S.No. Description Unit Rate List Quantity


I AIR TERMINATION SYSTEM
Supply of 8mm Aluminium Solid Round Conductor for building terrace as a air terminal to meet the requirements of
IS/IEC 62305 and IEC 62561-2.
1 Mtr 291
210
Supply of Parapet conductor holder for fixing 8mm Aluminium conductor on the parapet surface to meet the
2 requirement of IS/IEC - 62305 Nos 162
150
Supply of suitable Stainless Steel cross connector for 8- 10 mm round AL conductor to meet the requirement of IS/IEC -
3 62305. Nos 1318
10
Supply of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor
during temperature variations to be provided on conductors length over 20 meters with Expansion Piece Connector for
to connect Solid Roung Al. Conductor at both ends to meet the requirements for IS/IEC 62305
4 Nos 324

2
Supply of Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of
5 IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561. Nos 116
4
Supply of 2 metre Vertical Air terminal of dia 16-10 mm with Complete Support of Wall Clamp selected as per angle of
protection chart to meet the requirement of IS/IEC 62305. Tested for Electrical, Mechanical and Chemical as per IEC
6 62561. VAT 2 with mounting accessories on parapet surface (includes - VAT 2 + interception tip + Wall Clamp + Nos 8200
connecting point)
1
Supply of 3 metre Vertical Air terminal of dia 16-10 mm with Complete Support of Concrete Base(370mm dia) and Air
Terminal Conductor joining Clip selected as per angle of protection chart to meet the requirement of IS/IEC 62305.
Tested for Electrical, Mechanical and Chemical as per IEC 62561. VAT 3 with mounting accessories on flat surface
7 (includes - VAT 3 + interception tip + Base support stone + air terminal joining clip Nos 16161

1
II DOWN CONDUCTOR SYSTEM
Supply of Concrete Flat Roof conductor holder
8 Nos 324
6
Supply of conductor holder for fixing the (wall) 8 mm Aluminium down conductor to meet the requirement of IS/IEC -
9 62305 Nos 486
6

Page 1 of 7
Page 2

Supply of Test Joint with enclosure suitable connector for 8 mm round Al. conductor & 10 mm round copper coated
10 conductor to meet the requirement of IS/IEC Nos 2590
2
III EARTHING SYSTEM
Supply of 10 mm copper bonded Round steel solid Conductor for ring earthing meet the requirements of IS/ IEC 62305
11 and IEC 62561-2 Mtr 879
20
12 14 AWG cable as Per IEC 62305 Mtr 400 5
13 Copper bonded rod of 250 microns , 25 mm dia,1.5 mtr length Nos 5780 2
14 Equipotential Bonding Bar As Per IEC 62305 Nos 5000 1
PRO-CEM/PRO-SAN, Supply of earth enchancing mineral compound tested for leaching and TCLP with NABL accredited
15 Lab as per IEC 62561-7 -12.5 kg Nos 3468
2
Supply of make Universal Clamp made up of stainless steel for terminating cable / flat conductor with Connecting Point
16 Nos 2220
2
17 Supply of make Heavy duty Chamber Inspection Pit made up of plastic material. Nos 4740 1
18 Connecting Point Nos 555 4
19 Total

Page 2 of 7
Surge Protection Devices
1

2
Surge Protection Devices
For Main incoming Panel (three phase)

This panel should include Surge Protection Device Type 1+2 Tested as per IEC 61643 Part 11:2011 & UL 1449 4th Edition with following spe
Nominal voltage -230V 50/60Hz and MCOV ≥ 255 V.
The Surge Protection Devices shall have TOV Failsafe (L-N/N-PE) ≥ 440 V for 120 min/1200 V for 200 ms.
Lightning Impulse discharge current (L-N/N-PE) - 12.5 kA/50 kA (10/350µ sec).
Nominal Discharge current (L-N/N-PE) - 12.5 kA/50 kA (8/20µ sec & Max Discharge current (L-N/N-PE) - 50 kA/100 kA (8/20µ sec).
Protective Elements are High Energy MOV & GDT and the Protection Modes for : 3 numbers of Type 1 + 2 SPD for connection between Ph
Neutral and one number of SPD between Neutral and Earth.
Short- Circuit Current rating (Isccr) – 50 kA/50 Hz .
Back up fuse shall be 315 AgG/gL. Health Status Indication required in all catridge including N to PE and Remote monitoring facility.
Total Response time (L-N/N-PE) < 25 ns / < 100ns.
Make : CAPE (RAYCAP)
The supplier shall submit VDE test certificate (on line web link) for the above product.

For Sub DB Panel (three phase)

This panel should include Surge Protection Device Type 2 Tested as per IEC 61643 Part 11:2011 & UL 1449 4th Edition with following speci
Nominal voltage -230V 50/60Hz and MCOV ≥ 300 V.
The Surge Protection Devices shall have TOV Failsafe (L-N/N-PE) ≥ 440 V for 120 min/1200 V for 200 ms.
Nominal Discharge current (L-N/N-PE) - 20 kA/40 kA (8/20µ sec.
Max Discharge current (L-N/N-PE) - 50 kA/65 kA (8/20µ sec).
Protective Elements are High Energy MOV & GDT and the Protection Modes for : 3 numbers of Type 2 SPD for connection between Phase
Neutral and one number of SPD between Neutral and Earth.
Short- Circuit Current rating (Isccr) – 25 kA/50 Hz .
Back up fuse shall be 315 AgG/gL. Health Status Indication required in all catridge including N to PE and Remote monitoring facility.
Total Response time (L-N/N-PE) < 25 ns / < 100ns.
Make : CAPE (RAYCAP)
The supplier shall submit VDE test certificate (on line web link) for the above product.
Model Number Qty Price(NPR) Amount

ProTec T1 300
(3+1)R 1 68800 68800

ProTec T2 300
(3+1)R 2 32700 65400

134200
Protection Type
1 External
2 Internal

Total
Discount(10%)
Total
Installation(25%)
Total(ex. VAT)
VAT(13%)
Totan(incl. VAT)
Summary Sheet
Amount
188579
134200

322779
32277.9
290501.1
87150.33
377651.43
49094.6859
426746.1159