Professional Documents
Culture Documents
a
340
Voltage 335
(V) 330
1500
Current
(A) 1000
1000
kvar 500
d=3s
b
350
Voltage
(V) 340
1250
Current 750
(A)
500
kvar 0
d = 1.5 s
∆V ∆V
∆V
VS VS
VS Reactive VL
VL VL Welder
compensator
With Without
Fig. 18: Reduction in voltage drop obtained using a real time reactive compensator.
Solutions
After analysing equipotentiality and earthing of L L
the power system, followed by verification of N N
the installation of lightning conductors and
checking of the values of the earth electrodes,
the decision was taken to install surge
arresters. PF8 PF8
Secondary Secondary
Surge arresters were installed at the head of the distribution board distribution board
installation (main LV distribution board) and in Building 1 Building 1
cascade in each manufacturing building (see
fig. 19). As the neutral point connection was Fig. 19: Installation diagram for several surge arresters
TNC, protection would only be provided in in cascade.
common mode (between phases and PEN).
In conformity with guide UTE C-15443 regarding
operation in the presence of lightning
conductors, the characteristics of the
Merlin Gerin PF65 and PF8 surge arresters (see
fig. 20) are as follows:
c At the head of the installation
In = 20 kA – Imax = 65 kA – Up = 2 kV
PF65
c In cascade (at least 10 m apart)
In = 2 kA – Imax = 8 kA – Up = 1.5 kV
In cascade, good protection is provided for the
secondary distribution boards (offices and
security post).
As the neutral point connection was converted to
TNS, protection had to be provided in common
mode (between phase and PE) and differential PF8
mode (between phases and neutral). The Fig. 20: Low voltage surge arresters (Merlin Gerin
disconnection devices in this case are circuit PF65 and PF8).
breakers with a breaking capacity of 22 kA.