Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: For spaces with occupants coming in and out frequently, e.g., airport terminals and commercial buildings,
Received 3 June 2017 the intermittent opening of the entrance door causes masses of cold outside air to invade the heating
Received in revised form 16 October 2017 space in winter, and this leads to an increase in the heating energy demands. As impinging jet ventilation
Accepted 18 November 2017
(IJV) has a potential for reducing high energy consumption compared to the use of mixing ventilation
(MV), a series of experiments were conducted to investigate the temperature distribution and energy
Keywords:
consumption of IJV used in a space with cold air invading intermittently and compared with those in a MV
Cold air invasion
system. The results indicate that the door opening frequency only affects the amplitude of temperature
Space heating
Impinging jet ventilation
fluctuation with time for a fixed door opening duration. The floor-to-ceiling temperature difference in
Mixing ventilation the IJV is always less than 60% of that in the MV for different durations of door opening, proving that
Thermal environment the former consumes less heating energy. Moreover, the increase of the inertia to buoyancy ratio on the
Energy efficiency supply air can improve the thermal environment and reduce energy consumption for both IJV and MV,
with this improvement better in IJV than in MV, meaning that IJV is more energy efficient than MV when
used for heating space with cold air invasion.
© 2017 Elsevier B.V. All rights reserved.
1. Introduction When spaces with occupants coming in and out frequently, for
example, in airport terminals, station halls and commercial build-
Heating, ventilating and air conditioning (HVAC) systems are ings, etc., the intermittent opening of the entrance door causes
usually used for room cooling in summer and space heating in masses of cold outside air to invade the heating space in winter.
winter in almost all public buildings in China. Although displace- The cold invading air flows downwards to the ground because of the
ment ventilation (DV) is believed to have high energy efficiency, it negative buoyancy effect and then spreads along the floor after it
cannot be used for space heating because of its low supply momen- invades the heating room, so a cold air layer is generated next to the
tum [1–3]. As a traditional ventilation strategy, mixing ventilation floor. When the cold air passes through indoor heat sources (such as
(MV) has been widely used for both cooling and heating in various human bodies and electrical equipments), it is heated by convection
types of buildings, but it has poor ventilation and energy efficiency heat transfer and then flows upwards, and thus a thermal stratifi-
[4]. Particularly, when a MV runs in heating mode, the warm air cation is formed in the room. This is similar to that in a DV cooling
is hardly distributed into the lower part of the room due to the room [6]. In addition, the cold air layer near the ground also results
buoyancy effect, and the indoor temperature is lower in the occu- in a temperature difference between the warm supply air and sur-
pied zone and higher in the upper part of the room. Hence, the rounding air and the difference always remains at a high level in
temperature in the upper zone is much higher than the set value the room, but the momentum of the warm supply air drops with
in order to meet the thermal comfort requirement for occupants. the increase of spreading distance. As a result, the effect of upward
This results in the averaged indoor temperature being too high and thermal buoyancy on the supply air is strengthened. Therefore, the
causes much heating energy to be consumed [5]. heating energy is not efficiently delivered into the occupied zone,
a large amount of warm air accumulates beneath the ceiling, and
an evident vertical temperature gradient is generated between the
floor and the ceiling in the room. The experimental results by Saïd
∗ Corresponding author.
[5] indicate that the floor-to-ceiling temperature differentials in
E-mail address: zhongkeyx@dhu.edu.cn (K. Zhong).
https://doi.org/10.1016/j.enbuild.2017.11.038
0378-7788/© 2017 Elsevier B.V. All rights reserved.
X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522 1511
at the low room level, strikes the floor and then distributes along
Nomenclature the floor in the form of a very thin layer [2,8]. When IJV operates
in cooling mode, it ventilates the room in a similar manner to DV
ACE Air change rate (h−1 ) in terms of stratification and air motion [3,9]. When IJV is used
CN Normalized CO2 concentration of each test run at for space heating, the warm supply jet is directly delivered to the
time t occupied zone, overcoming the disadvantage of MV which cannot
Vs Supply velocity (m/s) distribute the warm supply air into the lower part effectively [8]. It
Ts Supply temperature (◦ C) seems that IJV has a promising application for the above mentioned
To Temperature difference between the indoor and public spaces with cold air invading intermittently, because the
outdoor air (◦ C) warm supply air mixes with the invading cold air at the floor level,
T Temperature (◦ C) which can reduce the effect of the invading cold air on the tem-
V Velocity (m/s) perature near the floor to some extent and avoid the phenomenon
CC CO2 concentration (ppm) that occurs in MV, i.e., the temperature of the occupancy zone is
tT Period of door opening (s) dominated by the incoming cold air.
tO Duration of door opening (s) Numerous studies have been carried out on the impinging jet.
lm Buoyancy jet length scale (m) Table 1 shows a short summary of these studies. It is worthy to note
M Momentum flux(kg/(m·s)) that the majority of existing studies of IJV are limited to isothermal
B Buoyancy flux (N/m2 ) and cooling conditions, while only few studies are related to the
Q Initial volume flux of the supply jet (m3 /s) heating mode [8,31]. Although cold air invading the heating room
S Area of the supply inlet (m2 ) through the opened entrance door is a common phenomenon in
Ts Temperature difference between the supply and winter, only Saïd et al. [5] studied the thermal environment in MV
indoor air (◦ C) rooms with cold outside air entering, and there is no investigation
Tr Reference temperature (◦ C) focusing on the heating performance of IJV operated in the case of
Toz,t Time-averaged temperature in the occupied zone cold air invasion. This leads to the advantages of IJV relative to MV
(◦ C) being not clear when both are used for space heating with cold air
Tuz,t Time-averaged temperature in the upper zone (◦ C) invasion, and thus restricts the application of IJV in practice.
