Supply of Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of
5 IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561. Nos 116
4
Supply of 2 metre Vertical Air terminal of dia 16-10 mm with Complete Support of Wall Clamp selected as per angle of
protection chart to meet the requirement of IS/IEC 62305. Tested for Electrical, Mechanical and Chemical as per IEC
6 62561. VAT 2 with mounting accessories on parapet surface (includes - VAT 2 + interception tip + Wall Clamp + Nos 8200
connecting point)
1
Supply of 3 metre Vertical Air terminal of dia 16-10 mm with Complete Support of Concrete Base(370mm dia) and Air
Terminal Conductor joining Clip selected as per angle of protection chart to meet the requirement of IS/IEC 62305.
Tested for Electrical, Mechanical and Chemical as per IEC 62561. VAT 3 with mounting accessories on flat surface
7 (includes - VAT 3 + interception tip + Base support stone + air terminal joining clip Nos 16161
1
II DOWN CONDUCTOR SYSTEM
Supply of Concrete Flat Roof conductor holder
8 Nos 324
6
Supply of conductor holder for fixing the (wall) 8 mm Aluminium down conductor to meet the requirement of IS/IEC -
9 62305 Nos 486
6
Page 1 of 7
Page 2
Supply of Test Joint with enclosure suitable connector for 8 mm round Al. conductor & 10 mm round copper coated
10 conductor to meet the requirement of IS/IEC Nos 2590
2
III EARTHING SYSTEM
Supply of 10 mm copper bonded Round steel solid Conductor for ring earthing meet the requirements of IS/ IEC 62305
11 and IEC 62561-2 Mtr 879
20
12 14 AWG cable as Per IEC 62305 Mtr 400 5
13 Copper bonded rod of 250 microns , 25 mm dia,1.5 mtr length Nos 5780 2
14 Equipotential Bonding Bar As Per IEC 62305 Nos 5000 1
PRO-CEM/PRO-SAN, Supply of earth enchancing mineral compound tested for leaching and TCLP with NABL accredited
15 Lab as per IEC 62561-7 -12.5 kg Nos 3468
2
Supply of make Universal Clamp made up of stainless steel for terminating cable / flat conductor with Connecting Point
16 Nos 2220
2
17 Supply of make Heavy duty Chamber Inspection Pit made up of plastic material. Nos 4740 1
18 Connecting Point Nos 555 4
19 Total
Page 2 of 7
Surge Protection Devices
1
2
Surge Protection Devices
For Main incoming Panel (three phase)
This panel should include Surge Protection Device Type 1+2 Tested as per IEC 61643 Part 11:2011 & UL 1449 4th Edition with following spe
Nominal voltage -230V 50/60Hz and MCOV ≥ 255 V.
The Surge Protection Devices shall have TOV Failsafe (L-N/N-PE) ≥ 440 V for 120 min/1200 V for 200 ms.
Lightning Impulse discharge current (L-N/N-PE) - 12.5 kA/50 kA (10/350µ sec).
Nominal Discharge current (L-N/N-PE) - 12.5 kA/50 kA (8/20µ sec & Max Discharge current (L-N/N-PE) - 50 kA/100 kA (8/20µ sec).
Protective Elements are High Energy MOV & GDT and the Protection Modes for : 3 numbers of Type 1 + 2 SPD for connection between Ph
Neutral and one number of SPD between Neutral and Earth.
Short- Circuit Current rating (Isccr) – 50 kA/50 Hz .
Back up fuse shall be 315 AgG/gL. Health Status Indication required in all catridge including N to PE and Remote monitoring facility.
Total Response time (L-N/N-PE) < 25 ns / < 100ns.
Make : CAPE (RAYCAP)
The supplier shall submit VDE test certificate (on line web link) for the above product.
This panel should include Surge Protection Device Type 2 Tested as per IEC 61643 Part 11:2011 & UL 1449 4th Edition with following speci
Nominal voltage -230V 50/60Hz and MCOV ≥ 300 V.
The Surge Protection Devices shall have TOV Failsafe (L-N/N-PE) ≥ 440 V for 120 min/1200 V for 200 ms.
Nominal Discharge current (L-N/N-PE) - 20 kA/40 kA (8/20µ sec.
Max Discharge current (L-N/N-PE) - 50 kA/65 kA (8/20µ sec).
Protective Elements are High Energy MOV & GDT and the Protection Modes for : 3 numbers of Type 2 SPD for connection between Phase
Neutral and one number of SPD between Neutral and Earth.
Short- Circuit Current rating (Isccr) – 25 kA/50 Hz .
Back up fuse shall be 315 AgG/gL. Health Status Indication required in all catridge including N to PE and Remote monitoring facility.
Total Response time (L-N/N-PE) < 25 ns / < 100ns.
Make : CAPE (RAYCAP)
The supplier shall submit VDE test certificate (on line web link) for the above product.
Model Number Qty Price(NPR) Amount
ProTec T1 300
(3+1)R 1 68800 68800
ProTec T2 300
(3+1)R 2 32700 65400
134200
Protection Type
1 External
2 Internal
Total
Discount(10%)
Total
Installation(25%)
Total(ex. VAT)
VAT(13%)
Totan(incl. VAT)
Summary Sheet
Amount
188579
134200
322779
32277.9
290501.1
87150.33
377651.43
49094.6859