BE1 Numerical Systems Time Current Characteristic Curves and Time Dial Calculator (BNS-TCC-Rev_G.

XLS)

Disclaimer
This spreadsheet presents information about Basler Electric relays. It has been prepared as a convenience to our customers, and there is no expressed or implied
commitment to maintain or update this file. In developing this software, Basler has attempted to offer the most accurate information possible, but Basler does not
warrant that the software is free from bugs, errors or other program limitations. Users are encouraged to consult with a Basler Electric representative to determine
the accuracy of the data and results for the specific use or purpose of the user.

By use of this program, the user agrees that Basler disclaims all warranties of noninfringement of third party rights, quality, performance, merchantability, or fitness
for a particular purpose. The user assumes the entire risk as to the quality and performance of the software. In no event will Basler be liable for any indirect, special,
or consequential damages. In the event of any litigation regarding this software, the user agrees that the venue shall be the State of Illinois.

Purpose of this Spreadsheet


The purpose of this spreadsheet is as a tool to inspect Basler Electric inverse time overcurrent relay time current curves (TCC's), develop programmable curve
constants, and to serve as a tool for converting time dial settings for electro-mechanical (e-m) relays to the nearest equivalent time dial setting for your Basler
Electric overcurrent relay.

Basler Electric inverse time overcurrent relays provide TCC's that very closely emulate most of the common e-m induction disk relays that were manufactured in
North America. To further improve proper relay coordination, selection of integrated reset or instantaneous reset characteristics is also provided in most Basler
Electric relays. Even though the TCC curve shapes have been optimized to emulate various electro-mechanical (e-m) induction disk overcurrent relays, the e-m
relay time dial settings and Basler Electric relay time dial settings are not perfectly equivalent and the user may need to perform a complete coordination study in
cases where curve coordination timing is very tight.

This tool applies to the following relays:

The Basler CT Powered Protective Relay line:


BE1-50/51B BE1-50/51M CO, IAC Retrofit Line: BE1-50/51B -214, -218, -219, -225, -226, etc.
The following Basler Numerical Multifunction Protective Relay lines:
BE1-11 BE1-700 BE1-951 BE3-GPR BE1-1051
BE1-851 BE1-CDS240 BE1-IPS BE1-GPS BE1-CDS220
Note:

Some versions of the CT powered BE1-50/51 products listed above do not provide all of the curve types covered in this spreadsheet.
Programmable curves are not available in the BE1-50/51B, BE1-50/51M, and BE3-GPR relays. Please consult the appropriate bulletin
or instruction manual for the capabilities of each individual device.

This spreadsheet does not apply to the BE1-51 and 67 series relays.

Instructions and Notes


Using the spreadsheet to determine nearest equivalent e-m relay time dial.
1. Go to the sheet "TCC Curves and Graphs." Load in the curve for the relay you are trying to emulate by clicking on the appropriate button.
2. If you have a time and multiple of tap test point that you have previously calibrated the electromechanical relay to, simply enter in these two values into the
appropriate fields (cells H37, I37). The nearest Basler Electric time dial for the chosen curve will be calculated for you.
3. As an alternative approach, if you have a time dial setting for the electromechanical overcurrent relay, you may use the cross reference provided on the "EM
Relay Cross Reference" sheet to obtain the nearest equivalent Basler Electric time dial.

Notes on e-m curve equivalence:


1. The values in the cross reference table were obtained by inspection of the published electro-mechanical time current characteristic curve. The closest
approximately equivalent Basler Electric time dial setting was then entered into the cross reference table. The match is not perfect; see further notes below.

2. If your electro-mechanical relay time dial setting is between the values provided in the table, it will be necessary to interpolate (estimate the correct intermediate
value) between the electro-mechanical setting and the Basler Electric setting
3. The maximum time dial setting provided by Basler Electric relays is 9.9. The Basler Electric equivalent time dial setting for the maximum time dial setting provided
in the electro-mechanical relay is provided in the cross reference table even if it is calculated to be above 9.9. This is provided for the purpose of allowing
interpolation as noted above.
4. Basler Electric time/current characteristics are determined by a linear mathematical equation. An induction disk has a certain degree of non-linearity due to inertia
and friction effects. For this reason, even though every effort has been made to provide equation constants that provide characteristic curves with minimum deviation
from the published electromechanical curves, slight deviations can be observed between them.
In applications where the time coordination between curves is extremely close, we recommend that you choose the optimal time dial setting by inspection of the
coordination study.