Tin,t Time-averaged temperature of the room (◦ C) The main purpose of the present study is to investigate the tem-
Ta,t Mean time-averaged temperature of the four test perature distribution and energy consumption in the IJV heating
poles at different heights h (◦ C) room with cold outside air invading intermittently and compared
Tt Time-averaged temperature (◦ C) with those in MV, and then to provide a theoretical basis for the
A Mean amplitude of temperature fluctuating with application and improvement of IJV. The experiments are con-
time (◦ C) ducted in a climate chamber. The temperatures and velocities are
h Height (m) measured in the IJV and MV heating rooms with different frequen-
Tg Floor-to-ceiling temperature difference (◦ C) cies and durations of door opening (being equivalent to different
E Total heat loss of the room (W) frequencies and amounts of cold air invasion, respectively), and the
K Averaged heat transfer coefficient of the envelope difference of indoor thermal environment between IJV and MV is
(W/(m2 ·◦ C) then discussed. Finally, the improvement effects of changing sup-
F Total area of the building enclosure surface (m2 ) ply parameters on the indoor thermal environment and energy
G Averaged cold air invasion rate for each period consumption for IJV are analyzed and compared with MV.
(m3 /s)
Te Outdoor air temperature (◦ C)
C Specific heat capacity of air (J/(kg ◦ C)) 2. Method and experimental cases
Greek symbols
2.1. Experimental set-up and measuring instruments
Door opening index (= tO /tT )
Air density (kg/m3 )
Fig. 1 gives the schematic diagram of the experimental system.
Increased percentage of the heat loss (%)
The tests were carried out in a climate chamber with dimensions of
3.0 m × 3.6 m × 2.6 m (Length × Width × Height), located in a large
Subscripts
laboratory, as shown in Fig. 1(a). The envelopes of the chamber
1 Actual situation
(including the roof, floor and side walls), with mean heat transfer
2 Ideal situation
coefficients of 0.9 W/(m2 ◦ C), were made of stainless steel plates
that were hollow and full of foaming polyurethane. The test cham-
ber originally had a side-hung door, but because the door’s opening
aircraft hangar buildings for cases with the entrance door opened and closing causes interference flow making it difficult to measure
are 9–17 ◦ C higher than that with the door closed when MV is used the amount of invading air, the door was replaced by a sliding door
for heating. This causes a poor thermal environment and as high (with a height and width of 1.5 m and 0.96 m, respectively) before
as a 40% increase in required heating energy. Although the heating the experiments were conducted. The door edges and door frame
energy utilization can be improved to some extent by adjusting the were sealed with rubber strips to ensure that the cold air invasion
supply condition or the positions of the supply and exhaust dif- pathway was only through the opened door.
fusers in MV [7], the problem of high heating energy consumption The chamber and laboratory, shown in Fig. 1, were used to
induced by thermal stratification cannot be solved fundamentally simulate the ‘indoor’ and ‘outdoor’ environments in winter, respec-
for a heated space with cold air invasion. tively. The whole experimental system comprised four modules,
Impinging jet ventilation (IJV), which combines the positive i.e., automatic control system, air handing unit (AHU), data record-
effects of the DV and MV systems, was proposed as a new ven- ing system and environmental simulation chamber. The supply air
tilation strategy [2,4] and has been studied for many years. In an parameters and the temperature in the large laboratory can be
IJV room, a high momentum supply jet is discharged downwards adjusted to the desired conditions through these modules.
Table 1
1512
A short summary of studies of IJV.
Beltaos and Rajaratnam Theoretical and experimental Air flow field of an impinging jet. • The flow field of the jet is composed of three regions.
(1973) [10] study
Gutmark et al. (1978) [11] Experimental study Turbulent structure of a • The turbulent properties (such as turbulent stresses, mean velocity and temporal derivatives) of
two-dimensional thermal impinging the jet change from their equilibrium levels near the impingement region.
jet.
Cooper et al. (1993) [12] Experimental study Turbulence model assessment. • The level of turbulence energy near the stagnation point computed by using k-ε eddy viscosity
models is higher than measured.
Kim (1993) [13] Experimental study Characteristics of flow and heat • The Nusselt number varies with the nozzle-to-plate distance.
transfer of an impinging jet.
• The heat transfer coefficients increase with the increase of Reynolds number.
Yoon et al. (1997) [14] Experimental study Behaviors of a two-dimensional • When the oblique angle is decreased, the stagnation point shifts to the minor flow region, and
oblique plate impinging jet. the positions of the stagnation point and maximum turbulent intensity are almost identical.
Karimipanah et al. (2000) Experimental and numerical study Local mean age of air, ventilation • IJV shows better velocity distribution in the occupied zone and higher ventilation efficiency
[15] efficiency in a cooling room by DV and compared to DV.
IJV.
Guerra et al. (2005) [16] Experimental study Near wall behavior of an impinging jet. • The level of the logarithmic portion of the velocity and temperature laws of the wall increases
with increasing the maximum jet velocity and decreasing the minimum temperature.
• IJV can provide better thermal comfort and IAQ, as well as consume less HVAC energy when
Fig. 1. Schematic diagram of the experimental system (1, IJV nozzle; 2, MV inlet).
