Seismic load Calculation

Input Data : (As per the specification, 301 Structural Loading and Forces)

Occupancy Category = Group I,Essential Facilities UBC 1997,

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = Very dense soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 4

Zone Factor = 0.075 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.09 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 1

hx is the element or component attachment As per layout drawing : FFL of


elevation with respect to grade. (hx ) SHAN 287.9m and MEZ Roof 312m
= 287.9 m (from where floor supports &
ceiling supports are taken).
structure roof elevation with respect to grade (hr) = 312 m
Kindly refer layout drawing.

Results:
Seismic Lateral Force:

Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2


Cs (min) = 0.09

b) Maximum lateral force Fp (max) UBC 1997, 1632.2


Cs (max) = 0.54

Total Design lateral force UBC 1997, 1632.2

Hence Total Lateral seismic Force coefficient Cs = 0.17 Cs - Seismic Coefficient


Within the limit
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 350 mm

Outer diameter = 355.6 mm

wall thinkness of pipe = 11.13 mm

Self weight of pipe . = 94.55 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 333.34 mm


Area of pipe
= 87226 mm2
lateral brace at distance (L)
= 4.5 m
fluid weight
= 87.23 kg/m
Total weight (pipe + fluid weight)
= 181.78 kg/m

= 1.818 kN/m
=
Total Vertical Load of pipe at Support (Wp) 8.18 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 1

Zone Factor = 0.075 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.09 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 1

hx is the element or component attachment As per layout drawing : FFL of SHAN


elevation with respect to grade. (hx ) 287.9m and MEZ Roof 312m (from
= 287.9 m where floor & hanger supports are
taken).
structure roof elevation with respect to grade (hr) = 312 m

Weight of the structure (Wp) = 8.18 KN


Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.09

Fp (min) = 0.77 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 0.54

Fp (max) = 4.42 kN
Seismic load Calculation for Pipe support for 250NB
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 250 mm

Outer diameter = 273.1 mm

wall thinkness of pipe = 9.27 mm

Self weight of pipe . = 60.31 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 254.56 mm


Area of pipe
= 50869 mm2
lateral brace at distance (L)
= 4.5 m
fluid weight
= 50.87 kg/m
Total weight (pipe + fluid weight)
= 111.18 kg/m

= 1.112 kN/m
=
Total Vertical Load of pipe at Support (Wp) 5.00 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 1

Zone Factor = 0.075 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.09 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 1

hx is the element or component attachment As per layout drawing : FFL of SHAN


elevation with respect to grade. (hx ) 287.9m and MEZ Roof 312m (from
= 287.9 m where floor & hanger supports are
taken).
structure roof elevation with respect to grade (hr) = 312 m

Weight of the structure (Wp) = 5.00 KN


Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.09

Fp (min) = 0.47 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 0.54

Fp (max) = 2.70 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 500 mm

Outer diameter = 508 mm

wall thinkness of pipe = 9.53 mm

Self weight of pipe . = 117.15 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 488.94 mm


Area of pipe
= 187664 mm2
lateral brace at distance (L)
= 3.6 m
fluid weight
= 187.66 kg/m
Total weight (pipe + fluid weight)
= 117.15 kg/m

= 1.172 kN/m
=
Total Vertical Load of pipe at Support (Wp) 4.22 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.20 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 3

Zone Factor = 0.3 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.33 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 2.5

hx is the element or component attachment


elevation with respect to grade. (hx ) = 3.6 m

structure roof elevation with respect to grade (hr) = 3.6 m


As per layout drawing : Bottom of
RCC slab = 22.225m (from where
Weight of the structure (Wp) = 4.22 KN hanger supports are taken).
Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.28

Fp (min) = 1.17 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 1.584

Fp (max) = 6.68 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 250 mm

Outer diameter = 273.1 mm

wall thinkness of pipe = 9.27 mm

Self weight of pipe . = 60.31 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 254.56 mm


Area of pipe
= 50869 mm2
lateral brace at distance (L)
= 3.6 m
fluid weight
= 50.87 kg/m
Total weight (pipe + fluid weight)
= 60.31 kg/m

= 0.603 kN/m
=
Total Vertical Load of pipe at Support (Wp) 2.17 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.20 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 4

Zone Factor = 0.3 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.33 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 2.5

hx is the element or component attachment


elevation with respect to grade. (hx ) = 3.6 m

structure roof elevation with respect to grade (hr) = 3.6 m


As per layout drawing : Bottom of
RCC slab = 22.225m (from where
Weight of the structure (Wp) = 2.17 KN hanger supports are taken).
Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.28

