the boiler plant is restarted.
Step B: Slowly open the drain valves of the impulse legs, and allow the legs to
blow-through for a few seconds.
Step D: Close the drain valves again when the reference leg is completely
depressurised.
Step E: Unscrew the filling plug of the reference leg and fill the leg with feed water.
Step F: Screw on the filling plug and slowly open the shut-off valve for the
reference leg.
Step H: After performing the blow-through check that the dp water level transmitter
unit and feed water control valve are fully operational.
In case of contaminated boiler water, e.g. sludge, mud, etc., the blow-through
procedure of the impulse legs must be done more often.
3.1.2 Blow-through procedure of the connection pipes
The blow-through procedure should be performed as describe below when the boiler
plant is stopped, but still pressurised. The procedure should be carried out at least
once each year.
Step A: Open the venting facilities located on the valve manifold for the impulse
legs. The transmitter connection valves must remain open and the
equalising valve closed during the blow-through procedure.
Step B: Close the venting facilities on the valve manifold when only clean water
escapes.
Step E: Close the drain valve again when the reference leg is completely
depressurised.
Step F: Unscrew the filling plug of the reference leg and fill the leg with feed water.
Step G: Screw on the filling plug and slowly open the shut-off valve for the
reference leg.
In case of contaminated boiler water, e.g. sludge, mud, etc., the blow-through
procedure of the connection pipes must be done more often.
3.1.3 Function test of the dp water level transmitter unit
During normal operation of the boiler plant a function test of dp water level
transmitter unit should be carried out at least once each month. The purpose of the
function test is to check that the connected alarms/shut downs and control functions
are operational. The boiler should be operated at normal working pressure during the
test to provide for correct indications. When the boiler is at normal water level and
the burner is in operation, carry out the following work steps:
Step A: Slowly increase the water level in the boiler by forcing operation of the feed
water pump until the water level has risen to the "High water level" level.
The control system should indicate an alarm, (if provided).
Note: Note that shut downs, alarms, and cut out functions can be delayed via
timers in the control system.
Step B: Increase the water level somewhat until the "Too high water level" mark is
reached. The burner should stop, and a shut down should be indicated on
the control system, (if provided).
Step C: Ensure that the boiler cannot be filled with feed water by closing the feed
water valves or stopping the feed water pumps.
Step D: Decrease the water level in the boiler by means of the blow down valves
until the water level has fallen to the "Low water level" level. The control
system should indicate an alarm.
Step E: Decrease the water level somewhat until the "Too low water level" mark is
reached. The burner should stop, and a shut down should be indicated on
the control system.
Step F: After completion of the function test open the feed water valves or start the
feed water pumps.
Table of contents
A three element level control system consists of three control elements being steam
flow, feed water flow, and level. Ideally the steam flow out of the drum and the feed
flow into the drum should be equal and both varying simultaneously with boiler
steam load variations. Only the best water level control systems would take such
variations into consideration and act accordingly.
Continuously adjusting the feed water flow to the same value as the steam flow
leaves a relatively simple job to the level controller. All it has to do is to compensate
when the level is drifting away from the desired value. Such drifting with the flows
outbalanced should be compensated for in a controlled and slow way as there is no
need for quicker actions.
l
Language UK Page 1/13
AALBORG THREE-POINT FEED WATER CONTROL OM9230#01.0
INDUSTRIES
When the boiler load is increased the pressure inside the drum decreases. This has a
huge effect on the physical behaviour in the zone between the steam in top of the
drum and the water in the bottom of the drum. With decreasing steam pressure many
of the bubbles in the steam layer will expand resulting in rapidly rising water level -
the swell phenomena.
However, it is well known that the level will start dropping soon after a load
increase. Hence the use of an inverted D-factor in the controlling equipment in order
to cope with this inverted signal may become necessary; inverted because of the
rising level with the rising steam load, and a D-factor because it should only last for
a limited period of time. The I-part and P-part of the controller will act according to
the inverted signal, i.e. wrong way operation from start.
Bearing the above in mind the P- and I-parameters must be considered carefully. A
short I-time will try to remove the deviation as quick as possible, i.e. with increasing
load it will try to close the feed valve. At the same time a high gain (P-factor) will
ultimately shut the valve momentarily even though the need for an open valve
shortly hereafter is obvious.
It means that the signs of P- and I-parameters cannot just be inverted in order to
cope with this fault signal. A true sign on the parameters is needed in order to
control the level as soon as the swell has gone.
In order to cheat the faulty signal from the level transmitter it is possible to utilize
the D-parameter as it operates in a relative short time, namely during changes in
measured value (or set point). However, the sign must be inverted to work correctly.
The result of a load increase will then be as follows:
— it seems like the water level rises
— the P- and I-parameters will start to close the feed valve
— the D-parameter with inverted sign will try to open the feed valve
— over time the level stabilises and the P- and I-parameters will work alone
The theory described requires carefully adjusted P-, I- and D-parameters. They are
different by nature and in various units. The result is very often that it is possible to
choose a set of parameters that will make level control possible within certain load
or level changes. Of course there will be situations where the level will be unstable
for a while due to these circumstances. But normally several hundred millimetres
water level space is available inside the drum before the alarm limits are hit.
• the steam or oil flow is below the setting in the "flow error" menu or
• the feed water flow is zero
The switch point will be in position B (part of three-point water level control) if:
• the water level controller is not in manual mode and
• the burner sequence step is between "safety time" to "steam purge 1" and
• the steam or oil flow is above the setting in the "flow error" menu and
• the feed water flow is higher than zero
Normally the switching of set points is activated from the burner sequence step. It is,
however, possible to achieve a faster action, so that switching back to the stop mode
set point will take place sooner. This feature can be set in the "follow oil valve"
menu.
4.1.1 Controller function
The water level controller receives a 4-20 mA signal from the water level dp-
transmitter as measured value input (MV) and a set point input (SP) from either the
"setp." value or the "setp.high" value.
When the "setp." value is active this input together with the measured value are
handled in the controller. The output value from the water level controller is
continuously adjusted and set to a value dependent on the result of the comparison
part, settings of the set 1 PID parameters as well as settings of the P-part limitation
and I-part limitations. The controller output is then fed directly to the I/P positioner
of the feed water valve.
When the "setp.high" value is active the water level controller works in a similar
way, just with the set 2 PID parameters. However, before the "setp.high" signal
enters the controller it passes a ramp function (w.reg.ramp). The ramp function is in
mm/sec, and is only active for a limited period of time when the set point changes
from "setp." to "setp.high". The "setp.offset" menu displays the actual ramp
function set point as a positive value.
Furthermore, the output signal passes both a minimum output limitation part
(wl.reg.min) and a maximum output limitation part (wl.reg.max) before it is send to
the calculation part for the first and second control elements. The purpose of the
limitation parts is to limit the effect of the output signal from the water level
controller on the steam and water flow balance.
The calculation part summaries the input signals from the water level controller and
steam/oil flow part. The output signal is then used as set point (SP) for the water
flow controller.
In order to have a measurement for the feed water flow a calculation part is
implemented in the flow circuit. The feed water flow is calculated by means of the
following formula:
Q = V open xVdp
As opening signal for the feed water valve the actual input signal to the I/P
positioner is used. The signal is first handled by a loop back filter which is used to
lower the influence of a jumpy output signal and hence reduce the possibility of
oscillations in the flow circuit. Then the opening signal is processed in the valve
correction part. In here the input signal to the I/P positioner is linearised, in steps of
10%, to fit the characteristic of the feed water control valve before it finally reaches
the feed water flow calculation part.
The 4-20 mA signals from the feed water line pressure transmitter and boiler
pressure transmitter are received by the calculation part via the calibration menus.
The two signals are then added, one positive value and one negative value, hereby
becoming a differential pressure.
The calculated feed water flow is then received by the water flow controller where it
is employed as measured value (MV).
It is possible to make a selection between display or no display of the feed water
flow in the "calc.flow" menu. By selecting "yes" the value will be available in the
SCADA trend system.
The water flow controller receives, as described above, a measured value input
(MV) from the feed water flow calculation part and a set point input (SP) from the
calculation part for water level and steam/oil flow. These two inputs are handled in
the controller. The output value from the water flow controller is continuously
adjusted and set to a value dependent on the result of the comparison part and the
settings of the PID parameters.
The controller output is the same as the input signal to the I/P positioner of the feed
water valve. However, before the signal is received by the I/P positioner it passes a
ramp function (w.out.ramp). The ramp function is in %/sec. and is only active for a
limited period of time when the set point changes from the stop mode set point to
operation mode set point. This means when the control system changes from the
ordinary PID control to three-point control.
Figure 1 3-point-reg_2.cdr
Figure 2 3-point-reg_l.cdr
Figure 3 3-pt_a.cdr
I
f From steam flow T From oil flow
I probeviafiowcom regulation valve level transmrtter
4-20 mA 4-20 mA 4-20 mA
pressure transmitter line transmitter
4-20 mA 4-20 mA
Figure 4 3-pt_b.cdr
I I
From bailer f From feed water From dp-water
level transmitter
4-20 mA
pressure transmitter line transmitter
4-20 mA 4-20 mA
Figure 5 3-pt_c.cdr
Figure 6 3-pt_d.cdr
^iSwitch point
Figure 7 3-pt_e.cdr
Figure 8 3-pt_f.cdr
Table of contents
-E
Probe
JB
N /
Connections to
Shut off valves' dp-transmitter
Figure 1 deltaflowl.cdr
Installation
To achieve the optimal accuracy the Deltaflow probe must be positioned in a fully
turbulent flow profile. After bends or other flow disturbances a straight pipe run is
recommended. See Figure 2 for optimal straight pipe runs. If it is not possible to
keep these recommendations the straight inlet runs must be doubled.
=£1 1
24xlD ' 4xlD
Figure 2 deltaflow2.cdr
Figure 3 deltaflow3.cdr
The Deltaflow probe is manufactured exactly for the inner diameter of the steam
pipe, so that it fits either to the end precisely at the opposite wall of the pipe or it is
exposed to a slight tension. By this, the probe is protected against vibrations. The
welding support of the Deltaflow probe is available with flange. The correct
positions of the flange and Deltaflow probe are shown in Figure 4, Figure 5, and
Figure 6. When mounting carry out the following work procedures:
Step A: Clean the surface of the steam pipe.
Step B: Drill a hole of 28 mm at the horizontal or vertical centre line of the steam
Pipe-
Step C: Use the probe to help to position and orientate the support flange correctly
considering the fitting position and inclination.
Step F: Weld the support flange. Please take into account that the weld may shrink
after it cools. Therefore it may be necessary to leave a small gap between
the support flange and the steam pipe. The probe is exactly adapted to the
geometry of the steam pipe and can be too long or too short, if it is not
mounted correctly.
Note: The condensate pots and internal pipe connections should not be
insulated.
Correct
Figure 4 deltaflow4.cdr
Figure 5 deltaflow5.cdr
Figure 6 deltaflow6.cdr
4 Maintenance
The Deltafolw probe is maintenance free apart from cleaning. The probe is very
insensitive to dirt. It is nevertheless possible, in particular during commissioning of
the boiler plant, that extreme amounts of particles can block the channels of the
probe. In that case a washing with compressed air or other mediums can be carried
out in regular intervals. Please make sure, that the dp-transmitter is disconnected
before cleaning. With regard to maintenance of the dp-transmitter please refer to the
specific instruction.
Table 1
Flow computer
1 General
The Flowcom is a device used to handle and calculate the steam flow from the
measurement equipment. It corrects pressure dependent errors made by the flow
measurement devices. The Flowcom is provided with two separate channels for
possible connection of separate flow measurement devices, e.g. in case of a double
boiler plant. Figure 1 illustrates the Flowcom.
The front panel is equipped with five keys and the display. By means of these the
Flowcom can be configured, parameters can be set, and operation data can be
viewed.
AE 4'J '••\h
"If
M
*:|?|E
Figure 1 flowcoml.cdr
Menu structure
The Flowcom has four basis menus which are the main menu, programming menu,
error record menu, and expanded menu. Inside each menu there are a number of
submenus. In normal operation the main menu is automatically displayed. Figure 2
illustrates the basis menus and how to reach them.
Figure 2 flowcom2.cdr
All parameters and settings necessary to configure the Flowcom for the measuring
application are located in the programming menu. The programming menu has three
submenus (common parameters, setup channel 1, and setup channel 2). In the
common parameters submenu the parameters and quantities common to both
measuring channels are set. In the setup channel 1 and setup channel 2 menus,
values for the respective channels are set. Please note that the setup channel 2
submenu only appears when there are analogue entries it does not share with
channel 1.
2.2.1 Common parameters menu
All generally applicable options and functions are set in the common parameters
submenu. These are e.g. the display option setup, analogue outputs setup, system
setup, etc. Figure 3 illustrates a detailed overview of the common parameters
submenu.
Display Options
Setup
Datalogger
Setup
Relay 1
Setup
Relay 2
Setup
Analoi
DP Output 1
Analog Output 2
Setup
Analog Output 3
Setup
Analog Output 4
alog Out|
Setup
System
Setup
Password
Options Setup
Baudrate
Setup
Totalizer
Setup
Figure 3 flowcom3.cdr
Medium C1
Define
Temperature C1
Define
Pressure C1
Define
Flow C1
Define
Pulse Output C1
Define
Totalizer C1
Zero Now
Figure 4 flowcom4.cdr
Main menu
(Various readings) Mr
2 sec.
Alarm name OK
Date/Time
Simultaneously
for 5 sec.
—•«—
Figure 5 flowcom5.cdr
Wiring
The Flowcom terminals are located on the back of the device. There are three 15-
pole data terminals and one 3-pole supply terminal. The Flowcom must be wired
according to Figure 6. Please note that terminal B is only wired in case of a double
boiler plant where both measuring channels are used. Finally the power cables
should be plugged in.
Terminal row A 1 2 3 4 5 f3 7 8 9 10 11 12 13 14 15
Terminal row B 1 2 3 4 5 (3 7 8 9 10 11 12 13 14 15
Terminal row C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Figure 6 flowcom6.cdr
Figure 7 flowcom7.cdr
Relay 1 1—MJJJ
Parameters
* Sffll Funct. Alert accepted
p
asss ssssssr \-
Figure 8 flowcom8.cdr
Relay 2
Setup
ym—i
Parameters
—T RinSM* accepted
Parameters
accepted |
Figure 9 flowcom9.cdr
Common
Parameters -m-
I Display Options | fc
1 setup ri
* E 3 IAna"s ° U| P U| 1 1
It
3
S AI Analog Output
__. 1. ^ ^ . L l 4mAAna.Out. 1 |_tSSLJ20mAAna.Out. 1 LJgJSLJ Error Ana.Out. 1 I B 8 , Parameters \
~ Mass"- - ~ ngB*1+P.0000E+0kg/hnHBH+Q.OOOuE-H)kg/hnMn+2.5000E+0mAlalri
flowCI accepted I
i
2see. iffifitol I' »»:--i Zeac lTil«iiH Mafrs&i 2sec W$M \z£sM 2sec.
• .• HJ settings I
Figure 10 flowcoml0.cdr
bggy I System
" ~WBB~I Setup
Parameters I
accepted I
im
itge To cftango
Figure 11 flowcomll.cdr
rameters
xepted |
Figure 12 flowcoml2.cdr
Date /Time
Setup >B 1
hJJH "GUEST H
Figure 13 flowcoml3.cdr
Parameters ,
accepted I
Figure 14 flowcoml4.cdr
Channel 1
Setup
Parameters
accepted |~~"
tjgjjgi
•
To charge
Figure 15 flowcoml5.cdr
Figure 16 flowcoml6.cdr
Attention: When "dp squarerooted" is selected in the Flowcom setup the same
must also be selected for the dp-transmitter setup.
Set the "Design differential pressure". The value can be found in the "Technical data
for steam flow equipment"' section. E.g. if the design differential pressure is 100
mbar the setting will be "+1.0000E+1 kPa". Next step is to set the "Design mass
flow" value. It should be set to the maximum boiler load, e.g. if the maximum load
is 25,000 kg/h enter the value "+2.5000E+4 kg/h".
Then set the "Design temperature" value from the "Technical data for steam flow
equipment" section. E.g. if the design temperature is 170°C the setting will be
"+1.7000E+2°C".
When asked to set the "Design pressure" value it should be the working pressure
when the boiler operates in low pressure mode. The value must be entered as
absolute pressure and is also found in the "Technical data for steam flow
equipment" section. E.g. if the working pressure is 7 barg the setting will be 7 + 1 =
8 bar, "+8.0000E+2 kPa".
Set the "Expansion factor" to the value found in the "Technical data for steam flow
equipment" section. Finally set the "Dead band". Due to the fact that dp-transmitters
can have a zero point drift, a reasonable value should be entered. It could e.g. be 2%
of the design differential pressure. E.g. if the design differential pressure is 100 mbar
the setting will be 2 mbar equal to a setting of "+2.0000E-1 kPa".
Figure 17 flowcoml7.cdr
Medium C1 Li
Define r1
Figure 18 flowcoml8.cdr
Repair
The Flowcom is equipped with two fuses located on the digital plate inside the
cabinet. In case of replacement of the fuses carry out the following work procedures:
Step A: Disconnect all electrical plugs.
Step B: Unscrew the six screws on the top side of the casing. The lid can then be
lifted off. Beneath it the analogue plate is located and under it the digital
plate which holds the fuses.
Step C: Carefully remove the front plate (display) from the unit by lifting it upward.
Please use care when handling the connecting cables between the front plate
and digital plate.
Step D: Open the brackets on the light grey plugs of the analogue plate outwards.
Step E: The analogue plate can now be lifted forward out of the casing.
Table 1
Warning: This device may only be assembled and operated after qualified
personnel has ensured, by providing suitable power supplies, that no
hazardous voltages can get into the device in normal operation or in
the event of a failure of the system or parts thereof.
Warning: The device may be operated with high pressure and corrosive media.
Therefore serious injuries and/or considerable material damage
cannot be ruled out in the event of improper handling of the device.
The perfect and safe operation of this equipment is conditional upon proper
handling, installation, and assembly as well as on careful operation and
commissioning.
Technical description
2.1 Application
Measuring spans are possible between 1 mbar and 30 bar depending on the type.
The output signal is a load-independent direct current of 4 to 20 mA. A linear
(proportional to the differential pressure) or square rooting characteristic
(proportional to the rate of flow) can be selected.
Transmitters conforming to the type of protection "Intrinsic safety" and "Explosion-
proof may be installed within potentially explosive atmospheres zone 1 or zone 0.
The transmitter is provided with an EU prototype test certificate and comply with
the corresponding harmonised European standards of the CENELEC.
Figure 1 shows a function diagram of the SITRANS P differential pressure and flow
transmitter. The item numbers referred to in the following description are those
mentioned in the in the figure.
The differential pressure is applied via the diaphragms (4) and the filling liquid (3)
to the silicon pressure sensor (7). If the measuring limits are exceeded, the overload
diaphragm (6) is flexed until one of the diaphragms (4) rests on the measuring cell
body (2), thus protecting the silicon pressure sensor (7) from overloading.
The measuring diaphragm of the silicon pressure sensor is flexed by the applied
differential pressure. The resistance of four piezo-resistors fitted in the diaphragm in
a bridge circuit th+us changes. This change in resistance results in a voltage output
from the bridge proportional to the differential pressure. This voltage is amplified
and converted into a frequency by means of a voltage-to-frequency converter (9).
This signal is evaluated by a micro controller (10), and its linearity and temperature
effect corrected.
The processed signal is converted by a digital-to-analogue converter (11) into an
output signal of 4 - 20 mA.
The data specific to the measuring cell as well as the parameters of the transmitter
are stored in a non-volatile memory (EEPROM).
The cable termination point and the electronics are arranged opposite one another.
Parameterisation of the transmitter is performed using a laptop, PC, HART®
Communicator, or the input keys. Normally the input keys are used to set-up the
transmitter.
Function diagram
12 13
2.3 Dimensions
Installation
The transmitter is fastened to the mounting bracket using the four screws supplied.
If necessary, the measuring cell of the transmitter can be rotated in relation to the
electronics housing, so that the digital display is visible and/or access the input keys
and the current connection for an external measuring instrument is possible.
Only a limited rotation is permitted. The range of rotation (7), see Figure 4, is
marked at the base of the electronics housing. At the neck of the electronics housing
there is an orientation mark (6) which always must be within the marked range when
rotated.
Step A: Loosen the locking screw (8).
Step B: Rotate the electronics housing in relation to the measuring cell (only within
the marked area.
Warning: Check that the auxiliary power supply matches that specified on the
rating plate.
The transmitter should be powered from a SELV (safety extra-low voltage) source.
If other power sources are used, it is recommended to earth the transmitter housing
and PE connection. The earth terminal in the connection box must be connected
internally to the PE connection.
Please note that:
• The sealing caps in the cable entries have to be replaced by relevant cable
glands or blanking plugs, which must be certified when using transmitters
conforming to protection type "Flame-proof enclosure".
• The following general guidelines apply when laying terminal (maximum cross
section 2.5 mm2)/signal cables:
— lay the signal cable separately from cables carrying voltages > 60 V
— use twisted-pair cables
— do not lay cables close to large electrical systems, or use screened cable
Electrical connection
Step A: Unscrew the cover of the connection box (marked "FIELD TERMINALS"
on the housing).
Step C: Connect the wires the "+" (2) and "-" (3) to the terminals, see Figure 5 and
observe the polarity. Position (4) is a test plug for an external DC amp-
meter.
Step A: Push the sleeve and screwed gland onto the cable.
output current
auxiliary power
If the device cannot be operated in a vertical position the digital display can be
turned to make it easier to read. To do this, proceed as follows:
Step A: Unscrew the cover .from the electronics housing.
Step B: Unscrew the digital display. Depending on the position of the transmitter it
can be screwed back in four different positions (rotation by +90° or ±180°
are possible).
Commissioning
The process data must correspond to that on the rating plate. The transmitter
functions as soon as the power is turned on.
• the venting valve and/or the sealing screw are missing or not tight enough
and/or
• the valves are operated wrongly or improperly
Warning: When working with a hot medium, the individual steps described
below must be performed in quick successions, otherwise the valves
and transmitter may overheat and be damaged.
The isolating valves should be operated in the following sequence, see Figure 7:
Measuring gases
1 Transmitter
2 Equalizing valve
3 Pressure Inlet valves
4 Impulse lines
5 Isolating valves
7 Outlet valves
9 Condensate traps
10 Pressure source
Step B: Open both isolating valves (5) at the pressure tapping points.
Step E: Check the zero point (4 mA) at start of scale (0) and correct if necessary.
The isolating valves should be operated in the following sequence, see Figure 8:
Measuring liquids
1 Transmitter
2 Equalizing valve
3 Pressure inlet valves
4 Impulse lines
5 Isolating valves
7 Outlet valves
8 Venting valves
10 Pressure source
12 Gas trap
Step B: Open both isolating valves (5) at the pressure tapping points.
Step D: If the transmitter is below the pressure source: open both outlet valves (7)
slightly, one after the other, until no more air escapes.
Step E: If the transmitter is above the pressure source: open both venting valves (8)
slightly, one after the other, until no more air escapes.
Step G: Open the pressure inlet valve (3A) and venting on the positive leg of the
transmitter (1) slightly until no more air escapes.
Step I: Open the venting valve on the negative leg of the transmitter slightly until no
more air escapes.
Step K: Open the pressure inlet valve (3B) slightly until no more air escapes, close
after.
Step L: Close the venting valve on the negative leg of the transmitter (1).
Step N: Check the zero point (4 mA) against start of scale (0) and correct if
necessary.
The isolating valves should be operated in the following sequence, see Figure 9:
Caution: The result will only be correct when the impulse lines (4) contain an
identical head of condensate at identical temperatures. Zero point
calibration should be repeated, if necessary, when this condition is
satisfied.
Caution: The flow of steam may damage the transmitter if the equalising valve
(2) is opened when both the isolating valves (5) and pressure inlet
valves (3) are open!
Measuring steam
1 Transmitter
2 Equalizing valve
3 Pressure inlet valves
4 Impulse lines
5 Isolating valves
7 Outlet valves
10 Pressure source
13 Condensate reservoir
14 Jacket
Figure 9 7mC3_09.tif
Step B: Open both isolating valves (5) at the pressure tapping points.
Step D: Wait until the steam in the impulse line (4) and in the condensate reservoirs
(13) has condensed.
Step E: Open the pressure inlet valve (3A) and venting valve on the positive leg of
the transmitter slightly until no more air escapes.
Step G: Open the venting valve on the negative leg of the transmitter slightly until
no more air escapes.
Step I: Open the pressure inlet valve (3B) slightly until no more air escapes.
Step J: Close the venting valve on the negative leg of the transmitter.
Step L: Check the zero point (4 mA) against start of scale (0) and correct if
necessary.
Step N: Open the pressure inlet valves (3A and 3B) fully.
5.1 General
The differential pressure and flow transmitter is adjusted in the field by three input
keys, located on the outside of the instrument, with which the start of scale and full
scale values are set or adjusted. By means of the digital indicator (optional)
additional parameters can be adjusted. The input keys can be accessed, by undoing
the two screws holding the protective cover in place, which can then be moved out
of the way.
—SPAN—r
IS J
g
1)
! M t I
' ZERO—' j
Symbols for
input keys
1 Digital display
2 Connecting plug
for digital display
3 Mode key
4 Increment key
5 Decrement key
The functions listed in Table 1 can be selected using the "M" key. When pressing
the "M" key (Mode) 2 appears in the bottom left corner on the LCD display. Every
additional key press increases the mode by one. The parameters, the current value,
or the unit of pressure can be modified using the f and i keys. In case of error
situations "Error" is displayed on the display, (see section 5.2.7). It generally
applies that:
• The transmitter changes to function "Measured value", if mode 14 is passed by
pressing the "M" key or if 2 minutes elapse without a key being pressed. In case
of the 2 minutes being passed the setting is automatically saved.
• The key lock must be released for keyboard operation.
• Numerical values are always set from the least significant digit still displayed. In
the case of an overflow in the key repetition mode it switches to the next
significant digit and only this continues to be counted. This procedure serves for
fast rough setting over a wide numeric range. For fine setting the desired key ( t
or \) have to be released and pressed again. Exceeding of the upper and lower
measured value limits are shown on the display with the signs T or X.
If the input pressure is displayed, selected in mode 13 (see section 5.2.10), and
the square rooting characteristic in mode 11 (see section 5.2.9) the differential
pressure corresponding to the flow and additionally the sign "V" is displayed on
the display.
0
Change mode by pressing the "M" key.
2)
The start of scale is in a vacuum in absolute pressure transmitters. The zero adjustment in ventilated transmitters leads to mis-adjustments.
Table 1
5.2.1 General
• Please note that the input keys might be disabled. To cancel a set keyboard
disable press the "M" key for 5 seconds.
Step A: Undo the two screws holding the protective cover in place, which can then
be moved out of the way.
Step B: On completion of calibration replace the protective cover and tighten both
screws.
Note: The measuring span is not changed when setting the start of scale. By
setting the full scale the start of scale remains unchanged. Therefore the
start of scale should be set first and then the full scale.
The relationship between the measured pressure and the generated output current is
linear. Please note that this does not apply if square rooting characteristic is selected.
In case of linear relationship the output current can be calculated with the following
equation shown in Figure 11:
I = output current
p = pressure
MA=start of scale
ME = full scale
Example
Given a transmitter with a measuring span of 0 to 16 bar. Set to a measuring span of
2 to 14 bar.
Step A: Apply 2 bar process pressure. Set the device to mode 2 with the "M" key.
The display shows the set mode at the bottom left. Set the start of scale by
pressing the t and -I keys on the value for about 2 seconds. An output
current of 4 mA is then generated at 2 bar input pressure.
Step B: Apply 14 bar process pressure. Set the device to mode 3 with the "M" key.
The full scale is set by pressing the t and I keys on the value for about 2
seconds. An output current of 20 mA is then generated at 14 bar input
pressure.
Step C: The output current for any input pressure can be calculated with the
specified equation shown in Figure 11.
Adjusting (theoretical relationship)
When adjusting, the start of scale and/or the full scale can be assigned to any desired
current value using one reference pressure. This function is particularly suitable if
the pressures necessary for start of scale and full scale are unavailable.
Requirements: applied pressure (reference pressure) and the set start of scale and full
scale are known. Please note that after adjusting, the measuring range specified on
the measuring point plate may no longer match Ihe setting.
Using the following equation shown in Figure 12 the current that should be adjusted
for the desired start of scale and full scale can be calculated.