The chamber was equipped with the IJV and MV systems, with rectional hotwire anemometer (HD103T.0, Delta OHM Inc., Italy),
Fig. 1(b) showing a 3-D perspective view of the test chamber. For Type-K thermocouple and CO2 transmitter (EE 85, E + E Elektronik,
the IJV system, the warm supply jet was introduced from a circular Austria). Point-0 and Point-8 were instrumented with Type-K ther-
duct and discharged at a height of 0.6 m above the floor. The duct mocouples to measure the temperature in the near wall regions.
with a diameter of 0.2 m was fixed at the middle of the east wall, as Table 2 summarizes the detailed parameters of the measuring
shown in Fig. 1(b) and (c). For the MV system, warm supply air was instruments. All the thermocouples were covered with aluminum
delivered through a double shutter (0.15 m × 0.2 m) at an angle of foil tape to eliminate radiation effects. The recording system and
15◦ from horizontal to the floor and the shutter was mounted on all measuring instruments were calibrated before the experiment.
the middle of the east wall at a height of 2.3 m above the floor (see
Fig. 1(b) and (d)). The exhaust device (0.2 m × 0.3 m) of the two 2.2. Measurement process and test results for determining the
systems was located at the center of the ceiling. cold air invasion rate
Generally, public spaces with the entrance door opened inter-
mittently are of all sizes (either small or large). For small spaces The method for determining the air change rate of a room pro-
(such as small stores and restaurants), the entrance door is usu- posed by Roulet and Foradini [32] was employed to measure the
ally a side-hung door and only partly opened (about 0.6 m) when cold air invasion rate through the opening door. This method cal-
people come in and out. In fact, the effective ventilation area culates the air change rate (ACE) as:
is usually smaller than the opened area during the air inva-
sion time because the human body obstructs the opening width, ACE = −lnC N /t (1)
and, briefly, it is assumed to be one-third of the size of the where t is the time elapsed since the start of CO2 decay, and CN is the
opening width, i.e., 0.2 m. For large spaces (e.g., airport termi- normalized CO2 concentration for each time, which is determined
nals, station halls, shopping malls, etc.), the entrance door is by:
usually an automatic sliding door, and the door is almost fully
opened when people come in and out. Take a large space building C(t) − Co
CN = (2)
(Height × Depth × Width = 10.0 m × 9.0 m × 12.0 m) for an exam- C(0) − Co
ple, and it is assumed that this building has an entrance door with a where C(0) is the CO2 concentration at the beginning of the decay
size of 1.2 m × 2.4 m (Width × Height). So the ratio of the entrance period, C(t) is the CO2 concentration at time t, and Co is the steady-
door’s area to the floor area is 0.027. According to the similitude law, state CO2 concentration.
for an equivalent situation the opening width of this experiment’s CO2 was used to conduct the test of cold air invasion rate since
chamber’s door should be 0.195 m due to the fact that the floor area it is easy to measure in the present study. The chamber’s door
of the chamber is 10.8 m2 and the height of the chamber’s door was opened and kept open with a width of 0.2 m before each test
is 1.5 m. Therefore, the chamber’s door with an opening width of run. The temperature and CO2 concentration in the large labora-
0.2 m was chosen as a representative for both situations (small and tory were always controlled at 12.0 ± 0.3 ◦ C and 1250 ± 50 ppm,
large spaces). Moreover, in order to obtain a similar amount of the respectively, by adjusting the operation and the supply air vol-
invading cold air per unit time for all experiments, the influences of ume of the air conditioning in the laboratory. When the experiment
the temperature difference between the indoor and outdoor air as began, the supply air system was first turned on to supply warm
well as the indoor temperature gradient (i.e., the effects of thermal air into the chamber. Meanwhile, the measuring instruments and
pressure) on the cold air invasion rate was reduced by increasing data recording system were also switched on to record the varia-
the wind pressure. A portable fan was used to blow against the tion of temperature, velocity and CO2 concentration in the chamber.
chamber’s door no matter whether the door was closed or opened. After the flow condition (velocity and temperature) in the cham-
The fan was put outside the chamber and the wind speed at the ber approached a steady state (both the measured temperature
position where the lateral axis of the fan intersects with the door and velocity for all measuring points did not vary with time), the
was about 0.6 m/s. temperature difference between the supply and indoor air To
The measuring poles were arranged at four different positions was calculated. If the value of To did not meet the experimen-
of the chamber. Seven measuring points (Point-1 to Point-7) were tal requirement, the fan frequency and the operating power of
set on each pole with same distance along the room height, and two the heating device in the AHU were adjusted till To met the
other measuring points (Point-0 and Point-8) were placed on the requirement. Then it began to inject CO2 into the chamber slowly
ceiling and the floor, which were on the extension line of the pole, from a CO2 cylinder (with an injection rate of about 0.2 m3 /h at
respectively. Fig. 2 gives the plan view of the four poles (denoted by normal atmospheric pressure) till the averaged CO2 concentration
‘×’) and the sketch of the measuring point height at each position. (calculated by the averaged value for all measuring points on the
Each measuring point on the pole was instrumented with omnidi- measuring poles) reached the value of 4350 ± 50 ppm in the cham-
1514 X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522
Fig. 2. Arrangements of the measuring poles and the sketch of the measuring point at each position.
Table 2
Detailed parameters of the measuring instruments.
Omnidirectional Air velocity Thermal sensor 0.05 ∼ 5.00 m/s 0.01 m/s ±2 fpm
hotwire anemometer (± 0.01 m/s)
Type-K thermocouple Air temperature Thermistor − 20 ∼ 80 ◦ C 0.1 ◦ C ±0.3 ◦ C
CO2 transmitter CO2 concentration Infrared absorption 0 ∼ 5000 ppm 0.1 ppm ±50 ppm
Table 3 The results shown in Fig. 3 indicate that the temperature and
Experimental cases for the determination of the cold air invasion rate.
