MLinstall Diffusers 2017
Field
Side Rail
Field
Assembled
Corners
Alignment
Strips Temporary
Gauge
• Mounting frame for Titus Modulinear diffusers • Diffusers can be removed and replaced
assures a clean, accurately dimensioned easily, without disfiguring the ceiling
Temporary
Gauge
ceiling opening to receive the diffuser • Furnished with the diffusers in Frame &
• Choice of designs for wet plaster Border Types 3, 4, 6, 7A, 7B and 11
End Frame
and other types of ceilings • Cut to length in the field
(Factory Welded)
• Allows the diffusers to be unpacked and
installed after construction is finished
Mitered
Corner
F
Spring Clip
Factory
Blade Spacer
Optional Support (Welded) Optional
End Border Bar Blank-Offs
Optional Alignment
End Cap Pins
• Diffusers can be joined together end- • Factory-made mitered corners are
to-end to form long, continuous slots accurately welded and carefully
#8 x 1¼ Oval Head Screw
(Border Type 1A only)
• End borders and end caps close off finished for a smooth, unbroken
the ends of the diffusers and simplify corner treatment. Mitered corners
Pattern installations ending at walls and are rendered inactive with factory-
Controller
other stopping points (see page F17) installed blank-offs. (see page F20)
• Alignment pins maintain close
#6 x ½ SMS joints between sections
(Border 22)
Align Y-Y ends using supplied SS1 Spline Support Clips
INSTALLATIONS
F22
INSTALLATIONS diffusers
• Titus Modulinear diffusers are so simple and rugged they are • Field-cut diffuser Model MLF (above) or MLRF is shipped in standard
routinely cut to length in the field with a fine tooth, high-speed 6-foot lengths
carbon steel metal cutting blade • Model MLF or MLRF diffuser can be cut to any length. Field-installed
• Factory-cut diffuser Model ML (above) or MLR is ordered for a spacers and other hardware are furnished with the diffuser for one
specified length from the factory, but can be trimmed as much as 3 field cut. Additional field cut kits are available at additional cost.
inches from each end in the field • Unit is shipped without end caps or end borders
Hanger Bracket
for Border Types 9A, 9B, 12, 15
Hanger Bracket
for Border Types 2A, 2B
Hanger Bracket
for Frame & Border
Types 3, 4, 6, 7A, 7B, 11
F
Duct
By Others
INSTALLATIONS
Ceiling
These hanger brackets are a convenient Here the diffuser is simply pushed up into the For installation in a Titus mounting frame,
means of attaching hanger wires to sup- duct until the outer legs of the hanger brack- these hanger brackets function like the duct
port the diffuser from the structural mem- ets snap into the hems of the duct. Screws type brackets at the left. The outer legs of the
bers of the building. then snug the diffuser against the ceiling. brackets engage the side rails of the mount-
ing frame.
F23