Equation for calculation of current (set the start of scale and full scale)
currant to be
set at MA „ „
current to be
Bet at M E ™ •i6mA+4rnA
ME MA
n«if nom
I = output currant
p ^ = applied reference pressure ^ = oW start of scale
ME n o m - new fill seals
MA new start of scale
11
To calculate the output currents when setlng start of w a l e and full scale, the reference pressure must
be selected so that a value between 4 and 2 0 mA Is obtained for the current.
Figure 12 7mf33_13.tif
Example
Given a transmitter with a measuring span of 0 to 16 bar. Adjust to a measuring span
of 2 to 14 bar. A reference pressure of 11 bar is available.
Step A: Set the device to mode 2 with the "M" key. Using the equation from Figure
12 first calculate the current that should be adjusted for the desired start of
scale (2 bar) at the applied reference pressure and then adjust it with the t
and I keys (13 mA in this example).
Step B: Set the device to mode 3 with the "M" key. Using the equation from Figure
12 calculate the current that should be adjusted for the desired full scale (14
bar) at the applied reference pressure and then adjust it with the T and -I
keys (16 mA in this example).
Set start of scale and full scale (practical application with actual pressures
available)
The device sets the output current for the start of scale to 4 mA and the full scale to
20 mA when the input keys are pressed according to the following instructions.
The start of scale is set by:
Step A: Apply the corresponding pressure.
Set start of scale and full scale (practical application with reference pressure
available)
If the output current is not set but adjusted continuously, the currents must be
calculated so they can be adjusted mathematically. It is possible to make an
adjustment for the start of scale, the full scale, or both values one after the other.
The start of scale is adjusted by:
Step C: Adjust the output current for the start of scale with the T and 4- keys.
Step G: Adjust the output current for the full scale with the t and 4- keys.
Step B: Set the device to mode 6 with the "M" key. Set the full scale to 14 bar by
pressing the t or -I- key. If 14 bar input pressure are applied later, an output
current of 20 mA is generated.
Set start of scale and full scale, blind (practical application)
The device sets the start of scale to the lower and the full scale to the upper sensor
limit when the keys are operated as follows:
The start of scale (blind) is set by:
Step A: Select mode 5 using the "M" key.
Step B: Press the t and 4- keys simultaneously and hold for 2 seconds. The start of
scale is set to the lower sensor limit.
The full scale (blind) is set by:
Step C: Select mode 6 using the "M" key.
Step D: Press the t and -I keys simultaneously and hold for 2 seconds. The full
scale is set to the upper sensor limit.
Adjust start of scale and full scale, blind (practical application)
If the pressures for the start of scale and full scale are not to be set but adjusted
continuously, the keys should be operated as follows:
The start of scale (blind) is adjusted by:
Step A: Select mode 5 using the "M" key.
Step B: Adjust the pressure value of the start of scale with the t or 4- keys.
Step E: Adjust the pressure value of the full scale with the t or I keys.
Step B: Activate the constant current mode by pressing the t and ^ keys
simultaneously for about 2 seconds.
Step D: Turn off the constant current mode with the "M" key.
Step E: Exit the constant current mode with the "M" key.
"0" no disabling.
"LA" input keys disabled, operation via HART® possible.
"LO" input keys disabled, only start of scale can be set. Operation via HART®
possible.
"LS" input keys partly disabled, only start of scale and full scale can be set.
Operation via HART® possible.
"L" write protection, operation via HART® not possible.
A set keyboard disable (LA, LO, LS) or a write protection for HART® (L) can be
cancelled with the input keys. To do this, press the "M" key for 5 seconds.
Note: When delivered with a blanking cover, the disable mode "LS" is active,
i.e. only zero and span can be changed. If the device permanently is
operated with a blanking cover, make sure that the disable mode "LS"
remains set.
current is linear up to the application point (see Figure 13 a) and when "SroFF" is
selected the output current is switched off up to the application point. The
application point can be set between 5% to 15% of the flow.
The characteristic is set by:
Step E: Select the application point between 5% and 15% with the t or X key.
Note: Mode 12 cannot be selected when the "linear" measuring mode 11 is set.
If the input pressure is selected as a display in mode 13 and square
rooting characteristic in mode 11, the differential pressure
corresponding to the flow and root sign are displayed.
0 1 2 3 4
; 20 40 60 SO 100
pressure [%]
0 1 2 3 4
5.3.1 Setting start of scale and full scale without LCD display
• Please note that the input keys might be disabled. To cancel a set keyboard
disable press the "M" key for 5 seconds.
Step A: Undo the two screws holding the protective cover in place, which can then
be moved out of the way.
Set start of scale (4 mA) and full scale (20 mA)
Assuming the input keys are pressed as described below, the transmitter sets the start
of scale to 4 mA and the full scale to 20 mA. An ammeter is not required.
Start of scale
Step A: Apply a differential pressure corresponding to the start of scale to the
transmitter.
Step B: Press the T and •!• keys simultaneously for about 2 seconds.
Full scale
Step A: Apply a differential pressure corresponding to the full scale to the
transmitter.
Step B: Press all three input keys, making sure that the "M" key is pressed first,
hold it, and press both the other keys ( t and -i).
Calibrate start of scale and full scale
If the output current is not to be set but freely adjusted continuously, the currents
must be calculated for mathematical adjustment. It is possible to make an adjustment
for the start of scale, the full scale, or both values one after the other.
Warning: For intrinsic safe current circuits only certified current meters are
permitted.
Start of scale
Step A: Apply a differential pressure corresponding to the start of scale to the
transmitter.
Step B: Set the output current for start of scale using the T and 4- keys.
Step C: The set output current is saved automatically when the key is released.
Full scale
Step A: Apply a differential pressure corresponding to the full scale to the
transmitter.
Step B: Set the output current for full scale using the "M" key and the t key or the
"M" key and the 4- key. Always press the "M" key first, hold it, and press
either the 1* or the -i key.
Step C: The set output current is saved automatically when the key is released.
Maintenance
The transmitter requires no maintenance. However, the start of scale value should be
checked occasionally.
If an error occurs:
• the output current is set to 22.8 mA or 3.6 mA, depending on the selection (see
section 5.2.7)
• using SIPROM P an appropriate message is displayed in the "Measured values"
field
• "Error" is displayed on the LCD display
Table of contents
General 1
Operation 2
Maintenance 3
General 1
Reversal of the actuator action 2
Manual operation device 3
Maintenance 4
General 1
Mechanic connection of the positioner 2
Electric connection of the positioner 3
Pneumatic connection 4
Commissioning 5
Diagnosis 6
Service and maintenance 7
Figure 1 vaI47x.cdr
Table 1
Operation
The control valves are normally delivered with actuators already fitted. For
alternations or maintenance of actuator, the assembly should occur in accordance
with the operation instructions for the actuator.
Maintenance
Before any maintenance of the control valve is carried out, the piping system must
be shut off and pressure free.
Step A: Open the valve fully and unscrew the hexagon nuts (17).
Step B: Lift the gland flange (7) and the spindle guiding (8) upwards.
3.1.2 Exchange
Step A: Drive the actuator into middle position and dismantle the actuator.
Step B: Unscrew the hexagon nuts (17) from the studs (15).
Step C: Remove the gland flange (7), the spindle guiding (8) and the old stuffing
box (10) and clean the packing compartment.
Step D: Clean the valve spindle and check for damage and if necessary replace. If
the damaged spindle is not replaced, the new packing will leak after a short
period.
StepE: Insert the new packing rings (split ring-displacement, splitting at 180° to
avoid overlapping).
Note: Strenuous tightening will prevent leakage, but will also have a brake
effect on the spindle which aggravates the movement of the spindle.
A PTFE-V-ring unit is spring loaded and has enough set pressure to ensure a good
seal even by low operation pressures. It is replaced as mentioned above.
The PTFE-V-ring sealing unit should be lubricated before it is inserted. The sealing
lips must face against the pressure direction.
Note: Special care should be given to the spindle surface. Rough surfaces wear
the sealing lips enormously and can be due to failure of the packing unit.
Step A: Drive the actuator into middle position and dismantle the actuator.
Step C: Unscrew the hexagon nuts (17) and remove the bellow housing (25).
Dismantle the plug as described in the next section.
Step D: Unscrew the hexagon nuts (17.1) and dismantle the mounting bonnet (3.1).
Step E: The bellow unit (26) is removed from the bellow housing (25).
Step F: Replace the two gaskets (14.1) and the gasket (14).
Step G: When the bellow unit (26) is replaced, the proper position of the anti-
twisting device must be observed.
Step H: The set pins (21) have to drive within the slots of the anti-twisting device.
Check for friction-free movement.
Step I: Replace mounting bonnet (3.1) and screw down the hexagon nuts (17.1)
crosswise.
Step A: Drive the actuator into middle position and dismantle the actuator.
Step A: Unscrew the hexagon nuts (17) and dismantle the mounting bonnet (3).
Step B: Pull out the plug with the spindle and exchange this unit.
Step C: Remove the spring-type straight pin (19) and unscrew the spindle (6).
Step E: Drill a hole through the plug shaft and insert a new pin.
Step F: Replace the gasket (14) and assemble the mounting bonnet (3).
Step A: Unscrew the hexagon nuts (17) and dismantle the bellow housing (25) with
plug (5).
Step B: Drive the spindle in the bottom position and remove the spring-type straight
pin (19).
Step D: Screw a new plug at the spindle and drill through the shaft. Drive the
spring-type straight pin (19) into the hole.
Step F: Assemble the bellow housing (25) with plug (5) together with the body (1)
and fix it by screwing the hexagon nuts (17) crosswise.
The spindle can only be completely replaced together with the bellow.
Operation mode:
Spring opens - Air closes Air opens - Spring closes
Figure 1 dpactuat.tif
Table 1 below shows a list of the position numbers in Figure 1 and Figure 2.
SNti
Part Denomination Part Denomination
Rolling diaphragm 15 Stroke indicator
Diaphragm housing 16 Hexagon nut
Diaphragm lid 17 Mounting rod
Diaphragm plate 18 Bellow
Spindle 19 Collar nut
Spring 21 O-ring (spindle)
10 Coupling flange 22 O-ring (bushing)
11 Guide flange 26 Slotted guide bearing
12 Rotation guard 27 Spindle guide
13 Socket screw 30 Hexagon nut
14 Threaded bushing 31 Hexagon nut
Table 1
The air supply should be dry and at a low service temperature. A heat-guard should
be installed to prevent high service temperature.
The pneumatic supply tube must be connected to the diaphragm housing (2) by
operation mode "spring closes" and to the diaphragm lid (3) by operation mode
"spring opens".
By air failure the stem automatically returns into the original position caused by the
inserted springs.
Warning: The actuator diaphragm may only be pressure loaded on the side
opposite of the springs. The vent hole in the other connection must
remain open.
The assembling of the actuator on the valve is shown in Figure 2. For both "spring
closes" and "spring opens" operation modes the following assembling procedure
should be followed:
Step A: If the actuator and the valve are separated, press the plug and spindle unit
(5) into the closed position for operation mode "spring closes" or into the
open position for operation mode "spring opens".
Warning: Make sure that the plug does not turn while pressing on the seat
during assembly.
Step B: Loosen the socket screws (13), remove the rotation guard (12) and the guide
flange (11). The threaded bushing (14) is now free.
Step C: Turn the locking hexagon nut (30) onto the valve spindle. Place the rotation
guard (12) and the guide flange (11) over the valve spindle and then turn
the threaded bushing (14) onto the valve spindle.
Step D: Check the actuator for proper operation mode and connect the pneumatic
supply to the connection piece in the diaphragm housing (2) for operation
mode "spring closes" or in the diaphragm lid (3) for operation mode "spring
opens".
Step E: Drive the actuator into approximately mid-stroke position over the air
supply and mount it onto the valve (read the value from the pressure gauge
- middle of the spring range).
Operation mode: Spring closes valve - Air opens valve Operation mode: Spring opens valve - Air closes valve
Pneumatic connection
Pneumatic connection
Figure 2 dpactspr.tif
Step A: Drive the actuator to the required spring-starting point over the air supply.
Step B: Turn the threaded bushing (14) up against the coupling flange (10) so that
the collar enters into the flange and presses against it. Make sure that the
plug is lying on the valve seat.
Attention: Note that sufficient thread of the valve spindle is inside the threaded
bushing (14). If not, turn the coupling flange (10) downwards from
the actuator spindle and pull the threaded bushing (14) against it.
— Attach the guide flange (11) and the rotation guard (12) with the socket screws
(13) to the coupling flange (10).
— Check that the plug lifts off the seat at the required spring starting point.
Step D: For operation mode: "spring opens":
— Check that the plug leaves the end position at the required spring starting point,
and finishes the valve stroke at the spring-range end value.
— The plug must then also press on the valve seat.
Step E: After the test operation set the stroke indicators (15) into the end positions.
Step F: Lock the hexagon nuts (16 + 30) at the valve mid-stroke.
Step G: Do not turn the plug on the seat when it is under force.
StepB: Loosen and remove the socket screws (13) from the coupling flange (10)
and drop the rotation guard (12) over the valve spindle.
Step C: Remove the hexagon nuts (31) from the actuator and lift off the valve.
Step D: Reduce the air supply until the chamber is pressure free.
Warning: The actuators DP 32 and DP 33 have two longer screws when fitted
with stronger spring ranges. The actuator DP 34 has four. These
screws should be the last screws to be loosened, and must be
loosened evenly to reduce the high spring tension.
— Remove the springs (7) and the diaphragm plate (4) with the diaphragm (1) and
the spindle (5).
— Loosen and remove the seal lock nut (19) and remove the spindle (5). Turn over
the diaphragm plate (4) with the diaphragm (1) and the diaphragm clamping
flange, and place it over the spindle (5).
— Tighten with the seal lock nut (19). Make sure that the spindle surface is not
damaged.
— Grease the spindle surface and the 0-ring.
— Place the diaphragm plate (4) with the diaphragm (1) into the diaphragm lid (3).
— Arrange the springs (7) onto the moulds pressed into the diaphragm plate (4).
— Place the diaphragm housing with the spindle sealing unit over the spindle, and
screw it together. Make sure that the springs stay properly arranged.
— Turn the hexagon nut (16) and the coupling flange (10) onto the spindle (5).
— Mount the actuator as described previously, and connect the air supply tube to
the diaphragm lid (3).
Step H: For reversal from "spring opens" into "spring closes":
— Remove the diaphragm (1) and the diaphragm plate (4) with the spindle (5) and
the springs (7).
— Loosen and remove the seal lock nut (19) from the spindle (5). Turn over the
diaphragm plate (4) with the diaphragm (1) and the diaphragm clamping flange,
and place it on the spindle (5).
— Tighten with the seal lock nut (19). Make sure that the spindle surface is not
damaged.
— Grease the spindle surface and the 0-ring.
— Stick the diaphragm plate (4) with the diaphragm (1) and the spindle (5) into the
diaphragm housing (2).
— Arrange the springs (7) onto the moulds pressed into the diaphragm plate (4).
Place the diaphragm lid (3) on the top, and screw it together. Make sure that the
springs (7) stay properly arranged.
— Turn the hexagon nut (16) and the coupling flange (10) onto the spindle (5).
— Mount the actuator as described previously, and connect the air supply tube to
the diaphragm housing (2).
Maintenance
The pneumatic actuator is maintenance free. To maintain a disturbance free
operation, the air should be supplied by an air-supply station.
The diaphragm, spindle sealing unit and springs are wear parts and should be
replaced when necessary.
When the spindle sealing is changed, the slotted PTFE-guide bearing and the 0-ring
should be replaced. The spindle surface must be clean and undamaged. Before the
actuator is assembled, the spindle unit and the spindle must be greased.
Comparison of the set point and the actual value takes place electronically in a micro
controller. If the micro controller detects a deviation, it uses a 5-way switch
procedure to control the piezoelectric valves, which in turn regulate the flow of air
into the actuating chambers. When connected in a two-wire system, the SIPART
PS2 draws its power exclusively from the 4 to 20 mA set point signal.
The piezoelectric valve converts the command into a pneumatic positional
increment. The positioner outputs a continuous signal in the area where there is a
large control deviation (high-speed zone). In areas of moderate control deviation
(slow-speed zone) it outputs a sequence of pulses. No positioning signals are output
in the case of a small control deviation (adaptive or variable dead zone).
Commissioning (initialisation) is carried out automatically to a large extend. During
initialisation, the micro controller automatically determines the zero, full-scale
value, direction of action, and positioning speed of the actuator. It uses these to
determine the minimum pulse time and dead zone, thus optimising the control.
The positioner can also be operated manually by the pushbuttons and the LCD of the
SIPART PS2.
The installation of the positioner must be carried out in the following order:
• Mechanic connection
• Electric connection
• Pneumatic connection
• Commissioning
Supply air
J__J
Figure 1 sips2_5a.tif
Figure 2 shows the mechanic connection of the positioner to an actuator for a control
valve.
Step A: Mount clamping assembly (3) with hexagon socket cap screws (17) and
lock washers (16) on the actuator spindle.
Step B: Insert the pick-up bracket (2) into the recesses of the clamping assembly.
Set the necessary length and tighten the screws so that the pick-up bracket
can still be shifted.
Step C: Push the roll (5), spring (13), and guide washer (22) onto the pin (4).
StepD: Insert the pin in the lever (6) and assemble with nut (18), spring washer
(14), and U-washer (12).
Step E: The value of the stroke range specified on the actuator should be set or if
this does not exist as a scaling value, the next greatest scaling value should
be set. The centre of the pin must be in line with the scaling value. The
same value can be set later under parameter "3.YWAY" in commissioning
to display the way in [mm] after initialisation.
StepF: Assemble the hexagon socket cap screw (17), spring washer (16), washer
(12), and square nut (19) on the lever.
Step G: Push the pre-mounted lever onto the positioner axis up to the stop and fix
with the hexagon socket cap screw (17).
Step H: Fit the mounting bracket (1) with two hexagon head screws (9), lock
washer (10), and flat washer (11) on the rear of the positioner.
Step I: Selection of the row of holes depends on the width of the actuator yoke. The
roll (5) should engage in the pick-up bracket (2) as close as possible to the
spindle but may not touch the clamping assembly.
Step J: Hold the positioner with the mounting bracket on the actuator so that the pin
(4) is guided within the pick-up bracket (2).
— Actuator with ledge: hexagon head screw (8), flat washer (11), and lock washer
(10).
— Actuator with plane surface: four hexagon head screws (8), flat washer (11), and
lock washer (10).
— Actuator with columns: two U-bolts (7), four hexagon nuts (21) with flat washer
(11), and lock washer (10).
Step M: Secure the positioner onto the yoke using the previously positioned
mounting parts.
Note: Set the height of the positioner so that the horizontal lever position is
reached as close to the stroke centre as possible. The lever scale can be
used as orientation. It must be guaranteed that the horizontal lever
position is passed through within the stroke range.
22
1) 2) 4
11
10
3)
Mounting on yoke
Mounting on yoke
•)•] with ledge with plane surface
Mounting on yoke
with columns
As required
Figure 2 sips2_5b.tif
Step B: Adhere pointer (4.2) onto the mounting console in the centre of the centring
hole.
Step C: Push coupling wheel (2) onto the positioner axis, pull back by about 1 mm
and tighten the hexagon socket head screw (18) with the Allen key
provided.
Step D: Place the carrier (3) onto the end of the actuator and secure using Fillister
head screw (16) and washer (17).
Step E: Carefully place the positioner with mounting console onto the actuator such
that the pin of the coupling wheel engages in the driver.
Step F: Align the positioner/mounting console assembly in the centre of the actuator
and screw tight (screws are not included in the delivery, they are part of the
actuator mounting console).
Step G: Follow the start-up sequence as described later. Drive the actuator to the
end position and adhere the scale (4.1) onto the coupling wheel (2)
according to the direction of rotation and rotary actuator. The scale is self-
adhesive.
Figure 3 sips2_5c.tif
11 10 9
Figure 4 sips2_5d.tif
Pneumatic connection
Ensure that the air quality is suitable. Grease-free instrumental air with a solid
content < 30 urn and a pressure dew point 20 K below the lowest ambient
temperature must be supplied.
Warning: For reasons of safety, pneumatic power may only be supplied after
assembly when the positioner is switched to operating level "P
manual" operation with electrical signal applied.
Step C: Connect actuating pressure Yl and/or Y2 (Y2*5 is only used with double-
acting actuators) according to the desired safety position.
Step D: Connect the supply air (1). The pressure should be between 1.4 to 7 bar.
Commissioning
Commissioning (initialisation) is carried out automatically to a large extend. During
initialisation, the micro controller automatically determines the zero value, full-scale
value, direction of action and positioning speed of the actuator. It uses these to
determine the minimum pulse time and dead zone, hereby optimising the control.
The positioner can also be operated manually by the pushbuttons and the LCD of the
SIPART PS2.
The commissioning of the positioner can be divided into the following steps:
• Preparation for initialisation
• Start the automatic initialisation procedure
Operation levels
Mode Display
Figure 5 sips2_5e.tif
Step A: Check and set the gear transmission switch to the correct position. Figure 4
(position 8) indicates the location of the switch. For linear actuators the gear
transmission switch is set according to the stroke range as described in
Table 1 for the parameter "3.YWAY". For part-turn actuators 90° must be
selected.
Step B: Check that the pneumatic supply power (inlet air) is present. The operating
pressure should be at least one bar greater than is necessary for
closing/opening the valve during initialisation.
Step C: Without initialisation the positioner is in "P manual mode" and "NOINIT"
flashes in the display. This level can also be reached by using "55.PRST"
function (see Table 1).
Step D: Check the free running of the mechanics in the whole actuating range by
moving the actuator with the keys "f" and " j " and driving to the respective
end position.
Step E: With linear actuators drive the actuator to horizontal lever position. The
display must indicate 48% to 52%. If necessary, correct the value by
adjusting the sliding clutch. After the check is completed, the actuator must
be approximately half way along its stroke. This is due to establishment of
the action direction during automatic initialisation.
Figure 6 shows the configuration mode including the operation in this mode and
Table 1 shows the parameter/configuration list. Figure 7 shows the initialisation
process of the positioner. The initialisation process is stored in the microprocessor.
This means that an additional initialisation only is necessary if any parts of the unit
have been changed.
Note: The numerical values used in Figure 5, Figure 6, and Figure 7 are
examples.
Step A: Call the configuration mode by pressing the hand symbol key for longer
than 5 seconds.
Step B: Set the actuator type, linear or part-turn, in the menu item line "l.YFCT".
Step C: Switch to the second parameter by pressing the hand symbol key briefly.
Step D: Set the rated angle of rotation for feedback in the menu item line
"2.YAGL". It is vital that this value corresponds to the setting of the gear
transmission ratio selector (Figure 4, position 8), 33° or 90°.
Step E: Switch to the next parameter by pressing the hand symbol key briefly.
Step F: This parameter ("3.YWAY") is only set for linear actuators and if the total
stroke in mm should be displayed at the end of the initialisation phase. To
do this, select the same value in the display to which the carrier pin to the
scale on the lever is set to.
Step G: Switch to the following parameter by pressing the hand symbol key briefly.
Step H: Start the initialisation ("4.INITA") by pressing the " f key for longer than 5
seconds.
Step I: During the initialisation phase "RUN1" to "RUN5" appear one after another
in the bottom of the display. Please note that the initialisation process may
last up to 15 minutes depending on the actuator.
Note: The ongoing initialisation can be aborted at any time by pressing the
hand symbol key. The previous settings are retained. All the parameters
are reset to the factory setting only after performing a preset
"55.PRST".
Step J: If problems occur, carry out the measures as described in the table "Possible
messages" shown in Figure 7.
Step K: The initialisation is completed when "FINSH" appears in the bottom of the
display.
Step L: When pressing the hand symbol key briefly the menu item line "4.INITA"
is displayed.
Step M: To exit the configuration operating mode, press the hand symbol key for
longer than 5 seconds. The software version is displayed after about 5
seconds. The instrument is in manual operation after releasing the key.
Step N: The positioner can be changed to automatic mode by pressing the " j " key
once as indicated in Figure 5.
Step O: The automatic mode is the normal mode. In this mode the positioner
compares the set point current with the current position and moves the
actuator until the control deviation reaches the dead zone.
Figure 6 sips2_5f.tif
Initialisation process
Acknowledge message
Part-turn turn 90° using the hand syrrbol key
actuator 1 YFCT 2 YAGL P 324 Actuatordoes
RUN 1 not move Check restrictor (§ and open
linear WAY 33° Strt if necessary
actuator 1 YFCT 2 YAGL 3 YWAY P 32.4 Drive actuator to working range
ERROR using the up and down keys
Press tte up keyfor> S sec.
Strt Restart initialisation
Remaining steps are carried out automatical;/
Cra nge gearing (7)
Acknowledge message
using the hand symbol key
P 19.8 Up/down span
Setthe na<t lowest travel
violated
valueontre lever
Restart initialisation
Figure 7 sips2_5g.cdr
5.3 Parameters
Table 1 shows the parameter list for the positioner. The parameter name is written in
plain text in the "menu line" column. The function of the parameter is described
briefly in the "Function column". In addition, the possible parameter values, the
physical unit and the factory setting of the parameters are shown.
After the initialisation process, the positioner can be configured to meet the
requirements of a specified task. The factory settings correspond to the requirements
for a typical application. This means that normally only a few parameters will need
to be changed.
The positioner can be installed and configured to fit linear and part-turn actuators
with reverse action. E.g. linear actuators with the set point in the falling direction or
part-turn actuators for counter clockwise operation direction. In this case the
parameters "7.SDIR" and 38."YDIR" should be set to "FALL".
Parameter list
Function Parameter values Unit Factory setting Customer
Menu line
setting
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
l.YFCT Type of actuator ncSt (part-turn actuator WAY
withNCS)
-ncSt (part-turn actuator
with NCS, inverted)
Rated angle of rotation for feedback 90°
2.YAGL0 (must correspond to gear ratio) Degrees 33°
33°
Stroke range (optional setting) OFF
5 , 1 0 , 15 ,20
When used, the value must correspond with (short lever 33°)
the set of the leverage ratio on ihe actuator
3.YWAY2) 25 , 30,35 mm OFF
Driver pin must be set to the value of the (short lever 90°)
actuator travel or, if this value is not scaled, 40,50,60,70,
to the next lager scale value 90,110,130
(long lever 90°)
4.INITA Initialisation (automatically) noini/no/###.#/Strt no
5.INITM Initialisation (manually) noini/###J/Strt no
0MA
6.SCUR Current range of set point JJ^OrnA 4MA
4MA
g riSE
7.SDIR Set point direction f "^i" riSE
FALL
8.SPRA Set point for start of split range 0.0 to 100.0 % 0.0
9.SPRE Set point for end of split range 0.0 to 100.0 % 0.0
Auto
10.TSUP Set point ramp up s 0
0 to 400
ll.TSDO Set point ramp down 0 to 400 s 0
Set point function
Linear Lin
12.SFCT Equal-percentage 1:25,1:33,1:50 1-25 ,1-33 ,1-50 Lin
Inverse equal-percentage 1:25,1:33,1:50 nl-25, nl-33 , nl-50
Freely adjustable FrEE
13.SL03) Set point turning point at 0% 0.0
14.SL1 5% 5.0
to to 0.0 to 100.0 % to
32.SL19 95% 95.0
33.SL20 100% 100.0
Auto
34.DEBA Dead zone of controller % Auto
0.1 to 10.0
35.YA Start of manipulated variable limiting 0.0 to 100.0 % 0.0
36.YE End of manipulated variable limiting 0.0 to 100.0 % 100.0
Standardisation of To mech. travel MPOS
37.YNRM MPOS
manipulated variable To flow FLOW
Direction of manipulated Rising riSE
38.YDIR variable for display Falling FALL riSE
Without no
Tight closing with Top only UP
39.YCLS manipulated variable Bottom only do no
Top and bottom uPdo
Customer
Menu line Function Parameter values Unit Factory setting
setting
40.YCDO Value for tight closing, bottom 0.0 to 100.0 % 0.5
41.YCUP Value for tight closing, top 0.0 to 100.0 % 99.5
Function of B I 1 :
None OFF
Only message (NO/NC contact) on / -on
Block configuring (NO contact) bLocl
42.BIN14' Block configuring and manual (NO contact) bLoc2
OFF
Drive valve to pos. up (NO/NC contact) uP/-uP
Drive valve to pos. down (NO/NC contact) doWn/-doWn
Block movement (NO/NC contact) StoP / - StoP
Function of BI 2:
None OFF
4) Only message (NO/NC contact) on / -on
43.BIN2 OFF
Drive valve to pos. up (NO/NC contact) uP/-uP
Drive valve to pos. down (NO/NC contact) doWn/-doWn
Block movement (NO/NC contact) StoP / -StoP
Without oFF
., „ .. Al=min. A2=max. N,NA
44.AFCT5) Alarm function .. . . . OFF
Al=min. A2=min. N,N
Al=max. A2=max. NA.NA
45.A1 Response threshold of alarm 1 0.0 to 100.0 % 10.0
46.A2 Response threshold of alarm 2 0.0 to 100.0 % 90.0
Function of alarm output
On fault 4
47.L1FCT6) Fault + not automatic 4nA 4
Fault + not automatic + BI 4nAb
("+" means logical OR operation)
Monitoring time for fault message Auto
48. h TIM s Auto
"control deviation" 0 to 100
Response threshold for fault message Auto
49.4LIM % Auto
"control deviation" 0.0 to 100.0
OFF
50.SSTRK Limit for stroke integral OFF
1 to 1.00E9
OFF
51.4DCHG Limit for direction change OFF
1 to 1.00E9
OFF
52.4 ZERO Limit for end stop monitoring, bottom % OFF
0.0 to 100.0
OFF
53. h OPEN Limit for end stop monitoring, top % OFF
0.0 to 100.0
OFF
54.hDEBA Limit for dead zone monitoring % OFF
0.0 to 100.0
Preset (factory setting)
"no" nothing activated no
"Strt" start of factory setting after pressing
55.PRST key for 5 sec. Strt
"oCAY" display following successful
factory setting oCAY
CAUTION: preset results in "NO INIT"
1}
If turn is selected it is not possible to set 33°.
