Professional Documents
Culture Documents
UNIFORMLY L O A D E D , COLUMN-SUPPORTED
INTERIOR SLAB P A N E L S
K. J. H i n d s o n
White-Young and Partners, U.K.
A . W. Chronowicz
Senior Lecturer, Department of Civil Engineering, Leeds University, U.K.
INTRODUCTION
The purpose of this paper, therefore, is to fill some of the gaps left by previous
investigations.
The two panels shown in Figure 1 are solved for the yield-line mechanisms
illustrated in Figures 3, 4 and 5; the solutions obtained are also applicable to
the affine panels shown in Figure 2(b). The influence of the strength of the
beams, and the size and shape of the columns, upon the moments of resistance
required to resist the various modes, and their effects in changing the critical
failure mechanism (that which gives the lowest failure load) are revealed.
The influence of the finite width of the beams in modifying the line-beam solutions,
as illustrated in Figure 6, and in adjusting the trends disclosed by them, is
discussed; as is the suitability of using the line-beam solutions to design
practical structures.
160
Yield Line Study of Interior Slab Panels 161
4 ^ — i
Μμ min
m (Bottom Steel)
Mu m
Mb
2 ,
1
! «
J ;
ad
!I!
ι I ι
2
a Mu aL
aML
ML Mb
(a) Rectangular Panel w i t h Eliptical Columns (b) Rectangular Panel with Rectangular Columns
r I
Ι Π τ
(a) Fan Around Circular Column (b) Fan Around Square Column
NOTATION
CIRCULAR COLUMNS
If it is assumed that fans of the type shown in Figure 3(a) form around all of the
columns which appear in Figure 1(a), and the centre of the panel undergoes unit
deflection, the following expressions for the work done by the load and the work
absorbed in the yield-lines are obtained:
W.D, q(L
2
- Trr )
2
+ q%(wc + 2π Γ) (r - |).V (~T1~) 3
(1)
Equating expressions (1) and (2) and introducing the parameter K, = (Mb + M £ ) /
(m + m*)L, gives:
2 2 3 3
r™ * «ι ϊ ,,24L r - 12L c - 8 π Γ + ttc ,
(m + m = ( } ) ( 3
'3 ^ 48π Γ + 96KL
1 1
When (m + m ) is a maximum, 3(m + m )/8r = 0. Thus from equation (3) the following
expression for the critical value of r (that which gives the maximum value of
1
(m + m ) ) is obtained:
2 3 2 2 3 2 3
16ir r + 487rKLr + t t c - 12ttL c - 48KL = 0 (but r <0.5L) (4)
3 3
(m + m') = 24(r/L) - 12(c/L) - 8ir(r/L) + tt(c/L)
(5)
^ L2 48Tr(r/L) + 96K
Yield Line Study of Interior Slab Panels 163
2 3 2 2 3
and 167T (r/L) + 48TrK(r/L) + tt (c/L) - 1 2 t t ( c / L ) - 48K = 0 (6)
Equations (5) and (6) can be used, together, to get solutions to the fan problem.
Curves given by these two expressions can be seen in Figures 7 to 11. The
variation of the critical fan radius with Κ and c/L, as given by equation (6), is
illustrated in Figure 12.
1 1
Simultaneous Failure Mode
This yield-line pattern,which is shown in Figure 4(a), has been called the
'simultaneous' mode since it is only kinematically possible if failure occurs in
both directions at the same time (whereas, in contrast, this is not necessary for
the yield-line mechanism shown in Figure 4(b)). The mechanisms shown in Figure
4(a) and (b) have been given the generic name of structural modes since they
involve both slab and beams and extend over the full width of the structure.
Assuming unit central deflection of the panel shown in Figure 4(a), the following
expressions are obtained:
2
W.D. = L
4 q ( t ( 2 L - 3c//2) + (L + 2c//?) (L - 2c//2) ^ (L + c//2) (L - 2c/i/2)) )( ?
8
3(L - c//2") 24 (L - c//2)(L + 2c//2)
L 1 (b W M +
Equating expressions (7) and (8), substituting Κ = (M^ + M£)/(m + m').L and
writing the result in terms of dimensionless parameters gives:
(m +
2
3
= ôTTTTT1 8 ( ) K
- ^.(c/L) +(/2/3)(c/L) )
3
(9)
qL
2
Plots of the relationship of (m + m')/qL with Κ given by equation (9) are shown in
Figures 7 to 11.