CO2 concentration at Point-1 (the ceiling level) were higher than
Case No. Supply system Vs (m/s) Ts (◦ C) To (◦ C) those at Point-7 (the ground level), this is because the cold and fresh
1 IJV 1.5 38.2 9.5 outside air enters the chamber continuously, which flows down-
2 IJV 2.5 41.9 14.6 wards to the floor and then exerts significant cooling and dilution
3 MV 2.1 34.2 9.7 effects on the air in the vicinity of the floor. Fig. 3 also indicates that
4 MV 3.0 40.1 14.8 the room averaged CO2 concentration (the averaged value of the
data for all measuring points on the poles) decreased rapidly in the
early stage of decay and then slowly decreased to the steady-state
value.
Based on Eq. (2) and the test values of CO2 concentration in Fig. 3,
the values of lnCN at different times are calculated, with the results
shown in Fig. 4. Fig. 4(a) shows the variation curves of lnCN with
time t for I, II and III, where t is measured from the start of CO2
decay for each span, and Fig. 4(b) gives the variations of lnCN with
time t for one time span of CO2 decay for the four cases given in
Table 3.
It is seen from Fig. 4(a) that the three curves for lnCN varying
with t are quite similar and the slopes of them in the first 1.2 h are
Fig. 3. Measured curves of temperature and CO2 concentration in IJV (To = 9.5 ±
0.3 ◦ C).
almost the same, which implies good repeatability of the experi-
ment. According to the results in Fig. 4(b) and Eq. (1), it is known
that the air change rate ACE ranges from 5.0 to 5.5 ± 0.05 h−1 in
ber. Then the CO2 concentration in the chamber started to decay. both the IJV and MV rooms and the difference was less than 10%,
When the CO2 concentration in the chamber almost did not vary, suggesting that the effects of the thermal pressure caused by To
CO2 was injected into the chamber once again. The process of CO2 and indoor temperature gradient on the cold air invasion rate can
injection and decay for each experiment was repeated three times be ignored by enhancing the wind pressure effect (i.e., by the fan).
to evaluate the consistency and repeatability of the test. When the The volume of the chamber is 28.08 m3 and therefore, the volumet-
averaged CO2 concentration in the chamber approached the steady ric flow rate of the incoming cold air Gin is 0.041 ± 0.002 m3 /s. In the
state again after the last injection of CO2 , the air supply system of subsequent experiments with cold outside air intermittently invad-
the chamber was turned off. During the whole process, the temper- ing the heating room, the value of Gin is taken as the calculation
ature and CO2 concentration in the chamber were recorded every criterion of the invading cold air volume.
1 s. The averaged data for 1 min were used for the further analysis.
A total of four cases for both the IJV and MV systems were
conducted herein. Table 3 gives the details of the experimental con- 2.3. Experimental procedures and cases for measurements of cold
ditions of IJV and MV, in which Vs and Ts are the supply velocity and air intermittent invasion
temperature, respectively, and To is the temperature difference
between the indoor and outdoor air. The experiments with cold air intermittently invading the
Fig. 3 gives the test curves of the temperature T and CO2 con- heating room were run by using the following procedure. The air-
centration CC in IJV with To = 9.5 ± 0.3 ◦ C (i.e., case 1), where I, II conditioning system in the laboratory was turned on first to keep
and III represent three time spans of CO2 decay, respectively. the temperature inside it at a constant value of about 6.5 ± 0.3 ◦ C
X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522 1515
Fig. 4. Test results of the decay of CO2 concentrations in the IJV and MV rooms.
and no obvious air flow inside the laboratory before each test case. 2.5 ± 0.1 m/s and 37.5 ± 0.3 ◦ C, respectively. A total of eight experi-
Then the air supply system of the chamber was turned on to deliver ments were performed.
warm air into the chamber, and the fan frequency and operating
power of the heating device in the AHU were adjusted to achieve 2.3.2. Experimental cases – the effect of door opening duration on
the desired supply velocity and temperature, respectively, and the thermal environment
data recording system was turned on at the same time. When it In order to study the effect of door opening duration on the
started to heat the chamber, one investigator stood in the large lab- indoor thermal environment, the second set of experiments was
oratory (away from the door) to open and close the door by using conducted under a varying with different values of tO and a con-
a long bar connected to the doorknob, and another person held a stant tT of 320 s (i.e., the number of times to open the door is the
timer to record the time of door opening and closing. The chamber’s same but the duration of door opening is different in every 320s).
door was opened (with a width of 0.2 m) and closed in a similar pat- The indoor air temperature and velocity were measured with six
tern until the indoor thermal environment reached a steady state different values of (i.e., = 0/320, 20/320, 40/320, 80/320, 160/320
(the fluctuations of the temperature and velocity for all measuring and 240/320) for IJV and MV. In this set of experiments, the sup-
points tend to be stable), and maintained the steady-state condition ply temperature and velocity for IJV and MV were 45.0 ± 0.3 ◦ C
for about 1.5 h to 2.5 h to thoroughly equilibrate the indoor envi- and 1.5 ± 0.1 m/s, respectively, and one more supply velocity of
ronment. The velocity and temperature at each measuring point 2.5 ± 0.1 m/s was performed for MV. So a total of eighteen tests
were recorded every 1 s during the whole process. were done.
A total of three sets of experiments were carried out to investi-
gate the effects of frequency and duration of door opening (being 2.3.3. Experimental cases – the effect of supply parameter on
equivalent to the frequency and amount of cold air invasion, respec- thermal environment
tively) on the indoor thermal environment of IJV and MV, as well The higher the inlet velocity and the smaller the temperature
as to evaluate the effects of supply parameters on the temperature difference between the supply and indoor air, the more easily and
in the lower parts of the heated room with cold air invasion. quickly the warm supply jet can be mixed with room air, thus mit-
Some definitions are used in the subsequent discussions: igating the adverse effects of the invading cold air on the indoor
thermal environment. This is because the effect of inertia relative
(1) Period of door opening tT (s): defined as the duration between to buoyancy on the supply jet increases with the increase of supply
two adjacent starting points of door opening (including two velocity and the decrease of temperature difference of the supply
time spans, i.e., an opening span and a closing span); and indoor air. Sandberg and Etheridge [33] concluded that the ratio
(2) Door opening index : defined as tO /tT , where tO (s) is the cor- of the inertia to buoyancy force of the supply air is determined by
responding duration of door opening in tT . the thermal length of the supply jet or buoyancy jet length scale
(lm ), where lm is calculated by [33–36]:
Fig. 5. Time series of the air temperatures in the IJV and MV rooms at steady thermal state.