Fp (min) = 0.60 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 1.584

Fp (max) = 3.44 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 150 mm

Outer diameter = 168.3 mm

wall thinkness of pipe = 7.11 mm

Self weight of pipe . = 28.26 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 154.08 mm


Area of pipe
= 18636 mm2
lateral brace at distance (L)
= 4.5 m
fluid weight
= 18.64 kg/m
Total weight (pipe + fluid weight)
= 46.90 kg/m

= 0.469 kN/m
=
Total Vertical Load of pipe at Support (Wp) 2.11 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 1

Zone Factor = 0.075 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.09 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 1

hx is the element or component attachment As per layout drawing : FFL of SHAN


elevation with respect to grade. (hx ) 287.9m and MEZ Roof 312m (from
= 287.9 m where floor & hanger supports are
taken).
structure roof elevation with respect to grade (hr) = 312 m

Weight of the structure (Wp) = 2.11 KN


Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.09

Fp (min) = 0.20 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 0.54

Fp (max) = 1.14 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 150 mm

Outer diameter = 168.3 mm

wall thinkness of pipe = 7.11 mm

Self weight of pipe . = 28.83 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 154.08 mm


Area of pipe
= 18636 mm2
lateral brace at distance (L)
= 4.5 m
fluid weight
= 18.64 kg/m
Total weight (pipe + fluid weight)
= 47.47 kg/m

= 0.475 kN/m
Factor (as per NFPA -13; cl 9.3.5.6.1) 1.00
=
=
Total Vertical Load of pipe at Support (Wp) 2.14 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, Section 210548)
(clause 1.5. PERFORMANCE REQUIREMENTS)

Occupancy Category = Special Occupancy Category UBC 1997,

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = Rocky soil

Soil Site Class = B Table-16-J , page 30

Zone = 2A

Zone Factor = 0.15 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 0.15 Table-16-Q , page 34
Component Response modification factor (Rp) = 3 Table-16-O , page 33

Component Amplification factor (ap ) = 1

hx is the element or component attachment


elevation with respect to grade. (hx ) = 22.225 m

structure roof elevation with respect to grade (hr) = 22.225 m As per layout drawing : Bottom
of RCC slab = 22.225m (from
where hanger supports are
Weight of the structure (Wp) = 2.14 KN taken).
Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 0.16

Fp (min) = 0.34 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 0.9

Fp (max) = 1.92 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:

INPUT DATA

Pipe Diameter (D) Sch 40s = 600 mm

Outer diameter = 609.6 mm

wall thinkness of pipe = 17.48 mm

Self weight of pipe . = 255.41 Kg/m

Density of water = 1000 kg/m3

Inner Diameter of pipe (d) = 574.64 mm


Area of pipe
= 259216 mm2
lateral brace at distance (L)
= 4.5 m
fluid weight
= 259.22 kg/m
Total weight (pipe + fluid weight)
= 514.63 kg/m

= 5.146 kN/m
=
Total Vertical Load of pipe at Support (Wp) 23.16 kN
(for length of 4.5m)

Seismic load Calculation


Input Data : (As per the specification, 301 Structural Loading and Forces) UBC 1997,

Occupancy Category = Group I,Essential Facilities

Importance Factor, I = 1.50 Table-16-K , page 30

Soil Type = soil,soft rock

Soil Site Class = Class SC Table-16-J , page 30

Zone = 1

Zone Factor = 0.075 Table-16-I , page 30


Seismic Coefficient Factor Ca
= 1.2 Table-16-Q , page 34
Component Response modification factor (Rp) = 5 Table-16-O , page 33

Component Amplification factor (ap ) = 2.5

hx is the element or component attachment


elevation with respect to grade. (hx ) = 22.225 m

structure roof elevation with respect to grade (hr) = 22.225 m


As per layout drawing : Bottom of
RCC slab = 22.225m (from where
Weight of the structure (Wp) = 23.16 KN hanger supports are taken).
Kindly refer layout drawing.

Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;

a) Minimum lateral force Fp(min) UBC 1997, 1632.2

Cs (min) = 1.26

Fp (min) = 29.18 kN

b) Maximum lateral force Fp (max) UBC 1997, 1632.2

Cs (max) = 7.2

Fp (max) = 166.74 kN