'Structural' Mode
By considering the mechanism shown in Figure 4(b), and replacing the square columns
with circular ones, it is easy to obtain:
2
(m + m').L + (M b + M£) = |k . ( L - c ) (10)
1
and from this (m + m' ) = 1# ( _ c / L 2)
2
qL
The relationships given by equation (11) are also shown in Figures 7 to 11.
Yield Line Study of Interior Slab Panels 165
Figure 7 Figure 8
Figure 9
Figure 10 Figure 11
166 K.J. Hindson and A.W. Chronowicz
Panel Mode
The yield-line patterns shown in Figure 5 were chosen since, in the first place,
the finite size of the columns made the adoption of some form of corner cut-off
unavoidable. At the same time, it was felt that the simple corner-lever systems
shown would give solutions which were acceptably close to those which would be
given by more complicated corner fans (2).
It can be seen from Figure 5(a) that the negative yield-lines which are tangential
to the columns intersect the beam lines at a distance c//2 from the column centres.
Now it can be shown (1) that this simple corner-lever mechanism gives a maximum
1 2
value of (m + m )/qL (= 0.0455) when the levers are a distance 0.159L from the
corners of the panel. Hence it was decided that when c//2* < 0.159L, i.e.
! 2
c/L < 0.225, the appropriate solution to use was (m + m ) / q L = 0.0455, i.e. it
was assumed that the columns could force the levers further out than 0.159L but
could not bring them closer to the column centres than this.
From Figure 5(a) it is possible to obtain the following full yield-line solution:
) ( 1 2
^
T
2 ' 2 * 3 2 ' 3) 0
/2
/2
W.A. = 4(m + m')((L - 2c//2) , [ + c , — — — ) (13)
(L - c//2)
2
m + m' = 1_ (1 - (c/L) )(l - Ç1//2) (c/L))
2 4 2
- iw*y ) \± - \LI " . j 2 I W W J ) (14)
qL 1 - /2(c/L) + (c/L)
f 2 1 2
Values of (m + m ) / q L given by equation (14), constrained such that (m + m ) / q L =
0.0455 when c/L < 0.225, can be found in Figures 7 to 11.
SQUARE COLUMNS
z
W.D. = q(L - -y- + — - — - 2rd) (15)
(17)
Yield Line Study of Interior Slab Panels 167
2 3 2 2
and 87T (r/L) - (127r .d/L - 48u,d/L - 24irK).(r/L) -
2 2
((48π - 6ir - 96).(d/L) + (24π - 96) .K.d/L) .r/L -
2 2 2 3
(24 - 6ïï(d/L) + 24(d/L) ).K + (12π - π - 24).(d/L) -
Curves given by equations (17) and (18) are shown in Figures 14 and 16 to 19.
1
Simultaneous Mode
Replacing the circular columns in Figure 4(a) with square ones again eventually
produces :
~f-
qL
- 8ΪΓΤΤ) · C 1
-
2
W • J (d/L) )
3
(19)
1
Structural Mode
f 2
Values of (m + m ) / q L from this expression can also be found in Figures 16 to 19.
Panel Mode
2
(m + m' ) = (1 - 2(d/L) )(l - d/L)
2 2
qL 24(1 - 2d/L + 2(d/L) )
f 2
however when d/L < 0.159, (m + m )/qL = 0.0455.
The above expressions gave the panel solutions shown in Figures 16 to 19.
It can be seen from the Figures that for both column shapes there are three possible
critical yield-line mechanisms. For a given column size, the relative strength of
the beams, as represented by the parameter K, determines which one of the three is
the actual critical mechanism. When beams are absent, or are very weak, the fan
mode is critical; with stronger beams the 'simultaneous* mode becomes critical with
168 K.J. Hindson and A.W. Chronowicz
Figure 19
Figure 16
Figure 18
170 K.J. Hindson and A.W. Chronowicz
circular columns and the 'structural* mode becomes critical with square, or
rectangular, columns. As the strength of the beams increases further the panel
mode eventually becomes crucial. The values of Κ at which the changes in
critical mechanism occur are plotted in Figure 13. It can be seen that these
values of Κ decrease almost linearly as the column size increases.