Table 4 experimental parameters for IJV and MV, respectively, where Tin ,t
Experimental parameters for the IJV heating system.
is the time-averaged temperature of the room.
Case No. (tO /tT ) Vs (m/s) Ts (◦ C) Tin ,t (◦ C) lm (m)
Fig. 6. Profiles of the mean amplitude of temperature fluctuation and time-averaged temperature of the four poles at different heights h for the same .
Fig. 7. Vertical profiles of the time-averaged temperature along the four poles for different in IJV (Vs = 1.5 ± 0.1 m/s, Ts = 45.0 ± 0.3 ◦ C).
the region far away from the supply inlet, because the spreading Figs. 7 and 8, respectively. Only the results for MV with the supply
distance of the warm air is constrained by the buoyancy effect, so velocity Vs of 2.5 ± 0.1 m/s are given herein.
the lower parts near the door (Pole-1) are the coldest (Figs. Fig. 5(a) Fig. 7(a) shows that the time-averaged temperatures in IJV are
and (c)). almost uniformly distributed along the room height when there is
Comparing Figs. 5(a)–(d), it can be observed that for the same no cold air entering the room. When tO is increased, see Fig. 7(b)
value of and supply parameter, the thermal stratification around to (f), the values of Tt at all measuring points are decreased and
the door (Pole-1) in IJV and MV are almost the same (see Fig. 5(a) an obvious increase in the vertical temperature gradient appears
and (c)), while the vertical temperature gradient near the supply gradually.
nozzle (Pole-4) in IJV is much less than that in MV and the temper- Fig. 7 also indicates that for the cases with short duration of
ature near the ground in the former is noticeably higher than that door opening (e.g., the cases of = 0/320, 20/320 and 40/320), the
in the latter (see Fig. 5(b) and (d)). Tt along Pole-4 (closes to the supply nozzle) is higher at the ground
Fig. 6(a) and (b) presents the mean amplitude of the temperature level and lower in the upper parts of the room, which is contrary to
fluctuation with time (A) and time-averaged temperature of the those along other three poles. With the increase of tO , the variation
four test poles (Ta,t ) at different heights h for the same in the IJV trend of Tt along Pole-4 gradually becomes similar to other three
and MV rooms, respectively. poles (Fig. 7(d)–(f)), i.e., the temperature is lower near the ground
Fig. 6 shows that the door opening frequency imposes the and higher at the ceiling level. This is mainly attributed to the fact
strongest effect on A in the lower zones of both IJV and MV. The that when tO is increased, the diffusion area of the incoming cold
values of A near the ground for the case with the smallest fre- air is expanded and the buoyancy effect on the warm supply air
quency (i.e., the case of = 40/640) in the two rooms are almost 3.5 is strengthened. This leads to the warm supply air rising upwards
times higher than those with the largest frequency (i.e., the case of to the ceiling before it reaches Pole-4, thus the temperature in the
= 5/80). Furthermore, Fig. 6 also shows that for the four different lower region of Pole-4 is no longer affected by the warm supply jet.
door opening frequencies, the value of A at the same height h varies The results in Fig. 8 show that there exists an evident thermal
obviously but the value of Ta,t remains almost unchanged. Thus, it stratification in the MV room, regardless of whether there is cold
can be concluded that the door opening frequency only influences outside air invading the room or not, and the vertical tempera-
the value of A but exerts no impact on Ta,t . ture gradient increases with the increase of tO . The temperature
distribution in the MV is similar to the results by Saïd [5], which
indicate that there exists two air layers, i.e., a warm air layer in
3.2. Effects of duration of door opening on the indoor thermal the upper part and a cold air layer in the lower part, in the hangar
environment bay area when MV is used for heating, and when cold air enters
into the hangar through the opened door, the temperature dif-
To investigate the effects of door opening duration (being equiv- ference between the ceiling and floor are increased by at least
alent to the amount of cold air invasion) on the time-averaged 9 ◦ C. Moreover, it is seen that when tO is increased, the unifor-
thermal and airflow fields, experiments were conducted under a mity of the temperature distribution along the horizontal direction
constant frequency, i.e., open the door once every 320 s (tT = 320), is decreased and the temperatures at the middle region of Pole-4
with the six different door opening indexes given in Section 2.3.2. become higher than those of other three poles, see Fig. 8(d)–(f).
