Professional Documents
Culture Documents
ARL-300
Type-Approval Certificate No: NL 06-400-1002-048-04 rev. 2
The car at bottom floor. Wait RE relay pulls Wait RVD relay pulls
Test completes
No records ~40 seconds ~10 seconds ~15 seconds ~10 seconds
*:ARL-300 menu " Selector Type" parameter "ML1 & ML2 COUNTER" is assumed.In "ML1 & ML2
COUNTER" mode, if the car gets out of the levelling area, 142 signal is cut off. In "ML1&2 A3 COUNTER" mode,
if the car gets out of the levelling area, the 142 signal comes.
1.3.3. Valve self-monitoring function test
Prior to testing unintended movement of the car, the stopping distance of the protection system with the worst-case data
(with the worst load condition and the drive / control system failure due to maximum acceleration) must be theoretically
calculated. The calculated stopping distances should be appropriate to the distances shown in Section 4.
Response time of the components (ms):
The chart below shows the theoretical curve of the car in case of UCM in worst case:
V (m/s)
Xdz X1 X2 Xsv
t1 t2 t (s)
Xdz: Max. door zone = 200 mm (Max. 40 cm strip magnet can be used)
Vmax = Maximum speed of a hydraulic lift when leaving the door zone = 1,3 m/s (see Note-1)
Note-1: In the worst case, the speed that the A3 safety valve must stop the lift is 0,3 m/s more than the rated speed.
For higher speed the lift must be stopped by the pipe explosion valve. In the worst case this speed is assumed as 1,3
m/s.
Note-2: For cabinets in which height of the car door is 2000 mm, the permitted stopping distance is 1000 mm.
When 40 cm strip magnet used, max. permitted braking distance for A3 safety valve can be calculated as follows (Xsv):
Xsv = X(total) – (Xdz + X1 + X2) = 1000 – (200 + 13 + 13) = 774 mm
If this braking distance is not sufficient for the A3 safety valve, then the door zone magnets need to be shortened. Door
zone strip magnets used in ARL-300 control systems are 30 cm. When 30 cm strip magnets are used, the remaining
braking distance for A3 valve will be as follows:
In unintended movement of the car, the permitted stopping distances to stop the cabinet is as below:
Car
Shaft
Floor
Apron
Car entrance
- The car shouldn’t be more distant than 1,2 m from the floor. (For cabins with 2m height this distance is 1 m).
- The falling gap from the car or the floor to the shaft must not exceed 200 mm.
- Must have a minimum height of 1 m escape.
- These values must be provided in all values, including 100% of the rated load.
4. Considerations before UCM (Unintended Car Movement) test
4.1. Before starting the test, the required connections and settings described shall be checked.
4.2. If power is cut off while the lift is at door zone, ARL-300 controller activates door bridging function after one proper
travel. At the first travel after the power is on, ARL-300 controller checks ML1-ML2 door zone signals. If there is no fault
and no short circuit at ML1-ML2 door zone signals then door bridging function is activated.
4.3. With the firmware version V2.16 or later, a test function for UCM safety valve is provided in ARL-300 menu. This test
function should be used for UCM test.
4.3.1. To be able to use the UCM test function, the door bridging function should be enabled as shown below:
- Menu > “DOOR PRE OPENING” > “ENABLED”
4.3.2. There is a parameter in the menu named “UCM Test Mode”. This parameter has 3 options:
This setting is not stored in the memory. After the power is switched off and then switched on, the “UCM Test Mode”
parameter turns to “DISABLED”.
4.3.3. Set “UCM Test Modu” parameter to “Test with fast speed” and exit from the menu. ARL-300 does the
followings:
- Closes the doors
- Disables landing calls and car commands
- Activates door bridging circuit (door contacts are bridged)
- Works in “MANUEL MOVMENT” mode only on the card. In this mode, the car can be moved by pressing and
holding on the direction buttons (Up or Down) on the ARL-300 control card.
- When down direction button is pressed and hold, the car moves with high speed in the down direction
4.3.4. The UCM test shall be done with doors closed for safety purposes. But in order to simulate an open door, the door
safety circuit needs to be interrupted manually after door circuits are bridged (after UCM test function is enabled). To do
this, remove the wire from terminal 130 on the KBK-5 board to open the door safety circuit.
4.3.5. In case of UCM, ARL-300 gives “H24:UCM DETECTION ERROR” error and this blocks the lift permanently, even if
the power is switched off and on. To correct this error the fault list should be cleared by using "ERASE FAULT LIST"
parameter. To do this:
- Enter menu and come to “ERASE FAULT LIST” parameter.
- First, press up button and then press down button to clear the fault list.
UCM test to simulate the worst load condition, can be done by moving fully loaded car, down from the top.
d) Remove the wire from terminal 130 on the KBK-5 board (see 4.3.4)
e) Press the down button on ARL-300 keypad. Drive accelerates to rated speed in the down direction (see 4.3.3)
f) After leaving the door zone, because door bridging is interrupted, the power of the A3 safety valve is also switched off.
An emergency stop (UCM fall) occurs. ARL-300 gives “H24:UCM DETECTION ERROR” error.
g) Measure the stopping distance. Test is successful if the stopping distance is lower than the limit value. (see 3)
h) By switching the power off and on ARL-300 card continues to give "H24: UCM DETECTION ERROR" error.
i) Delete error list in the ARL-300 menu by using "ERASE FAULT LIST" parameter. UCM error is recovered and the lift
returns to the normal operation(see 4.3.5)