The slab moments of resistance needed to resist all the modes decrease consider-
ably as the strength of the beams increases, as might have been expected. Both
slab and beam required moments of resistance decrease, quite significantly, as
the size of the columns increases. This is particularly true for the column fan
mode, as demonstrated in Figure 15. In this figure the fan solution for a flat
plate with square columns is compared with the solutions for the inscribed and
circumscribing circular columns. As expected the results for the square columns
fall between those for the circular columns.
Figures 12 and 14 show that the radii of the critical fans increase with both
column size and beam strength. In particular, in flat plates, the critical radii
increase rapidly from zero as the columns increase from points (with zero cross-
sectional area).
The effects on the previous solutions, and on the conclusions drawn therefrom, of
allowing for the finite widths of the beams have been examined in detail elsewhere
(6) and only the principal findings will be reported here.
Perhaps the most important conclusion was that for normal beam and slab construct-
ion the line-beam solutions can be safely used for design as long as the values of
Κ used in the calculations are based upon the line-beam definition of (M b + M £ ) /
(m + m' ).aL, rather than upon the more strictly correct definition of Κ = (M b + M D )
f 1
(m + m ).(aL - b ) . This is not true when the 'beams are wide and shallow, i.e.
wide but relatively weak; in this case the line-beam solutions should not be used.
Some of the other points disclosed by the examination carried out in reference (6)
were :
1 2 2
(m + m ) = 0.0455(1 - b/L) .qL (22)
iv) It can be seen from the above that the finite width of the
beams, in effect, prolongs the importance of the 'structural'
and 'simultaneous' modes, i.e. it has the effect of in-
creasing the value of Κ at which the panel mode becomes
critical, since the slab moments of resistance required to
resist the latter are decreased whilst, for a given value
of K, those required to resist the 'structural' and
'simultaneous' modes are increased. This is illustrated
in Table 1.
Κ
d/L b/L
Allowing for Line-beam
beam width* solution
* Κ = (M b + M£)/(m + m').(L - b)
CONCLUSIONS
Three yield-line failure mechanisms are possible in the interior panels of beam and
slab structures. With square, or rectangular, columns these are the column fan,
the 'structural' and the panel modes. With circular columns and square, or very
nearly square, panels (or elliptical columns and rectangular panels) the
'simultaneous' mode replaces the 'structural' mode as a possible failure pattern.
Column fans are only likely when beams are absent or are very weak (K < 0.2).
Unless the columns are very large (e.g. d/L ^ 0.2) and the widths of the beams are
small (b/L ^ 0.05) the beams must be quite strong (K > 1.25) before panel
mechanisms can be critical. In most practical cases, with beams of moderate
strength (K - 1.5), either the 'structural' or the 'simultaneous' mode will be the
critical yield-line mechanism.
172 K.J. Hindson and A.W. Chronowicz
The moments of resistance required for the various mechanisms decrease quite con-
siderably with increasing column size (especially relative to the point column
datum). This is particularly true of the column fan mode.
The solutions obtained for panels with line-beams (in fact really referring to the
solutions for the 'structural1 and 'simultaneous1 modes) can be safely used to
design panels with normal beams, i.e. beams which are not wide and shallow, as
long as the values of Κ used in the calculations are based upon the line-beam
definition of Κ = (M b + M^)/(m + m f).aL.
REFERENCES
1. R.H. Wood. Plastic and Elastic Design of Slabs and Plates, Thames and Hudson,
London (1961).
2. L.L. Jones and R.H. Wood. Yield-line Analysis of Slabs, Thames and Hudson,
Chatto and Windus, London (1967).
3. J.H. Appleton. Reinforced Concrete Floor Slabs on Flexible Beams, Civ. Engrg.
Studies, Struct. Res. Ser. No.223, Univ. Illinois (1961).
4. R.P. Johnson. Structural Concrete, McGraw-Hill, London (1967).
5. H. Gesund and O.P. Dikshit. Yield Line Analysis of the Punching Problem at
Slab/Column Intersections, Publ. SP-30, Am. Concr. Inst., Detroit (1971).
6. K.J. Hindson. The Analysis and Design of Reinforced Concrete Slab Structures,
Ph.D. Thesis, Univ. Leeds (1978).