The profiles of the time-averaged temperature (Tt ) along the four Additionally, the thermostat is the key component to achieve
poles for the six different values of in IJV and MV are shown in automatic control of HVAC systems, and the locations of the
1518 X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522
Fig. 8. Vertical profiles of the time-averaged temperature along the four poles for different in MV (Vs = 2.5 ± 0.1 m/s, Ts = 45.0 ± 0.3 ◦ C).
thermostats are particularly important in such a space with non- in both the IJV and MV rooms, which are in the acceptable range
uniform temperature distribution. It can be seen from Figs. 7 and 8 recommended by ISO 7730 [20].
that for both IJV and MV systems, although the temperature
changes obviously along the vertical direction, a uniform distribu-
tion forms along the horizontal direction except in the region near 3.3. Effects of supply parameters on the indoor thermal
the supply inlet (Pole-4), e.g., the temperatures on Pole-1 to Pole- environment
3 are almost the same at the same measuring height. Therefore, a
representative temperature can easily be obtained unless the ther- The above discussions indicate that when cold outside air
mostat is close to the inlet. Fig. 7 and Fig. 8 also indicate that the invades the heating room, the temperature in the occupied zone is
vertical influence range of the invading cold air in the IJV and MV greatly reduced and the vertical temperature gradient is increased.
are about to a height of 0.8 m and 1.3 m above the floor, respec- This leads to poor indoor thermal environment and increases the
tively, for different amounts of cold air invasion. Hence, when the heating energy consumption.
number of thermostats is limited, the thermostat can be placed at In order to investigate the effects of supply parameters on the
the height of 0.4 m in IJV and 0.6 m in MV, respectively. When more thermal environment in rooms with cold air invasion, the mean
thermostats are need for precise operating control, the thermostats time-averaged temperatures of the four poles (Ta,t ) at different
can be uniformly arranged at different heights in the occupied zone heights h in the IJV and MV rooms with different are shown in
for both the IJV and MV systems. Figs. 12 and 13, respectively. The time-averaged temperature in
Fig. 9 shows the floor-to-ceiling temperature difference (Tg ), the occupied zone, Toz ,t , remains constant (Toz ,t = 20.5 ± 0.3 ◦ C) for
which is determined by the difference of the mean time-averaged all of the tests (as listed in Tables 4 and 5), where the thermal length
temperature between Point-0 and Point-8 of the four poles, and the of the supply jet lm corresponds to the supply parameters.
time-averaged temperature of the room (Tin ,t ) for different in IJV It is found from Figs. 12 and 13 that Ta,t in IJV and MV show a
and MV. similar pattern, i.e., for a fixed door opening index , the larger the
It is seen from Fig. 9 that Tg increases with the increase of tO value of lm , the more uniform the distribution of Ta,t along the room
for both IJV and MV, and when tO is increased to a certain extent, height. This can be explained by the fact that the momentum of the
Tg no longer varies significantly. In addition, Tg in IJV is much supply jet increases as lm is increased (Eq. (3)), resulting in a better
less than that in MV and Tin ,t shows the opposite trend under the mixing between the supply and indoor air. In addition, it can also
condition of the same supply air parameters (Ts and Vs ) and , which be found from Figs. 12 and 13 that when the values of and lm in
suggests that IJV may be more energy efficient than MV. IJV are almost the same as those in MV, the vertical temperature
From Fig. 9 it can also be found that when Ts is fixed in MV, the gradient in the former is much less than that in the latter.
increase of Vs leads to a decrease in Tg and an increase in Tin ,t . Fig. 14 shows the variations of Tg and the time-averaged tem-
The reason is that the high momentum of the supply air weakens perature of the upper zone (h > 1.8 m) (Tuz ,t ) with lm for IJV and MV
the effect of buoyancy on the warm supply air, thus allowing it to with the same time-averaged occupied zone temperature (Toz ,t ).
be more easily distributed into the lower part of the room, so the Fig. 14(a) indicates that Tg decreases with the increase of lm
thermal stratification is reduced. and increases with increasing tO in both the IJV and MV rooms, but
Figs. 10 and 11 present the measured velocities (V) at different the value of Tg in the former is much less than that in the latter
measuring points of the four poles for the six in the IJV and MV when the value of tO and the value of lm in IJV and MV are similar.
rooms, respectively. The results in Fig. 14(b) show that for every lm and , when Toz ,t
Fig. 10 shows that the incoming cold air in IJV mainly influences is 20.5 ± 0.3 ◦ C, Tuz ,t in the IJV room is around 22.0 ± 0.6 ◦ C, only
the velocity in the lower parts of the room near the door (Pole- slightly higher than Toz ,t . Whereas in MV the values of Tuz ,t are
1) and supply inlet (Pole-4), with the former increased and the much greater than 20.5 ± 0.3 ◦ C, and the larger the value of tO or
latter decreased as tO increases. This is because the temperature the smaller the value of lm , the higher the value of Tuz ,t . It appears
difference between the supply and indoor air increases when tO is that MV would result in much more excess heat loss caused by the
increased, which causes the warm supply air to separate from the higher upper zone temperature when compared with IJV.
floor and rise to the ceiling earlier and earlier, thereby resulting in The increasing percentage of the heat loss of the room with an
a decrease in velocity around the nozzle (Pole-4). evident thermal stratification (i.e., actual situation) relative to that
For the MV system, it can be found from Fig. 11 that the incoming with a uniform indoor air temperature distribution (i.e., ideal sit-
cold air imposes a significant effect only on the velocity near the uation), , is defined in this paper to quantitatively determine the
ground in the vicinity of the door (Pole-1). With the increase of tO , excess heat loss due to thermal stratification, allowing for a com-
the velocity at the lower measuring point of Pole-1 is increased. parison of the heating energy consumption between the IJV and MV
This increase near the base of Pole-1 is similar to the results for IJV. systems. The expression for is given by:
It should be noted that the velocities above the floor except those
E1 − E2
in the region close to the door (Pole-1) do not exceed 0.25 ± 0.1 m/s = × 100% (6)
E2
X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522 1519
Fig. 9. Variations of the floor-to-ceiling temperature difference and the time-averaged temperature of the room with for IJV and MV.
Fig. 10. Measured velocities at different measuring points under different values of for IJV with Vs = 1.5 ± 0.1 m/s and Ts = 45.0 ± 0.3 ◦ C.
Fig. 11. Measured velocities at different measuring points under different values of for MV with Vs = 2.5 ± 0.1 m/s and Ts = 45.0 ± 0.3 ◦ C.
