OBJECT REQUEST ANSWER

Object Variation Description Function Qualifier Function Qualifier Codes


(dec) Codes Codes Codes (hex)
(dec) (hex) (dex)
1 0 Binary Input – All Variations 1 0,1,6,7,8
1 2 Binary Input with Status 1 0,1,6,7,8 129 0,1
2 0 Binary Input Change – All variations 1 6,7,8
2 2 Binary Input Change with Time 1 6,7,8 129,130 17,28
12 1 Control Relay Output Block 3,4,5,6 17,28 129 Echo of Request
20 0 Binary Counter – All Variations 1 0,1,6,7,8
22 0 Counter Change Event – All Variations 1 6,7,8
30 0 Analog Input – All Variations * 1 0,1,6,7,8
30 1 32 – Bit Analog Input * 1 0,1,6,7,8 129 0,1
30 2 16 – Bit Analog Input 1 0,1,6,7,8 129 0,1
32 0 Analog Change Event – All Variations 1 6,7,8
50 1 Time and Date 2 7
52 2 Time Delay Fine 129 07
60 1 Class 0 Data 1 6
60 2 Class 1 Data 1 6,7,8
60 3 Class 2 Data 1 6,7,8
60 4 Class 3 Data 1 6,7,8
80 1 Internal Indications 2 0
Cold Restart 13
Warm Restart 14

Event objects (02, 22, 32) must be associated with DNP classes (classes 1.2 or 3) via
parameterization software and generate information on object 80 (internal indications – IIN
showing that there are events of a class available). The equipment must allow associating an
object with a class.

The protocol DNP3 time sync period parameter must be configurable (in minutes) in the
configuration software only.

After the period has elapsed, the IIN – Need Time indicator (flag) must be turned on. This
indicator must be turned on when the equipment is restarted and after the parameterized
period has elapsed and turned off after the supervisor sent a write command for time (object
50).

The device should turn on the Device Restart indicator when it starts up and turn it off when
receive a “Clear Restart” information.

AVAILABLE DNP3 SIGNALS

The supervision of States(DIGITAL OUTPUS) - objects 01 (binary input) and 02 (binary input change)

· Recloser status - 52a and 52b (open / closed)

· PANEL MODE local/remote Button status

· Phase Fault Protection (50F/51F) (Switch Mode) ON/OFF Status

· Autoreclose (79) ON/OFF Status


· Earth Fault (50N/51N) ON/OFF Status

· Sensitive Earth Fault (50GS) ON/OFF Status

· CC Supply Voltage Alarm (LOW BATTERY)

· Opening by phase A1

· Opening by phase B1

· Opening by phase C1

· Opening by Earth/Neutral1

· Opening by SEF or SGF (sensitive neutral adjustment) 1

· High Current Opening (Phase and Neutral High Current Lockout)

· State of the normal setting group (on / off)

· Alternative setting group 1 status (on / off)

· End of sequence blocking (Lockout) 2

· Problem with electronic control

· Failure to open the mechanism

· Status of Live Line Function

· Mechanical Lock Status (yellow lever)

· Reclose Sequence Running

Telecommands (DIGITAL INPUTS) (object 12)

· OPEN / CLOSE command.

· Protection ON/OFF Command (Protection Lock)

· Autoreclose (79) ON/OFF Command

· Earth Fault Protection ON/OFF Command.

· Sensitive Earth Fault Protection ON/OFF Command.

· Group Selection (normal and alternative).

· Live Line ON/OFF.

· Panel Mode Local/Remote command.

Tele supervision of Analog Measurements (for remote supervision of quantities analogs - objects 30
and 32)

· Current in phase A (currents from 0 to 10kA with an accuracy of +/- 5%);

· Current in phase B (0 to 10kA currents with an accuracy of +/-5%);


· Current in phase C (0 to 10kA currents with an accuracy of +/-5%);

· Current in neutral (0 to 10kA currents with an accuracy of +/-5%);

· VAN, VBN, VCN, VAB, VBC and VCA voltages (with an accuracy of +/- 2%);

· Three-phase active power;

· Three-phase reactive power;

· Lifetime of each vacuum interruptor;

· Fault distance (in km).