You are on page 1of 3

‫مستشفى الزينية‬

‫مقايسة أعمال التكييف‬

Top Engineering Services

‫وحدة هو‬

Egypt

Bill Of Quantities
HVAC Works

April 2017

Page 1 of 3
‫مشروع تحويل مستشفيات التكامل‬
‫إلى مستشفيات نسا ووالدة‬ Ministry of Health

‫أقسام النسا والوالدة والحضانات وإستقبال نسا بهو‬

Ministry Of Health
‫مقايسة أعمال تكييف الهواء‬
NOTES:
1-The contractor should submit the shop drawings before installation for approval.
2-The contractor should submit the As Built drawings.
Total Unit Qty. Unit Description Item
‫الحلفاية‬ ‫هو‬
LE. LE.
SPLIT UNITS ( HI WALL): 1
Supplying , installing & commissioning of HI WALL split air conditioning unit,
c/w hermatic compressor, condenser coil copper tube with aluminum fins,
condenser fan and motor, expansion device, charging valves and controls,
evaporator unit , remote control switch, overloads, controls, wirring contactors
, refrigerant charge, refrigerant piping, hangers, supports,
All civil and builder work in connection with HVAC works. and all necessary accessories
as per specifications and drawings, with the following capacities @105° F ambient temp. :-
No. BTU/hr
16243.5 8,122 2 0 2 NO Hi wall -01 12,000 1.1
101639.175 9,240 11 9 2 NO Hi wall -02 18,000 1.2
24990 12,495 2 0 2 NO Hi wall -03 24,000 1.3

CONDENSING UNIT: 2
Air-cooled condensing unit at saturated suction temperature of 42°F, ambient
temperature 110°F using R22, complete with Air-cooled condenser, screw
compressor(s), microprocessor controller,dedicated refrigerant circuit for each
compressor, low noise fans, bird screen, sight glass ,filter,drier controls
and all other necessary accessories, all in a neat workmanlike manner :-
DXU Cooling @ Temp
No. TR F

68212.5 68,213 1 1 NO DX-01 7 110


138975 69,488 2 2 NO DX-01,02 8 110 2.1
96900 96,900 1 1 NO DX-02 11 110 2.3

AIR HANDLING UNITS: 3


Supply and Install Air Handling Units according to specification,schedules,AHU arrangement,
and drawings complete with DX cooling coils, fans, aluminum foil pre filter, bag filter , sand
trap and supply plenum as per equpment table and all standard accessories. Item including
base, duct connection, hookup valves temp,pressure gauges and air vent,piping connection
, … etc., testing, startup and commissioning of the units :-
AHU Cooling SUPPLY AIR
No. TR CFM
74587.5 74,588 1 1 NO A.H.U-01 7 1075 3.2
75862.5 75,863 1 1 NO A.H.U-01 8 1200 (for 31 m2) 3.1
86062.5 86,063 1 1 NO A.H.U-02 8 1200 with HEPA Filter ( for 31 m2) 3.2
127181.25 127,181 1 1 NO A.H.U-02 11 1670 with HEPA Filter ( for 45 m2) 3.3

EXHAUST AIR FAN: 4


WALL MOUNTED FANS 4.1
Supplying , installing and commissioning of axial wall mounted , direct drive, exhaust fan c/w
automatic shutters, All civil and builder work in connection with the fans ………etc , according
to P.T.S & P.D and as herein specified:
FAN EXHAUST AIR
No. CFM
22491 1,250 18 7 11 NO WM-01 100 0.1
6247.5 1,250 5 5 NO WM-02 150 0.1

CENTRIFUGAL EXHAUST AIR FANS 4.2


Supplying, installing, & commisioning of centrifugal exhaust (DIDW) air fans, c/w casing,
gravity shutter, and bird screen at discharge side, hangers, supports, canvass duct
connections, electrical power and control cables connection, and all necessary accessories
as per the specifications, drawings, and according to P.T.S & P.D and as herein specified:
FAN EXHAUST AIR ESP
No. CFM in.wg.
11602.5 11,603 1 1 NO EX.F-01 915 0.4
23587.5 11,794 2 2 NO EX.F-01 1020 0.5
12112.5 12,113 1 1 NO EX.F-02 1420 0.6

AXIAL INLINE FANS 4.3


Supplying , installing and commissioning of axial inline, exhaust fan c/w automatic shutters, All
civil and builder work in connection with the fans ………etc , according to P.T.S & P.D and as
herein specified:
FAN EXHAUST AIR
No. CFM ESP
2231.25 2,231 1 1 NO AX.I-01 135 0.2
3187.5 3,188 1 1 NO AX.I-01 300 0.1
6387.75 3,194 2 2 NO AX.I-02 320 0.2

AIR OUTLETS : 5
Supplying, installing, & commisioning of supply, exhaust and returm air outlets diffusers /
grills,disc valves ....etc, manufactured from electrostically painted aluminum sections … c/w
all necessary accessories for proper installation and operation as per drawings and
specifications confirming the requiremnets of ASHRAE & SMACNA
SUPPLY CEILING DIFFUSER: 5.1
4998 500 10 4 6 NO S.C.D 24''X24''
4060.875 406 10 10 NO EX.C.D 24''X24''
2436.525 406 6 6 NO R.C.D 24''X24''
24000.6 3,000 8 4 4 NO PERFORATED SUPPLY CEILING DIFFUSER with HEPA FILTER 24''X24'' 5.2

Page 2 of 3
‫مشروع تحويل مستشفيات التكامل‬
‫إلى مستشفيات نسا ووالدة‬ Ministry of Health

‫أقسام النسا والوالدة والحضانات وإستقبال نسا بهو‬

Ministry Of Health
‫مقايسة أعمال تكييف الهواء‬
NOTES:
1-The contractor should submit the shop drawings before installation for approval.
2-The contractor should submit the As Built drawings.
SHEET METAL DUCT WORK: 6
Supplying, Installing, and commisioning of sheet metal duct work for supply, return,exhuast
and fresh air ducts, fabricated from galvanized steel sheets, c\w hangers
, supports, sealant, canvass joints, volume dampers, fire dampers,installing flexible duct
, All civil and builder work in connection with the duct work , and all necessary accessories
100272.375 33,424 3 1 2 TON for proper installation and operation as per the drawings and specifications confirming the
requirements of ASHRAE & SMACNA.

DUCT THERMAL INSULATION: 7


Supplying, Installing, and commisioning of thermal insulation for supply and return air ducts
manufactured from fiberglass with aluminum foil, 1'' thickness and 24 kg\m3 density for indoor
ducts and 2'' thickness for outdoor duct proteted with 0.5mm aluminium cladding for proper
installation and operation as per drawings and specifications, c\w all necessary confirming the
requirements of ASHRAE & SMACNA
13049.625 57 230 80 150 M2 1" thickness 24 kg/m3 7.1
12954 81 160 60 100 M2 2" thickness 24 kg/m3 7.2
8976 112 80 30 50 M2 0.5mm aluminium cladding for outdoor duct 7.3

MOTOR CONTROL CENTER: 8


Supplying,Installing,and commisioning of all motor control centers for serving HVAC equipments
,Condensing units , AHU and Dryers. c\w steel enclosure IP54 for exposedpanels,main isolation
switches,push buttons, indication lamps,MCCB, relays,overloads, interlockings,contactors,wirring
,gands,voltage, ampere measuring devices,electrical cables from motor control centers to HVAC
equipment all necessary accessories asper specifications and drawings.
108375 54,188 2 1 1 No. MCC-01

1177624.425 TOTAL

Page 3 of 3