2)
Parameter does not appear if 1.YFCT = turn has been selected.
3)
Turning points only appear with selection 12.SFCT = FrEE.
4
^ Alternatively "no" if initialisation has not yet been carried out
5)
NC contact means; action with opened switch or low level. NO contact means; action with closed switch or high level.
6)
Normal means: high level without fault. Inverted means: low level without fault.
Table 1
Diagnosis
In the diagnostic mode the current operating data (such as number of strokes,
number of changes in direction, number of fault messages, etc.) can be displayed.
From the automatic or manual modes the diagnostic mode can be reached by
simultaneously pressing all three keys for at least 2 seconds.
Table 2 shows an overview of the displayable values. The diagnostic display has a
similar structure as the parameter menu displays. The respective next diagnostic
value can be selected with the hand symbol key. Certain values can be set to zero by
pressing the "f" key for at least 5 seconds. These are menu item line "1,2, 3, and 4".
Some diagnostic values may be greater than 99999. In this case the display switches
to exponential display.
Table 2
Step A: Switch off the pneumatic power supply and remove the pipes.
Step C: Remove the three screws from the pneumatic connector strip.
Step D: Remove the filters and O-rings behind the connector strip.
Step G: Align the pneumatic connector strip on the two lugs and screw tight with
the three self-tapping screws.
Note: Make sure that the same thread is used. To do this, turn the screws anti-
clockwise until they snap into the thread audibly. Only then should the
screws be tightened.
Table of contents
KSB Multitec
Data sheets
Datasheets.
Works No.:
Type Series:
Contents
Page Page
1 General 4 7 Maintenance / Repair 14
2 Safety 4 7.1 General Instructions 14
2.1 Marking of Instructions in the Manual 4 7.2 Maintenance / Inspection 14
2.2 Personnel Qualification and Training 4 7.2.1 Supervision of Operation 14
2.3 Non-compliance with Safety Instructions 4 7.2.2 Bearings and Lubrication 14
2.4 Safety Awareness 4 7.2.3 Shaft Seal 15
2.5 Safety Instructions for the Operator / User 5 7.2.4 Coupling 15
2.6 Safety Instructions for Maintenance, Inspec- 7.3 Dismantling 15
tion and Installation Work 5 7.3.1 General Instructions 15
2.7 Unauthorized Modification and Manufacture 7.3.2 Preparations for Dismantling
5 15
of Spare Parts
5 7.3.3 Dismantling the Bearings 16
2.8 Unauthorized Modes of Operation
5 7.3.4 Dismantling and Replacement of Shaft Seal 18
3 Transport and Storage
c 7.3.5 Removing the Mechanical Seal 18
3.1 Transport / Handling
5 7.3.6 Dismantling the Hydraulic Elements 20
3.2 Storage / Preservation
7.3.7 Recommended Spare Parts Stock for 2
4 Description of the Product and Accesso-
ries 6 years 20
7.4 Reassembly 20
4.1 Technical Specification 6
6 7.4.1 Tightening Torques - Tie Bolts part No. 905 21
4.2 Designation
Q 7.4.2 Reassembly of Hydraulic System 21
4.3 Design Details
a 7.4.3 Seals 21
4.4 Fields of Application \j
7 7.4.4 Bearings 22
5 Installation at Site
7 7.5 Re-adjusting the Clearance Gaps 25
5.1 Safety Regulations/Special Instructions
7.5.1 Max. Clearance Gaps 25
5.2 Foundation/Checks to Be Carried out Prior to
Installation 7 7.5.2 Repairs 25
5.3 Installing the Pump / Unit 7 8 Trouble-shooting 26
5.3.1 Aligning the Pump / Drive 8 9 General Drawings 27-29
5.4 Connecting the Piping 9 9.1 List of Components 30
5.4.1 Vacuum Balance Line 10 Tightening of Shaft Nuts of the Multitec 23
5.5 Connection to Power Supply 10 Adjusting Dimensions for Coupling Alignment,
Pump sizes 32 to 65, Pump versions E, Ex, F, Fx, V,
5.5.1 Connecting the Motor 10 Vx 31
5.5.2 Setting the Time-Lag Relay 10
5.5.3 Checking the Direction of Rotation 10
6 Commissioning, Start-up / Shutdown 11
6.1 Commissioning 11
6.1.1 Lubricating agent 11
6.1.2 Priming the Pump and Checks to be Carried
out 11
6.1.3 Contact Guard 12
6.1.4 Connection to Power Supply 12
6.1.5 Start-up 12
6.1.6 Shutdown 12
6.1.7 Final Check 12
6.2 Operating Limits 13
6.2.1 Temperature of Medium Handled 13
6.2.2 Switching Frequency 13
6.2.3 Minimum Flows 13
6.2.4 Density of the Medium Handled 13
6.3 Shutdown / Storage / Preservation 13
6.3.1 The Unit/Pump Remains Installed, with pe-
riodic check of operation 13
6.3.2 The pump is removed from the pipe and
stored 13
6.4 Returning to Service after Storage 13
2
Multitec
Index
Section Page Section Page
Adjusting Dimensions for Coupling Align Removing the Mechanical Seal 7.3.5 18
ment, Pump sizes 32 to 65, Repairs 7.5.2 25
Pump versions E, Ex, F, Fx, V, Vx 31
Returning to Service after Storage 6.4 13
Aligning the Pump / Drive 5.3.1 8
Safety 2 4
Bearings 7.4.4 22
Safety Awareness 2.4 4
Bearings and Lubrication 7.2.2 14
Safety Instructions for Maintenance, In-
Checking the Direction of Rotation 5.5.3 10 spection and Installation Work 2.6 5
Commissioning 6.1 11 Safety Instructions for the Operator / User 2.5 5
Commissioning, Start-up / Shutdown 6 11 Safety Regulations/Special Instructions 5.1 7
Connecting the Motor 5.5.1 10 Seals 7.4.3 21
Connecting the Piping 5.4 9 Setting the Time-Lag Relay 5.5.2 10
Connection to Power Supply 5.5 10 Shaft Seal 7.2.3 15
Connection to Power Supply 6.1.4 12 Shutdown 6.1.6 12
Contact Guard 6.1.3 12 Shutdown / Storage / Preservation 6.3 13
Coupling 7.2.4 15 Start-up 6.1.5 12
Density of the Medium Handled 6.2.4 13 Storage / Preservation 3.2 5
Description of the Product and Accessories 4 6 Supervision of Operation 7.2.1 14
Design Details 4.3 6 Switching Frequency 6.2.2 13
Designation 4.2 6 Technical Specification 4.1 6
Dismantling 7.3 15 Temperature of Medium Handled 6.2.1 13
Dismantling and Replacement of Shaft The pump is removed from the pipe and
Seal 7.3.4 18 stored 6.3.2 13
Dismantling the Bearings 7.3.3 16 The Unit/Pump Remains Installed, with
Dismantling the Hydraulic Elements 7.3.6 20 periodic check of operation 6.3.1 13
Fields of Application 4.4 6 Tightening of Shaft Nuts of the Multitec 23
Final Check 6.1.7 12 Tightening Torques - Tie Bolts part No.
905 7.4.1 21
Foundation/Checks to Be Carried out Prior
to Installation 5.2 7 Transport / Handling 3.1 5
Transport and Storage 3 5
General 1 4
General Drawings 9 27-29 Trouble-shooting 8 26
° MULTITEC KSB< o
Foundation bolts
Fig. 5 Fitting required shims
Tighten the foundation bolts evenly and firmly after the concrete
has set.
o 2N 3804-AxxXxxuO
is essent al t 0 m a k e s u r e t n a t t n e
Straight-edge ™ Gauge
Fig 8 Aligning a spacer-type coupling
The radial and axial deviation between the two coupling halves
shall not exceed 0.1 mm.
Multitec
Ipossibly
Caution I ' 9 motor, check whether the
I connection of the terminals is tight and re-tighten
loose wires.
A starting (low voltage)
r; W2fOlU2 fO|V2!
U1 lOjVI lOiwi1
LI L2 L3
10
Multitec
11
Multitec
6.1.3 Contact Guard If the pump has to remain operational during shutdown periods,
it must be started up regularly for at least 5 minutes (see also
A In compliance with accident prevention regulations
the pump must not be operated without a coupling guard.
If the customer specifically requests not to include a coupling
6.3):
- fire-fighting pumps at least once a month
guard in our delivery, then the operator must supply one. - drinking water pumps at least once in 48 hours
- standby pumps at least once a week.
6.1.4 Connection to Power Supply (It is better to operate the pumps by alternating daily)
If the pump is equipped with an electric motor, connection to the During these periodic check runs, also check the tightness and
power supply must be effected by a trained electrician only. proper functioning of the auxiliary feed lines.
Check available mains voltage against the data on the motor
rating plate and select appropriate start-up method. 6.1.7 Final Check
Make sure that in the case of three-phase motors with star-delta After the pump has been primed, it must be easy to rotate the
starting method switching over from star to delta will be effected coupling/shaft by hand.
at very short intervals. Prolonged switch—over intervals may re- There must be no impermissible leakage at the shaft seal
sult in pump damage. during pump operation.
Time-lag relay setting for star-delta starting Gland packing
Motor rating Y-time to be set The gland packing has been fitted in the factory. Its permanent
s 30 kW 3 sec. ± 30 % compression can only be set after several hours of pump
> 30 kW 5 sec. ± 30 % operation. During this running-in period, seal leakage will be
higher than during normal pump operation. Check the
6.1.5 Start-up temperature of the leakage.
Start-up procedure: Final adjustment of the gland packing is made gradually after
- The discharge-side shut-off valve must be closed. having allowed for a sufficient running-in period, so that leakage
- Start-up must proceed without abnormal vibrations or is reduced to individual drops (approx. 20 drops per minute).
noises. Tightening the gland cover too early or too hard without allowing
- An automatic check valve installed must open steadily when a sufficient running-in period would cause a local temperature
the operating speed has been reached, without abnormal rise and insufficient lubrication, resulting in the destruction of
noises, vibrations or increased power consumption of the the gland packing, premature wear on the shaft protecting
unit. sleeve and higher, uncontrollable leakage.
- Open the discharge-side shutoff element. For speed controlled pumps or fluctuating inlet pressure, no
- After the duty point has been reached, check motor input packing should be used, if possible. Changing pressures make
power and bearing temperature. the setting of an even and controlled leakage rate very difficult
After the operating temperature has been reached, switch off to achieve.
the unit and re-tighten the bolts at the connecting flanges. . . th
ese conditions occur, leakage of the
Caution I ' n *^ e e v e n * °f abnormal noises, vibrations,
I p g
| Caution | gland packing may not be stopped during any
g y
operating condition whatsoever. With iincreased inleti pressure
immediatelyIandtemperatures or leakage,
re-start it only after theswitch
cause off
for the
the unit
problem and/or increased speed, the inevitably higher leakage of the
has been eliminated. gland packing must not be reduced by subsequent
Increased temperature of the rolling element bearings after re-tightening the gland bolts. The setting of the minimum
commissioning are caused by the running-in processes. The leakage may only be done at lowest speed and/or lowest inlet
final bearing temperature will be established only after some pressure.
operating time (depending on the conditions up to 48 hours).
Mechanical seal
6.1.6 Shutdown The mechanical seal assembly has been adjusted and installed
Close the shut-off element in the discharge line. in the factory. It is maintenance-free. Check the seal for leakage
If the discharge line is equipped with a non-return or check occasionally.
valve, the shut-off valve may remain open, provided there is During commissioning, increased leakage may occur for a
sufficient backpressure in the line. short period of time. If leakage remains high, immediately
- Switch off the drive, making sure that the pump set runs switch off the unit and investigate the leakage cause, e.g.
smoothly down to a standstill. contaminated medium handled or previous dry running due to
- In the case of prolonged shutdown, the shut-off valve in the inadequate venting of the pump.
inlet line has to be closed. Also close any shut-off elements
in the auxiliary feed lines.
- The shaft seal in pumps where the liquid is fed in under Cooled mechanical seal (seal code 64)
vacuum must also be fed with sealing liquid during standstill.. If the pump is fitted with a cooled mechanical seal (seal code
- In the event of frost and/or prolonged shutdowns, the pump 64), vent the seal chamber as described in section 6.1.1.
must be drained or otherwise protected against freezing.
12
Multitec
6.2 Operating Limits ln t n e c a s e of non zontal
13
Multitec
7 Maintenance / Repair 7.2.2 Bearings and Lubrication
For the variant with grease lubrication, the rolling element
7.1 General Instructions bearings of the Multitec 32 as well as the rolling element bearing
The operator is responsible for ensuring that all maintenance, of the non-drive end of the Multitec 50 and 65 in design C and
inspection and installation work is carried out by authorised, D are lubricated for life and do not require any relubrication. In
duly qualified staff who are thoroughly familiar with these this case, there are no lubricating nipples on the bearing
operating instructions. brackets.
A regular maintenance schedule will help avoid expensive
repairs and contribute to trouble-free, reliable operation of the
pump with a minimum of maintenance expenditure and work. Pump
L Before commencing any work on the pump unit, al- Depending on the pump version, the rolling element bearings
/ ways make sure that the drive unit (electric motor, are grease-lubricated or oil-lubricated.
turbine, I.C. motor,...) cannot be started up. Grease Quality / Grease Change
Pumps handling liquids posing health hazards must The bearings are packed with high-quality lithium-soap grease.
Depending on the size of the pump and the operating hours of
be decontaminated. When draining the medium see
the pump, the rolling element bearings must be re-lubricated or
to it that there is no risk to persons or the environment. All the grease in the rolling element bearings must be replaced.
relevant laws must be adhered to.
Speed (1/min)
7.2 Maintenance / Inspection
7.2.1 Supervision of Operation Size MTC <1800 -2950 ~3550
Caution I ^ n e PumP m u s t r u n quietly and free from 32-50-65 10000h 7200h 5700h
' vibrations at all times. 100-125 9000h 5700h 3900h
The pump must never be allowed to run dry.Max. ambient
temperature: 40 °C. 150 8300h 4000h 3100h
The bearing temperature may exceed ambient temperature by If re-lubrication intervals are short, it is recommended to
up to 50 °C but must never rise above +90 °C (measured on the completely exchange the grease once a year. If this is not the
outside of the bearing bracket), see section 7.4.4.1. case, a complete exchange must take place at least every two
years. When doing so, the rolling element bearings must be dis-
A Prolonged operation against a closed shut-off element is
not permitted, to prevent the medium handled from
heating up.
mantled, cleaned, and packed with new grease.
In case of unfavourable operating conditions, e.g.. high ambient
Caution: Required minimum flows see 6.2.3. temperatures and high air humidity, dust-filled air, aggressive
The shut-off element in the inlet line must not be closed industrial atmospheres etc., the bearings should be controlled
during pump operation. earlier and, if necessary, cleaned and packed with new grease.
The mechanical seal leaks only slightly or invisibly (vapour) Under normal conditions grease-lubricated rolling element
during operation. It is maintenance-free. bearings will run for 15,000 operating hours or 2 years. Thereaf-
Gland packings must leak slightly (individual drops). ter, the bearings have to be dismantled, cleaned and re-packed
Any stand-by pumps installed shall be switched on and then with grease. Under unfavourable operating conditions, e.g.
high room temperature, high atmospheric humidity, dust-laden
immediately off again once a week to keep them operational.
air, aggressive industrial atmosphere etc., the bearings should
Attention shall be paid to the correct functioning of the auxiliary
be checked earlier and cleaned and re-lubricated, if required.
connections.
Use a high-quality lithium-soap grease, free of resin and acid,
not liable to crumble and with good rust-preventive
characteristics. The grease shall have a penetration number
between 2 and 3, corresponding to a worked penetration
between 220 and 295 mm/10. Its drop point must not be below
175 °C. The bearing cavities must only be half-filled with
grease.
If required, the bearings may be lubricated with greases of other
soap bases. Since greases of differing soap bases must not be
mixed, the bearings must be thoroughly cleaned beforehand.
The re-lubrication intervals required must then be adjusted to
the greases used.
14
Multitec
Oil Quality /Oil Change 7.2.4 Coupling
Quality: ISO VG 46 When the flexible coupling elements show signs of wear after a
The first oil change shall be made after 300 operating hours, all certain operating period, they must be replaced in due time and
subsequent oil changes after every 3000 operating hours. the alignment motor/pump has to be checked.
Unscrew the plug in the re-fill hole and the drain hole. After the
bearing housing has been drained completely, plug the drain 7.3 Dismantling
hole again. If you need additional information or instructions, please
contact KSB's customer service!
7.3.1 General Instructions
Drainage/Flushing
If the pump was used for handling liquids posing health
hazards, see to it that there is no risk to persons or the
environment when draining the medium. All relevant laws must
be heeded. If required, wear safety clothing and a protective
mask.
The flushing liquid used and any liquid residues in the pump
Fig. 16 Oil fill must be properly collected and disposed of without posing any
risk to persons or the environment.
Hinge down the reservoir of the constant-level oiler 638.
Pour in the oil through the hole until oil appears in the vertical 7.3.2 Preparations for Dismantling
portion of the connection elbow (see Fig. 7.2-1). Then fill the Caution I M a ^e sure to switch off the pump unit before start-
reservoir of the constant-level oiler with oil and snap it back into
operating position. After a short time check whether the oil level
I I ing any dismantling activities. Secure the pump
so as to make sure it cannot be switched on accidentally!
in the reservoir has dropped. The shut-off elements in the suction head/lift line and the dis-
It is important to keep the reservoir two thirds full at all times. charge line must be closed and secured against inadvertent
Lubricant quantities opening.
Grease quantities The pump must have cooled down to ambient temperature. The
pump casing must be drained and its pressure must be
Quantity per bearing unit in g released and the casing must be drained.
Pump size
Driven end non-drive end Noxious, explosive, hot or other hazardous media shall be
32 - -
drained without posing any risk to persons or the environment.
We strongly recommend to flush the pump after drainage.
50/65 15 - Flushing and cleaning the pump is an absolute necessity before
100/125 25 15 sending the pump to the workshop. In addition, all pumps must
150 40 30 be supplied with a cleaning certificate.
Note: For several designs the rolling element bearings are After a prolonged operating period, some components may be
lubricated for life. In these cases there is no lubricating nipple on hard to pull off. We recommend to use a brand name de-rusting
the bearing bracket. agent or a suitable pull-off device.
Oil quantities Under no circumstances use force.
Dismantling must always be carried out in accordance with the
Oil quantity in ml *) sectional drawings at the end of these operating instructions
Pump size
Driven end non-driven end (see section 9 - general drawings).
32 330 330
Heavy components must be sufficiently supported during
50 500
dismantling. The components shall be marked with their se-
330
quence of dismantling, to make sure that they will be re-
65 490 510
assembled in the correct sequence.
100/125 880 920
Thoroughly clean all dismantled components and inspect their
150 1000 1040
condition. Careful examination may help to find the cause for
*) oil quantity without oil in the reservoir of the constant level oiler
pump failure, if any. If in doubt, replace the components. Always
Motor replace parts which are subject to wear (gaskets, O-rings,
Motors without lubricating nipple: The rolling element bearings casing wear rings, rolling element bearings).
have been lubricated in the supplier's factory for an operating
period of 15000 h or 2 years under normal operating conditions.
Motors with lubricating nipple: The rolling element bearings
must be re-lubricated at the intervals indicated on the motor
nameplate (appr. 500 h).
7.2.3 Shaft Seal
Mechanical seal:
The mechanical seal is maintenance-free.
Gland packing:
The nuts of the gland cover must only be tightened slightly. The
gland cover must be at right angles to the shaft. After the pump
has been primed and prior to start-up, make sure.the gland
packing is set to allow a larger amount of leakage. After
approximately 1 operating hour, tighten the nuts at the gland
cover gradually until leakage has been reduced to individual
drops (approx. 7 l/h).
15
Multitec
7.3.3 Dismantling the Bearings
The sections below describe partial dismantling (bearings,
seals, etc.) and complete dismantling of the pump unit.
7.3.3.1 Dismantling the Non-Drive-End Bearings
Plain bearing
The plain bearing is removed without dismantling the hydraulic
system of the pump.
Axial suction nozzle:
Fig. 19
Rolling element bearings:
If the pump is oil-lubricated, drain the oil before dismantling.
- Unscrew bolts 901.4 or 914.5 and remove non-drive end
bearing cover 361.1 or 361.2.
- Unscrew nut 920.7 with lockwasher 931 or the nut with
castellated nut 920.6.
- pull out sleeve 520.2 with rolling element bearing 320.2
Grease lubrication
Multitec 32 -125 Multitec 150
901.4
920.6—.
Fig. 17
- Pull off bearing cover 160.2 using forcing screws.
- Remove circlip 932.1 (shaft in C45) or bolt 901.2 and disc
550.7 (shaft in 1.4021 /1.4462).
- Take out bearing sleeve 529.
520.2
- Pull out bearing cartridge 381 with its two O-rings 412.2.
N.B.: The anti-torsion pin 561.1 remains in position.
320.2-
Radial suction nozzle: Fig. 20 Fig. 21
Oil lubrication with lip seal
412.2 Multitec 32-125 Multitec 150
160.
361.2
914.5
550.10
412.12 920.6
320.2
Fig. 22 Fig. 23
Fig. 18 Oil lubrication with labyrinth seal
- Undo bolts 901.3 and remove cover 160.1 with O-ring
412.3 and bearing cartridge 381 with O-rings 412.2. Multitec 32 -125 Multitec 150
- Remove circlip 932.1 (shaft in C45) or screw 901.2 and disc
550.7 (for shafts in 1.4021/1.4462) 36I.2
320.2
Fig. 24 Fig. 25
16
Multitec
7.3.3.2 Dismantling the Drive-End Rolling Element I The rotating unit is adjusted axialiy by means of
Bearings I spacers 551.1. When reassembling the pump
N.B.: The ceramic plain bearing installed at the non-drive end after partial dismantling (bearing or seal replacement), the
need not be dismantled in order to remove the drive-end rolling same spacer discs 551.1 must be mounted on the side of the
element bearings. If the pump is oil lubricated, the oil must be bearing to reproduce the original rotor adjustment (see also
drained before dismantling. Section 7.4.4).
- After loosening the grub screw in the coupling hub When dismantling keywayed nut 920.6, all relevant positions
pull out coupling half with key 940.3. such as sequence and orientation of the contact face must be
Grease lubrication (Fig 26 and 27) marked accordingly, to ensure identical reassembly (see also
- Remove joint ring (V-ring) 411.7 section 7.4.4).
- Undo bolt 901.1 - Undo nut 920.2 with lockwasher 931 or nut with
- Remove bearing cover 360.1 locknut 920.6, depending on the pump size.
Oil lubrication with radial seal (Fig. 28) To undo the nut, hold onto shaft with key 940.3.
- Loosen bolts 914.4 and pull out together with - Pull off shaft protecting sleeve 520.1 with rolling element
washer 550.10 and O - ring 412.12 bearing 320.1 (The shaft is centered in the sleeve without
- remove bearing cover 360.2 locking device.)
- Remove sleeve 520.4 with ring 500.1 (tolerance - Remove spacers 551.1, see text above.
ring) and O-ring 412.11
N. B.: In the versions V, Vx, E, Ex, F, Fx of sizes 32,50, 65 the
Oil lubrication with labyrinth seal (Fig. 29) pump does not have a fixed bearing as this function is being
- Pull out labyrinth ring 423.2 taken over by the motor bearings. In the versions Multitec V100,
- Loosen bolts 914.4 and pull out together with V125 and V150 the fixed bearing is located in the support
washer 550.10 and O-ring 412.12 lantern 342. Dismantling and installation are the same as for the
- remove bearing cover 360.2 horizontal versions.
320.1
Fig. 27
320.1 520.1
Fig. 26
551.1
551.1 914.4
550.10
412.12
920.2
931
423.1
Fig. 28-3 2 0 .
17
Multitec
7.3.4 Dismantling and Replacement of Shaft Seal 7.3.5 Removing the Mechanical Seal
Gland Packings 7.3.5.1 Removing the Mechanical Seal
7.3.4.1 Replacing the Packing Rings - Remove the bearings as described in sections
Access to packing rings without removing the bearing or the 7.3.3.1 and 7.3.3.2.
lantern: - For grease lubricated version pull V- ring 411.6 off
- Undo both nuts 920.3 and pull gland cover 452 out of spacer sleeve 525.1
- Remove O-ring 412.10
seal housing 441.1. - Pull off spaces sleeve 525.1
- Remove packing rings 461. - Remove any auxiliary pipe work (circulation, etc.),
7.3.4.2 Replacing the Shaft Protecting Sleeve depending on the pump version.
- Loosen nuts 920.3 at the mechanical seal cover
- Remove the bearing as described in sections 7.3.3.1 and until the spring is relaxed.
7.3.3.2. - Remove bearing housing 350.1.
- Remove packing rings as described in section 7.3.4.1. - Take off mechanical seal cover 471.1 with the seat ring and
- Grease-Lubricated version pull V-ring 411.6 off gasket 400.1, remove spring loaded ring (not in case of
spacer sleeve 525.1. bellows seal).
- Remove O-ring 412.10. - Remove key 940.2.
- Take off spacer sleeve 525.1. - Pull off sleeve 523.1 with the rotating assembly of the
- Remove bearing housing 350.1. mechanical seal. (Two holes are supplied in the sleeve for
- Remove the seal housing 441.1 together with gland engaging a pull-off device.)
cover 452. - Take off shaft seal housing 441.1
- Remove key 940 - Remove O-ring 412.4.
- Take off sleeve 524 with a pull-off device. Use the groove
in the sleeve to do so.
- Remove O-ring 412.4.
N.B.: If the sleeve 524 proves difficult to remove, the balance
drum can be used for leverage.
- Remove balance drum 59-4, disc 550.3 and sleeve 524 with
a pull-off device engaged in the threaded holes on the drum.
This is not possible on pumps without balance drum.
902.2 5 2 5 . 1 4 1 2 . 1 0
920.3
441.1 5 2 3 . 14 0 0 . 1 3 5 0 . 1 940.2 5 0 7
Fig. 32
59-4 .1 412.10
920.3
550.3 461 524 350.1 940.2 507
Fig. 30
Fig. 31
525.4
18
Multitec
7.3.5.2 Removing an Air-Cooled Mechanical Seal 7.3.5.3 Dismantling of a water-cooled mechanical seal
(Seal code 64) (Sealing Code 64)
506 4 1 2 . 4 4 4 1 . 4 5 2 3 . 1 9 0 1 . 1 1 9 4 0 . 5 4 1 2 . 10 6D
412.4 731.15 400.1 903.11 471.1
152 i 561.5 411.21 441.4 I 411.17 433.7
Fig. 33
N.B.: This mechanical seal design is used for
application temperatures from 140[JC to 200 °C and Multitec 525.8 | 523.1 I 412.13 66-2 902.2 940.5 421.1 551.1 525.1 412.10
506 350.1 920.3
sizes 32 to 100. The pump shall only be coupled to a motor with
enclosure IP 55.