Using the spreadsheet to plot curves.

1 12/29/2021 567461935.xls
It is fairly straightforward, but simply click on the appropriate button on the "TCC Curves and Calcs" sheet, and a plot of the curve shows up. You may either print
the entire sheet, or by clicking on the graph, print an enlarged graph the fills the page. Also, the TCC Curves and Calcs sheet provides a means of adding the
specific time dial that one will be using to the plot. Please inspect the sheet for this and other features.

Using the spreadsheet to develop the programmable curves constants.


The sheet "Programmable Curve Calcs" provides a means to develop a programmable curve from a set of points from your existing target TCC curve that you may
wish to emulate. See that sheet for instructions.

This spreadsheet is best viewed at 1024x768 or higher resolution.

Revision Notes:
Rev. A (2/6/98)
Corrected error in S2 curve constant B, which was set to 0.0280 rather than the correct 0.0208.
Rev. B (2/18/98)
Corrected drawing number reference for M curve.
Rev. C
Added graph page to TCC curves. Added some ability for users to plot programmable curves.
Rev. D0 (09/03)
General update. Added IEC curves A, B, C, and G. Added method to determine programmable curve constants via the Excel Solver Routine. Removed the multiple
sheets for various relay curves and moved info and calcs on those pages to the "Curve Constants" and "TCC Curves and Calcs" sheets. Renamed "Graphs" sheet
Rev E (05/09)
as "TCC
Added Curves
Curves F,and Calcs"
46, A1, sheetD1,
B1,C1, rearranged
E3, F1, P,content and added
T and updated a means
drawing for customer to plot user's time dial, the calculations for T given M and D, and D given T
numbers.
and M.
Rev F (05/09)
Removed reference to Publication 9-2520-00-999 which is obsolete
Rev G (12/16)
Added BE1-11 curves A1, B1, C1, D1, E3, and F1 to calculations

Basler Electric Company, 12570 State Route 143, Highland, Illinois 62249-1074 USA
Phone: 618/654-2341 - Fax: 618/654-2351 - Website: www.basler.com

2 12/29/2021 567461935.xls
Curve Plotting and Time Dial Calculations
S, S1 S2 Click the appropriate Curve Type E3 -- Time Characteristic Curves
Short Inverse
(CO-2) (IAC-55) button to plot a graph of 1000.00
L, L1 L2 G the time current
Long Inverse
(C0-5) (IAC-66) (IEC) characteristic.
D
Definite Time
(CO-6) Good viewing: It is intended that the
M D1 most important data on this sheet
Moderately Inverse
(CO-7) (IEEE MI) will fit onto a screen with a monitor
I, I1 I2 A A1 set at 1024x768 resolution, with
100.00
Inverse Excel's zoom set at 75%. It may be
(CO-8) (IAC-51) (Inv.) (IEC Inv.) helpful for one to experiment with
V, V1 V2 B B1 E3 zoom settings for best viewing on
Very Inverse the monitor being used.
(CO9) (IAC-53) (VI) (IEC VI) (IEEE VI)
E, E1 E2 C C1 F1
Extremely Inverse
(CO-11) (IAC-77) (EI) (IEC EI) (IEEE EI)

