INSTALLATION & INSTRUCTION

MANUAL

AIR TO WATER
HEAT PUMP
Notice
1.1 In order to use this product better and safer, please read this instruction
carefully before install and operate it. Please pay attention to all the notice in
operation and maintenance. Save all manuals and documentation for future
reference.

1.2 Air to water pump is a special appliance. Improper installation will cause
damage and danger. It should be installed and maintained by the professionals.
Please contact our authorized local service point for installation and maintenance.
Please read and follow this instruction carefully before and during installation.
Remarks:
We will not bear the responsibility for any personal injury or unit damage caused
by non-Compliance of the regulations and instruction in this manual.

1.3 Please check whether the distribution power capacity, switch and socket
are compliance with the requirements of our unit power. Details please refer
to the rating label or parameter table in this manual.

1.4 The power should be equipped with leakage protection separately.


Power cable should be chosen in accordance with the operation
requirements of the unit.

1.5 The unit must be grounded safely. Do not use the unit if grounded unsafely.
Do not connect the ground line to the neutral and or tap water pipe.

1.6 The wire must be joined in compliance with the requirements of the wiring chart.
Do not alternate and or repair the unit personally.

1.7 Do not install the unit closed to inflammable, explosive and naked light spot.

1.8 To ensure the unit operate properly, please equipped with a filter in the water
input when installation.
CONTENTS
I.Specification.................................................. .............................1
1.Model Nomenclature .............................................................. 1
2.Parameter of multi-function air to water heat pump.................... 1
3.Product appearance and installation dimension........................ 3
II.Installation................................................................................ 5
1.Unit installation position......................................................... 5
2.Installation requirement......................................................... 6
3.Water tank installation select.................................................. 6
4.The unit and water tank installation ......................................... 6
5.Water system installation drawing........................................... 7
6.Installation of terminal equipment............................................ 8
7.Pipe connection..................................................................... 8
8.Installation of the temp.detector.............................................. 9
9.Electrical wiring .................................................................... 9
10.Electrical wire selection ........................................................ 10
11.Trial operation ...................................................................... 12
III.Use........................................................................... .............. 13
1. Single unit controller interface displays................................... 13
2. Operation of wired controller.................................................. 14
3. Check the unit running state.................................................. 18
4. Modify parameters of user level............................................. 18
V.Maintenance and repair............................................. . ............... 21
1.Malfunction indicating table................................................... 21
2.Note..................................................................................... 24
3.Determine and solve malfunction by below table....................... 24
V.Wiring diagram .......................................................... ................ 26
1.MK5064 PCB input and output port definition............................ 26
2.MK5065 PCB input and output port definition............................ 27
3.Unit wiring diagram ............................................................... 30
I.Specification
1.Model Nomenclature
MA CHR W S *** ZA / PS(B D)
Source medium
MA: Air source
MW: Ground source D:With electrical heating
MD: Double soruce (Without electrical heating omitted)

