YORK Marine screw chiller units

Type MCSH-S

Features Condenser pressure safety relief valve set to open at the


• Marine Screw Chiller Units, designed and manufactured design pressure.
by Johnson Controls Marine for long service in heavy sea
conditions Refrigerant filter/drier system
• Condenser with integrated liquid receiver, suction gas Refrigerant filter/drier system is included and provides:
heat exchanger and liquid sub-cooler, for minimum • liquid refrigerant filter/drier with isolation valves
space requirements and easy installation • liquid line sight glass with moisture indicator
• Designed for various HFC or HCFC refrigerants • refrigerant charging valve.
• Designed for air conditioning cooling capacities,
120-900 kW Evaporator
The evaporator is a fully welded and insulated plate heat
Compressors / Unit exchanger. Plate material is AISI 316. Chilled water pipe are
Compressors are semi hermetic screw type. insulated as well and lead to the unit frame edge for easy
They include: connection.
• capacity regulation 25-100%
• positive lubrication by integral oil pump Gauge panel
• integral safety valve Gauge panel with suction, discharge and oil pressure gauges.
• integral suction strainer These glycerin filled gauges are easy to read and provide a
• suction and discharge isolating valves long service lifetime.
• crankcase heater
• oil level sight glass Control Panel
• suction filter for start-up & running-in. Control panel mounted on the unit base frame. Including all
• electronic expansion valve internal wiring. Including signal for cooling / chilled water
• PT-100 sensors for measurement of chilled water supply pump start
and return temperature
• flow switch in chilled water pipe system as safe guard for
freezing

Condenser, with built-in liquid receiver


and heat exchanger
The condenser is a cleanable, shell-and-tube type with
build-in receiver, suction gas heat exchanger and liquid
sub-cooler. The tubes are CuNi for seawater and Cu for fresh
water.
For seawater cooling the shell are steel, tube-plate CuNi /
steel compound and the end-covers are red brass.
For freshwater cooling the shell and tube-plates are steel.
The end covers are coated cast iron.
The build in suction/liquid heat exchanger ensures safe
operation, minimize the risk of liquid hammering, secure
sufficient liquid sub-cooling and improve the compressors
performance.
PLC unit control Optional
PLC-based control is standard. • Sequence control for running up to 4 units in a sequence
With PLC control the low/high and oil pressure cut-outs • Pump control & starter for condenser water pumps
switches are replaced by pressure sensors with and/or chillwater pumps
readings and settings from the PLC control panel. • Control of air handling unit(s) (AHU), complete HVAC
control.
• Low pressure cut-out, which will stop the compressor at a • Remote operating panel
pre-set minimum suction pressure. • Double unit with two compressors
• High pressure cut-out, which will stop the compressor at • Evaporator for Propylene Glycol/Ethylen Glycol
a pre-set maximum discharge pressure. • Capacity test with test report
• Low oil pressure cut-out, which will stop the compressors • FAT in own factory
at a pre-set minimum differential pressure.

Length Width Height Service Weight Capacity


Unit type Drawing
area
for R407c No.
mm mm mm (mm) *** Kg ** 50/60 Hz
MCSH-S-CSH6561 - CRxC2723 2950 1610 1850 800/2300 1210/1309 123/148 662702-0003

MCSH-S-CSH6561 - CRxC4119 2630 1610 1850 800/1900 1310/1420 129/155 662702-0004

MCSH-S-CSH7551 - CRxC4119 2685 1610 1850 800 / 1900 1480/1590 142/170 662702-0005

MCSH-S-CSH7561 - CRxC4119 2685 1610 1850 800 / 1900 1495/1605 169/203 662702-0006

MCSH-S-CSH8561 - CRxC4119 2885 1610 1850 800 / 1900 1675/1785 189/227 662702-0016

MCSH-S-CSH7571 - CRxC5019 2860 1610 1850 800 / 1900 1675/1802 193/231 662702-0007

MCSH-S-CSH8561 - CRxC5019 2810 1610 1850 800/1900 2045/2172 276/331 662702-0008

MCSH-S-CSH8571 - CRxC6023 3495 1610 1850 800/2300 2460/2535 286/343 662702-0001

MCSH-S-CSH8561 - CRxC4119 2635 1610 1850 800 / 1900 1890/2000 295/350 662702-0020

MCSH-S-CSH8571 - CRxC5023 3190 1610 1850 800/2300 2110/2165 315/378 662702-0009

MCSH-S-CSH9551 - CRxC6023 3195 1610 1850 800/2300 2880/2955 413/495 662702-0002

MCSH-S-CSH9561 - CRxC6023 3165 1610 1925 800/2300 2985/3060 478/573 662702-0014

MCSH-S-CSH9571 - CRxC6023 3165 1610 1925 800/2300 3025/3100 520/628 662702-0013

MCSH-S-CSH9571 - CRxC7023 3340 1610 2065 800/2300 3210/3285 543/652 662702-0011

MCSH-S-CSH9581 - CRxC7023 3365 1610 2210 800/2300 3390/3465 617/740 662702-0012

MCSH-S-CSH9591 - CRxC7023 3265 1610 2210 800/2300 3450/3525 667/800 662702-0010

Length Width Height Service Weight Capacity


Unit type Drawing
area
for R134a No.
mm mm mm (mm) *** Kg ** 50/60 Hz
MCSH-S-CSH7571 - CRxC4119 2685 1610 1850 800/1900 1500/1610 133/160 662702-0015

MCSH-S-CSH8551 - CRxC5019 2810 1610 1850 800/1900 1980/2107 165/198 662702-0019

MCSH-S-CSH8571 - CRxC5019 2785 1610 1850 800 / 1900 2160/2287 225/270 662702-0017

MCSH-S-CSH8581 - CRxC5019 2785 1610 1850 800 / 1900 2195/2322 250/300 662702-0018

** Approx weight Capacity based on Note:


*** Service area / withdraw of condenser tube +3°C Evaporating temperature Minimum capacity for continuous operation is
+ 45°C Condensing temperature equal to the lowest capacity step of the compressor
Chilled water 12°C / 6°C fresh water in question.
Sea water cooling 32°C
11.08

Fresh water cooling 36°C


60 Hz

Johnson Controls Marine - HVAC&R


Jens Juuls Vej 28 · 8260 Viby J · Denmark
Phone +45 87 36 35 00 · Fax +45 87 36 35 01
www.yorkref.com · cg-eur-dk-vibymarine@jci.com The above technical information is subject to reservations of errors and updated product changes.