Fig. 12. Vertical profiles of the mean time-averaged temperature of the four poles in IJV with the same Toz ,t for different values of .
1520 X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522
Fig. 13. Vertical profiles of the mean time-averaged temperature of the four poles in MV with the same Toz ,t for different values of .
Fig. 14. Variations of Tg and Tuz ,t with lm for different values of at the same Toz ,t .
where E1 and E2 are the total heat loss of the actual and ideal However, it is observed from Fig. 15(b) that may be up to 44% for
rooms, respectively. The larger the value of , the more the required a small value of lm and a large value of tO and barely reduce to 10%
heating energy. when the supply air with a high value of lm is provided in the MV
The total heat loss of the heating room usually includes the heat room.
loss through the building envelope (i.e., surrounding walls, floor Consequently, it can be concluded that the improving effect
and ceiling) and the heat loss caused by cold air invasion, and its of the supply parameter on the indoor thermal environment and
expression is described as: heating energy consumption is much better in IJV than in MV.
Fig. 15. Variations of with lm for different values of in IJV and MV at the same Toz ,t .
Therefore, to get more information of the heating performance efficiency for heating spaces with cold air invasion, and the tem-
of IJV in large-height buildings of different sizes with various out- perature distribution in the occupied zone will be more uniform.
door climates, some other techniques, e.g., numerical simulation, The present study mainly focused on investigating the temper-
full-scale experimental system, field measurement, etc., can be ature distribution and energy consumption in an IJV heating room
employed to evaluate the indoor thermal environment. with cold air invasion intermittently and compared these with MV.
On one hand, the results can be used to provide a theoretical basis
4. Conclusion for the application and optimization of IJV. On the other hand,
the designers can optimize the air supply system according to the
During the winter heating season, masses of cold outside results given in Section 3.3, i.e., the unnecessary energy consump-
air invade the heating room through the intermittent opened tion can be reduced by increasing the thermal length of the supply
entrance door due to occupants coming in and out frequently, jet appropriately.
which decreases the temperature in the lower parts of the room
and strengthens the indoor thermal stratification. Although MV
Acknowledgements
is widely used for space heating, it consumes a large amount of
energy to meet the requirement of thermal comfort. IJV has excel-
This work was supported by the National Natural Science
lent energy conservation potential because it supplies a warm jet
Foundation of China (Grant Nos. 51278094 and 51478098), the
directly into the occupied zone and weakens the disturbance of the
Innovation Foundation of Shanghai Education Commission, China
incoming cold outside air on the indoor air temperature.
(Grant No. 13ZZ054) and the Chinese Universities Scientific Fund
In the present study, the heating performance of IJV and MV
(Grant No. CUSF-DH-d-15D311311). The authors would like to
are compared by conducting systematic experiments in a climate
thank Dr. D. Gottfried for his helpful discussions and recommenda-
chamber with cold outside air invading the heating space. The
tions.
intrusion of cold outside air is simulated by opening the door of
the chamber intermittently, and both the frequency and duration
of the door opening are considered, which are corresponding to the References
frequency and amount of cold air invasion, respectively.
The measured results indicate that the air temperature in the [1] H.B. Awbi, Ventilation of Buildings, Taylor and Francis, 2003.
[2] H.J. Chen, B. Moshfegh, M. Cehlin, Numerical investigation of the flow
lower parts of the room fluctuates with the opening and closing behavior of an isothermal impinging jet in a room, Build. Environ. 49 (2012)
of the door. When the duration of the door opening is the same, 154–166.
the frequency of the door opening only influences the amplitude [3] H.J. Chen, B. Moshfegh, M. Cehlin, Investigation on the flow and thermal
behavior of impinging jet ventilation systems in an office with different heat
of temperature fluctuation with time and has no effect on the loads, Build. Environ. 59 (2013) 127–144.
time-averaged temperature for both the IJV and MV systems. The [4] T. Karimipanah, H.B. Awbi, Theoretical and experimental investigation of
temperatures in the occupied zone in IJV and MV are decreased by impinging jet ventilation and comparison with wall displacement ventilation,
Build. Environ. 37 (2002) 1329–1342.
at least 2.0 ◦ C when cold air invades the room. With the increase of
[5] M.N.A. Saïd, R.A. MacDonald, G.C. Durrant, Measurement of thermal
the duration of door opening, the decrease of temperature is fur- stratification in large single-cell buildings, Energy Build. 24 (1996) 105–115.
ther increased and the floor-to-ceiling temperature difference in [6] X. Yuan, Q. Chen, L. Glicksman, A critical review of displacement ventilation,
ASHRAE Trans. 104 (1) (1998) 78–90.
IJV and MV are increased but the former is always much less than
[7] M. Krajčík, A. Simone, B.W. Olesen, Air distribution and ventilation
60% of the latter. The results also show that when compared with effectiveness in an occupied room heated by warm air, Energy Build. 55
the ideal situation (i.e., the indoor air temperature distributes uni- (2012) 94–101.
formly), the increasing rate of the heat loss of the room with an [8] X. Ye, H. Zhu, Y. Kang, K. Zhong, Heating energy consumption of impinging jet
ventilation and mixing ventilation in large-height spaces: a comparison
evident thermal stratification for MV is almost 2.4 ∼ 4 times higher study, Energy Build. 130 (2016) 697–708.
than that for IJV. For most IJV cases, the increasing rates are within [9] H.J. Chen, B. Moshfegh, M. Cehlin, Computational investigation on the factors
10%, while this increasing rate can be up to 44% and barely reduce influencing thermal comfort for impinging jet ventilation, Build. Environ. 66
(2013) 29–41.
to less than 10% even though the supply jet with large buoyant [10] S. Beltaos, N. Rajaratnam, Plane turbulent impinging jets, J. Hydraul. Res. 11
jet length scale is present for MV. Therefore, the adverse effects (1973) 29–59.
caused by the invading cold air on the indoor thermal environment [11] E. Gutmark, M. Wolfshtein, I. Wygnanski, The plane turbulent impinging jet,
J.Fluid Mech. 88 (1978) 737–756.
and heating energy consumption can be weakened in IJV by chang- [12] D. Cooper, D. Jackson, B.E. Launder, G.X. Liao, Impinging jet studies for
ing the supply parameters, but it does not work well in MV. It can turbulence model assessment—I. Flow-field experiments, Int. J. Heat Mass
be concluded that compared with MV, IJV will have higher energy Transfer 36 (1993) 2675–2684.
