You are on page 1of 3

F-DD-05

TECHNICAL SPECIFICATION
UNIT QTY - 1 NO

Fan CFM
36000
SPECIAL INSTRUCTIONS ITEM BY CUSTOMER
1- MOTOR WILL HAVE IE-2 1. NIL
2- LIGHT , LIMIT SWITCH , WIRE GUARD & VIEW GLASS WILL BE PROVIDED IN FAN SECTION ONLY.
3- WEATHER PROOF CANOPY OF G.I WILL BE PROVIDED.

Outer Skin Inner Skin Panel Thk Insulation Profile Frame Work
0.6 PRE COATED GI 0.6 PLAIN GI 25±2MM 40±2KG/M³ CFC FREE PUF AL HOLLOW PROFILE Aluminium
Unit Colour Panel const. Unit Base Suspension arrangment Type of unit
ORANGE DOUBLE SKIN G.S.S NA FLOOR MOUNTED

Supply Air Fan Static Pressure-mmwg r.p.m Outlet Velocity(M/S) Fan Discharge Fan Make
BACKWARD-1000 100 846 10.6 TH KRUGER/NICOTRA
Motor Kw Pole Motor RPM Frame Motor Mounting Motor Make
ABB/
30 4 1470 200 180-200 BB/CROMPTON/HAVELLS/MARA
Motor Pulley Fan Pulley Belt Size Isolator-Model/Qty
204X4SPB 355X4SPB 129SPB# 4 NOS STANDARD
Motor Phase 3 PH
Cooling Coil 1NO
FH FL RD FPI Area (Sqft.) Tube Size(OD)

Heating Coil NO
FH FL RD FPI Area (Sqft.) Tube Size(OD)

Coil Tube Material Fin Material Header Material

Air Filter Type Flange/ Box Qty Size eff. EU

Air Filter Type Flange/ Box Qty Size eff. EU

Air Filter Type Flange/ Box Qty Size eff. EU

Unit Condition - Assembled SKD


Packing- crate wooden Pallet Polythene Flexible conn.
CONSULTANT:- FIRE RETARDENT
CLIENT PROJECT MODEL
M/S.BLUE STAE LIMITED HILTON HOTLE PROJECT AT
ZDFS-360
(BANGALORE) BANGALORE
Revision Description Rev Date DRG. NO. DRN. BY DATED
A ZAL-21738-1 POONAM 16.08.2021
B Appd by ZECO AIRCON LIMITED
C
F-DD-04 2400
2350
PLAN
REV. DESCRIPTION DATE REV. BY

2100

2180
80
CLIENT:-
-M/S. BLUE STAR LIMITED (BANGALORE)
SECTION
PROJECT:-
-HILTON HOTEL PROJECT AT BANGALORE.
NOTE:- GI. DAMPER WIDTH> 1000 MM, AL. DAMPER WIDTH> 1200 MM, WILL BE OPERATED FROM BOTH SIDES EXCEPT OUTLET
DAMPER (IF DAMPER IN ZECO SCOPE). AIR VOLUME - 36000 CFM
KINDLY TICK THE FOLLOWING WHILE APPROVING UNIT DISPATCH CONDITION UNIT QUANTITY - 1 No.
THE DRAWING (FACING FROM FILTER SIDE)
ASSEMBLED ZECO AIRCON LIMITED
# O1 - O5 OLD INDUSTRIAL AREA, BAHADURGARH PH # 01276-244650,
1) MOTOR LOCATION:- RHS LHS SEMI KNOCK DOWN 244651, 244652, 244653 FAX # 01276-244568 EMAIL #
design@zecoaircon.com
COMPLETE KNOCK DOWN DRG. NO. DRN. BY CHKD. BY APPD. BY DATE SCALE
2) FAN DISCHARGE:- ALL UNIT WILL BE SUPPLIED ZAL-21738-01 POONAM A.K. SHARMA S.K. BAJWA 16-08-21 NTS
IN ASSEMBLED CONDITION
ALL DIMENSION ARE IN MM UNLESS, OTHERWISE SPECIFIED.
DULY FACTORY RUN TESTED. MAX. TOLERANCES ON OVERALL DIMENSIONS - ± 3 MM.
Date 16-08-2021 Kruger Ventilation Industries Pte Ltd
Company - No. 17 Tuas Avenue 10
Attention - Singapore 639141
Project -
Reference Tel: +65 6861 1577 Fax: +65 6861 3577
Email: mktg@krugerasia.com

Fan Selection
Fan Type
Unit BDB1000/TM (I)
Operating Conditions Ducted
Air Volume 36,000 cfm
Static Pressure 100 mmwg
Velocity Pressure 6.23 mmwg
Total Pressure 106 mmwg
Outlet Velocity 10.60 m/s
Fan Total Efficiency 82.6 %
Fan Static Efficiency 77.8 %
Fan Speed 874 rpm
Air Temperature 20 °C
Altitude 921 m
Fan Absorbed Power 21.4 kW
Motor Selection
Recommended Motor D225M (30.0 kW)
Motor Speed 950 rpm
Service Factor 0%
Operating Limits
Max. Absorbed Power 35.00 kW
Max. Fan Speed 1000 rpm
Temperature (Min-Max) -20° to 100°C

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 92 95 98 92 86 81 77 74 101 dB
Lwi(A) 66 79 90 89 86 82 78 73 94 dB(A)
Lpi(A) 59 72 83 82 79 75 71 66 87 dB(A)
* Sound data is for the inlet side * Sound Pressure Level 1m, Room Conditions

0DL A B C D E F F1 G H J K L M P R t t1 UxS w z
70 1810 1540 1066 1266 1266 500 200 656 1450 1316 1366 1724 179 90 9 20 12 17x22 110 74.5

Version: 1.19.12.103 (Database: 33.7) (CLT) Date: 16-08-2021 Time: 17:10:16