- Remove bearing ace. to sections 7.3.3.1 or 7.3.3.2. Fig. 35
- Remove O-ring 412.10
- Pull off spacer sleeve 525.1. N.B.: This application concerns the operation at temperatures
- Loosen bolts 901.11. ranging from 140 to 200°C and sizes 125 and 150 (optional for
- Remove bearing housing 350.1 sizes 32 to 100).
- Remove mechanical seal cover 471.1 with the seat
ring and gasket 400.1. - Drain pump and unscrew circulation line using the pipe
- Remove key 940.5 unions 731.15
- Pull off sleeve 523.1 with the rotating assembly of - Remove rolling element bearing according to chapters
mechanical seal 433.7. (Two holes are supplied in 7.3.3.1 and 7.3.3.2
the sleeve for engaging a pull-off device.) - Remove O-ring 412.10
- Take off sealing housing 441.1 - Pull off spacer sleeve 525.1
- Remove O-ring 412.4. - Unscrew nuts 920.3
In case of a between-bearings pump (installation type/pump - Take off bearing housing 350.1
version C or D) the mechanical seal shall be removed as fol-
lows: - Remove mechanical seal cover 471.1 together with the seat-
- Remove screws 900.2 and hood 683.1. ring and gasket 400.1
- Undo axle 87-5 together with fan impeller 831.1 - Remove key 940.5
- the threaded insert 915 has to remain in the shaft 210 - Pull off sleeve 523.1 with the rotating assembly of the
mechanical seal 433.7. (Two holes are provided in the
Caution I ^ o r P r e v i o u s versions (prior to 03/2002) and
I I assembly in the factory, the axle 87-5 and the fan
impeller 831.1 were assembled using Loctite 222.
sleeve for engaging a pull-off device).
- Remove cooling jacket 66-2
Caution I ' = o r P r e v ' o u s versions and re-installation, the axle - Take off seal housing 441.4
I 87-5 and the fan impeller 831.1 must be - Remove O-ring 412.4
secured with Loctite 222. 7.3.5.4 Removing a Double-Acting Mechanical Seal
- Remove support 59-7. Mechanical seals in tandem, face-to-face and back-to-back
- Dismantle the bearing as described in section arrangement are fitted as per customer specifications. There is
7.3.3.1 as well as spacer sleeve 525.1 and bearing a wide variety of variants, types and brands. Please refer to the
housing 350.1. general drawing and the documentation supplied with the pump
The removal of the mechanical seal is done as described for orientation.
above.
831.1
Fig. 34 19
Multitec
7.3.6 Dismantling the Hydraulic Elements 7.3.7 Recommended Spare Parts Stock for 2 Years'
- Remove the bearings as described in sections 7.3.3.1 and Coutinuous Operation
7.3.3.2 and the shaft seals as described in sections I Caution I recommend to replace different wear parts
7.3.4 and 7.3.5.
' ' (such as rolling element bearings, sealing
If possible, place the hydraulic system in vertical position and elements, circiips etc.) whenever the entire hydraulic system is
start dismantling it from the discharge end. dismantled (See spare parts list below.)
- Loosen the four tie bolts 905. Part Description Number of pumps
- Remove discharge casing 107 and then the hydraulic No. (including stand-by pumps)
system. 2 3 4 5 6+7 8+9 10 and
N.B.: The pump versions A/B/C/D in material variants 22/23/30 more
have an intermediate bearing in the middle stage as of the
For shaft seal codes 65 and 66 (gland packing)
number of stages listed in the table (see Fig. 36).
210 Shaft with small parts 1 1 2 2 2 3 30%
Pump Size 32 50 65 100 125 150 230 lmpeller(set = S) 1 1 1 2 2 3 30%
231 Suction impeller 1 1 1 2 2 3 30%
No. of Stages 8 7 6 6 5 6 320.1 Fixed bearing (set) 1 1 2 2 3 4 50%
320.2 Radial bearing 1 1 2 2 3 4 50%
381 Bearing cartridge 1 1 2 2 3 4 50%
411 V-ring( set) 4 8 8 8 g 12 150%
412 O-ring(set = S) 4 8 8 8 9 12 150%
461 Gland packing (set) 4 6 8 8 9 12 150%
5021> Casing wear ring (set) 2 2 2 3 3 4 50%
520 Sleeve 1 1 2 2 3 4 50%
524 Shaft protecting aleeve 2 2 2 3 3 4 50%
525 Spacer sleeve 2 2 2 3 3 4 50%
529 Bearing sleeve 1 1 2 2 3 4 50%
540 Bush 1 1 1 2 2 3 30%
550.12> Disc 2 2 2 3 3 4 50%
59-4 Balance drum 1 1 1 2 2 3 30%
For shaft seal codes 61, 62,63 and 64 (with mechanical seal)
433 Complete mechanical seal 2 3 4 5 6 7 90%
523 3) 2 2 2 3 3 4 50%
Shaft sleeve (set)
For oillubrication
4214> Radial seal ring 4 8 8 8 9 12 150%
171.5 540.3 230.1
Fig. 36 423") Labyrinth ring 2 3 4 5 6 7 90%
20
Multitec
7.4.1 Tightening Torques - Tie Bolts part No. 905 The gland cover must be tightened by hand at first. Use a feeler
Material codes 10,11,12,13 (casing: cast iron) gauge to check the level position of the gland cover. It must be
easy to rotate the rotor by hand.
Pump size Tightening torque (Nm) Leakage is normal during pump commissioning. After approx.
Multitec 32 85 5 minutes' operating period, the amount of leakage can be
Multitec 50 140 reduced by steadily tightening the nuts of the gland cover by 1 /6
Multitec 65 250 of a turn. Keep an eye on the amount of leakage and the water
Multitec 100 395 temperature, it takes several hours of pump operation for the
Multitec 125 600 gland to be adjusted completely. There must be a high leakage
Multitec 150 700 rate during the running-in period.
Repeat this procedure every five minutes until a minimum value
Material codes 20 to 30 is reached.
(casing: steel or stainless steel) Pump size
Dimensions in
Operating pressure Tightening torque
Pump size mm 32 - 50 - 65 100 125 150
(bar) (Nm)
Multitec 32 150 Packing cross-
section
10D 12,5 • 16D
Multitec 50 240
Length of
Muititec 65 All 430
packing cord
= 181 «223 =254 «306
Multitec 100 680
Number of
Multitec 125 1370 5 6
packing rings
< 40 1500
Multitec 150 Gland housing
> 40 2000
7.4.2 Reassembly of Hydraulic System
Pump reassembly starts at the suction side and proceeds
towards the discharge side. It is advisable to place the pump in
vertical position for reassembly. The sequence of reassembly
does not pose special problems and should be done according
to detailed sectional drawings showing the list of individual
parts. The components shall be re-installed in the same place
as before dismantling.
A clearance of 0.7 to 1.2 mm shall be set between the last
impeller 230.1 or 230.3 and the balance drum 59-4 (or spacer
sleeve 525.4).
When tightening the tie bolts, proceed as follows:
- Tighten the nuts of the tie bolts 905 gently, with the pump
in vertical position.
Pump size di da I
- Place the pump in horizontal position upon its feet on the
assembly table. 32 - 50 - 65 45 65 50
- Tighten the nuts of tie bolts 905 in two steps (first step: 100 56 80 60
50 % of nominal torque, second step: nominal torque) in
the sequence 1.4.2.3. 125 66 90 72
150 78 110 96
o o Fig. 38 Gland chamber dimensions
1 2
3 4
Fig. 37
o o
7.4.3 Seals
Gland packing
Before re-packing, thoroughly clean the gland packing
chamber and the gland cover.
I Caution I P a c k i n 9 n n 9 s m u s t be inserted so that the cut
» * edge is displaced by approx. 90° to 120° in
relation to the previous one.
Slip the pre-stressed packing rings onto the shaft protecting
sleeve, press home the first packing ring with the help of the
gland follower. Each packing ring must be pressed into the
packing chamber individually, using the gland cover.
For gland packings with lantern ring (for use in vacuum oper-
ation), the lantern ring is mounted instead of the next to last
packing ring (the last packing ring is located in the seal chamber
on the pump side).
21
Multitec
Mechanical Seals 7.4.3.1 Leakage at the Mechanical Seal
- Check axial alignment of the seal.
I Caution I Mechanical seals are precision components. The
* seat ring and the spring-loaded ring must always
be replaced together, i.e. always replace the entire mechanical
- Check gasket 400.1.
- Remove seal cover 471.1 (471.2 for bellows seal) and check
seal. position of seat ring in the cover.
To ensure trouble-free operation of the mechanical seal. The - Check the O-ring on shaft sleeve 523.1.
seal faces and any tools used must be absolutely clean. - Check O-ring 412.4.
Mechanical seals must be installed with utmost care. 7.4.4. Bearings
The seal faces shall only be cleaned immediately before
assembly takes place. They must not be greasy (grease, Plain bearings
smudges...) or damaged. in installation types A, B, E, Ex, F, Fx, V, Vx are re-installed in
Individual seal components such as O-rings made of EPDM reverse order to dismantling.
must never come into contact with oil or grease. Rolling element bearings
The mechanical seal shall be re-assembled in the reverse The rolling element bearings are generally mounted on a
sequence of dismantling. bearing sleeve and tightened with the shaft nut
When mounting the seat ring, the shaft sleeve may be wetted 920.2/920.6/920.7. They are re-installed in reverse order to
with clean medium handled to reduce the friction forces. dismantling. The position of keywayed nuts 920.6 (contact
The seat ring and the spring-loaded ring shall always be surface = plane surface with recess) marked during dismant-
mounted by hand resp. fingers, making sure that pressure is ling (7.3.3.2) must be complied with.
applied evenly, without tipping. Check the concentricity and face run-out of ring 500.1 with a
dial gauge for variants with oil lubrication.
Horizontal baseplate-mounted pumps
Caution I ^ n PumP versions C and D, the rotational
I I direction has to be observed for mechanical seals
fitted with uni-directional springs.
View
towards
the spring-
Fig. 3 9 loaded ring
Sealing elements
22
Multitec
The shaft nuts must be tightened according to the values indicated in the table "Tightening Torques of Shaft Nuts",
Tightening of the Shaft Nuts of the Multitec
Shaft nuts without lockwasher
Does nota
I Caution I PP' v to d r i v e s i d e o f M T C
32/50/65 with self-locking shaft nut.
Tightening torques for shaft nuts
DriveiEnd Non-dri ve End
Size A,B, C,D ",v A,B,I=,F,V c,D
Nut Nm Nut Nm Nut Nm Nut Nm
801) 80 1 ) 801)
MTC 32 M 25x1,5 40(***) M 25x1,5 40(***) M 25x1,5 40 M 25x1,5 40
100(*)
801) 801> 80 1 )
MTC 50 M 30x1,5 40(***) M 25x1,5 40(***) M 30x1,5 40 M 30x1,5 40
120(*)
1001) 80 D 100
1500
1501) 1501) 1501)
M 42x1,5 M 42x1,5 50 50 50
MTC 100 50
(2x) M 42x1,5 M 42x1,5
(2X)
Nut with lockwasher - (drive end and non-drive end for versions C and D)
Nut with counter-nut - drive end (and non-drive end for versions C and D)
1.) Tighten first nut with torque M1, then loosen again
2.) Tighten first nut with torque M2
3.) Tighten second nut with torque M3, at the same time block first nut
Self-locking nut - old design MTC E/F/V 32/50/65 (drive side) No torques specified.
No torques given
23
Multitec
If there is no suitable torque wrench available for the tightening After installation of the bearings, the following controls need
of the shaft nuts, proceed as follows with respect to each to be made:
design: - Grease lubricated bearings: Check the clearance
between cover 360.1 and bearing housing 350.1 after
Self-locking nut on drive end or non-drive end (versions having tightened the bolts 901.1. There should be a
C and D) clearance between 0.2 mm and 0.8 mm. The cover 360.1
• Tighten fast the shaft nut firmly must not rest on the bearing housing 350.1.
• Loosen the shaft nut again - Oil lubricated bearings: Check the clearance between
• Apply adhesive to thread (e.g. LOCTITE) cover 360.2 and bearing housing 350.1 by verifying the
• Moderately tighten the shaft nut dimensions prior to re-assembly (if bearings or cover
have to be replaced).
Nut with lockwasher on drive end (or non-drive end
versions C and D)
Rolling element bearings
• Tighten the shaft nut firmly Grease lubricated bearings
• Loosen the shaft nut again 0.2 ...0.8 mm
• Moderately tighten the shaft nut
• Bend over lockwasher
Nut with counter-nut on drive end or non-drive end
(versions C and D)
• Tighten fast first shaft nut firmly
• Loosen first shaft nut again
• Moderately tighten first shaft nut
• Block first shaft nut using suitable tool and tighten
counter-nut firmly against first shaft nut
Nut with counter-nut on non-drive end
(all versions except C and D)
• Moderately tighten first shaft nut
• Block first shaft nut using suitable tool and tighten
counter-nut closely against first shaft nut
Fixed bearings
The fixed bearing is the coupling-side bearing on the cou-
pling end. Deep groove ball bearings are installed in size 32.
The other sizes are equipped with angular contact ball Fig. 40
bearings mounted in X arrangement (see sectional drawing). Pump stee Drive end 320.1 Non-drive end 320.2
The spacer discs 551.1 serve to position the rotor in axial 32 6309ZZC3-HT 6309ZZC3-HT
direction. 50 2 x 7309 BUA 6309ZZC3-HT
Axial adjustment of the rotor in not required. 65 2X7309BUA 6309ZZC3-HT
The correct axial position of the rotor is achieved by putting in 100 2x7312 BUA 6312 C3
the bearing housing 350.1 spacer discs 551.1 to a total 125 2x7312 BUA 6312 C3
thickness of 1.6 mm (1 x 1 mm + 3 x 0.2 mm) on the side of 150 2x7315 BUA 6315 C3
the bearing (or angular contact ball bearings).
I Caution I ^ n P r e v ' o u s versions, the axial alignment of the
• * rotor is set by putting on both sides of the bearing Oil-lubricated bearings
(or the angular contact ball bearing) spacer discs 551.1 to a total 0.2... 0.8 mm
thickness of 1.6 mm.
The tightening of the cover bolts 901.1 (or 901.8 for
oil-lubricated bearings) must be done in diagonally opposite
sequence taking into consideration the tightening torques as
follows:
MTC 32/50/65: 30 Nm
MTC 100/125/150 40 Nm
Fig. 41
The same rolling element bearings will be installed for oil
lubrication as for grease lubrication.
Exception: Instead of bearing design 6309 ZZC3-HAT, rolling
element bearing type 6309C will be used for oil lubrication.
24
Multitec
Radial bearing
Versions C and D are equipped with a deep-groove ball bearing 7.5.2 Repairs
as radial bearing. (The other versions are fitted with a plain Clearance between impeller 231 and suction casing:
bearing in the suction casing.) The outer race of the Pump size 32 to 65 for material codes 10,11,12,13:
deep-groove ball bearing must have axial play. The bearing is Re-working the suction casing and mounting a spare casing
installed without spacer discs 551.1. wear ring as per ZN 1095 and re-working the impeller.
For other pump sizes and material codes:
Replacing the casing wear ring 521.1 by a spare ring as per
ZN 1095 and re-working the impeller.
Clearance between impeller 230 and disc 550.1 resp.
casing wear ring 502.2:
(Size 125 and 150):
Replace the casing wear ring 502.2 with a spare ring as per
ZN 1095 and re-working the impeller.
(Size 32 to 100):
Two repair methods are possible:
a) Replacing the impellers 230 and discs 550.1 with new parts.
Quick repair method, no re-work of parts required.
b) Re-working the impellers at the impeller eye by deposit
welding and subsequently machining to the original diameter.
This repair method is used for impellers made of stainless steel.
25
Multitec
8 Trouble-Shooting
Cause Remedy
Pump delivers against an excessively high discharge pressure. Re-adjust duty point.
Check plant for Impurities.
Fit one or several larger Impellers.
Increase the speed (turbine, I.C, engine).
Pump or piping are not completely vented or primed. Vent and/or prime.
Supply line or impeller clogged. Remove deposits in the pump and/or piping.
Formation of air pockets in the piping. Alter piping layout.
Fit a vent valve.
Suction head is too high/NPSH available (positive suction head) Is too low. Check/alter liquid level.
Fully open shut-off valve in the suction line.
Change suction line, If the friction losses in the suction line are too high.
Check strainer / foot valve and suction line for clogging.
Air Intake at the shaft seal. Clean sealing liquid channel, supply with external sealing liquid 2) 3)> if
required, or increase its pressure.
Fit new shaft seal.
Reverse rotation. Interchange two of the phases of the power supply cable.
Speed is too low.2) Increase speed.
Wear of internal pump parts. Replace worn components by new ones.
Pump back pressure is lower than specified in the purchase order. Adjust duty point accurately.
Insufficient or excessive quantity of lubricant or unsuitable lubricant. Top up, reduce or change lubricant.
Non-compliance with specified coupling distance. Correct distance according to the installation plan.
The motor is running on two phases only. Replace the defective fuse.
Check the electric cable connections.
Rotor is out of balance. Clean the impellers.
Re-balance the rotor.
Inadequate cooling of shaft seal chamber. Check the free cross-section of the cooling liquid feed line.
Change in the free cross-section of the return line of the balancing liquid. Check the balancing line.
Wear in balancing device. Check the clearance on the throttling bush/balance drum
1) The pump pressure must be released before attempting to remedy faults on parts which are subjected to pressure.
2) Contact KSB.
3) Pump version with sealing liquid supply only available on request.
26
Multitec
9 General Drawing
Sizes 32 to 100
Radial suction nozzle 106.1 412.1 230.1 905
903.2 920.4
411.2 .1 550 4
- 107 *11-2 59-4 S40.1
350.1
81-92
411.7
940.3
412
27
Multitec
Close-coupled pump up to size 65
Radial suction nozzle B61.1 901.5 901.6 920.10
1O6,1 412.1 230.1
903.2
411-2 I ?¥i I 550.1
Vertical version
Pump size 100,125 and 150
aoo-
901.7—~
920.10
661.2 •
920.9-
901.5-
861.1-
902.1-
920.1
350.1
81-92
7) 732.1
59-4 902.1 900.4 551.1901.1 411.7
940.3
520.1
320.1
Version C
--W-
182
914.1
932.2
920.7 320
931
29
Multitec
his list of components contains all spare parts mentioned in this document.
Part No. Description Part No. Description
106.1 1.2 Suction casing 540.1/2 Bush 1>
107 Discharge casing 550.1/2/3/4/6/8/9/10/11 Disc1)
108.1 Stage casing 551.1 1.2 Spacer disc
160.1 1.2 Cover 561.1 Grooved pin
171.1 Diffuser 565 Rivet
181 Pump stool 59-4 Balance drum 1)
182 Foot 59-7 Support
210 Shaft 1> 636 Lubricating nipple
1
230 Impeller ) 638 Constant level oiler
1
231 Suction impeller ) 681.2 Coupling guard
320.1 1.2 Rolling element bearing 1) 683.1 Hood
341 Drive lantern 710.1/2 Pipe
342 Thrust bearing lantern 723.1 Flange
350 Bearing housing 731.1/3/4/5 Pipe union
360.1 Bearing cover 800 Motor
361.1 Non-drive end bearing cover 831.1 Fan impeller
1
381 Bearing cartridge ) 861.1/2/3/4 Coupling half
400.1 Gasket 87-5 Axle
411.1/2/3/4/5/6/7/8/13 Joint ring 1) 89-8 Foundation rail
412.1/2/3/4/5/10/11/12 O-ring 1) 900.2 Screw
421.1/2/3 Radial seal ring 901.1/2/3/4/5/6/7/8/9/
423.1/2 Labyrinh ring 10/11/12 Hex. head bolt
30
Multitec
Adjusting Dimensions for Coupling Alignment, Pump sizes 32 to 65, Pump Versions E, Ex, F, Fx, V, Vx
Cotes de reglage pour alignement de raccouplement tailles 32 jusqu'a 65, Executions E, Ex, F, Fx, V, Vx
EinstellmaBe fur Kupplungsausrichtung BaugroRen 32 bis 65, Ausfiihrung E, Ex, F, Fx, V, Vx
0 Bride raoteur
0 Motor flange
fl Motor flansch
-Cale de reglage
Adjusting disci
Einsiellscheibsn
SSI. 7
Bild 44
Fig. 44
lAttenzionl T ' 1 e m o t o r s °f versions Ex, Fx and Vx are special motors with reinforced bearing which cannot be replaced by
i standard motors!
Caution I L " es m o t e u r s P o u r l e s versions Ex, Fx et Vx sont des moteurs speciaux a paliers renforces qui ne peuvent pas etre
! remplaces par des moteurs standard!
I Achtuna II Bei den Motoren
wiotoren furmr die aie Version
version Ex,
tx, Fx
t-x und
una Vx handelt es sich urn Sondermotoren mit verstarkter Lagerung, die nicht
vx nana
I 91 durch Standard-Motoren ersetzt werden konnen!
31
Data sheet
KSB b.
Page 1 V.3.4.0
Date 05.05.04 Offer no. 45419364
Enquiry No. Position (Item) 1
Client Item No. PO1
Operating data
FlowQ 62.5 m3/h pumped liquid
Flow rate by wt. 60.73 t/h Boiler feed water AF ( 0 2 specified)
mnimumflow 11.92 m3/h Quality AF, pH>9 (aim >=9.3) at 25 oC
Discharge head 308.96 m Content of O2 <= 0.02 mg/kg
Pumping pressure 29.46 bar solids content
NPSH available 5.52 m (max. 20 ppm)
Pump NPSH 2.85 m Operating temperature t/o 80 C
inlet pressure 0.00 bar Density (t/o) 0.972 kg/dm3
discharge pressure 29.46 bar viscosity (t/o) 0.37 mm2/s
adm. op. press, (t/o) 40 bar vapor pressure (t /o) 0.47 barabs
discharge pressure 34.15 bar Design speed 3564 1/min
Q=0 (+/- 5%) Efficiency 71 %
discharge pressure 35.13 bar Power input of pump (P2) 72.03 kW
(Density =1) motor power 84 kW
Head (enquiry) 294 m
Design (version)
Materials
Material-Code 10
Suction casing JL1040 Bearing housing JL1040
Pressure (delivery) casing JL1040 Shaft seal housing JL1040
Stage casing JL1040 Wear ring 1.4571
Diffuser JL1040 Shaft sleeve 1.4057
Shaft 1.4021+QT Plain bearing SiC/SiC
Impeller 1.4408 casing gasket EPDM 80
Suction impeller 1.4408 tie bolts C45K
Balance drum 1.4021 Bush JL1040
Accessories Drive
Coupling Eupex Electric motor IMB3 60Hz ;46C
Size NH160 Rated power P2 84 kW
Spacer 140 mm size / insu. class 280S
Material JL1040 Type of protection IP55
PTC resistor 3
VIK version -
Motor standstill heater -
Model (make) KSB
Drive supplied by KSB
Baseplate
code GP12 internal piping
Material Steel
balancing pipe
Coupling guard
Size BS189
Material Steel monitoring (roling element bearings)
Anchor bolts
n u i t tec 65-5C
350 • »
300 1 s
\
s
\
•»
100
100
••••£
II**
-*—
——
*-—
r
*——
-—*
•^.
- 60
- i
rcj
£ 40 /
an
**- - i i
»••'•*
—***
«-*
^ ^
^
— p. - ^
20 40 60 80 Q [m3/h)
Table of contents
I GENERAL Page
1.1 Introduction G1.1
1.2 Operating principle G1.1
1.3 Technical characteristics G1.2
II INSTALLATION
2.1 Unpacking and storage G2.1
2.2 Recommendations for installing the pump G2.1
2.3 Electrical installation G2.2
2.4 Hydraulic system G2.2
2.5 Installation sketches G2.3
2.6 Installation of accessories G2.5
2.7 Calculations for installation G2.6
INSTRUCTION MANUAL
FOR INSTALLATION,
OPERATING,
AND MAINTENANCE.
Dosing pump
mROY A & B
This manual should be made available to the person responsible for installation,
operating and maintenance.
Fig.1
A = stroke. I = backward
G1.1
1.3 - TECHNICAL CHARACTERISTICS
The nominal pump flow depends on the piston diameter and the actual pumping stroke speed. The influence
of pressure is low, on the order of-2% per section of 10 bars.
1.3.1 Technical characteristics for mRoy A
piston diameter 0 15
•G1.2
1.3.3 Technical characteristics for mRoy B with a 0 22.2 piston
(3)Maximum flowrate in UH (Q):at pressure of 10b 80 80 124 124 200 200 310 310
Motor power in kW 0.55 0.75 0.55 | 0.75 0.55 0.75 0.75 1.5
G1.3
II. INSTALLATION
2.1 - UNPACKING AND STORAGE
The packing must be carefully examined at reception in order to ensure that the contents have not suffered
any obvious damage. Open the packing carefully; one should be careful not to damage certain accessories
which may be fastened to the inside of the packing. Examine the contents and check them against the
delivery slip.
The packing contains:
- One pump.
- Oil, depending on versions (see chapter 3.9)
- A list of wear-and-tear parts, accompanied by section drawings and space-requirement drawings.
- An instruction manual for pump installation, upkeep and maintenance
Storage precautions
For storage less than 6 months:
Storage is to be carried out preferably in the original packing and protected from inclement weather
conditions.
For storage longer than 6 months:
Preserve the original packing. Also provide packing under plastic heat-sealing wrapping and dehydrating
bags. Store the pump in protected, covered premises with full oil charge.
2.2.1 Manutention
Put the sling under the motor terminal box and under
the motor flange.
Cross the two ends of the sling and close the loop
(see diagrams).
Before attempting to move it, check that the entire
unit is well balanced.
G2.1
2.3 - ELECTRICAL INSTALLATION
Verify the motor data against your available mains supply for the plant before carrying out connections.
Connect the motor according to the indications given in the terminal box.
A
For 230 V delta connection
Before operating the pump, check the direction of rotation of the motor which must be
according to the arrow stamped on the motor (Counter-clockwise direction when seen
from top). To reverse the direction of rotation, just reverse A and B or A and C.
G2.2
Ill
2.5 - INSTALLATION SKETCHES
2.5.1 Installation on suction side
2.5.1.1 Recommended installations
[
D -,
n
\
L1
y Ha Ha
L
T1
Fi
Fig.2 Fig.3 9-4
Fig.2: The pump in suction placed above the tank(Ha = maximum 2.5 m water column) is equipped with a
foot valve fitted at the suction end (F). Vertical suction.
Fig.3: Long sized pipework (L) requires the installation of a damper which is to be placed as close as
possible to the pump. L1 = Maximum 10 metres water column.
Fig. 4: The pump "in suction" offset in relation to the tank (Height [Ha] see chapter 1.3), is equipped with a
foot valve (F).
1: Max level
2: Min level
V: Valves
G: Vent
R:degassing vessel
Fig.8
Fig. 8: Setting up a degassing vessel (Chap. 2.6.3.) at the pump suction (one thus avoids frequent un-
priming). Connection between the pump and the inclined degassing vessel in order to facilitate degassing.
G2.3
2.5.2 Installations on delivery line
lr--.gr-
Fig.10
Fig.9
Fig. 9: Long pipe lengths and delivery in a pressurized conduit (P): Install an injection pipe (E), a buffer tank
(D) and a safety valve (C).
Fig. 10: Long pipe lengths and delivery in a non-pressurized conduit: Install a nonreturn valve (B) or check
valve (A) and a buffer tank (D).
For short lengths of discharge pipe (L), the buffer tank (D) can be dispensed with although it increases the
service life of the metering pump and of the installation.
If the delivery pressure is less than 2 bars, an injection pipe or nonreturn valve should be used.
G2.4
2.6 - INSTALLATION OF ACCESSORIES
Proper functioning of the pump depends on whether certain accessories available from DOSAPRO MILTON
ROY are fitted or not. The salesman is at your disposal to determine the accessories which are best adapted
to your plant.
2.6.2 Filter
It is very CAUTION when there is gravity feed; it avoids accumulation of solid particles in the valve
assemblies and guarantees precision and pump life.
G2.5
2.7 - INSTALLATION CALCULATIONS
2.7.1 General
Sizing of the plant suction line corresponds to the NPSH calculation (Net Positive Suction Head) and it aims
to avoid any risk of cavitation. Very often when processing non viscous liquids (typically less than 50 cp), the
NPSH calculation is needed to verify the following condition:
with
W= Liquid density.
Pa = Suction pressure (bars absolute).
Tv = Vapour pressure (in bars).
Ha = Suction height (in m). (Ha is negative with the pump placed above the suction point; it is positive when
gravity fed).
L = Length of the piping (in m).
Q = Max flowrate of the pump (in l/h).