Function of the unit B: DC Inverter


C: Air cooling E: EVI
R: Air heating (Without inverter or EVI omitted)
H: Hot water S:3phase (single phase omitted)
CR: Air cooling and heating
CHR: Air (heating+cooling) and hot water P:With built in pump
(Without built in pump omitted)
Energy exchange medium
A: Refrigerant A: Horizontal fan direction
W: Water B: Upward fan direction
S:with solar (Omit the split type unit model)
(Without solar omitted)
The figure represents the horse power of unit
Z: Integrated type
eg:010 means 1 horse power
W: Split type(indoor unit )
2.Parameter of multi-function air to water heat pump
2.1 Horizontal fan direction type
① Cooling : DB 35℃/WB 24℃ ,Outlet water temp. :7℃,Input water temp.:12℃
② Heating : DB 7℃/WB 6℃ ,Outlet water temp. :35℃,Input water temp.:30℃
③ Heating : DB 7℃/WB 6℃ ,Outlet water temp. :45℃,Input water temp.:40℃
EVI Technology Using in ambient temperature: -25℃~43℃
Normail Technology Using in ambient temperature:-15℃~43℃
NOTE:If the unit only have cooling model ,only the cooling parameter effective for it.
Unit Model 1 MAHW 010ZA/P(E)(01)
015ZA/PS(E)(01)
020ZA/PS(E)(01)
025ZA/P(E)(01)
030ZA/P(E)(01) 040ZA/P
(E)
(01)
035ZA/P(E)(01) 045ZA/P(E)(01)
060ZA/P(E)(01)
080ZA/P(E)(01)
090ZA/P(E)(01)
100ZA/P(E)(01)
040ZA/PS(E)(01)
050ZA/PS(E)(01)
060ZA/PS(E)(01)
070ZA/PS(E)(0
Unit Model 2 MAHRW / / / 030ZA/P(E)(01)
025A/P(E)(01) 035ZA/P(E)(01)
040ZA/P
(E) 045ZA/P(E)(01)
(01) 060ZA/P(E)(01)
080ZA/P(E)(01)
090ZA/P(E)(01)
/ 040ZA/PS(E)(01)
050ZA/PS(E)(01)
060ZA/PS(E)(01)
070ZA/PS(E)(0
Unit Model 3 MACRW010ZA/P(E)(01)
015ZA/PS(E)(01)
020ZA/PS(E)(01) 030ZA/P(E)(01)
025ZA/P(E)(01) 035ZA/P(E)(01)
040ZA/P
(E) 045ZA/P(E)(01)
(01) 060ZA/P(E)(01)
080ZA/P(E)(01)
090ZA/P(E)(01) 040ZA/PS(E)(01)
100ZA/P(E)(01) 050ZA/PS(E)(01)
060ZA/PS(E)(01)
070ZA/PS(E)(0
Unit Model 4 MACHRW / / / 030ZA/P(E)(01)
025A/P(E)(01) 035ZA/P(E)(01)
040ZA/P
(E) 045ZA/P(E)(01)
(01) 060ZA/P(E)(01)
080ZA/P(E)(01)
090ZA/P(E)(01)
/ 040ZA/PS(E)(01)
050ZA/PS(E)(01)
060ZA/PS(E)(01)
070ZA/PS(E)(0
Rated Output Water L/h 75 115 150 188 225 265 300 338 450 600 675 750 300 375 450 525