1522 X. Ye et al. / Energy and Buildings 158 (2018) 1510–1522
[13] K.S. Kim, An experimental study on the flow and heat transfer characteristics [26] B. Zuo, K. Zhong, Y. Kang, An experimental study on particle resuspension in a
of an impinging jet, J. Mech. Sci. Technol. 7 (1993) 258–271. room with impinging jet ventilation, Build. Environ. 89 (2015) 48–58.
[14] S.H. Yoon, M.K. Kim, D.H. Lee, Turbulent flow and heat transfer characteristics [27] M. Fénot, E. Dorignac, Heat transfer and flow structure of an impinging jet
of a two-dimensional oblique plate impinging jet, J. Mech. Sci. Technol. 11 with upstream flow, Int. J. Ther. Sci. 109 (2016) 386–400.
(1997) 476–483. [28] X.T. Trinh, M. Fénot, E. Dorignac, The effect of nozzle geometry on local
[15] T. Karimipanah, M. Sandberg, H.B. Awbi, A comparative study of different air convective heat transfer to unconfined impinging air jets, Exp. Therm. Fluid
distribution systems in a classroom, Reading, UK, in: Proceedings of the Sci. 70 (2016) 1–16.
Roomvent, 2, 2000, pp. 1013–1018. [29] Ş. Simionescu, N. Tǎnase, D. Broboanǎ, C. Bǎlan, Impinging air jets on flat
[16] D.R.S. Guerra, J. Su, A.P.S. Freire, The near wall behavior of an impinging jet, surfaces at low Reynolds numbers, Energy Procedia 112 (2017) 194–203.
Int. J. Heat Mass Transfer 48 (2005) 2829–2840. [30] T. Kobayashi, K. Sugita, N. Umemiya, T. Kishimoto, M. Sanberg, Numerical
[17] J. Varodompun, M. Navvab, HVAC ventilation strategies: the contribution for investigation and accuracy verification of indoor environment for an
thermal comfort, energy efficiency, and indoor air quality, J. Green Build. 2 impinging jet ventilated room using computational fluid dynamics, Build.
(2007) 131–150. Environ. 115 (2017) 251–268.
[18] J. Varodompun, Architectural and HVAC Applications of Impinging Jet [31] X. Ye, Y. Kang, B. Zuo, K. Zhong, Study of factors affecting warm air spreading
Ventilation Using Full Scale and CFD Simulation, University of Michigan, 2008 distance in imping jet ventilation rooms using multiple regression analysis,
(Ph.D Thesis). Build. Environ. 120 (2017) 1–12.
[19] Z. Xu, H. Hangan, Scale, boundary and inlet condition effects on impinging [32] C.A. Roulet, F. Foradini, Simple and cheap air change rate measurement using
jets, J. Wind Eng. Ind. Aerod. 96 (2008) 2383–2402. CO2 concentration decays, Int. J. Vent. 1 (2002) 39–44.
[20] ISO, Ergonomics of the Thermal Environment – Analytical Determination and [33] D.W. Etheridge, M. Sandberg, Building ventilation: theory and measurement,
Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Chichester N.Y. Wiley lc 48 (1996) 223–232.
Indices and Local Thermal Comfort Criteria, ISO 7730, Geneva, 2005. [34] M.P. Wan, C.Y. Chao, Numerical and experimental study of velocity and
[21] ASHRAE, Standard 55–2010, Thermal Environmental Conditions for Human temperature characteristics in a ventilated enclosure with underfloor
Occupancy, ASHRAE, Atlanta, USA, 2010. ventilation systems, Indoor Air 15 (2005) 342–355.
[22] S. Yao, Y. Guo, N. Jiang, J. Liu, Experimental investigation of the flow behavior [35] T. Arghand, T. Karimipanah, H.B. Awbi, M. Cehlin, U. Larsson, E. Linden, An
of an isothermal impinging jet in a closed cabin, Build. Environ. 84 (2014) experimental investigation of the flow and comfort parameters for
238–250. under-floor, confluent jets and mixing ventilation systems in an open-plan
[23] S. Yao, Y. Guo, N. Jiang, J. Liu, An experimental study of a turbulent jet office, Build. Environ. 92 (2015) 48–60.
impinging on a flat surface, Int. J. Heat Mass Transfer 83 (2015) 820–832. [36] X. Xie, Z. Huang, J. Wang, Z. Xie, Thermal effects on vehicle emission
[24] M. Fénot, E. Dorignac, G. Lalizel, Heat transfer and flow structure of a dispersion in an urban street canyon, Transp. Res. Part D 10 (2005) 197–212.
multichannel impinging jet, Int. J. Ther. Sci. 90 (2015) 323–338.
[25] H.J. Chen, S. Janbakhsh, U. Larsson, B. Moshfegh, Numerical investigatipn of
ventilation performance of different air supply devices in an office
environment, Build. Environ. 90 (2015) 37–50.