N = No of pump strokes (in str./min).
d = Inside diameter of the piping (in mm).
2.7.2 Example
Calculation carried out to deliver a flow of 200 L/H.
W 1 L 1
Pa 1 Q 560
Tv 0.025 N 144
Ha d :12.5
1x144x560
This condition shows: (1-0.025) + l> 2 + 0.016
;
thus: 10.945 > 4.064 12.52
The condition is met and the pump will not give rise to cavitation.
When the NPSH condition is not obtained, the installation conditions must be improved by making or
envisaging the following modifications:
- Place the pump under load: Ha increases
- Place the pump near the tank : L decreases
- Increase the diameter of the piping: d increases (the most effective solution)
- Place an pulsation dampener at the suction (see chapter 1.3)
Do not hesitate to consult your usual DMR representative for complete calculations.
G2.6
I l l OPERATION AND MAINTENANCE
3.2 - STARTUP
- Tun the pump ON
- Place the vernier on the 50% position, for 10 minutes.
- Untighten by around 1/4 turn, drain plug (B) located on the liquid end (Fig. 19) and (Fig.
20). Thus, the air trapped in the suction piping and the pump head can escape via the drain. Wait
until the liquid comes up to the evacuation level of this drain.
Let it flow for a few seconds in order to degas it completely, then retighten the drain plug.
Intervention Frequence * *
- Renewal of safety valve assembly (Chap. 3.8.1 and Chap. 3.8.2). 8000 h
* See list of wear parts for the ordering of the various parts.
* * Approximate no of hours when operating under max performance and normal conditions of
use.
G3.1
3.5 - ORDERING OF SPARE PARTS
To simplify your order and ensure the best delivery times of spare parts, we recommend giving
our services the correct code of your pump and its DOSAPRO MILTON ROY serial no. This
information is shown on the Nameplate fixed on the side of the pump.
Pump code f •
TYPE
DOSAPRO
MILTON ROY
A 112 F 3 H 2 1
PONT ST PIERRE
2 7 3 6 0 FRANCE
^
1
1
serial no N* 92.01.100A.01.01 1
Item 1
N'serie 1
J
Our product identification tells us precisely the kind of equipment involved and gives us details on
each item comprising it.
Code : 1 A | 112 | F | 3 1 H I 21 |
I I I I I I
Zone : 1 2 3 4 5 6
G3.2
3.7 - SERVICING AND MAINTENANCE OF LIQUID END
Before carrying out any servicing operation on the metering unit or pipes, take the necessary
steps to ensure that the harmful liquid they contain cannot escape or come into contact with
• personnel. Suitable protective equipment must be provided. Check that there is no pressure
before proceeding with dismantling.
024.
438
-0^4
\J ft
438B ^ _ ;
mm
k F<
Fig. 14
Discharge check vdve assembly Fig.15
Suction check valve assembly
G3.3
3.7.3 Renewal of check-valve boxes _ plastic version
438B-
Fig. 17
Discharge check valve assembly
438A-
Fig. 18
Suction check valve assembly
Fig.16
Plastic liquid end
Disassembly
- Unscrew both nuts (435) located on pressure plate (004).
- Remove pressure plate (004) with both washers (434)
- Remove the Discharge check valve assembly.
- Pull on strap bolt (032) to release the suction check valve assembly
- Remove box cap (013), spring (080), ball guide (003), seal (438), ball (407).
Reassembly
- Fit spring (080), ball guide (003) and seal (438) on box cap (013), and mount ball (407) on its
seat (A).
- Fit seals (438B) and (438A) on the check-valve boxes.
- Fit the check-valve boxes onthe liquid end.
- Fit the pressure plate on strap bolt (032) with two washers (434).
- Hand-tighten screws (435) by pressing on the pressure plate.
- Orient the suction check valve assembly, then tighten two nuts (435).*
Connect the piping making sure of perfect watertightness.
Note: The items comprising the suction check valve assembly cannot be taken apart; this is also the case
for ball (B) and seat (A) of the Discharge check vaVe assembly.
* For information concerning tightening torque as well as which spanners to use, see Chapter 3.7.7.
G3.4
3.7.4 Diaphragm Renewal
Before carrying out any operations, place the vernier on the 0% position, check that all the isolating valves
are closed, then disconnect the piping.
Disassembly Reassembly
- Drain the pump (Chapter 3.9.2). - Mount contour plate (298B). It is CAUTION for
- Lay the pump on the side opposite one of holes in the contour plate to be placed at
the liquid end the highest point (see detail C).
- Remove suction check valve
assembly (A) (Chapter 3.7.2 or CAUTION: For metallic versions, contour plate (298B) on
Chap. 3.7.3) the mechanical side is made of steel and contour plate
- Remove screws (405A) (Fig. 19) or (298) on liquid end side is made of stainless steel.
(405) (Fig. 20) from the liquid end. - Fit diaphragm (298A).
- Remove diaphragm (298A) and - Fit contour plate (298). It is CAUTION for one
pressure plates (298), (298B) using a of the holes in the contour plate to be placed at
pointed object. the highest point (see C detail)
- Clean all the parts. - Fit the liquid end and tighten screws (405A) or
(405) in star-pattern (Fig. 22).*
- Refit the suction check valve assembly
(Chap. 3.7.2 or Chap. 3.7.3).
- Fill up with oil (Chap. 3.9.2).
- Put into service (Chap. 3.1, Chap. 3.2)
298
405
Fig. 19 Fig.20
Metallic version Plastic version
A In order to prime the pump, it is necessary to purge the liquid end (to release air) by opening
purge nozzle (B). For toxic liquids, it is recommended to collect this fluid to safe drain point during
this operation.
* For information concerning tightening torque as well as which spanners to use, see Chap. 3.7.7.
G3.5
3.7.5 Renewal of double diaphragm, "C" type
Before carrying out any operation, place the vernier on the 0% position, check that all the isolating valves
are closed, then disconnect the piping.
Disassembly
- Drain the pump (Chap. 3.9.2).
- Untighten ring pipe fitting (432A) by 1/2 turn.
- Lay the pump on the side opposite the liquid end
- Remove suction check valve assembly (A) Chap. 3.7.2 or Chap. 3.7.3)
- Unscrew the tightening screws from liquid end (405A), beginning with those in support lug (050A).
- Remove the two diaphragms (298) and the 2 contour plates (098).
- Clean all of the parts.
Reassembly
- Fit contour plate (098) on the mechanical side.
- Centre diaphragm (298) on contour plate (098).
- Fit double-diaphragm body (050) on diaphragm (298).
- Centre second diaphragm (298) on double diaphragm body (050).
- Centre second pressure plate (098) on double diaphragm body assembly (050)
- Fit the liquid end and hand-tighten 2 tightening screws (405A) diametrically opposite.
- Fit support lug (050A) and its detection.
- Connect the detection pipe of double-diaphragm body (050) to ring connection (432A).
- Hand-tighten the connection and tighten by 1/4 to 1/2 turn.
- Pre-screw in star-pattern (Fig. 22) tightening screws (405A) of the liquid end
(torque: 2 Nm)
- Tighten tightening screws (405A) of the liquid end in star-pattern. *
- Refit the suction check valve assembly (Chap. 3.7.2 or Chap. 3.7.3).
- Fill up with oil (See Chapter 3.9.2).
- Put into service (Chap. 3.1, Chap. 3,2)
- Degas the double diaphragm (Chap. 3.7.6)
Fig.21
Type "C" double diaphragm, metallic version
* For information concerning tightening torque as well as which spanners to use, see Chapter 3.7.7.
G3.6
3.7.6 Degassing of double-diaphragm
body, "C"type
Fig.21A
B detail of Fig. 21
If the degassing can not be done by the above procedure there some possibility to perform this operation
with a syringe. This syringe is available on request at the Spare Part Departement
Fig. 22
Tightening in star-pattern-shape
G3.2
IB
3.8 - SERVICING AND MAINTENANCE OF THE MECHANICAL ASSEMBLY
-023
Fig.23
Disassembly of the relief valve
G3.1
3.8.3 Renewal of adjustment liner O-rings(Fig. 24, Fig. 25, Fig. 26)
Disassembly
- Place the vernier on the 0% position
- Drain the pump (Chap. 3.9.2).
- Remove the lantern (Chap. 3.8.8)
- Remove circlips (434) (Fig. 25).
- Completely unscrew adjustment knob (255).
- Unscrew screw (256).
- Pull liner (012A) of housing toward you. (Fig. 26)
- Remove 3 O-rings (438B) located on liner (012A) (Fig. 24).
- Remove sleeve (E) from drive pin (214A) (Fig. 26)
- Clean the housing as well as the liner / sleeve assembly
Reassembly
- Refit the 3 O-rings (438B) using the tool (011) (Fig. 24):
-Reference 0110031071 forthemRoyA.
-Reference 0110032071 forthemRoyB.
- Coat the 3 O-rings (438B) with tallow.
- Fit sleeve (E) on drive pin (214A) (Fig. 26).
- Insert liner (012A) very slowly in the housing, turning it whilst holding sleeve (E) in the axis of liner
(012A).
- Screw in screw (256).
- Screw in adjustment knob (255) (Fig. 25)
- Fit circlips (434).
- Fit lantern (Chap. 3.8.8)
- Fill up with oil (see Chap. 3.9.2).
Fig.24
Liner / sleeve
255
434
Fig.25
Adjustment knob
G3.2
3.8.4 Renewal of eccentric shaft seals (Fig. 26).
For disassembly and reassembly of the eccentric shaft, the pump adjustment knob must be opposite you.
Disassembly
- Place the vernier on the 0% position
- Drain the pump (Chap. 3.9.2).
- Remove the 2 circlips (434A) from eccentric shaft (068)
- Drive out eccentric shaft (068) to the right to release seal (438A).
- Remove seal (438A)
- Drive out eccentric shaft (068) to the left to release seal (438A)
- Remove the other seal (438A)
Reassembly
Before reassembly, degrease all parts
- Fit an O-ring (438A) on eccentric shaft (068)
- Put glue (loctite 638) on the end of eccentric shaft (068) until it exceeds the other side of the housing by
one centimetre.
- Fit the other O-ring (438A) on eccentric shaft (068); put glue (loctite 638) on the end of eccentric
shaft (068)
- Position eccentric shaft (068) in the centre of the housing (see Fig. 26)
- Fit circlips (434A) on each end of eccentric shaft (068)
- Allow the glue to harden for 30 minutes
- Fill up with oil (see chap. 3.9.2).
438A
Fig.26
Simplex pump
Fig.27
Duplex pump
G3.3
3.8.5 Renewal of connecting rod and shaft for mRoy A, simplex and duplex (Fig. 26, Fig. 28).
Disassembly
- Place the vernier on the 0% position
- Drain the pump (Chap. 3.9.2).
- Remove the lantern (Chap. 3.8.8)
- Remove eccentric shaft (068) (Chap. 3.8.4)
- Unscrew screws (435) and remove drive pin (214A) (Fig. 26)*
- Remove plunger assembly (012) / connecting rod (214) / wheel (052) from the housing, by lifting
wheel (052)
- Drive out connecting rod shaft (011)
- Clean the housing and the parts removed
Reassembly
- Refit piston (012) / connecting rod shaft (011) / connecting rod (214) assembly by gluing the end of
connecting rod shaft (011) with Ioctite glue 556 and being careful to position the lubricating groove (detail: A)
of connecting rod (214) opposite the threaded holes of the piston (Fig. 28)
- Insert piston / connecting rod assembly in housing
- Fit wheel (052) with connecting rod (214) (Fig.26)
- Fit concentric shaft (068) (Chap. 3.8.4)
- Fit drive pin (214A), then screw in and glue (Ioctite 221) the two screws (435)
- Refit the lantern (Chap. 3.8.8).
- Fill up with oil (Chap. 3.9.2).
- Put into service (Chap. 3.1, Chap. 3.2)
"012
Fig.28
Piston / connecting rod assembly
' Fur information concerning which spanners are to be used, see Chapter 3.7.7.
G3.4
fii
3.8.6 Renewal of connecting rod and shaft for mRoy B, simplex (Fig. 26, Fig. 28).
Disassembly Reassembly
- Drain the pump (Chap. 3.9.2). - Refit piston (012) / connecting rod shaft (011) /
- Remove the lantern (Chap. 3.8.8) connecting rod (214) assembly, being careful to
- Unscrew nut (435F) and screws position the lubricating groove (detail: A) of
(435), (435E) Fig. 26)*. connecting rod (214) opposite the threaded holes of
- Remove eccentric shaft (068) the piston. (Fig. 28)
(Chap. 3.8.4) - Screw in and glue (loctite 566), locking screw (435E)
- Remove drive pin (214A) on the side where the groove of connecting rod shaft
- Remove plunger assembly (012) / (011) is located
connecting rod (214) / wheel (052) - Insert piston / connecting rod assembly in housing
from the housing, by lifting wheel - Fit wheel (052) with connecting rod (214) (Fig.26)
(052) - Fit eccentric shaft (068) (Chap. 3.8.4)
- Drive out connecting rod shaft (011) - Fit drive pin (214A), then screw in and glue
(Fig. 28) (loctite 221) screw (435) and nut (435F)
- Clean the housing and the parts - Refit lantern (chap. 3.8.8)
removed. - Allow glue to harden 30 minutes
- Fill up with oil (Chap. 3.9.2).
- Carry out startup and operating procedures
(Chap. 3.1, Chap. 3.2).
Disassembly Reassembly
- Drain the pump (Chap. 3.9.2). - Place plunger (012) in the housing tapped holes up
- Remove the lantern (Chap. 3.8.8) ward
- Unscrew 2 screws (402) (Fig. 27) - Assemble connecting rods (214) with wheel (052)
- Unscrew nut (435F) and screws being careful to position the lubricating groove
(435), (435E) (Fig. 26). (detail: A) of connecting rod (214) downwards
- Remove drive pin (214A) (Fig. 26) (Fig. 28)
- Drive out the 2 shafts of connecting - Place excentric wheel (052) / connecting rod (214)
rod shaft (011) by the threaded holes assembly in the housing
of screws (402) - Fit eccentric shaft (068) (Chap. 3.8.4)
- Remove eccentric shaft (068) - Fit the 2 shafts of connecting rod shaft (011) by the
(chap. 3.8.4) threaded holes of screws (402) (Fig. 27)
- Remove excentric wheel (052) / - Screw in and glue (loctite 566) locking screws
connecting rod (214) assembly in the (435E) of the side where the groove of connecting
housing rod shaft (011) is located
- Remove plunger assembly (012) / - Fit drive pin (214A) then screw in and glue
connecting rod (214) / wheel (052) (loctite 221) screw (435) and nut (435F) (Fig. 26)*
- Remove plunger (012) off the housing - Refit the lantern (Chap. 3.8.8).
- Clean the housing and the parts - Screw in and glue screws (402) with loctite glue 221
removed. (Fig. 27).
- Allow the glue to harden 30 minutes.
- Fill up with oil (Chap. 3.9.2).
- Carry out startup and operating procedures
(Chap. 3.1, Chap. 3.2).
For information concerning which spanners are to be used, see Chapter 3.7.7.
G3.5
3.8.8 Disassembly of the lantern (Fig. 26, Fig. 29)
Disassembly *
- Disconnect the power supply cables from the motor
- Unscrew 4 screws (435A), (434C) from lantern (072) and turn while pulling up the
lantern vertically with the motor
Reassembly
- Put sealing compound on side B (Fig. 26)
- Fit lantern (072) being careful not to bump drive pin (214A) with the worm shaft
- Screw in screws (435A) (434C)
- Connect the motor power supply cables
3.8.9 Renewal of the worm shaft (Fig. 29).
Disassembly
- Remove the lantern (Chap. 3.8.8)
- Unscrew screw (435B) from coupling (052D).
- Remove the 2 washers (280) and washer (219) being careful not to separate them.
- Remove the worm.
Reassembly
- Fit washers (280) / washer (219)
- Fit coupling (052D) on the screw whilst adhering to measurement H (H = 5 mm for the mRoy B, or fit
coupling (052D) in mechanical thrust block for the mRoy A)
- Screw in screw (435B)
- Fit the lantern (Chap. 3.8.8)
- Mount the motor
3.8.10 Renewal of worm bearing.
Same procedure as for the Renewal of the worm shaft (Chap. 3.8.9), but by replacing bearings (409A) and
(409).
3.8.11 Renewal of the wheel / worm.
Same procedure as for Renewal of the connecting rod and shaft (Chap. 3.8.5 to Chap. 3.8.7), but without
removing connecting rod shaft (011) (Fig. 28) for the mRoy A
435D/434B/435C
409
Fig.29
Motor lantern
* For information concerning which spanners are to be used, see chapter 3.7.7.
G3.6
3.9 - LUBRICATION
The oil level must be checked every month. Fill the housing up to the middle of the level indicator. Use the oil
supplied with the pump or an equivalent oil (see table below). The oil must be changed every 2500 hours of
operation or every six months. The pump must be placed in a zone where the ambient temperature is
between -5°C and 50°C.
QUANTITY:
mROYA mROYB
Simplex 1L 3L
Duplex 2L 4L
TABLE OF CHARACTERISTICS
EQUIVALENCY TABLE
Make Type
COFRAN MECANEP 150
B.P. GRXP150
CASTROL ALPHA SP 150
ELF REDUCTELFSP150
FINA GIRAN 150
IGOL DYNAMSP150
MOBIL OIL MOBILGEAR 629
SHELL OMALA150
TOTAL CARTER EP 150
ESSO SPARTAN EP 150
G3.1
IV FAULT LOCATION PROCEDURES
If, during the initial startup, the pump does not work properly, check the pump installation (SECTION:
INSTALLATION II).
4.1 - THE PUMP DOES NOT DELIVER:
CAUSE REMEDY
A - Motor stopped A-
- The thermal relay has been overloaded and has tripped. - Reset the thermal relay (Check the
reason for the overload)
B - No more product to pump.
B - Check the product level
C - Piping clogged up.
C - Unclog the piping
D - Filter blocked.
D - Clean the filter
E - Suction piping valve closed.
E - Open the valve
F - Diaphragm pierced.
F - Change the diaphragm
G4.1
Connecting diagram for
chemical dosing pump unit.
012
Dosing line not A I supply.
The distances between the dosing pump and feedwater line max. 4 mtrs. Fitting
Dosing tine 012 x 1.5mm. Standless steel or (steel).
-J A I supply.
Shutdown valve 3/8'BSP. :
U pcs of fittings 3/8"BSP / 012 as sketch.
r
%
CM
3
Oil fired boiler Hotwell Feed water pump Dosing pump
> ••• «
II TABLE OF CONTENTS
AALBORG
INDUSTRIES
Table of contents
Description
The salinometer is used in combination with a conductive electrode to measure and
supervise the salinity of feed water. Figure 1 illustrates the control device and
electrode.
The control device is provided with indication LED's for monitoring the salinity
level and two LED's for alarm purpose. The measuring range as well as the
adjustable alarm range is 0 - 20 ppm (sea salt). The alarm limit can be adjusted by
means of the set screw located on the front panel. The alarm limit is indicated by a
flashing LED in the indication LED row. If the salinity level exceeds the alarm limit
the alarm LED's start flashing.
During commissioning it is not necessary to carry out any adjustments of the
equipment except setting the alarm limit. When the power is turned on, the
salinometer will perform a self test. This calibration will take approximately 5 sec.
Connector
plug
1 2 3 4 5 6 7 6 9 10 12 14 16 18 20
Packing
Gold-plated
electrodes
Terminals
Figure 1 sl700c.cdr
Installation
The conductive electrode may be installed vertically, horizontally, or radial inclined.
However, the electrode tips must be constantly submerged in feed water. Figure 2
illustrates the salinity system.
Condensate
Figure 2 sI700d.cdr
2.1 Wiring
The wiring should be carried out in accordance with the diagram shown in Figure 3.
Wiring diagram
4-20 mA
90-115 VAC
Figure 3 s!700e.cdr
The mains supply of the control device is 90-115 VAc or 190-230 VAC, 50-60 Hz.
Ensure that the mains supply is secured against over current by a fuse (max. 100mA).
The recommended cable for the conductive electrode is a multi-screened twin
twisted pair like Farnell no. 385-4334, where the screen is connected to connector
14, one pair is used for connector 11+12, and the other pair is used for connector
13+15. The length of the cable must not exceed 200 m.
Important: The cable may not be placed together with power cables, as this
will cause damage to the gold plating on the electrodes.
Maintenance
The accuracy of the salinometer equipment is very dependent on the electrodes are
kept clean. The electrodes should be taken out and cleaned at least once a week. Use
only a clean and soft reg. When cleaning the electrodes it is important that oil or
other chemicals do not pollute the electrodes. Any pollution will immediately result
in an inaccurate measurement of the salinometer.
Note: Avoid damaging the gold plating. If the gold plating is damaged, the
conductive electrode must be replaced.
The expected longevity of the conductive electrode is approximately 1.2 - 2.2 years.
Table of contents
1 General
This chapter contains installation, operation, and maintenance instructions for the
ultrasonic interface detection system, Mobrey type 402 SD, using control unit type
MCU200.
Each Mobrey ultrasonic control system requires a sensor to suit the specific
application, plus a control unit. These instructions cover the control units in the
MCU200 series.
Sensor installation
The ultrasonic sensor contains two piezoelectric crystals. A high frequency signal
(3.7 MHz) generated by the control unit is transmitted to one piezoelectric crystal by
coaxial cable. This crystal converts the electrical signal into an ultrasonic oscillation.
The sensor design allows the ultrasonic oscillation to pass from the transmitter
crystal to the receiver piezoelectric crystal. The sensors of type 402 are "gap" type
sensors, where the two piezoelectric crystals are separated by a gap. When the gap is
in liquid the signal reaches the receiver, because of the low ultrasonic attenuation of
the liquid. When the gap is filled with air, no ultrasonic signal can pass from
transmitter to receiver. See Figure 1.
Seiuorgabwot
i TTT^t^Ti
•«•
1 1
Figure 1 mobrey01.tif
When the gap is filled with liquid, the piezoelectric receiver crystal converts the
ultrasonic wave into an electrical signal, which is transmitted back to the control unit
using a second coaxial cable. Usually the two coaxial cables to the sensor are in one
overall sheath. The control unit circuitry is a feedback amplifier, which oscillates
when the sensor is wet, and is quiescent for the sensor dry. The "oscillating" or
"non-oscillating" sensor states dictate the output relay states of the MCU200.
For interface detection the sensor "oscillates" in a clear liquid, and is "non-
oscillating" at the interface.
Table 1
When double coaxial cable needs to be extended, two sets of coaxial plugs and
sockets will be needed, one set for transmit and one receive. Care must be taken that
the connectors are not connected to earth or shorted together in any way, to prevent
cross-talk or pick-up. The coaxial connections must be made in a waterproof
junction box. Terminal blocks should not be used.
3.1 Mechanical
The control unit is supplied with three holes drilled in the bottom (longer) side of the
box. Two glands are supplied for the power input cable and relay output cable. The
sensor is normally supplied fitted with a suitable gland on the cable. Two further
holes can be drilled in the bottom side of the box should these be needed: it is
recommended that the circuit board is removed whilst drilling extra gland holes.
Figure 2 shows the dimensions of the MCU200 housing box.
Mounting
Holes
Figure 2 mobrey04.tif
All cable connections are made to the terminal blocks along the bottom edge of the
pcb, see Figure 3. Release the terminal screw before inserting the wire.
MCU201 PC board
Output
Logic Switches - LED
Indicators
Cain
Controls
Figure 3 mobrey05.tif
3.2.1 AC mains
AC mains is connected between the "N" terminal for neutral and one of the "115V"
or "230V" terminals depending on the voltage supply available - BEWARE - the
terminal not connected externally will be "live" once the transformer is powered via
the other terminals.
3.2.2 Mains earth
Mains earth should be connected to the terminal marked "E". This provides an earth
contact for the pcb mounting pints.
3.2.3 The relay
The relay output connections are labelled:
• NC - Normally closed (relay de-energised)
• C - Common
• NO - Normally open (relay de-energised)
There are also two sets of contacts for DPCO relay, labelled 1 & 2.
3.2.4 The sensor
The sensor connections are labelled "1", "E" for the receiver crystal and "2", "E" for
the coax cable to the transmitter crystal. The screens of these coax cables are
connected to the terminals marked "E".
Orange 3 \
E = Red
Yellow 4
Delay to E
Green 5
OSC = NE
Blue 6
Figure 4 mobrey77.tif
Set the switches in the following order, starting at the bottom and working upwards:
BLUE:
If the MCU200 relay is to be energised (E) when the sensor is oscillating (OSC)
then set the No 6 blue switch to the right (OSC=E). This is the preferred setting, to
give a de-energised relay in the ALARM state for a gap sensor as a low level alarm.
GREEN:
This selects the relay change which is subject to the time delay selected on the top
switches. When the No.5 green switch is set to the right, the delay occurs between
the sensor changing state and the relay de-energising or becoming "not energised"
(NE). This time delay is a minimum of 0.15 seconds, (achieved by switching the top
BROWN switch to the right) and is used to prevent relay chatter at the changeover
point. Longer time delays are selected on the top three slide switches as shown in
Figure 5.
The relay change in the opposite direction is immediate (within 50 milliseconds).
Brown 1
• * • 2
Red 2
- * - 3
Orange 3
2 seconds* 8 seconds' 30 seconds*
Figure 5 mobrey08.tif
YELLOW:
Only one of the GREEN or RED LEDs will be illuminated at any one time. These
LEDs show the state of the MCU200 output relay. The RED LED is labelled
"ALARM" and the GREEN LED is labelled "NORMAL". The yellow slide switch
(Number 4) determines which LED will be illuminated when the relay is energised
(E). It is usual to have the GREEN/NORMAL condition occur with the relay
energised, i.e. with switch Number 4 to the right (E=GREEN).
4 Applications
Correct adjustment of the gain (HI/LO switch and potentiometer) is essential for
proper operation of any ultrasonic sensor system. This adjusts the gain of the
feedback amplifier in the control unit, which produces oscillation of the sensor when
the coupling between the ultrasonic crystals is sufficient. Therefore the higher the
gain setting, the lower the coupling needed to produce an oscillating sensor.
The universal control unit of the MCU200 operates with many sensors, so the
correct setting for the particular sensor and application should be found on site by
experiment, if possible. This will take account of particular site conditions like RF
coupling between extension cables, which can affect the maximum allowed gain.
Other liquid characteristics, such as presence of suspended solids, or air bubbles, can
mean that for reliable operation the MCU200 gain must be set as high as possible, to
overcome future solids build up, but at least one potentiometer division below the
maximum allowed level, to ensure temperature and component ageing stability.
The particular procedures outlined below for gain adjustments give the mid point
gain settings, which may need to be adjusted to meet specific site/sensor future
requirements as indicated above.
OIL miiiniil
JT
Receiver Transmitter
Crystal Crystal
WATER
— - Receiver Transmitter
Crystal Crystal
Figure 6 mobreyl5.tif
Step A: Reduce the gain potentiometer with the sensor immersed in one of the
liquids until a "false dry" indication is obtained. Note the position of the
pot.
Step C: Set the potentiometer half way between these two values. Correct
performance requires a total difference between the two set points of at
least 3 divisions.
Note: The Mobrey 402 sensor in the hot well tank is installed as shown in
Figure 7.
Paraffin
Water
Paraffin
Transmitter
Crystal
i Receiver
Crystal
Figure 7 mobreyl6.tif
The gain adjustment is made so that the gain is 3 divisions higher than the highest
false dry position obtained, as in section 4.2.1. Performance at the interface should
then be checked.
Note: That the non oscillating state of the sensor, at the interface, also occurs
throughout any emulsion layer at the interface, and also when the sensor
is in air.
5.1 Spares
Step A: At least one LED should be illuminated. If not check the power supply to
the unit.
Step B: If the "Fault" LED is on, check the coax cable to the sensor for incorrect
wiring or damage. Particularly check continuity of extension cables,
connection of crimped connectors on cable ends. The pcb board can be
checked by linking the two terminals labelled E on the sensor terminals -
this should cancel the fault indication LED.
Step C: If the sensor is giving incorrect indications check the gain adjustment (see
section 4.0).
Check for correct sensor operation whenever the gain is adjusted away from the
normal set point. Assume an overlap of 2 divisions between the "LO" and "HI" gain
ranges.
Step D: Check that the incorrect operation has not been produced by incorrect
setting of the frequency selection switch, or an external short circuit on the
Auxiliary input terminals.
Step E: The circuit board can be checked by linking the sensor terminals 1 and 2
with a wire, to simulate an oscillating sensor.