Rated Cooling Capacity kW 2.5 3.8 5.0 6.3 7.5 8.8 10.0 11.2 15.0 20.0 22.5 25.0 10.0 12.5 15.0 17.5
Rated Input power(Cooling) kW 0.88 1.33 1.75 2.21 2.63 3.09 3.51 3.93 5.26 7.02 7.89 8.77 3.51 4.39 5.26 6.14
Rated Input Current(Cooling) A 4.0 6.1 8.0 10.0 12.0 14.0 15.9 17.9 23.9 31.9 35.9 39.9 6.7 8.3 10.0 11.7
Rated Heating Capacity ① KW 3.5 5.3 7.0 8.8 10.5 12.3 14.0 15.8 21.0 28.0 31.5 35.0 14.0 17.5 21.0 24.5
COP ① W/W 4.30 4.30 4.30 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65
Rated Input power(Heating)① KW 0.81 1.23 1.63 1.89 2.26 2.65 3.01 3.40 4.52 6.02 6.77 7.53 3.01 3.76 4.52 5.27
Rated Input Current(Heating)① A 3.4 5.6 7.4 8.6 10.3 12.0 13.7 15.4 20.5 27.4 30.8 34.2 5.7 7.2 8.6 10.0
Rated Heating Capacity② KW 2.8 4.1 5.5 6.9 8.3 9.6 11.0 12.4 16.5 22.0 24.0 27.5 11.0 13.75 16.5 19.3
COP ② W/W 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26
Rated Input power(Heating)② KW 0.86 1.26 1.69 2.12 2.55 2.94 3.37 3.80 5.06 6.75 7.36 8.44 3.37 4.22 5.06 5.92
Rated Input Current(Heating) ② A 3.9 5.7 7.7 9.6 11.6 13.4 15.3 17.3 23.0 30.7 33.5 38.3 6.4 8.0 9.6 11.3
Rated Heating Capacity ③ KW 3.0 4.5 6.0 7.5 9.0 10.5 12.0 13.5 18.0 24.0 27.0 30.0 12.0 15.0 18.0 21.0
COP ③ W/W 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12
Rated Input power(Heating) ③ KW 0.73 1.09 1.46 1.82 2.18 2.55 2.91 3.28 4.37 5.83 6.55 7.28 2.91 3.64 4.37 5.10
Rated Input Current(Heating)③ A 3.3 5.0 6.6 8.3 9.9 11.6 13.2 14.9 19.9 26.5 29.8 33.1 5.5 6.9 8.3 9.7
Power supply V/PH/Hz220/1/50220/1/50 220/1/50 220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50220/1/50380/3/50 380/3/50 380/3/50 380/3/50
Max.current A 6.0 9.1 12.0 15.1 17.9 21.1 23.9 26.8 35.9 47.8 53.8 59.8 10.0 12.5 15.0 17.5
Noise dB(A) 48 48 48 50 52 52 54 54 55 58 59 59 54 54 55 55
Compressor Rotary Rotary Rotary Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Water Outlet/Water Inlet inch 3 /4″ 3 / 4″ 1″ 1″ 1″ 1″ 1″ 1″ 1″ 1-1/4″ 1-1/4″ 1-1/4″ 1″ 1″ 1″ 1″
Water Flow volume m3/h 0.60 0.91 1.20 1.51 1.81 2.12 2.41 2.72 3.61 4.82 5.42 6.02 2.41 3.01 3.61 4.21
Refrigerant type R410a/R407C