Time, Sec
Programmable P
10.00
Displayed Curve Name: E3
Approximately Equivalent to: N/A 9.
9
Curve Name IEEE Very Inverse
7
Drawing No. D2570-07 5
T=(A*D)/(M^N-C)+B*D+K 3
2
Curve Constants 1.
A B C N K 5
1.00 1
19.61000 0.49100 1.000 2.00000 0.0000 29.1 0.
7
Curve E3: Time delay T at your time dial D and multiples of pickup M: 0.
5
Time Dial Mult of PU Trip Time
Select a curve using buttons above, then enter a time dial (D) and multiple (D) (M) (T)
0.
3
of pickup (M). The trip time (T) will be calculated. 0.
1.0 2.000 7.028
2
0.
Curve E3: Finding Time Dial D closest to your test data or old E-M relay response: 1
0.10 0.
To find a setting nearest your old E-M relay, a) select nearest curve type Trip Time Mult of PU Time Dial 0
from buttons above, then b) enter a set of T and M points from your old (T) (M) (D) 4.
0
relay. D is shown to 2 decimal points, but the relays accept
increments of 0.1 only, in the range of 0.0 to 9.9. 1.000 3.000 0.34

Want to add your selected time dial to the TCC curve? Enter the time dial (D) that Time Dial
you wish to add to the TCC curve. Relay accepts time dials in 0.0 to 9.9 in 0.1 (D)
increments. 4.0
0.01
The cell to the right checks that all time dials above are in the All time dials above are in the relay's 1 10 100
range of 0.0 to 9.9. acceptable range Multiple of PU

3 12/29/2021 567461935.xls
Time Dial Setting Cross Reference Rev. B

This list is to assist a person that is trying to emulate an old electromechanical relay time with a Basler relay. The table gives the time dial of a Basler relay that most
closely matches the indicated time dial of the indicated relay. For instance, if one had a GE IAC 51 relay set at time dial 3, the appropriate curve in the Basler relay
would be the I2 curve set at a time dial of 2.7. If one is using some time dial that is between two time dials given in the table, one must interpolate and pick an
appropriate value between the two time dials.
The valid range for Basler numerical relay time dials is 0 to 9.9 in steps of 0.1. The table indicates some time dials outside this range, indicating that the relay cannot
reproduce the curve, but may be useful for interpolation purposes.

Electromechanical Relay Time Dial Setting


Approximately Curve Dwg. 0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0
Curve Name Equivalent to Number Basler Electric Approximately Equivalent Time Dial Setting
S, S1, Short Inverse ABB CO-2 99-1369 0.3 0.8 1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7
L, L1, Long Inverse ABB CO-5 99-1370 0.4 0.8 1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9
D, Definite Time ABB CO-6 99-1371 0.5 1.1 2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1
M, Moderately Inverse ABB CO-7 99-1372 0.4 0.8 1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8
I, I1, Inverse Time ABB CO-8 99-1373 0.3 0.7 1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0
V, V1, Very Inverse ABB CO-9 99-1374 0.3 0.7 1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6
E, E1, Extremely Inverse ABB CO-11 99-1375 0.3 0.7 1.5 2.4 3.2 4.2 5.0 5.7 6.6 7.8 8.5 10.3

I2, Inverse Time GE IAC-51 99-1597 0.6 1.0 1.9 2.7 3.7 4.8 5.7 6.8 8.0 9.3 10.6
V2, Very Inverse GE IAC-53 99-1596 0.4 0.8 1.6 2.4 3.4 4.3 5.1 6.3 7.2 8.4 9.6
S2, Short Inverse GE IAC-55 99-1595 0.2 1.0 2.0 3.1 4.0 4.9 6.1 7.2 8.1 8.9 9.8
L2, Long Inverse GE IAC-66 99-1594 0.4 0.9 1.8 2.7 3.9 4.9 6.3 7.2 8.5 9.7 10.9
E2, Extremely Inverse GE IAC-77 99-1598 0.5 1.0 1.9 2.7 3.5 4.3 5.2 6.2 7.4 8.2 9.9