Table of contents
General description
General description 1
Steam dump valve 2
Actuator 3
I/P positioner 4
Steam pipe connections to dump valve 5
Process controller/local panel 6
Pressure transmitter 7
Air reducing set 8
General 1
Operation 2
Maintenance 3
General 1
Reversal of the actuator action 2
Manual operation device 3
Maintenance 4
General 1
Mechanic connection of the positioner 2
Electric connection of the positioner 3
Pneumatic connection 4
Commissioning 5
Diagnosis 6
Service and maintenance 7
Steam/condensate line
Figure 1 steamdump2.cdr
•ndwheel
Actuator
VP Positioner
Control valve
Under normal circumstances the control valve, actuator and I/P positioner is
delivered as a complete unit already assembled.
The air supply to the actuator is controlled by the air reduction set (4). The
compressed air at the inlet of the air filter must have a max. pressure of 17 bar and a
temperature laying in the interval from -20 to +65°C. Furthermore, the supplied air
must be instrument air.
Any adjustment of the system must be carried out on the process controller/local
panel (5).
The installation point should allow sufficient space to ensure correct maintenance of
the valve and actuator. The valve should be inserted so that the spindle has a vertical
position and the actuator being up above. The valve can also be tilted to a maximum
horizontal position if the installation point does not allow any better condition. If
painting is necessary, ensure that valve and actuator spindle as well as mechanical
links are free from paint. The flow direction is signalled through an arrow on the
valve body. The valves should be insulated against high temperatures to guard the
actuator. Sufficient space must be left to undertake maintenance on the spindle-
sealing.
To guarantee a disturbance free function of the control valve, the inlet and outlet
stretches of the piping should be of straight piping length min. 2 times pipe diameter
by inlet and 6 times by outlet. The piping must be aligned to prevent any strain on
the valve. Precautions to restrict strain on the piping should be regarded. In no case
supporting must be fitted to the valve to hold the piping system.
The piping should be rinsed to clear out any pollution, welding beads, rust etc.
before inserting the control valves. A strainer should be fitted in front of the control
valve to catch remaining particles. Bolts should be re-tightened after taking into
operation.
When the piping system is filled and set under pressure, the spindle sealing should
be checked for leakage, and if necessary be carefully tightened until the leakage is
stopped. The PTFE-V-ring unit does not require any re-tightening, the spring tension
maintains the necessary force.
The bolts must be tightened gradually in steps, diametrically in pairs but not tighter
than it is necessary for sealing.
Flange connections bolts should never be loosened or tightened when the valve is
under temperature or pressure, even if a leakage may arise.
Actuator
Select the site of installation so that the actuator is readily accessible and that there
is adequate room for later maintenance work.
The mounting position is preferably with the actuator and valve spindle in the
vertical position. For assembly onto the valve please see the separate instructions
described in the sections for valve and actuator (see also Figure 4).
The instrument air supply should be dry for low temperature service. A heat-guard
should be installed for high temperature service.
Warning: The actuator diaphragm may only be pressure loaded on the side
opposite of the springs. The vent hole in the other connection must
stay free.
Pneumatic oonnecton
I/P positioner
The positioner must be installed and commissioned in exactly the same sequence as
described in the section for the positioner. It is essential that the warnings in the
relevant sections are heeded during this process.
Pressure transmitter
The pressure transmitter converts the steam pressure to an electrical signal
proportional with the pressure. The unit is supplied as two-wire transmitters with an
output signal of 4-20 mA.
4— Max. 70 °C
Thin (= Low heat conductivity) uninsulated tube
- Condensed liquid
Figure 5 emp2_2a.cdr
There are facilities for adjusting zero point and span. Zero point adjustment is
necessary to equalise pressure arising from any differences in level between the
pressure transmitter and the medium being measured. Zero point adjustment results
in a parallel adjustment of span.
8.1 Installation
Before installation the operating conditions of temperature and pressure must be
checked. The unit should be mounted securely in an accessible and visible location
upstream from lubricators and near components being served. Strain on pipe work
and fittings should be avoided and directional flow arrows observed.
With cyclic demand systems the filter-regulator should be installed upstream of
directional control valves. Airline piping should be the same size as unit ports with
air flow in the direction of the arrow. A pressure gauge may be connected to the
appropriate 1/8 port after removing the plug and should have a range exceeding the
maximum proposed outlet setting. Figure 6 shows an illustration of the filter-
regulator.
Filter-regulator
8.2 Adjustment
With the regulator adjustment completely backed-off the air supply can be turned
on. The adjusting knob can be rotated clockwise to increase the spring load and the
pressure increase observed on the gauge.
Minor adjustment after setting changes can be avoided by always approaching the
desired setting from the lower level. When a lower setting is required, firstly reduce
to a lower level and then increase to the desired setting.
Decreasing the pressure setting on a relieving type regulator will cause air to exhaust
through the bonnet vent hole.
The non rising adjusting knob includes a locking feature;
• Push knob in after setting to lock and prevent adjustment.
• To release pull knob out.
If the adjustment knob is fitted with the tamper resistant screw option, the screw
must be removed to enable the knob to be unlocked.
Auto drain units should have a 1/4" (6 mm) bore flexible tube pushed over the
bottom protrusion to pipe away expelled liquid. Avoid restricting the drain pipe.
Manual drain units must be drained before the contaminant level reaches the
element. Should this occur then liquid contaminant will be carried downstream.
1 General
This type of control valve is suited to regulate fluids, gases and steams. The valve
plug is normally a parabolic plug, but can also be supplied in a perforated design.
Both types of plugs can have either linear or equal percentage flow characteristic.
The flow direction for parabolic plugs is always against the closing direction.
However, with perforated plugs for steam and gases, it is in the closing direction. If
a valve with a perforated plug is operated by means of a pneumatic actuator with the
flow in the closing direction, the pneumatic actuator should have a stronger thrust
force. This is necessary to prevent thumping near to the closing position.
All control valves can be fitted alternately with manual-, pneumatic-, electric- or
hydraulic operation devices.
Figure 1 va!47x.cdr
Table 1
Operation
Maintenance
Before any maintenance of the control valve is carried out, the piping system must
be shut off and pressure free.
Step A: Open the valve fully and unscrew the hexagon nuts (17).
Step B: Lift the gland flange (7) and the spindle guiding (8) upwards.
3.1.2 Exchange
Step A: Drive the actuator into middle position and dismantle the actuator.
Step B: Unscrew the hexagon nuts (17) from the studs (15).
Step C: Remove the gland flange (7), the spindle guiding (8) and the old stuffing
box (10) and clean the packing compartment.
Step D: Clean the valve spindle and check for damage and if necessary replace. If
the damaged spindle is not replaced, the new packing will leak after a short
period.
Step E: Insert the new packing rings (split ring-displacement, splitting at 180° to
avoid overlapping).
Note: Strenuous tightening will prevent leakage, but will also have a brake
effect on the spindle which aggravates the movement of the spindle.
A PTFE-V-ring unit is spring loaded and has enough set pressure to ensure a good
seal even by low operation pressures. It is replaced as mentioned above.
The PTFE-V-ring sealing unit should be lubricated before it is inserted. The sealing
lips must face against the pressure direction.
Note: Special care should be given to the spindle surface. Rough surfaces wear
the sealing lips enormously and can be due to failure of the packing unit.
Step A: Drive the actuator into middle position and dismantle the actuator.
Step C: Unscrew the hexagon nuts (17) and remove the bellow housing (25).
Dismantle the plug as described in the next section.
Step D: Unscrew the hexagon nuts (17.1) and dismantle the mounting bonnet (3.1).
Step E: The bellow unit (26) is removed from the bellow housing (25).
Step F: Replace the two gaskets (14.1) and the gasket (14).
Step G: When the bellow unit (26) is replaced, the proper position of the anti-
twisting device must be observed.
Step H: The set pins (21) have to drive within the slots of the anti-twisting device.
Check for friction-free movement.
Step I: Replace mounting bonnet (3.1) and screw down the hexagon nuts (17.1)
crosswise.
Step A: Drive the actuator into middle position and dismantle the actuator.
Step A: Unscrew the hexagon nuts (17) and dismantle the mounting bonnet (3).
Step B: Pull out the plug with the spindle and exchange this unit.
Step C: Remove the spring-type straight pin (19) and unscrew the spindle (6).
Step E: Drill a hole through the plug shaft and insert a new pin.
Step F: Replace the gasket (14) and assemble the mounting bonnet (3).
Step A: Unscrew the hexagon nuts (17) and dismantle the bellow housing (25) with
plug (5).
Step B: Drive the spindle in the bottom position and remove the spring-type straight
pin (19).
Step D: Screw a new plug at the spindle and drill through the shaft. Drive the
spring-type straight pin (19) into the hole.
Step F: Assemble the bellow housing (25) with plug (5) together with the body (1)
and fix it by screwing the hexagon nuts (17) crosswise.
The spindle can only be completely replaced together with the bellow.
The seat ring is screwed into the valve body. The seat ring can be obtained after
removing the bonnet and can then be refinished or replaced as required.
Step A: Clean and lubricate the thread and conical sealing surface before insertion.
Operation mode:
Spring opens - Air closes Air opens - Spring closes
Figure 1 dpactuat.tif
Table 1 below shows a list of the position numbers in Figure 1 and Figure 2.
Table 1
Warning: The actuator diaphragm may only be pressure loaded on the side
opposite of the springs. The vent hole in the other connection must
remain open.
Warning: Make sure that the plug does not turn while pressing on the seat
during assembly.
Step B: Loosen the socket screws (13), remove the rotation guard (12) and the guide
flange (11). The threaded bushing (14) is now free.
Step C: Turn the locking hexagon nut (30) onto the valve spindle. Place the rotation
guard (12) and the guide flange (11) over the valve spindle and then turn
the threaded bushing (14) onto the valve spindle.
Step D: Check the actuator for proper operation mode and connect the pneumatic
supply to the connection piece in the diaphragm housing (2) for operation
mode "spring closes" or in the diaphragm lid (3) for operation mode "spring
opens".
Step E: Drive the actuator into approximately mid-stroke position over the air
supply and mount it onto the valve (read the value from the pressure gauge
- middle of the spring range).
Operation mode: Spring closes valve - Air opens valve Operation mode: Spring opens valve - Air closes valve
Pneumatic connection
Pneumatic connection
Figure 2 dpactspr.tif
Step A: Drive the actuator to the required spring-starting point over the air supply.
Step B: Turn the threaded bushing (14) up against the coupling flange (10) so that
the collar enters into the flange and presses against it. Make sure that the
plug is lying on the valve seat.
Attention: Note that sufficient thread of the valve spindle is inside the threaded
bushing (14). If not, turn the coupling flange (10) downwards from
the actuator spindle and pull the threaded bushing (14) against it.
— Attach the guide flange (11) and the rotation guard (12) with the socket screws
(13) to the coupling flange (10).
— Check that the plug lifts off the seat at the required spring starting point.
Step D: For operation mode: "spring opens":
— Check that the plug leaves the end position at the required spring starting point,
and finishes the valve stroke at the spring-range end value.
— The plug must then also press on the valve seat.
Step E: After the test operation set the stroke indicators (15) into the end positions.
Step F: Lock the hexagon nuts (16 + 30) at the valve mid-stroke.
Step G: Do not turn the plug on the seat when it is under force.
Step B: Loosen and remove the socket screws (13) from the coupling flange (10)
and drop the rotation guard (12) over the valve spindle.
Step C: Remove the hexagon nuts (31) from the actuator and lift off the valve.
Step D: Reduce the air supply until the chamber is pressure free.
Warning: The actuators DP 32 and DP 33 have two longer screws when fitted
with stronger spring ranges. The actuator DP 34 has four. These
screws should be the last screws to be loosened, and must be
loosened evenly to reduce the high spring tension.
— Remove the springs (7) and the diaphragm plate (4) with the diaphragm (1) and
the spindle (5).
— Loosen and remove the seal lock nut (19) and remove the spindle (5). Turn over
the diaphragm plate (4) with the diaphragm (1) and the diaphragm clamping
flange, and place it over the spindle (5).
— Tighten with the seal lock nut (19). Make sure that the spindle surface is not
damaged.
— Grease the spindle surface and the 0-ring.
— Place the diaphragm plate (4) with the diaphragm (1) into the diaphragm lid (3).
— Arrange the springs (7) onto the moulds pressed into the diaphragm plate (4).
— Place the diaphragm housing with the spindle sealing unit over the spindle, and
screw it together. Make sure that the springs stay properly arranged.
— Turn the hexagon nut (16) and the coupling flange (10) onto the spindle (5).
— Mount the actuator as described previously, and connect the air supply tube to
the diaphragm lid (3).
Step H: For reversal from "spring opens" into "spring closes":
— Remove the diaphragm (1) and the diaphragm plate (4) with the spindle (5) and
the springs (7).
— Loosen and remove the seal lock nut (19) from the spindle (5). Turn over the
diaphragm plate (4) with the diaphragm (1) and the diaphragm clamping flange,
and place it on the spindle (5).
— Tighten with the seal lock nut (19). Make sure that the spindle surface is not
damaged.
— Grease the spindle surface and the 0-ring.
— Stick the diaphragm plate (4) with the diaphragm (1) and the spindle (5) into the
diaphragm housing (2).
— Arrange the springs (7) onto the moulds pressed into the diaphragm plate (4).
Place the diaphragm lid (3) on the top, and screw it together. Make sure that the
springs (7) stay properly arranged.
— Turn the hexagon nut (16) and the coupling flange (10) onto the spindle (5).
— Mount the actuator as described previously, and connect the air supply tube to
the diaphragm housing (2).
Maintenance
The pneumatic actuator is maintenance free. To maintain a disturbance free
operation, the air should be supplied by an air-supply station.
The diaphragm, spindle sealing unit and springs are wear parts and should be
replaced when necessary.
Comparison of the set point and the actual value takes place electronically in a micro
controller. If the micro controller detects a deviation, it uses a 5-way switch
procedure to control the piezoelectric valves, which in turn regulate the flow of air
into the actuating chambers. When connected in a two-wire system, the SIPART
PS2 draws its power exclusively from the 4 to 20 mA set point signal.
The piezoelectric valve converts the command into a pneumatic positional
increment. The positioner outputs a continuous signal in the area where there is a
large control deviation (high-speed zone). In areas of moderate control deviation
(slow-speed zone) it outputs a sequence of pulses. No positioning signals are output
in the case of a small control deviation (adaptive or variable dead zone).
Commissioning (initialisation) is carried out automatically to a large extend. During
initialisation, the micro controller automatically determines the zero, full-scale
value, direction of action, and positioning speed of the actuator. It uses these to
determine the minimum pulse time and dead zone, thus optimising the control.
The positioner can also be operated manually by the pushbuttons and the LCD of the
SIPART PS2.
The installation of the positioner must be carried out in the following order:
• Mechanic connection
• Electric connection
• Pneumatic connection
• Commissioning
Supply OH
"straloj
Figure 1 sips2_5a.tif
Step B: Insert the pick-up bracket (2) into the recesses of the clamping assembly.
Set the necessary length and tighten the screws so that the pick-up bracket
can still be shifted.
Step C: Push the roll (5), spring (13), and guide washer (22) onto the pin (4).
StepD: Insert the pin in the lever (6) and assemble with nut (18), spring washer
(14), and U-washer (12).
Step E: The value of the stroke range specified on the actuator should be set or if
this does not exist as a scaling value, the next greatest scaling value should
be set. The centre of the pin must be in line with the scaling value. The
same value can be set later under parameter "3.YWAY" in commissioning
to display the way in [mm] after initialisation.
Step F: Assemble the hexagon socket cap screw (17), spring washer (16), washer
(12), and square nut (19) on the lever.
Step G: Push the pre-mounted lever onto the positioner axis up to the stop and fix
with the hexagon socket cap screw (17).
Step H: Fit the mounting bracket (1) with two hexagon head screws (9), lock
washer (10), and flat washer (11) on the rear of the positioner.
Step I: Selection of the row of holes depends on the width of the actuator yoke. The
roll (5) should engage in the pick-up bracket (2) as close as possible to the
spindle but may not touch the clamping assembly.
Step J: Hold the positioner with the mounting bracket on the actuator so that the pin
(4) is guided within the pick-up bracket (2).
— Actuator with ledge: hexagon head screw (8), flat washer (11), and lock washer
(10).
— Actuator with plane surface: four hexagon head screws (8), flat washer (11), and
lock washer (10).
— Actuator with columns: two U-boIts (7), four hexagon nuts (21) with flat washer
(11), and lock washer (10).
Step M: Secure the positioner onto the yoke using the previously positioned
mounting parts.
Note: Set the height of the positioner so that the horizontal lever position is
reached as close to the stroke centre as possible. The lever scale can be
used as orientation. It must be guaranteed that the horizontal lever
position is passed through within the stroke range.
17 22
1) 2) 4
11
10
3)
Mounting on yoke
with columns
As required
Figure 2 sips2_5b.tif
Step B: Adhere pointer (4.2) onto the mounting console in the centre of the centring
hole.
Step C: Push coupling wheel (2) onto the positioner axis, pull back by about 1 mm
and tighten the hexagon socket head screw (18) with the Allen key
provided.
Step D: Place the carrier (3) onto the end of the actuator and secure using Fillister
head screw (16) and washer (17).
Step E: Carefully place the positioner with mounting console onto the actuator such
that the pin of the coupling wheel engages in the driver.
Step F: Align the positioner/mounting console assembly in the centre of the actuator
and screw tight (screws are not included in the delivery, they are part of the
actuator mounting console).
Step G: Follow the start-up sequence as described later. Drive the actuator to the
end position and adhere the scale (4.1) onto the coupling wheel (2)
according to the direction of rotation and rotary actuator. The scale is self-
adhesive.
Figure 3 sips2_5c.tif
12
11 10
Figure 4 sips2_5d.tif
Pneumatic connection
Ensure that the air quality is suitable. Grease-free instrumental air with a solid
content < 30 um and a pressure dew point 20 K below the lowest ambient
temperature must be supplied.
Warning: For reasons of safety, pneumatic power may only be supplied after
assembly when the positioner is switched to operating level "P
manual" operation with electrical signal applied.
Step C: Connect actuating pressure Yl and/or Y2 (Y2** is only used with double-
acting actuators) according to the desired safety position.
Step D: Connect the supply air (1). The pressure should be between 1.4 to 7 bar.
Commissioning
Commissioning (initialisation) is carried out automatically to a large extend. During
initialisation, the micro controller automatically determines the zero value, full-scale
value, direction of action and positioning speed of the actuator. It uses these to
determine the minimum pulse time and dead zone, hereby optimising the control.
The positioner can also be operated manually by the pushbuttons and the LCD of the
SIPART PS2.
The commissioning of the positioner can be divided into the following steps:
• Preparation for initialisation
• Start the automatic initialisation procedure
Operation levels
Mode Display
Figure 5 sips2_5e.tif
Step A: Check and set the gear transmission switch to the correct position. Figure 4
(position 8) indicates the location of the switch. For linear actuators the gear
transmission switch is set according to the stroke range as described in
Table 1 for the parameter "3.YWAY". For part-turn actuators 90° must be
selected.
Step B: Check that the pneumatic supply power (inlet air) is present. The operating
pressure should be at least one bar greater than is necessary for
closing/opening the valve during initialisation.
Step C: Without initialisation the positioner is in "P manual mode" and "NOINIT"
flashes in the display. This level can also be reached by using "55.PRST"
function (see Table 1).
Step D: Check the free running of the mechanics in the whole actuating range by
moving the actuator with the keys " | " and " | " and driving to the respective
end position.
Step E: With linear actuators drive the actuator to horizontal lever position. The
display must indicate 48% to 52%. If necessary, correct the value by
adjusting the sliding clutch. After the check is completed, the actuator must
be approximately half way along its stroke. This is due to establishment of
the action direction during automatic initialisation.
Figure 6 shows the configuration mode including the operation in this mode and
Table 1 shows the parameter/configuration list. Figure 7 shows the initialisation
process of the positioner. The initialisation process is stored in the microprocessor.
This means that an additional initialisation only is necessary if any parts of the unit
have been changed.
Note: The numerical values used in Figure 5, Figure 6, and Figure 7 are
examples.
Step A: Call the configuration mode by pressing the hand symbol key for longer
than 5 seconds.
Step B: Set the actuator type, linear or part-turn, in the menu item line "l.YFCT".
Step C: Switch to the second parameter by pressing the hand symbol key briefly.
Step D: Set the rated angle of rotation for feedback in the menu item line
"2.YAGL". It is vital that this value corresponds to the setting of the gear
transmission ratio selector (Figure 4, position 8), 33° or 90°.
Step E: Switch to the next parameter by pressing the hand symbol key briefly.
Step F: This parameter ("3.YWAY") is only set for linear actuators and if the total
stroke in mm should be displayed at the end of the initialisation phase. To
do this, select the same value in the display to which the carrier pin to the
scale on the lever is set to.
Step G: Switch to the following parameter by pressing the hand symbol key briefly.
Step H: Start the initialisation ("4.INITA") by pressing the "f" key for longer than 5
seconds.
Step I: During the initialisation phase "RUN1" to "RUN5" appear one after another
in the bottom of the display. Please note that the initialisation process may
last up to 15 minutes depending on the actuator.
Note: The ongoing initialisation can be aborted at any time by pressing the
hand symbol key. The previous settings are retained. AH the parameters
are reset to the factory setting only after performing a preset
"55.PRST".
Step J: If problems occur, carry out the measures as described in the table "Possible
messages" shown in Figure 7.
Step K: The initialisation is completed when "FINSH" appears in the bottom of the
display.
Step L: When pressing the hand symbol key briefly the menu item line "4.INITA"
is displayed.
Step M: To exit the configuration operating mode, press the hand symbol key for
longer than 5 seconds. The software version is displayed after about 5
seconds. The instrument is in manual operation after releasing the key.
Step N: The positioner can be changed to automatic mode by pressing the " j " key
once as indicated in Figure 5.
Step O: The automatic mode is the normal mode. In this mode the positioner
compares the set point current with the current position and moves the
actuator until the control deviation reaches the dead zone.
Figure 6 sips2_5f.tif
Initialisation process
Ccntinueushg up key
P 324 Direction of action is determined
a RUN 1 Down tolerance Or adjust slicing clutch up
P 88.4 todspby
H dim IU band violated
Checking oftravel and adjustment of
92.4 zero andstroke (from stop to stop)
RUN 2
Deterrriration and display of positioning time Then only
P 824 down(dxx.x), up(uxx.x).Stopwiththedownkey Centime ushg the down key
rj RUN 3 Pressing t he up key initiates leakage measurement Linearactuator set pick-up
Clice the slipping lever into horizontal position
SEt dutch has been using the tp and down keys
P 32.4 Determination of m'nimumhcrement length MIDDL adjusted
D RUN 4 Continueushg hand symbol key
Acknowledge message
using the rand symbol key
19.8 Up/down span
Set the ne<t lowest travel
violated
value on tre lever
Restart initialisation
Figure 7 sips2_5g.cdr
5.3 Parameters
Table 1 shows the parameter list for the positioner. The parameter name is written in
plain text in the "menu line" column. The function of the parameter is described
briefly in the "Function column". In addition, the possible parameter values, the
physical unit and the factory setting of the parameters are shown.
After the initialisation process, the positioner can be configured to meet the
requirements of a specified task. The factory settings correspond to the requirements
for a typical application. This means that normally only a few parameters will need
to be changed.
The positioner can be installed and configured to fit linear and part-turn actuators
with reverse action. E.g. linear actuators with the set point in the falling direction or
part-turn actuators for counter clockwise operation direction. In this case the
parameters "7.SDIR" and 38."YDIR" should be set to "FALL".
Parameter list
Customer
Menu line Function Parameter values Unit Factory setting
setting
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
l.YFCT Type of actuator WAY
ncSt (part-turn actuator
withNCS)
-ncSt (part-turn actuator
with NCS, inverted)
Rated angle of rotation for feedback 90°
2.YAGL0 Degrees 33°
(must correspond to gear ratio) 33° .
Stroke range (optional setting) OFF
5 , 10, 15 , 20
When used, the value must correspond with (short lever 33°)
the set of the leverage ratio on the actuator
3.YWAY2' 25 , 30, 35 mm OFF
(short lever 90°)
Driver pin must be set to the value of the
40,50,60,70,
actuator travel or, if this value is not scaled,
90,110,130
to the next lager scale value
(long lever 90°)
4.INITA Initialisation (automatically) noini/no/###.#/Strt no
5.INITM Initialisation (manually) noini/###J/Strt no
„ . . . . . 0 to 20 mA 0MA
6.SCUR Current range of set point 4 1 0 20 mA 4MA
4MA
riSE
7.SDIR Set point direction fir riSE
FALL
8.SPRA Set point for start of split range 0.0 to 100.0 % 0.0
9.SPRE Set point for end of split range 0.0 to 100.0 % 0.0
Auto
10.TSUP Set point ramp up s 0
0 to 400
ll.TSDO Set point ramp down 0 to 400 s 0
Set point function
Linear Lin
12.SFCT Equal-percentage 1:25,1:33,1:50 1-25 ,1-33 ,1-50 Lin
Inverse equal-percentage 1:25,1:33,1:50 nl-25 , nl-33 , nl-50
Freely adjustable FrEE
13.SLC Set point turning point at 0% 0.0
14.SL1 5% 5.0
to to 0.0 to 100.0 % to
32.SL19 95% 95.0
33.SL20 100% 100.0
Auto
34.DEBA Dead zone of controller % Auto
0.1 to 10.0
35.YA Start of manipulated variable limiting 0.0 to 100.0 % 0.0
36.YE End of manipulated variable limiting 0.0 to 100.0 % 100.0
Standardisation of To mech. travel MPOS
37.YNRM MPOS
manipulated variable To flow FLOW
Direction of manipulated Rising riSE
38.YDIR riSE
variable for display Falling FALL
Without no
Tight closing with Top only UP
39.YCLS no
manipulated variable Bottom only do
Top and bottom uPdo
Table 1
Diagnosis
In the diagnostic mode the current operating data (such as number of strokes,
number of changes in direction, number of fault messages, etc.) can be displayed.
From the automatic or manual modes the diagnostic mode can be reached by
simultaneously pressing all three keys for at least 2 seconds.
Table 2 shows an overview of the displayable values. The diagnostic display has a
similar structure as the parameter menu displays. The respective next diagnostic
value can be selected with the hand symbol key. Certain values can be set to zero by
pressing the " | " key for at least 5 seconds. These are menu item line "1, 2, 3, and 4".
Some diagnostic values may be greater than 99999. In this case the display switches
to exponential display.
Table 2
Step C: Remove the three screws from the pneumatic connector strip.
Step D: Remove the filters and O-rings behind the connector strip.
Step F: After cleaning first insert the filters in the recesses in the housing and then
place the O-rings on the filters.
Step G: Align the pneumatic connector strip on the two lugs and screw tight with
the three self-tapping screws.
Note: Make sure that the same thread is used. To do this, turn the screws anti-
clockwise until they snap into the thread audibly. Only then should the
screws be tightened.
Table of contents
VENT. TO DECK
OPEN AIR
Temp.switch+pocket+4m cap.tube
40-105 °C
Control valve
DN80 PN25
Description
A flanged bellows sealed stop valve, type BSA-1, for use on
steam, condensate and water systems.
Limiting conditions
Body design conditions PN16
Max. design temperature 300°C
Max. hydraulic test pressure 24 bar g
Material specification
1 Body Cast iron DIN GG25
2 Bonnet SGiron DIN GGG 40.3
3 Seat Stainless steel AISI420
4 Disc Stainless steel DIN 17440 X30 Crl3
5 Bellows Stainless steel DIN 17440 X6
CrNiTil810
6 Stem Stainless steel AISI420
7 Handwheel Pressed steel BS 1449 CR4
8 Stem packing Graphite
9 Bonnet screw Steel DIN 931 Gr 5.6
10 Body/
Bonnet gasket Graphite laminate with
stainless steel insert
Dimensions in mm
DN 80
A 310
B 287
C 200
Weight, kg 21
Data Sheet
Stop Valve DN80, PN16 6010 000065
Page 1 of 1
AALBORG
INDUSTRIES
Version: A Date: 1998-11-10 Pos. M83
Description
Standard screen stainless steel 0.8 mm perforations,
type Fig. 33
Limiting conditions
Body design conditions PN 16
Max. design temperature 300°C
Max. hydraulic test pressure 24 bar g
Materials
1 Body Cast iron DIN 1691 GG20
2 Cap Cast iron DIN 1691GG20
3 Cap gasket Reinforced exfoliated graphite
4 Strainer screen Stainless steel ASTMA240 316L
5 Cap studs Steel BS 4439 Gr 8.8
Cap nuts Steel BS 3692 Gr 8
Dimensions (approximate) in mm
DN 80
A 310
B 210
C 340
Screening area, cm2
Weight, kg
361
25.9 1
Installation Withdrawal
Distance i
The strainer should be installed in the direction of flow
as indicated on the body, in a vertical or horizontal
pipe line.
