Professional Documents
Culture Documents
WYE-WYE
CONNECTION
(Three-Phase Transformer)
• Large third harmonic voltages would appear in both primary and secondary windings without the
neutral tie. This may lead to the insulation failures.
• This connection considerably generates interference with communication lines and hence with this
connection configuration, telephone lines cannot be run in parallel.
• Due to these disadvantages, the star-star connection is rarely used and not employed in practice.
TRANSFORMER WYE-WYE CONNECTION
The voltage between any line of the three-phase transformer is called the “line voltage”, VL, while the voltage
between any line and the neutral point of a star connected transformer is called the “phase voltage”, VP. This
phase voltage between the neutral point and any one of the line connections is 1/√3 × VL of the line voltage.
Then above, the primary side phase voltage, VP is given as.
1 1
𝑉𝑝 = × 𝑉𝐿 = × 100 = 57.7 𝑉𝑜𝑙𝑡𝑠
3 3
The secondary current in each phase of a star-connected group of transformers is the same as that for the line current of
the supply, then IL = IS.
TRANSFORMER WYE-WYE CONNECTION
Three-phase Voltage and Current Characteristics
Wye(Star) 𝑉𝑝 = 𝑉𝐿 ÷ 3 𝑉𝐿 = 3 × 𝑉𝑝 𝐼𝑝 = 𝐼𝐿 𝐼𝐿 = 𝐼𝑃
Where: VL = Line Voltage
VP = Phase Voltage
IL = Line Current
IP = Phase Current
This type has both star windings on the primary and secondary sides. Line voltages on each side are √3 times the voltage
of a single phase. The main advantage of a star-star connection is the access to the neutral terminal on both sides of the
transformer which can be grounded if desired. By connecting the star neutral to ground, distortion to the waveform is
eliminated. Without grounding, this configuration‘s operation is satisfactory only if the loads on all the three phases are
balanced.
When the primary and secondary have different types of winding connections, star or delta, the overall turns ratio of the
transformer becomes more complicated. If a three-phase transformer is connected as delta-delta ( Dd ) or star-star ( Yy )
then the transformer could potentially have a 1:1 turns ratio. That is the input and output voltages for the windings are the
same
TRANSFORMER WYE-WYE CONNECTION
Three-phase Line Voltage and Current
𝐼𝐿
Wye-Wye (Star-Star) 𝑉𝐿 = n𝑉𝐿 𝐼𝐿 =
𝑛
Where: n equals the transformers “turns ratio” (T.R.) of the number of secondary
windings NS, divided by the number of primary windings NP.
( NS/NP ) and VL is the line-to-line voltage with VP being the phase-to-neutral
voltage.
Handle Heavy Load
FACTORS OF Y-Y CONNECTION AND ITS Due to star connection, phase current is same as line current. Hence
windings have to carry high currents. This makes cross section of the
EFFECTS IN ITS LOAD windings high. Thus the windings are mechanically strong and windings
can bear heavy loads and short circuit current.
(ADVANTAGES)
Required Less Insulation Level
If the neutral end of a Y-connected winding is grounded, then there is an
opportunity to use reduced levels of insulation at the neutral end of the
winding. A winding that is connected across the phases requires full
insulation throughout the winding.
the measured line-to-neutral voltages are not 57.7% of the system phase-to-phase voltage at no load but are about
68% and diminish very rapidly as the bank is loaded.
The effective values of voltages at different frequencies combine by taking the square root of the sum of the voltages
squared. With sinusoidal phase-to-phase voltage, the third-harmonic component of the phase-to-neutral voltage is
about 60%.
Delta-Star Connection
On the primary side, the line and phase voltages are the same, while on the secondary side, the line voltage is
equal to the phase voltage multiplied by √3. Thus, for a 1:1 turns ratio, the secondary line will provide an
increased voltage by a factor of √3. Delta-star transformers are used for step-up applications. Another
application of this type is distribution systems. Since the secondary side has a neutral, it can also serve as a
single-phase power supply aside from supplying the full three-phase.
Like the star-delta, by having different windings of the primary and secondary sides, the resulting electricity is
out of phase.
Delta-Delta Connection
In this configuration, the line-to-line voltages on both the primary and secondary sides are equal to the phase
voltage. The main advantage of this type is that even under unbalanced loads, the three-phase voltages
remain equal. Also, since both sides have the same type of windings, there is no phase shift between them.
Sources:
https://www.electronics-tutorials.ws/transformer/three-phase-transformer.html
https://www.electronicshub.org/three-phase-transformer/
https://www.iqsdirectory.com/articles/transformer/three-phase-
transformer.html#:~:text=Three%2Dphase%20transformers%20are%20a,delta%2C%20and%20delta%2Dstar.
https://electrical-engineering-portal.com/transformer-connection-star-star