4. ALL DUCTS JOINTS/CONNECTIONS MUST BE SEALED BY VULCA SEAL SEALANT OR ITS APPROVED EQUAL.
7. FRESH AIR DUCT SHOULD BE MADE OF PLAIN GALVANIZED IRON SHEET GAUGE 22(minimum). 12.5mmØ
9. PROVIDE 5/8" PLASTIC STRAP & CONTINUOUS CORNER BEADS (GA.26) AFTER INSULATION. Dynabolts
10. PROVIDE FLEXIBLE CONNECTOR USING CANVASS CLOTH AS VIBRATION ISOLATOR.
11. ALL EXHAUST DUCTING JOINTS AND DROPPINGS SHALL BE FULLY WELD. 50x6.3mm thk. Angle Bar 38x4.7mm
12. TENANT TO SUBMIT AS-BUILT PLAN DULY SIGNED & SEALED BY MECHANICAL ENGINEER. Mounted on Beam/Slab thk. Flat Bar
13. ALL DUCT WORKS AND HANGERS SHALL BE PROPERLY INSTALLED, TO CONFORM TO NFPA 90A
w/ 12.5mmØ Dynabolt
14. ALL DUCT WORKS FRESH AIR AND EXHAUST SHALL PASS LIGHTING TEST AND SMOKE TEST 1.5"x1/8" Flat Bar 4pcs. Vibration
15. PROPER TESTING AND COMMISSIONING SHALL BE CONDUCTED BY QUALIFIED ENGINEERS WITH Isolator
SIGNED REPORTS AND AS-BUILT DRAWING. 50mmx6.3mm thk.
Angle Bar Frame
M-01 EXHAUST AND FRESH AIR BLOWER AND HANGER DETAIL CONDENSATE TRAP
TO NEAREST DRAIN
NTS
01
300mm 25mm DIA. PVC DRAIN PIPE
Appliances
GA. #26 BOND
FAN COIL UNITS
LOCATION
AREA COOLING ACCU
Finish Line
64 kg/m3 FIBERGLASS WOOL DESIGNATION QTY
SERVED
TYPE
CAPACITY CAPACITY
OF BRAND
ACCU
INSULATION
FLOOR
M-01 HOOD DETAIL FCU-1 1 DINING AREA
MOUNTED
5 TR 5 TR ROOF DECK CARRIER
M-01 EXHAUST EXHAUST DUCT INSULATION DETAIL 1 KEB -1 CENTRIFUGAL BLOWER 9,650 2.0 7.5 380 3 60 BACKWARD CURVE
NTS 1 FAB-1 CENTRIFUGAL BLOWER 7,250 2.0 5.0 380 3 60
02 FORWARD CURVE
1 TEF-1 CEILING MOUNTED CASSETTE TYPE 160 0.25 28 230 1 60 CASSETTE TYPE
R. A. 9 2 6 6 HENRY
CEBU CITY, 6000 CEBU X 1:50 MTRS. FRESH AIR AND EXHAUST
VENTILATION SYSTEM
FOR CONSTRUCTION 12/11/2023