Data Sheet
Cast Iron Strainer, DN80, PN16 7040 000026
Page 1 of 1
AALBORG
INDUSTRIES
Version: A Date: 1998-11-10 Pos. M84
Description
Normally open, double seat control valve, type NS.
Limiting conditions
Max. differential pressure, DN 80 10 bar
Material specification
1 Body Gun-metal BS 1400 LG2
2 Body gasket Semi-ridged graphite BS 2815 Gr.A
3 Valve closure
Member Gun-metal BS 1400 LG2
4 Plunger Brass BS 2874 CZ 121
5 Plunger guide Brass BS 2874 CZ 121
6 Return spring Stainless steel BS 2056 302 S 26
7 Spring housing Gun-metal BS 1400 LG 2
8 Bonnet Gun-metal BS1400LG2
9 Stem - Brass BS 2874 CZ 121
10 Body studs Steel BS 4439 Gr 8.8
Body nuts Steel BS 3692 Gr 8
DN 80 Ml6
Dimensions (approximate) in mm
DN 80
A 236
B 160
Weight, kg 22.7
Installation
The valve should be fitted in a horizontal line with the
actuator vertically below the line. Full details are supplied
with each valve.
Data Sheet
Control Valve, DN80, PN 25 6000 000041
Page 1 of 1
AALBORG
INDUSTRIES
Version: A Date: 2003-09-05
Description
A range of self powered control systems that
-Z
incorporate sensor, actuator, set point controller /
indicator, type 121. ©-Y
4
Temperature range 40 to 105°C
M"BSP
Material specification
1 Sensor Brass
2 Actuator Brass
3 Capillary tube Copper PVC Covered
4 Adjustment head Polypropylene
5 Union kit Brass
6 Mounting bracket Steel
7 Clip Polypropylene
8 Adaptor plate Steel
9 Pocket Stainless steel
BS3605CFS316S18
Dimensions (approximate) in mm
Control system
A 271
B 148
C 424
D 25
3 4000
Weight, kg 2.0
Pocket
F 430
G 28
D G
Pocket
Data Sheet
Temperature switch, 40-105°C 8070 000010
Page 1 of 1
AALBORG
INDUSTRIES
Version: B Date: 2002-09-26
Description
DCV2 Water check valves are designed to be sandwiched between
flanges. They are suitable for use on a wide range of fluids for
applications in process lines, hot water systems, steam and
condensate systems etc.
Material specification
1 Body Ferritic Stainless steel WS 1.4313
2 Disc Austenitic Stainless steel BS 1449 316 S 11
3 4 21
3 Spring retainer Austenitic Stainless steel BS 1449 316 S 11
4 Heavy duty spring Austenitic Stainless steel BS 2056 316 S 42
Dimensions in mm
DN 80
A 154
B 133
C 128
D 50
E 111.5
F 80
Weight, kg 2.42
Installation
DCV Water Check Valves must be fitted in accordance
with the direction of flow arrow indicating correct fluid
flow direction.
Flange Joint
When fitted with a spring they can be installed in any Gasket (Supplied
plate. When supplied without a spring these must be by Installer)
Note:
Dies Check valves are not suitable for use where heavily
pulsating flow exists, such as close to a compressor.
Data Sheet
6020 000011
Water Check Valve, DN80, PN40
Page 1 of 1
AALBORG
INDUSTRIES
Version: B Date: 1998-09-11 Pos. M87
Description
The VB14 is a small purpose designed vacuum breaker
for general purpose applications on condensing vapour
(steam) or liquid systems.
Limiting conditions
Body design conditions PN16
Max. design temperature 260°C
Max. cold hydraulic test pressure 24 bar g
Material specification
1 Cap Brass CUZN39PB2
2 Valve Stainless steel Z 100 CD 17
3 Valve seat Stainless steel Z15CN16 02
4 Body Brass CUZN39PB2
5 Gasket Stainless steel AISI304
Dimensions (approximate) in mm
Size 1/2"
A 55
B (A/F) 34
C 39
Weight, kg 0.35
Installation
The VB14 Vacuum Breaker must be installed in a
vertical position with the system connection at the
bottom.
Data Sheet
6000 000010
Vacuum Breaker, BSP 1/2"
Page 1 of 1
AALBORG
INDUSTRIES
Version: A Date: 2000-10-30 Pos. M88
Description
• Steam injectors use steam to raise the
temperature of water or other liquids. They
work by using a jet of steam to draw in the
liquid through radial ports, mix it, and
distribute the heated liquid throughout the
tank or vessel. The circulation induced by
the injector ensures thorough mixing and
avoids temperature stratification.
Limiting conditions
• Body design rating: PN25
• Max. saturated steam condition: 17 bar g at
207°C
• Maximum heated liquid temperature 88
(tank/vessel vented to atmosphere): 90°C
• Weight: 1.6 kg
Materials
-115-
• Austenitic stainless steel grade 316L.
• • • • •
• • • • • Data Sheet
Steam Injector, BSP 7000 000014
Page 1 of 1
AALBORG
INDUSTRIES
AALBORG TABLE OF CONTENTS
INDUSTRIES
Table of contents
Soot-blower
General data 1
Data for soot-blower 2
Soot-blower
Description 1
Soot-blower procedure 2
Soot-blower unit
General 1
Installation and mounting notes 2
Operation 3
Maintenance 4
Description 1
Lubrication
Description 1
Soot-blower
1 Description
The purpose of the soot-blower is to clean the heating surface for combustible
deposits. In order to clean the heating surface air is blown at high pressure through
the nozzles of the soot-blower element that extend and retract as well as rotate in the
heating surface of the boiler. The combustible deposits dislodged in the process get
removed via the exhaust gas system. The engine load should be at least 75% when
soot-blowing, to ensure that increased gas velocity through the boiler helps to carry
away the deposits dislodged by the soot-blowers.
Figure 1 illustrates the arrangement of the soot-blower system. The illustration is
shown with four manually operated soot-blowers, but the actual boiler can be
equipped with any number of soot-blowers.
Air supply
Soot-blowing procedure
To avoid damage of the heat surface and soot-blowers it is important that the air
supply is dry before soot-blowing is commenced.
Step A: Open the air supply valve and allow drainage of condensate through the
drain valve.
Step C: During soot-blower operation the air supply pressure must be kept
sufficiently high to ensure that the cleaning procedure is carried out
satisfactorily. The supply pressure should therefore be checked
continuously.
Step D: Turn the hand-wheel clockwise. The mechanical indicator will move
downwards. During the first turning, the element will be projected forward
into the heating surface of the boiler at which point the soot-blower valve
will be opened and admit air "Initial blow position". During the final
turning in the same direction, the element is projected further into the
heating surface emitting air for soot-blowing, in the pattern corresponding
to the blowing angle. When the hand-wheel cannot be turned further the
limit of the blowing angle has been reached.
Step F: Turn the hand-wheel clockwise again to the foil blowing angle limit and
then return to the "Initial blow position".
Step G: Repeat the soot-blowing operation once again. The total blowing time
should be carried out over a period of approximately 45 seconds.
Step H: When the soot-blowing is completed, return the blower to the "Full off
position by turning the hand-wheel counter-clockwise until the mechanical
indicator is pushed up.
Step I: Ensure that the soot-blower is left in the "Full off' position.
Step J: Repeat the same operation with all the equipped soot-blowers.
Step L: Open the drain valve when soot-blowing is finished and the air supply valve
is closed.
Soot-blower unit
General
The soot-blower unit consists of a pressure chest including hand-wheel, mechanical
indicator, lubrication nipples and, scavenge air valve. The pressure chest is
connected to a soot-blower element with nozzle ports via a coupling. The soot-
blower unit is operated manually by means of the hand-wheel, thereby running in
and out as well as rotating the nozzle ports of the element inside the boiler.
Step B: Drain pipes leading from the supply pipe-line should be arranged to permit
easy access.
Step C: The coupling and element are marked to give the correct setting for the
blowing angle. When assembling, those marked must be lined up before
locking in position.
Step D: The soot-blower should be carefully slung and the element carefully
inserted through the soot-blower socket and internal bearings of the boiler.
The blowing angle should be inspected from inside the boiler when
operating the soot-blower in manual operation.
Step E: Connection to the scavenge air supply should be minimum 025 mm piping.
To ensure a constant air flow, no other ancillary equipment should be
connected to this supply.
Operation
The frequency of the soot-blower operation depends on the operating conditions of
the boiler. Indicators of the need to soot-blow are boiler gas temperatures and boiler
slag inspections. As a general guideline the boiler should be cleaned shortly after
start up when full boiler working pressure is obtained and approximately 2 -3 times
per day. The engine load should be at least 75% when soot-blowing, to ensure that
increased gas velocity through the boiler helps to carry away the deposits dislodged
by the soot-blowers.
Maintenance
4.2 Lubrication
Step D: Remove the four nuts (23) to detach the sleeve assembly from the pressure
chest.
Step E: Rotate the hand-wheel in a clockwise direction (looking from the hand-
wheel) to disengage the operating screw from the operating nut (7), which
will then be free and permit removal of the sleeve assembly.
Step F: Remove the operating nut (7), now loose in the ported spindle (4).
Step H: Coat the new packing with Clydspin® lubricant or similar and insert
packing taking care not to damage the faces of the packing. Note the
position of the neck ring (19) in the bottom of the stuffing box and ensure
that it remains secure during replacement of the packing.
Step C: Remove cap nut (13) at the boiler end of the soot-blower chest (1) and
withdraw the ported spindle (4), see Figure 2.
Step D: The liner (5) can now be inspected. If the liner is to be replaced, set the
soot-blower on to a solid foundation and drive the liner out with a suitable
drift. The new liner may then be pressed into the chest (1), see Figure 2.
Step E: Removal and fitting of the piston rings (20, Figure 2) is facilitated by the
use of circlip pliers.
Step F: The element (13) is attached to the spindle of the pressure chest by a fixed
coupling (2) and lock nut (12). To disconnect the element, remove grub
screws (8) and slacken back the lock nut, see Figure 4. The element can
then be disconnected by turning in anti-clockwise direction.
Step G: When re-assembling the soot-blower and reconnecting the element (13,
Figure 4), the setting marks on the spindle (4, Figure 2), coupling (2, Figure
4), and the element (13, Figure 4) must always be in line.
Figure 1 sb 15.cdr
Figure 2 sb 14.tif
Figure 3 sb 18.cdr
Figure 4 sb 6.cdr
Table 1
25 mm
O/D pipe
Figure 1 sb l.cdr
Lubrication
1 Description
The efficiency, availability and reliability of a soot-blower are maintained by
adopting the recommended lubrication schedule which is detailed in Table 1. The
identification of lubricating points can be found in Figure 1.
Table 1
Lubricating points
•—-—i
Figure 1 sb ll.cdr
Note: It is recommended that the grease is not stored longer than three years.
The gearbox is factory filled with Shell Tivela Compound A, which is a specially
formulated non-tracking grease lubricant. The gearbox is pre-packed for life and it is
therefore not necessary to lubricate or change oil. However, in case of major
overhaul of the soot-blower an oil change is required. Below are some typical
physical characteristics of the gearbox oil:
• Penetration: 400-420
• Ash (sulphated): 0.5%
• Soap base: lithium
• Oil base: synthetic
• Oil viscosity: 128 cSt at 40°C
• Viscosity index >200
Note: It is not permitted to top up the gearbox with any other lubricant other
than specified.
Table of contents
Drawings
General arrangement 05Y:029875g
2 boiler arrangement 05Y:029916d
Sketch of uptake 05K37:032015b
37.5
C17
Positive pressure
connection 1"BSPT-Mato
Air consumplfon=0.73
NM3MN
S1-76mmH"O Above
TufTtoco pressure*
Alignment of foundation:
The tolerance between
the feet levels to be Weight of boiler unit, dry - 6 3 ton
+ 2 mm. Weight of boiler unit, operation ~ 74 ton
Weight of boiler unit, full with water ~ 80 ton
Centre of gravity based on operation condition.
Starboard boiler
Title: Date
Project No. 737695 737697 737699 738154 738156 738158 738160 iiiiiiiii 2 boiler arrangement Article/Drawing No:
1:25 A3
Port side boiler Boiler No. 14187 14190 14193 14784 14787 14790 14793 AALBORG THIS DRAWING AND DESIGN SHOWN HEREIN IS THE PROPERTY OF AALBORG INDUSTRIES
Starboard boiler Boiler No. 14188 14191 14194 14785 14788 14791 14794 INDUSTRIES AND MUST NOTBE USED BY OR REPRODUCED FOR THIRD PARTY 05Y:029916
Description Appf.
Drawing changed
Uptake changed from 2400 to 2070
700
1 1
28
Society LRS LRS LRS LRS LRS LRS LRS PTh 041209
Newb. No. T3000-8 T3000-9 T3000-10 T3000-11 T3000-12 T3000-13 T3000-14 50000 Kg/h 2.2 Mpa Seals:
Table of contents
Type:
Y/////X
• Safety valve, full lift
• 25.912
Size:
• Nominal diameter: DN 65/100
Application:
• To blow off saturated steam, air or water
Material:
• Body: GGG 40.3
DIN-Material No.: 0.7043
• Seat: X6CrNi Mo Ti 17122
DIN-Material No.: 1.4571
• Disc:X35CrMo 17
DIN-Material No.: 1.4122.05
Technical data:
• Nominal pressure: PN 40/16
• Weight: 40 kg
• Flanges according to DIN
• Inlet: DN 65, PN40
• Outlet: DN 100, PN16
Type: Material:
• Stop globe valve, angle • Body:GS-C25N
• 34.007 with stellited seat and cone DIN-Material No. 1.0619.1
• Seat: X5CrNiNb 19 9 with stellite
Size:
Din-Material No. 1.45 51
• Nominal diameter: DN 250 • Disc: P265 GH (Kbl. HE) - X 8 Cr Ti 18
Application: DIN Material No. 1.4025 - 1.4502
• For steam and/or water flow Technical data:
• Nominal pressure: PN25
• Weight: 170 kg
• Flanges according to DIN
Disc
Seat
Body
V .
Language UK Page 1/1
AALBORG DATA SHEET
INDUSTRIES
Type: Material:
• Stop globe valve, straight • Body:GS-C25N
• 35.006 with stellited seat and cone DIN-Material No. 1.0619.01
• Seat: X5CrNiNb 19 9 with stellited
Size: DIN-Material No. 1.4551
• Nominal diameter: DN 100 • Disc:X20Crl3
Application: DIN -Material No. 1.4021.05
• For steam and/or water flow Technical data:
• Nominal pressure: PN 40
• Weight: 39.5 kg
• Flanges according to DIN
0 225
Body
Type: Material:
• Stop check globe valve, screw down non • Body:GS-C25N
return, straight DIN-Material No. 1.0619.01
• 3 5.006 R with stellited seat and cone • Seat: X5CrNiNb 19 9 with stellite
DIN-Material No. 1.4551
Size: • Disc:X20Crl3
• Nominal diameter: DN 100 DIN -Material No. 1.4021.05
Application: Technical data:
• For steam and/or water flow • Nominal pressure: PN 40
• Weight: 39.5 kg
• Flanges according to DIN
0 225
Body
Type: Material:
• Stop check globe valve, screw down non • Body:GS-C25N
return DIN-Material No. 1.0619.01
• 3 5.006 R with stellited seat and cone • Seat: X5CrNiNbl9 9 with stellited
DIN-Material No. 1.4551
Size: • Disc:X20Crl3
• Nominal diameter: DN 40 DIN-Material No. 1.4021.05
Application: Technical data:
• For steam and/or water flow • Nominal pressure: PN 40
• Weight: 11.5 kg
• Flanges according to DIN
0I6O
Body
Type No.: 6030 Stop valve, straight, non return 6030 000016
Version: A DN 40, PN 40
Type: Material:
• Stop globe valve, straight • Body:GS-C25N
• 35.006 with stellited seat and cone DIN-Material No. 1.0619.01
• Seat: X5CrNiNb 19 9 with stellited
Size: DIN-Material No. 1.4551
• Nominal diameter: DN 40 • Disc:X20Crl3
Application: DIN-Material No. 1.4021.05
• For steam and/or water flow Technical data:
• Nominal pressure: PN 40
• Weight: 11.5 kg
• Flanges according to DIN
0 160
Body
Type: Material:
• Stop check globe valve, screw down non • Body:GS-C25N
return DIN-Material No. 1.0619.01
• 35.006 R with stellited seat and cone • Seat: X5CrNiNbl9
DIN -Material No. 1.4551 with stellite
Size: • Disc:X20Crl3
• Nominal diameter: DN 50 DIN-Material No. 1.4021.05
Application: Technical data:
• For steam and/or water flow • Nominal pressure: PN 40
• Weight: 13.5 kg
• Flanges according to DIN
0I6O
Body
Type: Material:
• Stop globe valve, straight • Body:GS-C25N
• 35.006 with stellited seat and cone DIN-Material No. 1.0619.01
• Seat: X5CrNiNbl9 9 with stellite
Size: DIN -Material No. 1.4551
• Nominal diameter: DN 50 • Disc:X20Crl3
Application: DIN-Material No. 1.4021.05
• For steam and/or water flow Technical data:
• Nominal pressure: PN 40
• Weight: 13.5 kg
• Flanges according to DIN
0 160
Body
Type: Material:
• Instrument stop cone valve, straight • Body: C 22.8
DIN- Material No. 1.0460
Size: • Seat:X20Crl3
• G I / 2 "x0l2 DIN- Material No. 1.4021
• Nominal diameter: DN 8 • Needletip:X35CrMol7
Application: DIN-Material No. 1.4122
• For steam, water and/or air Technical data:
• Nominal pressure: PN 160
• Inlet: GW male DIN
19207, form R
• Outlet: For steel tube 0 12
• Weight: 0.8 kg
0 80
Type:
• Opening pressure at horizontal flow (60°
• Wafer check valve, type WCV 6100 open): 19 mbar
Application: • Opening pressure at vertical flow
upwards: 22 mbar
• For steam and liquid media • Standard Kv value: 2200 m3/h
Design: • Operating temperature max.: 250°C
• The wafer check valve is designed to be • Operating temperature min.: -10°C
sandwiched between welding neck • Weight: 13.1 kg
flanges or slip-on flanges, with Installation:
horizontal flow or vertical flow • The check valve can be installed
upwards. The disc is eccentrically
sandwiched between welding neck
placed in relation to the body to obtain a
flanges or slip-on flanges
self-centring effect at installation
• Determine the correct installation
Size: situation and the direction of flow. It
• Nominal diameter: DN 250 must be installed either in a horizontal
flow or where the flow is vertically
Connection requirements: upwards
• Min. inline diameter of connection • The valve is self-centring. However, it
pipe/flange: 258.8 mm must always be ensured that it is
• Length of required min. inline diameter: completely centred in relation to the
200 mm connection pipe/flange. Use the body
rim (external) diameter for this purpose
Material: • The check valve can be installed directly
• Body: carbon steel on a valve, but a distance of 2-3 times
. Waferdisc:AISI316L the pipe diameter is preferable.
• Disc seating: metallic • In case of a steam system with vertical
installed check valve a steam trap should
Technical data: be installed for drainage of condensate
• Operating pressure max: 25 bar
• Max. cold hydraulic test pressure: 37.5
bar
Installation examples:
Type: Material:
• Stop globe valve, straight • Body: GGG 40.3
• 23.006 DIN-Material No. 0.7043
• Seat:X20Crl3
Size: DIN-Material No. 1.4021.05
• Nominal diameter: DN 25 • Disc:X20Crl3
Application: DIN -Material No. 1.4021.05
• For steam and/or water flow Technical data:
• Nominal pressure: PN 25
• Weight: 5.4 kg
• Flanges according to DIN
0 140
Type:
• Stop valve, gate straight
Size:
• Nominal diameter: DN 50
Application:
• Sea water, fresh water, oil, steam etc.
Material:
• Body: GG25
Technical data:
• Nominal pressure: PN 10
• Max. temperature: 150 °C
• Weight: 11.5 kg
120
Material:
Type:
• Body: Carbon steel
• Reflective water level gauge, left
• Drain valve body: ASTMA105
• Model 26
Technical data:
Size:
• Nominal pressure: PN 25
• Nominal diameter: DN 25
• Weight: 22 kg
Application: • Connections between body and cocks are
• For boiler water level indicator made by end tubes and stuffing boxes
160
Type No: 7010 Water level gauge, left, model 26 7010 000136
Version: B DN 25, PN 25
Material:
Type:
• Body: Carbon steel
• Reflective water level gauge, right
• Drain valve body: ASTM A105
. Model 26
Technical data:
Size:
• Nominal pressure: PN 25
• Nominal diameter: DN 25
• Weight: 22 kg
Application: • Connections between body and cocks are
• For boiler water level indicator made by end tubes and stuffing boxes
160
Type:
• Safety valve, full lift
. 25.941
Size:
• Nominal diameter: DN 15
Application:
• To blow off steam and/or air.
Material:
. Body: GGG 40.3
• DIN-Material No.: 0.7043
Technical data:
• Nominal pressure: PN 40
• Weight: 3.5 kg
Body
Type: Material:
• Stop globe valve, straight • Body: GGG 40.3
• 23.006 DIN -Material No. 0.7043
• Seat:X20Crl3
Size: DIN-Material No. 1.4021.05
• Nominal diameter: DN 80 • Disc:X20Crl3
Application: DIN-Material No. 1.4021.05
• For steam and/or water flow Technical data:
• Nominal pressure: PN 25
• Weight: 23 kg
• Flanges according to DIN
0 200
Type No.: 8540 Soot blower with air scavenge valve for 8540 000009
Version: C manual operation
Material:
Type:
• Valve body: Forged carbon steel
• Mark 0 300
• Valve: Stainless steel
Size: • Seat: Stainless steel
• 3/4" BSP Technical data:
Application: • Steam pressures: Up to 21 bar
• The drain valve is designed to keep the • Temperature: Max. 3 50°C
soot blower pipeline free from • Weight: 8 kg
condensate. It employs a simple spring Installation:
loaded mechanism which can be pre-set
• The valve must be mounted vertical with
to suit the operating pressure of the
the inlet at the top
system and the valve is designed so that
it remains open when the blowers are
not in use. The valve closes during soot
blowing and automatically re-opens
when blowing is completed.
0 70
Seat
Strainer
Method of operation:
• The valve may be opened manually with
the hand wheel provided while under
full boiler pressure, but it cannot be
closed by hand. This is an effective safe
guard against water accumulation in the
pipes.
• A fine mesh strainer is incorporated at
the valve inlet to prevent the valve from
becoming choked.
• Before using the blowers the master
steam supply valve is cracked. After a
pre-set time period the supply line to the
blowers will have warmed up and all
condensate removed from the pipes. As
the master supply valve is turned fully
open, the drain valve automatically
shuts, the blowers may be operated.
When the master supply valve is shut
the drain valve will open as the pressure
in the pipe line falls and any condensate
will be discharged.
0219
Yard piping
oo
CO
co
o
<
Flange DN100-PN16
Flange DN25-PN16
Plot Date: AND MUST NOT BE USED BY OR REPRODUCED FOR THIRD PARTY 85Y:013427 b
^ ^ ^ Description Index D a ^ ^Drawn Appr.
Article no. for i t e ^ B ^ a n g e d a 97iH V JA TCG
Item 4 from 16 m. to 8 m. b 000518 JA BF
Detail of Item 1 removed c 030131 JA BZ
Item nos. changed d 040608 JA BZ
C186.2
— • • • ' •
Approx.1500
-
Limiting conditions
Maximum body design conditions PN 40
PMA — Max. allowable pressure 40 bar g
TMA — Max. allowable temperature 400°C
Cold hydraulic test 60 bar g
Operating range
10 20 30 32» 40
Pressure bar g
Capacities
2 3 4 5 10 20 32
Differential Pressure bar (x 100 = kPa)
Materials
No Part Material
1 Body Stainless Steel
DIN 17445 G-X20 Cr14 Ws 1.4027
2 Cap Stainless Steel AISI416
3 Disc Stainless Steel BS 1449 420 S45
4 Strainer Screen Stainless Steel ASTMA240 316L
5 Strainer Cap Stainless Steel AISI416
B. Strainer Cap Gaske I Stainless Steel BS1449 304S16
7 Insulating Cover Aluminium
(optional extra. Not DN 25)
8 Flanges Steel DIN 17243 C22.8 Ws 1.0460
Installation
Preferably fitted in a horizontal pipe but can be fitted in other
positions.
Optional extras
Insulating cover:- to prevent the trap being unduly influenced by
excessive heat loss such as when subjected to low outside
temperatures, wind, rain etc. (Not available for DN 25)
Note: The internal blowdown valve is not available for the TD 32F
Spare parts
The spare parts available are shown in heavy outline. Parts drawn in
broken line are not supplied as spares.
AVAILABLE SPARE ITEM
Disc(Pktof3) 3
Strainer Screen and Gasket 4,6 Withdrawal
Strainer Cap Gasket (Pkt of 3) 6 distance
Insulating Cover (Not available for DN 25) 7 for Strainer
Maintenance
Before undertaking any maintenance on the trap it must be isolated
from both supply line and return line and any pressure allowed to
safely normalise to atmosphere. The trap should then be allowed to
cool.
How to service
Remove insulating cover if fitted and unscrew cap using spanner.
Do not use Stillsons or a wrench of similar type which may cause
distortion of the cap. If the disc and body seating faces are only
slightly worn they can be refaced by lapping individually on a flat
surface such as a surface plate. A figure of eight motion and a little
grinding compound such as the Carborundum Co's Compound I.F.
gives the best results.
If the wear is too great to be rectified by simple lapping, the seating
faces on the body must be ground flat and then lapped and the disc
replaced by a new one. The total amount of metal removed in this
way should not exceed 0.25 mm.
When re-assembling, the disc is normally placed in position with the
grooved side in contact with body seating face. Screw on cap, no
gasket is required but a suitable high temperature anti-seize grease
should be applied to the threads.
To clean or replace strainer
Unscrew strainer cap using spanner, withdraw screen and clean, or
if damaged replace with new one.
To re-assemble, insert screen into cap, then screw cap into place. A
fine smear of 'Molybdenum Disulphide' grease should be applied to
the first few threads. Care should be taken to ensure that the gasket
and gasket faces are clean. Tighten cap to the recommended torque.