4 12/29/2021 567461935.xls
Programmable Curve Constants Calculations
This Sheet calculates constants for the programmable curves given a user supplied set of time/current pairs and a target
time dial setting.
Notes:
1) To calculate the Programmable Curve constants, this sheet makes use of the Excel "Solver" Add-In. Solver is supplied with Excel, but
may not be installed in a partial installation of Excel, and even if installed, it needs to be enabled. You enable the Solver Add-In by the
clicking on the appropriate box in the Excel Menu: TOOLS / ADD-INS.
1b) Even if one cannot load and run the Solver Add-In, or if one has specific constants that need to be evaluated, one may enter
constants directly into the "Solution" fields below and plot the curves in the TCC Curves and Calcs Sheet.
2) When the Solver routine is run, the program minimizes cell G24, which is the RMS of "time error x sqrt(MOP)". The sqrt(MOP) factor forces
improved error at high MOP for higher accuracy at the fast end of the TOC curve.
3) Though an inspection of the time delay equation may at first make it appear there are 5 user-adjustable constants in the time equation (A, B, C,
N, and K), there are actually only 3 constants that can be varied: A, B, and N. The value of C is fixed at 1 so that curves will give a time delay that
rises to infinity at 1 multiple of pickup, and K is fixed at 0.028 in all Basler relays.

Desired
Step 1) a: Enter 5 data points from the time-current Multiple of Time Delay Time Dial (D) of Basler Relay to
curve of interest in the fields to the right. Pickup (M): (T) be used in calculations:
b: Enter in the Time Dial (D) of the Basler relay that Point 1 (Low MOP) 1.300 10.6580 1.0
you want to match to these points.
Point 2 2.000 2.4300
Point 3 4.000 0.5060
Point 4 10.000 0.1190
Point 5 (High MOP) 20.000 0.0700
Step 2) a: Run the Excel "Solver" routine by clicking on the Excel Menu: TOOLS / SOLVER.
b: Accept the Solver settings that you will see and click on "SOLVE."
c: When Solver is done, a dialog box will pop up. Select the option, "Keep Solver Solutions."
d: Go to the "TCC Curves and Calcs" sheet to plot the results.

Equation for time delay: T = A*D / ((M^N)-C) + B*D + K Curve Coefficient Definitions:
T: Time to Trip.
Allowed Curve Constants Ranges. If any of cells C17 to G17 below are red, D: Time Dial Setting.
user has entered a constant that is out of range. M: Multiples of Pickup.
Constant: A B C N K A, B: Curve Coefficients. Have a large role in
Min 0 0 1.00 0.50 0.028 Time Dial effects.
Max 600 25 1.00 2.50 0.028 C: Fixed at 1. Affects where curve rises to
infinite time.
Solution (Solver), or N: Curve coefficient. Has a major role in
7.762688 0.027509 1.000000 2.093918 0.028000
user data entry: inverseness of relay curve.
Desired Calculated Error Error x K: A fixed time delay adder.
Comparison: MOP
Time Time (seconds) sqrt(MOP)
1.300 10.6580 10.6580 0.0000 0.0001
2.000 2.4300 2.4301 -0.0001 -0.0001
4.000 0.5060 0.5062 -0.0002 -0.0004
10.000 0.1190 0.1185 0.0005 0.0014
20.000 0.0700 0.0702 -0.0002 -0.0008
RMS Error: 0.0002 0.0008

5 12/29/2021 567461935.xls
TEST1

0 0 1 0.5 0.028

Page 6
Curve Descriptions and Constants List
Equation
T=(A*D)/(M^N-C)+B*D+K
Where
Parameter Description Explanation
T Time to Trip Time that the 51 function will take to time out and trip.

D Time Dial Setting Time dial setting for the 51 function.

M Multiple of pickup Measured current in multiples of pickup. Timing algorithm


has a dynamic range of 0 to 40 time pickup.
A Coefficient specific Affects the effective range of the time dial.
to selected curve
B Coefficient specific Affects a constant term in the timing equation. Has greatest
to selected curve affect on curve shape at high multiples of tap.
C Coefficient specific Affects the multiple of PU where the curve would approach
to selected curve infinity if allowed to continue below pickup. Has greatest affect
on curve shape near pickup.
N Exponent specific Affects the inverseness of the characteristic. Has greatest
to selected curve affect on curve shape at low to medium multiples of tap.
K Constant Characteristic minimum delay term

