Spec. XXW Parallel Oper.

Controller 0P1922A
Project: XXW Reg. No. 0P1922A SPEC
Originator: SKI Date: 22.02.2010 Rev. No. 1
Checked: THA Rev. Date: Page: 1/5

Summary:
This document specifies the XXW Parallel Operation Controller 0P1922A.

Rev. Date Initials Remark


1 22.02.2010 SKI Taken over specification of 0P1922 from document
“7.600.120GB” and updated according new rules.

Table of Contents:
1. Functionality of the Board ............................................................................................................. 2
1.1. SYNCHRONIZATION ............................................................................................................. 2
1.2. OPERATION CONTROL ........................................................................................................ 2
1.3. LOAD SHARING..................................................................................................................... 2
2. Power supply ................................................................................................................................ 3
3. Connection cable .......................................................................................................................... 3
4. Configuration................................................................................................................................. 3
5. Mechanical .................................................................................................................................... 4
6. Reference Documents .................................................................................................................. 5

0P1922A_SPEC.doc
Spec. XXW Parallel Oper. Controller 0P1922A
Project: XXW Reg. No. 0P1922A SPEC
Originator: SKI Date: 22.02.2010 Rev. No. 1
Checked: THA Rev. Date: Page: 2/5

1. FUNCTIONALITY OF THE BOARD


The parallel operation controller is used for controlling two or more, however max. 9 parallel
Datapower or UPS systems. The function of this controller is synchronization, operation control
between different operational modes as well as load sharing. Communication between the parallel
systems is galvanically insolated.

1.1. SYNCHRONIZATION
Frequency range: 45-65Hz.
Synchronization speed: About 2Hz/Sec.
(The synchronization of the main controller must be set to fixed slew-rate 4Hz/Sec., meaning that
adaptive slew-rate is set off).

1.2. OPERATION CONTROL


Redundant principle, meaning that the systems being able to operate in inverter operation will
continue operating in this mode in case of inverter failures in other systems. At overload of a
system operating in inverter operation, all systems will switch over to bypass.
As regards Datapower systems, the systems being able to operate in normal operation will
continue operating in this mode in case of mains voltage failures in other systems. At overload of a
system operating in normal operation, all systems will switch over to battery operation.

1.3. LOAD SHARING


Principle:
Automatic regulation of output voltage, to obtain optimum load sharing of reactive load.
Automatic regulation of phase angle, to obtain optimum load sharing of ohmic load.
Symmetric up/down regulation round nominal output voltage ensures statically stable output
voltage at 0 to 100% load.
Accuracy:
Max. difference in load between two arbitrary systems at full load: 5% at nominal output current per
system.
Typ. difference in load: 2%.
Max. current between two no-load systems: 10% of nominal output current.
(Condition of specified load sharing:
Max. tolerance on measuring values of current transformers ±1%.
Max. tolerance on pre-adjusted output voltage ±1%.
Max. tolerance on filter components, that is AC-choke, capacitor module on output, and
magnetizing current in main transformer ±10%).

0P1922A_SPEC.doc
Spec. XXW Parallel Oper. Controller 0P1922A
Project: XXW Reg. No. 0P1922A SPEC
Originator: SKI Date: 22.02.2010 Rev. No. 1
Checked: THA Rev. Date: Page: 3/5

2. POWER SUPPLY
+12V (+10...15V) max. 200mA
12V (10...15V) max. 100mA
+ 5V (+4,75...5,5V) max. 200mA

3. CONNECTION CABLE
Multiple cable 14-link + shield, for example 14 x 0,14mm2 + shield.
Max. cable length between systems: total 100m (at typical cable about 120pF/meter, 140mÙ/m).
Internal connection in systems: 2 pcs. 14-link ribbon cables to 2 pcs. 15-pole SUB-D female plugs,
crimp type.
1 pc. 40-link ribbon cable to main controller.

4. CONFIGURATION
No configuration need to be done on the hardware of the XXW Parallel Operation Controller board.

0P1922A_SPEC.doc
Spec. XXW Parallel Oper. Controller 0P1922
Project: XXW Reg. No. 0P1922 SPEC
Originator: SKI Date: 22.02.2010 Rev. No. 1
Checked: THA Rev. Date: Page:

MECHANICAL
 Size of the PCB is 160 x 233 x 30mm.
 The PCB is populated on one side only.
 Component technology is THT only.
 PCB thickness is 1.6mm
 PCB is a 2 layer board
 The copper layer thickness is 35um
 Assembly weight: 300 g

POWER SUPPLY +12V (+10...15V) max. 200mA


12V (.10...15V) max. 100mA
+ 5V (+4,75...5,5V) max. 200mA

0P1922_SPEC.doc
Spec. XXW Parallel Oper. Controller 0P1922A
Project: XXW Reg. No. 0P1922A SPEC
Originator: SKI Date: 22.02.2010 Rev. No. 1
Checked: THA Rev. Date: Page: 5/5

6. REFERENCE DOCUMENTS
For more details please refer to the following documents, where “x” stands for the latest revision:
 0P1922A Schematic.pdf Schematic drawing
 0P1922A Block Diagram.pdf Block diagram
 0P1922A_Functional_Description.doc Functional description
 640-4054A_REV06.zip PCB fabrication data
 0P1922A_rev01_x_BOM.xls Bill of material
 0P1922A_rev01_x_MTS.doc Module test specification

0P1922A_SPEC.doc