Recommended Tightening Torques
Item DN or p Nm
mm | |
2 15LC 36 135-150
• 15 36 180-200
20 41 180-200
25 55 250-275
5 32 170-190
Yard piping
Supplied loose
BALL VALVE
Dimensions
DN25- 100
Full Reduced H 1 L M N O ISO
bore bore 5211
DN25 DN32 M12 x 1.25 7.5 20.0 10.0 42 M5 F04
DN32 DN40 M15x1.5 8.9 27.0 13.0 50 M6 F05
DN40 DN50 M15x1.5 8.9 28.0 14.0 50 M6 F05
DN50 DN65 M15x1,5 8.9 25.0 12.5 50 M6 F05
DN65 DN80 M22 x 1,5 16.0 3b.O r/,o 70 M8 F07
DN80 DN100 M24x1.5 18.0 37.5 15.0 70 M8 F07
DN 25 -100
Arrangement of bolts
DN Full Reduced
8 6.8
6+6 bolts: 10 6.8
DN 65-80 reduced bore
15 12.8 6.8
DN 50-65 full bore
20 29.1 12.8
25 50.0 29.1
32 72.6 50.0
40 106.8 72.6
8+8 bolts: 50 213.7 106.8
DN 100 reduced bore
65 275.0 213.7
»DN 80 full bore
_>80 500.0 275.0
Parts/Material specifications
Shown with encapsulated seat on the end piece
Standard versions
Item Quant. Part Body - Carbon steel Body - Stainless steel
1 1 Handle Galvanized and plastic- Galvanized and piastic-coated
coated carbon steel carbon steel (Stainless steel
A 316 to special order)
2" 1+1 Handle retaining nut (2A) Cadmium-plated Stainless steel A 316
Locknut(2B) carbon steel
3 1 Stem packing Graphite Graphite
4" 2 Spring washer Stainless steel A 302 Stainless steel A 302
5" 1 Antistatic stem Stainless steel A 316 Stainless steel A 316
« 1 Packing ring Stainless steel A 316 Stainless steel A 316
7* 1 Thrust washer PTFE PTFE
8' 1 O-ring Viton PTFE
9" 1 Ball Stainless steel A 316 Stainless steel A 316
10" 2 Seat seal PTFE + 20% carbon + PTFE + 20% carbon +
5% graphite 5% graphite
ir 2 Primary body seal PTFE + 20% carbon + PTFE + 20% carbon +
5% graphite 5% graphite
12 1 Body Carbon steel A 1 0 5 Stainless steel A 316
13 2 End piece Carbon steel A 1 0 5 Stainless steel A 316
14 1 Antistatic spring Stainless steel A 316 Stainless steel A 316
unit in stem
15* 4+4 or Body bolt (see "Arrange- Stainless steel A193 B7 Stainless steel A 1 9 3 B8
6+6 or ment of bolts")
8+8
16 4+4 or Bolts Carbon steel Carbon steel
6+6 or
8+8
17" 1 Lockwasher Stainless steel A 316 Stainless steel A 316
18" 2 Secondary body seal Graphite Graphite
19" 2 Seat seal PTFE or graphite PTFE or graphite
Flange Dimensions
ISO 5211 F07 F10
df8 55 70
Q1 70 102
W1 M8xl2 1/110x15
I 55 70
M5XS Square 22 22 27
PortT Port'4' Lmin. 24 24 29
hmin. 1,5 1.5
M 2,5 2
Position Indicator Z=65
tor Proximity
12 \ G1/4" ISO228 -1 Pressure connection B2
Ancillary Attachment AA2
345
Spigot optional
2,5 bar 3 bar 3,5 bar 4 bar 4,2 bar 4,5 bar 5 bar 5,5 bar 6 bar 7 bar 8 bar stroke Weight
0' 90° 0" 90° 0° 90° 0° 90° 0° 90° 0° 90" 0° 90° 0° 90° 0° 90° 0° 90° 0° 90° 90° 0° (Kg)
138 166 194 222 233 249 277 305 332 388 443 10,2
End Start
S05 86 56 114 84 141 111 169 139 180 150 197 167 224 195 82 53 11
S06 75 40 103 67 131 95 159 123 170 134 186 150 214 178 242 206 99 63 11,1
S07 93 51 120 79 148 106 159 117 176 134 203 162 231 189 259 217 115 74 11,3
S08 110 62 138 90 149 101 165 117 193 145 221 173 248 201 304 256 132 84 11,4
S09 127 73 138 84 155 101 182 129 210 156 238 184 293 239 349 295 148 95 11,6
S10 144 84 172 112 200 140 227 168 283 223 338 278 165 105 11.8
S11 161 96 189 123 217 151 272 206 328 262 181 116 11,9
•S12 179 107 206 135 262 190 317 245 198 126 12,1
Max. Rotation Screw stroke Chamber Air Volume (L) Moving Time (Sec.) (A) Operating Temperature (°C) (B)
Pressure Adjustment 0(mm) Opening Closing Opening Closing STD (standard) HT (high temp.) LT (low temp.)
90° ±4° For1° D 0,90 1.1 NBR "O"-Ring FPM "O'-Ring Silicon "O'-Ring
8 bar at 0° and 90' need 1/4 Turn 125 1,54 2,34 S 1,20 1,40 -20 to+80 -15 to+150 - 40 to +80
Notes: (A) The above indicated moving time of the actuator, are obtained in the following test conditions^"]) Room Temperature, (2) Actuator Stroke 90",
(3) Solenoid Valve with Orifice Of 4 mm and a flow capacity Qn 400 L/minC4) Inside pipe diameter 8 mm, (S) Medium clean air. (6) Air supply pressure
5.5 bar (79,75 Psi)(7) Actuator .without external resistance load.
Cautions: obviously on the field applications when one or more of the above parameter are different, the moving time will be different.
(B) For HT (high temperature) and LT (low temperature) services, a special Lubricant is requested. Please contact Air Torque factory.
Description:
Specifications
Box Poiycarbonat
Shaft POM
Cam Brass
Protection IP 65
O-ring Viton
Technical data
EGO BOX M
Manufacture Honeywell
Consumption -
Max. frequency -
Dimensions 82x80x67
CONNECTION DIAGRAM
GENERAL
Differential pressure 2-10bar[1bar=100kPa]
Flow (Qv at 6 bar) 700 l/min (ANR)
fluids (*) temperature range (TS) sealings (*)
air, inert gas, filtered NBR (nitrile)
-25°C to +60°C
PUR (polyurethane)
ELECTRICAL CHARACTERISTICS
Coil insulation class F
Coil Epoxy resin
Spade plug connection coil 3 x DIN 46244
Connector Type 22, spade plug (Pg 9P)
Electrical safety VDE 0580
Standard voltages DC (=):24V
AC (~): 230V 7 60 Hz
power ratings ambient
coil inrush holding hot/cold temperature protection
type range (1) (TS)
(VA) (VA) (W) (W) (°C)
CM22-2.5W 6 3,5 2,5 2,5/3 -25 to +60 moulded IP65
SPECIFICATIONS
operating pressure
flow
operator
coefficient coil
size size maximum (PS) type (C) catalogue number
Kv
min. air (*)
(G) (mm) (m3/h) | (l/min) ~/ =
Single solenoid pilot operated - spring return (monostable), with or without exhaust reducers
^QM2pi5W; : 1 • . ^ / ^ S C - G S M M O O I M S - G F ' ; .. >.
1/4 6 0,6 10 2 10
GM22'*2;5.W 1 • •> ., \ v ^caif!ApfigMs;if f: . : '„••
Dual solenoid pilot operated and air return (bistable), with or without exhaust reducers
• 6M22#5Vfr 2 • SG G5MA002JMS .. ' :
1/4 6 0,6 10 2 10
CM22-2.5W 2 • * '; •;. , Sfi/G|^jWJD2,MS;i-. ;,
(C) Construction type • : screw-type manual operator "0" : exhaust reducer
INSTALLATION
The solenoid spool valves can be mounted in any position
Spool valve supplied with two interface plates with mating surfaces. Depending on function (NC 3/2 or 5/2),
position one of the two plates on the spool valve body before installing on actuator
Dowel pin (if necessary), bolts and gaskets are standard supplied
Connect or protect the exhaust ports to isolate the internal atmosphere of the internal parts of the spool valve.
Range of 1/8 fitting available
Pipe connections have standard thread according to ISO 228/1
The third digit in the catalogue number indicates the standard pipe connection
Other pipe threads are available on request
Installation/maintenance instructions are included with each solenoid spool valve
Replacement coils are available
Port 1 : G1/4
Ports 3 and 5: G1/8
6)
ptz)
33.
kj 1
^
19J
Type:
• Level float switch
• RBA 24
Size:
• DN25 in
Application:
• Low water level switch rrm urn rrm mn
Material:
TWK
• St. 35.9
• C22.8
Technical data:
• Drain connection: 0 12 mm
• Cable connection: PG 11
• Nominal pressure: PN 40
• Max. working pressure: 32 bar
• Max. working temperature: 239°C
• Flanges according to DIN 263 5-C
• Magnetic switch: 2 x M130
• Switching voltage: 6-250V
• Switch current max: 1A ac; 0.5A dc
• Protection of switch housing: IP 54
Type:
• Pressure transmitter
• MBS 5100
Size:
• 0-25 bar
Application:
• The pressure transmitter converts pressure to an electric signal. This is proportional to, and linear
with, the value of the pressure to which the pressure-sensitive element is subjected by the
medium. The units are supplied as two wire transmitters with an output signal of 4-20 mA. The
transmitters have a zero-point displacement facility for equalizing static pressure.
Span adjustment is also possible.
Material:
• Housing material: Anodized AlMgSiPb
IS
D
m
m
o>
7 J I 1,
FTP • i
n
|
/
25.5
p g ' 11 in
0 5.8'
co III .
I
o
CM
>
l_ J I t
G 1/2" -m
15
4 30 , 30
73
84
Technical data:
Performance:
• Accuracy (incl. non-linearity, hysteresis and repeatability): ±0.1% fs (typ.) / ±0.3% FS (max.)
• Non-linearity (best fit straight line): < ±0.2% FS
• Hysteresis and repeatability: < ±0.1% FS
• Thermal zero point shift: < ±0.1 % FS/1 OK (typ.) / < ±0.2% FS/1 OK (max.)
• Thermal sensitivity (span) shift: £ ±0.01% FS/K (typ.) / < ±0.02% FS/K (max.)
• Response time: < 4 rms
Electrical specification:
• Rated output signal: 4 to 20 mA
• Supply voltage, Vsuppiy (polarity protected): 10 to 32 Vd.c.
• Voltage dependency: < 0.01% FS/V
• Current limitation (linear output signal up to 1.5 x nom range): 28 mA (typ.)
• Max. load RL: RL < [(Vsuppiy -10V)/0.02A] - 10 D
Mechanical:
Connection: G 1/2" -m (EN 837-1-G XA A)
Max. operating pressure: 50 bar
Min. burst pressure: 100 bar
Operating temperature range: - 40 to 85°C
Compensated temperature range: 0 to 80°C
Transport temperature range: - 50 to 85°C
Cable entry: PG 11
Enclosure: IP 65
Weight: 0.4 kg
Installation:
• There are facilities for adjusting zero point and span.
Zero point adjustments is necessary to equalise pressure arising from any differences in level
between the pressure transmitter and the medium being measured.
Zero point adjustment results in a parallel displacement of span.
Both zero point and span must be adjusted on the side of the unit with cover removed
-5 to > + 10% FS
4 - 2 0 mA
1. Supply*
2. Supply _
3. Function test
•4 Connected to MBS transmitter enclosure
Type:
• Pressure gauge valve needle straight.
Size:
• 1/2" x 1/2"
Application:
• For instrument connections
Material:
• Body:C22.8
• DIN-material No. 1.0460
Technical data:
• Nominal pressure: PN400
• Test connection: M20 x 1.5 mm threaded male
• Weight: 0.4 kg
Type:
• Pressure gauge, type P1116
Size:
• 0 63
Application:
• For all gaseous and liquid media
Material:
• Case: Stainless steel
• Socket: Cu-alloy
• Liquid filling: Glycerine
Technical data:
• Connection: G l/4"-m (1/4 BSP)
• Measuring unit: bar — Mpa - kg/cm2
• Measuring range: 0 - 40 / 4.0 / 40
• Pressure utilisation:
Static pressure: 75% of Pmax.
Dynamic pressure: 66% of Pmax.
• Operating temperature: -20 to +80°C
• Accuracy: EN 837 Class 1,6
32
6.5 r _
0
\
00
co
0 \
X
1 1
G1/4"A
Type:
• Pressure gauge, type P1116
Size:
• 0 63
Application:
• For all gaseous and liquid media
Material:
• Case: Stainless steel
• Socket: Cu-alloy
• Liquid filling: Glycerine
Technical data:
• Connection: G l/4"-m
• Measuring unit: bar - Mpa - kg/cm2
• Measuring range: -1 to +5 / - 0.1 to +0.5 / -1 to +5
• Pressure utilisation:
Static pressure: 75% of Pmax.
Dynamic pressure: 66% of Pmax.
• Operating temperature: -20 to +80°C
• Accuracy: EN 837 Class 1,6
32
6.5r _
0
\
CO
CD
Q
0 \
X
. G1/4"A
1 t
•m •
Type:
Material:
• Bellows: Stainless steel 18/8
• Pressure switch
• Spring: Stainless steel 17/7
• RT117
• Housing: Brass
Size: • Bellows ring: Brass
• 10-30bar
Application:
• The pressure switch is a single-pole
changeover switch where the contact
position depends on the pressure in the
connection port and the set value.
83
. 28,
Technical data:
Electrical switch contact load:
• Alternating current:
AC-l(ohmic): 10 A, 400 V
AC-3 (motor): 4 A, 400 V
AC-14/15 (coil transformer): 3A, 400V
Blocked rotor, 28 A, 400V
• Direct current:
DC- 13/14: 12 W, 230 V
Mechanical-
Connection: G 3/8", -m
Ambient temperature: - 50°C to + 70°C
Medium temperature: max. 150°C
Operating pressure: Max. 22 bar
Test pressure: Max. 47 bar
Adjustable/fixed mechanical differential:
1 to 4 bar
• Enclosure: IP 66
The pressure control housing is made of
bakelite to DIN 53470 while the cover is
powder painted deep-drawn steel plate.
To ensure the IP 66 degree of enclosure
is obtained, the front cover and screwed
cable entries must be correctly
tightened.
• Cable entry: Two Pg 13.5 for cable from
6 to 14 mm
Installation:
• The range is set by using the knob (5)
while at the same time reading the scale
(9). The differential is set by rotating the
differential disc (19).
Type
• Full Bore ball valve
• EURO-SFER 1720
Size:
• Nominal diameter: DN8
Application:
• Assembly in rigid pipe system
• Direction of low in both directions
Material:
• Body: CW617N UNI EN 12165
• Lever: aluminium handle UNI 5076
painted black with epoxy powder
Technical data:
• Nominal pressure: PN 64
• Thread ends: female - female UNI ISO
7/1
R<R0.1
0.5x45c
082
Plate
082x3 AISi 316
Designation Material code Article No.
Item Pcs. Cert.
Dimension Material type Detail drawing No.
Title: Drawn Date
LD 050216
Appr. Date
• • • • •
Orifice DN 32/07,9 PRu 050216
Weight Scale: Size
1:1 A4R
AALBORG Article/Drawing No: Index
INDUSTRIES
THIS DRAWING AND DESIGN SHOWN HEREIN IS THE PROPERTY OF AALBORG INDUSTRIES
Plot Date: AND MUST NOT BE USED BY OR REPRODUCED FOR THIRD PARTY K18:035884
AALBORG DATA SHEET
INDUSTRIES
120
85
Start/operation
incl. lamp function
Stop
105
e-
Type:
30
• Filter regulator with automatic drain
Haidle r
Size: Body l
CD
• Connections ports 1/4" BSP
• Gauge ports 1/8" BSP
9 8
Application: ipn Fitting
• Instrument air for regulating pressure L£
Technical data: Q
0)
• Medium: instrument air only
• Max. inlet pressure: 17 bar s? s
• Operating temp.: -20 °C to + 65 °C
S
• Filter element: 5 jum
• Recommend pressure regulating range:
0.14-7.0 bar Bin
• Pressure gauge: 0 - 1 0 bar
• Weight: 0.4 kg Connections ports
Material:
• Body: Steel SWi9"f
• Bin: Steel 1
• Handle: Acetal 41
Flow characteristics
X
•
— .
tS
— - —
- - —
33
O 2 —==; •
\
V
1
— .
— _
— - — - .
1 • — .
• — • — .
—
—
— - —
~ — — - — • —
— —
- —
1 2 3 4 5 6 7 8 9 10
^ir flow [dm7s]
Block Diagram:
Communication
2-wire Inputgnd.
transm. v> mA V < =
2.5 2.5
5514A2
Type:
• Temperature transmitter
• PT100
Cable gland
Size: PG16
• 0 15x300
Range:
• 0-500°C
Application:
• For measuring temperatures in gases, 2. Cooling neck
vapours, and fluids
Material:
• Stainless steel:
Technical data:
• Housing: Form B, DIN 43729
• Connection at instrument: G 1/2" BSP
• Protection: IP65
• Cable gland: PG 16
• Response time (mean values) at
velocities in water at 0.4 m/s:
T0.5 = 29 sec.
• Response time (mean values) at
velocities in air at 3.0 m/s:
T0.5 = 120 sec.
• Recommended measuring current:
max. 2 mA 3. Sensor tube with
• Number of conductors: 4 PT 100 element
• Number of elements: 1 x PT 100
• Tolerance class, DIN C1JB: ± 0.3°C
• Resistance in Q at 0°C: 100
Electrical connection:
16 4 3
Technical data:
Type:
• Max pressure: 123 bar
• Dosing pump P.E. 100 with chemical
• Capacity: 2.5 1/h
tank
• Max pressure suction side: 35 bar
Application: • Max operating temperature: 50°C
• For chemical dosing • Enclosure rating: IP 44
• Insulation class: F
Material: • Chemical tank volume: 100 1
• Pump • Colour: RAL 1028
• Liquid end: PVC • Weight: 28 kg
• Check valve cartridge: PVC
• Seats: PVC
• Balls: Glass
• Contour plate: PVC
• Seals: Viton
• Chemical tank: Polyethylene
• Dosing head: Stainless steel
Chemical dosing unit item 9296 000002
Foundation
680
12 ... 12.5
c
..._.j
Performance curves
CO
O
20--
10 l/h
10-
8 l/h
10 20 40 80 Pressure (bar)
Material:
Type:
• Sample cooler: austenitic stainless steel
• Sample cooler
grade316L
Size: • Cooling water inlet valve: stainless steel
• SCS20 • Sample inlet valve: stainless steel.
• Compression fitting: carbon steel
Application:
Technical data:
• The sample cooler is designed for taking
manual samples of boiler water for • Coil design pressure: 32 bar g
analysis. The cooling water is turned on • Coil design temperature: 300°C
and the sample inlet valve is adjusted • Body design pressure: 10 bar g
until a sample of boiler water is obtained • Body design temperature: 100°C
at a suitable temperature. For manual
sampling it is not normally necessary to
measure sample or cooling water flow
rates.
Sample in a 6 mm O/D
Customer supply
. 1. Sample cooler
Type:
• Filter regulator with automatic drain
Handle 1 • •
Size:
• Connections ports 1/4" BSP
• Gauge ports 1/8" BSP
-CD- I
—9-
T 1
Application:
Fitting
• Instrument air for regulating pressure
Technical data:
• Medium: instrument air only
• Max. inlet pressure: 17 bar
• Operating temp.: -20 °C to + 65 °C
• Filter element: 5 pm
• Recommend pressure regulating range:
0.14-7.0 bar
• Pressure gauge: 0 - 1 0 bar
• Weight: 0.4 kg
Material:
• Body: Steel
• Bin: Steel
• Handle: Acetal
Flow characteristics
3 - " - —
-^.
—
—
X
"3
O 2 1
\
— .
— — _
• — _
.
— — . — .
—-—.1
• - - —
— —
.
•
——_
2 3 4 5 6 7 8 9 10
A'r flow [dm7s]
Approx. 325
Steam flow ,APP"».3IO
Control device 8210000026
19
230 V - 50/60 Hz
Pressure transmitter 8010000008
18
0-25 (max. 40 bar) Bar G 1/2"
Gasket 2911602
17 0i8/06.5t=2 Copper
Pressure gauge valve DIN 17243 2541002
16 1/2" PN400 C22.8
Diff. pressure transmitter 8020000001
15
2.5-250 mBar
/JIILQJJJQ 14
Gasket
018.64x3.53 Rubber/viton
3520000013
Steam flow
Measuring range
• Span (continuously adjustable)
• Upper measuring limit 100 % of max. span (max. 160 bar with oxygen measurement
and inert filling liquid)
Output
Output signal 4 to 20 mA
• Lower limit (continuously adjustable) 3.55 mA, factory-set to 3.84 mA
• Upper limit (continuously adjustable) 23.0 mA, factory-set to 20.5 mA or optional 22.0 mA
• Ripple (without HART communication) IOD < 0.5 % of max. output current
• Electric damping
- Adjustable time constant (T63) 0 to 100 s in steps of 0.1 s, factory-set to 0.1 s
• Current transmitter Adjustable from 3.55 to 23 mA
• Signal on alarm Adjustable from 3.55 to 23 mA
Load
• Without HART communication RB <. {UH -10.5 V) / 0.023 A in Q, UH: power supply in V
Characteristic Linear rising or falling or square-rooted
Accuracy
Reference conditions Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm (with level:
mounting flange without tube), silicone oil filling and room temperature (25 °C)
r = max. span/set span = span ratio
Error in measurement with fixed-point
setting (including hysteresis and
repeatability)
- Linear characteristic
r<10 <0.1 %
10<rS30 <0.2%
30<r<100 < (0.005 • r + 0.05 %)
- Square-root characteristic
Flow > 50 % <0.1 % a t r < 1 0
< 0.2 % at
10<rS30
Flow 25 to 50 % £0.2%atr<10
< 0.4 % at
10<r<30
Noise U r m s £1.2mV(0.5to10kHz)
* 45 for Pg 13.5
1 a Process connection of low-pressure side VA - 1 8 NPT 5 Terminal side
1 b Process connection of high-pressure side Y« - 1 8 NPT 6 Electronics side, digital display
2 Mounting thread M10, M12 or 7/16 - 20 UNF 7 Protective cover over keys
3 Blanking plug 8 Sealing screw with valve
4 Electrical connection: 9 Vent on side for liquid measurements
screwed gland Pg 13.5 (adapter), M20 x 1.5 or 10 Vent on side for gas measurement (suffix H02)
14-14 NPT or Han 7D/Han 8U plug 11 Mounting bracket (option)
II II II II
by the medium. The units are supplied
as two wire transmitters with an output
signal of 4-20 mA. The transmitters
have a zero-point displacement facility
for equalizing static pressure
Material:
• Wetted parts: 1.4301 / A12O3 (ceramic
measurement cell)
• Housing: brass nickel-plated CM"
Technical data:
Performance:
• Average temperature coefficient of the
zero signal: < 0.15% / 10 K
• Deviation in characteristics relating to
measuring range:: < 0.5%
• Hysteresis relating to measuring range:
<0.1%
• Longterm stability: < 0.15% / year ZEJ
IO
Electrical specification:
• Supply voltage: 12 to 30 VDC G Vik
• Current limitation: to approx. 23 mA 0 38
• Interference: > 21.6 mA
Mechanical
• Ambient temperature: -20 to 85°C
• Product. Temperature: -20 to 100°C
• Storage and transport temperature:
-50tol00°C
• Protection: IP 65
• Connection plug / cable outlet: PA
Installation:
• The pressure transmitter can be mounted
in any individual position. For mounting
please use an appropriate process seal
(copper, Aluminium, steel-Viton etc.)
• Remove the plug from the sensor and
1. Supply +
push / pull the plug screw out of the 2. Supply-
plug. Remove the plug insert with a i Connected to Vegabar transmitter enclosure
small screwdriver out of the plug
housing. Hence the screw terminals of
the plug are accessible for cable
connection.
• The zero point can be modified in the
range of approx. 3 to 5 mA. If necessary
adjust the zero point to a 4 mA. Hence
pull out the plug and remove the plug
screws. Now insert the plug again to the
sensor and insert the 2 mm-screwdriver
(attached to the instrument) approx. 45
mm into the hole of the plug screw.
Then a small potentiometer is reached
by which the zero point can be adjusted.
Type:
• Pressure transmitter
• MBS 5100
Size:
• 0 - 40 bar
Application:
• The pressure transmitter converts pressure to an electric signal. This is proportional to, and linear
with, the value of the pressure to which the pressure-sensitive element is subjected by the
medium. The units are supplied as two wire transmitters with an output signal of 4-20 mA. The
transmitters have a zero-point displacement facility for equalizing static pressure.
Span adjustment is also possible.
Material:
• Housing material: Anodized AlMgSiPb
0 5.5'
Technical data:
Performance:
• Accuracy (incl. non-linearity, hysteresis and repeatability): +0.1% fs (typ.) / +0.3% FS (max.)
• Non-linearity (best fit straight line): < +0.2% FS
• Hysteresis and repeatability: < +0.1% FS
• Thermal zero point shift: < ±0.1% FS/10K (typ.) / < ±0.2% FS/10K (max.)
• Thermal sensitivity (span) shift: < ±0.01% FS/K (typ.) / < ±0.02% FS/K (max.)
• Response time: < 4 rms
Electrical specification:
• Rated output signal: 4 to 20 mA
• Supply voltage, Vsuppiy (polarity protected): 10 to 32 V d.c.
• Voltage dependency: < 0.01 % FS/V
• Current limitation (linear output signal up to 1.5 x nom range): 28 mA (typ.)
. Max. load RL: RL < [(Vsuppiy -10V)/0.02A] - 10 Q.
Mechanical:
Connection: G 1/2" -m (EN 837-1-G XA A)
Max. operating pressure: 80 bar
Min. burst pressure: 800 bar
Operating temperature range: - 40 to 85°C
Compensated temperature range: 0 to 80°C
Transport temperature range: - 50 to 85°C
Cable entry: PG 11
Enclosure: IP 65
Weight: 0.4 kg
Installation:
• There are facilities for adjusting zero point and span.
Zero point adjustments is necessary to equalise pressure arising from any differences in level
between the pressure transmitter and the medium being measured.
Zero point adjustment results in a parallel displacement of span.
Both zero point and span must be adjusted on the side of the unit with cover removed
-5to> + 10%FS
4-20 mA
1. Supply+
2. Supply -
3. Function test
i Connected to MBS transmitter enclosure
Type:
Nozzle, Couplings (2" Storz) Hose,
• Water washing hose with nozzle item No. 29,4 1101 \ item No. 294 1001
Size:
• V-nozzle: 12 mm
• Length: 15 metre (hose)
• Inner diameter: 52 mm (hose)
Application:
• For spraying of water
Material:
• Hose: full-synthetic material (polyester)
woven in 1/1 binding, with inner rubber
lining 2" BSP connection Couplings (2" Storz),
(male) item No. 294 1201
Technical data:
• Max allowable working pressure: 20 bar
• Water temperature area: -3 0°C-+60°C
• Weight: 5.5 kg
Water flow
l/min
210
200
190
180
170
160
150
140
130
120
/
110 /
100 /
90 /
80
70 t
60
50
40
30
20
10
1 8 9 10 Bar
765 4 x 6 mm holes
410
610
f
r
A
Type:
• Ultrasonic sensor for oil detection
equipment
Application:
• The ultrasonic sensor is operated
together with a control unit.
• The equipment provides for oil detection
in feed/make-up water.
Material:
• Sensor: Stainless steel
Technical data:
• Temperature: -70°C to 150°C
• Design of duty: Chemical interface
• Liquid type: Clean, viscous with solids
• Cable: 6 metre
258
10 20 ,.25 152 .26
Type:
• Control unit for oil detection equipment
Application:
• The control unit is operated together with
an ultrasonic sensor.
• The equipment provides for oil detection
in feed/make-up water.
Material:
• Control device cabinet: Polycarbonate
Technical data:
• Power supply (selector switch):
110/120Vor220/240VAC
• Relay output: DPCO
• Enclosure: IP 65
• Holes for glands 3 of 0 16
•0 O Normal c
O Alarm
00
O Fault
OO
•0
188 —^ Holes for mounting
- 40 ,
130
160
200
Type:
• Conductive electrode, type SL 700 E Electrical:
• Total cable length: max. 200 m
Application: • Connection to control device via junction
• The conductive electrode is used in box:
combination with a control device to Sensor pin 1 to pin 11 (white)
measure and supervise the salinity of Sensor pin 2 to pin 12 (black, white)
feed water. Sensor pin 3 to pin 13 (red)
Sensor pin 4 to pin 14 (shield)
Technical data:
Sensor pin 5 to pin 15 (black, red)
Instrument: Installation:
• Salinity range: 0 - 2 0 ppm (sea salt) • The conductive electrode must be
• Accuracy: +/-10% installed in the supplied T-piece (item
8500 000115). The cable must be
connected to the control device via a
junction box (not AI supply).
•u Cable lenght:
Y[/2.5 metre
Connector
plug:
6 pol GLC •
Packing
Gold-plated
electrodes
Type:
• Control device for salinometer, type SL Electrical:
700 • Mains supply: 90 - 115 VAC or
190-230 VAC, 5 0 - 6 0 Hz
Application: • Mains current: mains supply must be
• The control device is used in secured against over current externally
combination with a conductive electrode by using a fuse (max. 100 mA)
to measure and supervise the salinity of • Power: max. 3.5 W
feed water. • Cable connections:
Terminal 1-4: mains supply
Technical data:
Terminal 5-10: relay contacts for alarm
Instrument: and solenoid
• Salinity range: 0 - 2 0 ppm (sea salt) Terminal 11-16: electrode unit
• Accuracy: +/- 10% of displayed value Terminal 17 - 18: 4 - 20 mA current
• Adjustable alarm range: 1-20 ppm loop (I = 0.8 x (ppm) + 4 mA)
• Display: LED indication bar • Relay contacts: 8 A / 24 VDC
0 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20
86
Alarm ; ilili: Alarm set |
liiiiijli
AALBORG - I
' " • " " " Salinometer type SL 700
105
Material:
Type:
• Housing: RG 5
• T-piece for salinity alarm equipment
• Nut for electrode: RG 5
Size:
Technical data:
• DN25
• Nominal pressure: PN16
Application: • Flanges according to DIN 2501
• Housing for salinity electrode
110