Curve Description: Curve Constants:


Curve Short Designation: S or S1 A B C N K R
Approximately Equivalent to: ABB CO-2 0.26630 0.03393 1.000 1.2969 0.028 0.5000
Curve Name S, Short Inverse
Drawing No. D1089-10
Curve Short Designation: S2 A B C N K R
Approximately Equivalent to: GE IAC-55 0.02860 0.02080 1.000 0.9844 0.028 0.0940
Curve Name S2, Short Inverse
Drawing No. D2307-02
Curve Short Designation: L or L1 A B C N K R
Approximately Equivalent to: ABB CO-5 5.61430 2.18592 1.000 1.0000 0.028 15.7500
Curve Name L, Long Inverse
Drawing No. D1089-11
Curve Short Designation: L2 A B C N K R
Approximately Equivalent to: GE IAC-66 2.39550 0.00000 1.000 0.3125 0.028 7.8001
Curve Name L2, Long Inverse
Drawing No. D2307-01
Curve Short Designation: D A B C N K R
Approximately Equivalent to: ABB CO-6 0.47970 0.21359 1.000 1.5625 0.028 0.8750
Curve Name D, Definite Time
Drawing No. D1089-09
Curve Short Designation: M A B C N K R
Approximately Equivalent to: ABB CO-7 0.30220 0.12840 1.000 0.5000 0.028 1.7500
Curve Name M, Moderately Inverse
Drawing No. D1089-01
Curve Short Designation: I or I1 A B C N K R
Approximately Equivalent to: ABB CO-8 8.93410 0.17966 1.000 2.0938 0.028 9.0000
Curve Name I1, Inverse Time
Drawing No. D1089-02
Curve Short Designation: I2 A B C N K R
Approximately Equivalent to: GE IAC-51 0.27470 0.10426 1.000 0.4375 0.028 0.8888
Curve Name I2, Inverse Time
Drawing No. D2307-04
Curve Short Designation: V or V1 A B C N K R
Approximately Equivalent to: ABB CO -9 5.46780 0.10814 1.000 2.0469 0.028 5.5000
Curve Name V, Very Inverse

7 12/29/2021 567461935.xls
Drawing No. D1090-03
Curve Short Designation: V2 A B C N K R
Approximately Equivalent to: GE IAC-53 4.43090 0.09910 1.000 1.9531 0.028 5.8231
Curve Name V2, Very Inverse
Drawing No. D2307-03
Curve Short Designation: E or E1 A B C N K R
Approximately Equivalent to: ABB CO-11 7.76240 0.02758 1.000 2.0938 0.028 7.7500
Curve Name E, Extremely Inverse
Drawing No. D1090-04
Curve Short Designation: E2 A B C N K R
Approximately Equivalent to: GE IAC-77 4.98830 0.01290 1.000 2.0469 0.028 4.7742
Curve Name E2, Extremely Inverse
Drawing No. D2307-05
Curve Short Designation: A A B C N K R
Approximately Equivalent to: N/A 0.01414 0.00000 1.000 0.0200 0.028 2.0000
Curve Name Standard Inverse
Drawing No. D2570-06
Curve Short Designation: B A B C N K R
Approximately Equivalent to: N/A 1.46360 0.00000 1.000 1.0469 0.028 3.2500
Curve Name Very Inverse
Drawing No. D1089-07
Curve Short Designation: C A B C N K R
Approximately Equivalent to: N/A 8.25060 0.00000 1.000 2.0469 0.028 8.0000
Curve Name Extremely Inverse
Drawing No. D1089-05
Curve Short Designation: G A B C N K R
Approximately Equivalent to: N/A 12.12120 0.00000 1.000 1.0000 0.028 28.0000
Curve Name Long Time Inverse
Drawing No. D2570-07
Curve Short Designation: P A B C N K R
Approximately Equivalent to: N/A 7.76269 0.02751 1.00000 2.09392 0.02800
Curve Name Programmable - User
Drawing No. N/A
Curve Short Designation: F A B C N K R