Input Data : (As per the specification, 301 Structural Loading and Forces)
Zone = 4
Results:
Seismic Lateral Force:
INPUT DATA
= 1.818 kN/m
=
Total Vertical Load of pipe at Support (Wp) 8.18 kN
(for length of 4.5m)
Zone = 1
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.09
Fp (min) = 0.77 kN
Cs (max) = 0.54
Fp (max) = 4.42 kN
Seismic load Calculation for Pipe support for 250NB
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 1.112 kN/m
=
Total Vertical Load of pipe at Support (Wp) 5.00 kN
(for length of 4.5m)
Zone = 1
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.09
Fp (min) = 0.47 kN
Cs (max) = 0.54
Fp (max) = 2.70 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 1.172 kN/m
=
Total Vertical Load of pipe at Support (Wp) 4.22 kN
(for length of 4.5m)
Zone = 3
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.28
Fp (min) = 1.17 kN
Cs (max) = 1.584
Fp (max) = 6.68 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 0.603 kN/m
=
Total Vertical Load of pipe at Support (Wp) 2.17 kN
(for length of 4.5m)
Zone = 4
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.28
Fp (min) = 0.60 kN
Cs (max) = 1.584
Fp (max) = 3.44 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 0.469 kN/m
=
Total Vertical Load of pipe at Support (Wp) 2.11 kN
(for length of 4.5m)
Zone = 1
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.09
Fp (min) = 0.20 kN
Cs (max) = 0.54
Fp (max) = 1.14 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 0.475 kN/m
Factor (as per NFPA -13; cl 9.3.5.6.1) 1.00
=
=
Total Vertical Load of pipe at Support (Wp) 2.14 kN
(for length of 4.5m)
Zone = 2A
structure roof elevation with respect to grade (hr) = 22.225 m As per layout drawing : Bottom
of RCC slab = 22.225m (from
where hanger supports are
Weight of the structure (Wp) = 2.14 KN taken).
Kindly refer layout drawing.
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 0.16
Fp (min) = 0.34 kN
Cs (max) = 0.9
Fp (max) = 1.92 kN
Seismic load Calculation for Pipe support
CHILLER WATER PIPE WEIGHT CALCULATION:
INPUT DATA
= 5.146 kN/m
=
Total Vertical Load of pipe at Support (Wp) 23.16 kN
(for length of 4.5m)
Zone = 1
Results:
Seismic Lateral Force:
Lateral force Fp should be within the below shown cases a & b ;
Cs (min) = 1.26
Fp (min) = 29.18 kN
Cs (max) = 7.2
Fp (max) = 166.74 kN