1
2.2.Upwards fan direction type
Unit Model 1 MAHW 010ZB/P(E)(01)
015ZB/P(E)(01)
020ZB/P(E)(01) 030ZB/P(E)(01)
025ZB/P(E)(01) 035ZB/P(E)(01)
040ZB/P(E)(01) 060ZB/P(E)(01)
045ZB/P(E)(01) 090ZB/P(E)(01)
080ZB/P(E)(01) 100ZB/P(E)(01)
040ZB/PS(E)(01)
050ZB/PS(E)(01)
060ZB/PS(E)(
Unit Model 2 MAHRW / / / 030ZB/P(E)(01)
025ZB/P(E)(01) 035ZB/P(E)(01) 060ZB/P(E)(01)
045ZB/P(E)(01)
040ZB/P(E)(01) 090ZB/P(E)(01)
080ZB/P(E)(01) / 040ZB/PS(E)(01)
050ZB/PS(E)(01)
060ZB/PS(E)(
Unit Model 3 MACRW 010ZB/P(E)(01)
015ZB/P(E)(01) 030ZB/P(E)(01)
025ZB/P(E)(01)
020ZB/P(E)(01) 035ZB/P(E)(01) 045ZB/P(E)(01)
040ZB/P(E)(01) 060ZB/P(E)(01) 090ZB/P(E)(01)
080ZB/P(E)(01) 100ZB/P(E)(01)
040ZB/PS(E)(01)
050ZB/PS(E)(01)
060ZB/PS(E)(
Unit Model 4 MACHRW / / / 030ZB/P(E)(01)
025ZB/P(E)(01) 035ZB/P(E)(01) 060ZB/P(E)(01)
045ZB/P(E)(01)
040ZB/P(E)(01) 090ZB/P(E)(01)
080ZB/P(E)(01) / 040ZB/PS(E)(01)
050ZB/PS(E)(01)
060ZB/PS(E)(
Rated Output Water L/h 75 115 150 188 225 265 300 338 450 600 675 750 300 375 450
Rated Cooling Capacity kW 2.5 3.8 5.0 6.3 7.5 8.8 10.0 11.2 15.0 20.0 22.5 25.0 10.0 12.5 15.0
Rated Input power(Cooling) kW 0.88 1.33 1.75 2.21 2.63 3.09 3.51 3.93 5.26 7.02 7.89 8.77 3.51 4.39 5.26
Rated Input Current(Cooling) A 4.0 6.1 8.0 10.0 12.0 14.0 15.9 17.9 23.9 31.9 35.9 39.9 6.7 8.3 10.0
Rated Heating Capacity ① KW 3.5 5.3 7.0 8.8 10.5 12.3 14.0 15.8 21.0 28.0 31.5 35.0 14.0 17.5 21.0
COP ① W/W 4.30 4.30 4.30 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65 4.65
Rated Input power(Heating)① KW 0.81 1.23 1.63 1.89 2.26 2.65 3.01 3.40 4.52 6.02 6.77 7.53 3.01 3.76 4.52
Rated Input Current(Heating)① A 3.7 5.6 7.4 8.6 10.3 12.0 13.7 15.4 20.5 27.4 30.8 34.2 5.7 7.2 8.6
Rated Heating Capacity② KW 2.8 4.1 5.5 6.9 8.3 9.6 11.0 12.4 16.5 22.0 24.0 27.5 11.0 13.75 16.5
COP ② W/W 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26 3.26
Rated Input power(Heating)② KW 0.86 1.26 1.69 2.12 2.55 2.94 3.37 3.80 5.06 6.75 7.36 8.44 3.37 4.22 5.06
Rated Input Current(Heating) ② A 3.9 5.7 7.7 9.6 11.6 13.4 15.3 17.3 23.0 30.7 33.5 38.3 6.4 8.0 9.6
Rated Heating Capacity ③ KW 3.0 4.5 6.0 7.5 9.0 10.5 12.0 13.5 18.0 24.0 27.0 30.0 12.0 15.0 18.0
COP ③ W/W 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12 4.12
Rated Input power(Heating) ③ KW 0.73 1.09 1.46 1.82 2.18 2.55 2.91 3.28 4.37 5.83 6.55 7.28 2.91 3.64 4.37
Rated Input Current(Heating)③ A 3.3 5.0 6.6 8.3 9.9 11.6 13.2 14.9 19.9 26.5 29.8 33.1 5.5 6.9 8.3
Power supply V/PH/Hz220/1/50 220/1/50 220/1/50 220/1/50 220/1/50 220/1/50 220/1/50 220/1/50220/1/50 220/1/50220/1/50 220/1/50 380/3/50 380/3/50 380/3/50
Max.current A 6.0 9.1 12.0 15.1 17.9 21.1 23.9 26.8 35.9 47.8 53.8 59.8 10.0 12.5 15.0
Noise dB(A) 48 48 48 50 52 52 54 54 55 58 59 59 54 54 55
Compressor Rotary Rotary Rotary Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Water Outlet/Water Inlet inch 3/4" 3/4" 1" 1″ 1″ 1″ 1″ 1″ 1″ 1-1/4″ 1-1/4″ 1-1/4″ 1″ 1″ 1″
Water Flow volume m3/h 0.60 0.91 1.20 1.51 1.81 2.12 2.41 2.72 3.61 4.82 5.42 6.02 2.41 3.01 3.61
Refrigerant type R410a/R407C

Indoor Unit Model 1 MAHW 080ZB/PS(E)(01)


100ZB/PS(E)(01)
120ZB/PS(E)(01)
200ZB/PS(E)(01)
250ZB/PS(E)(01)
300ZB/PS(E)
Indoor Unit Model 2 MAHRW 080ZB/PS(E)(01)
100ZB/PS(E)(01)
120ZB/PS(E)(01)
200ZB/PS(E)(01)
250ZB/PS(E)(01)
300ZB/PS(E)
Indoor Unit Model 3 MACRW 080ZB/PS(E)(01)
100ZB/PS(E)(01)
120ZB/PS(E)(01)
200ZB/PS(E)(01)
250ZB/PS(E)(01)
300ZB/PS(E)
Indoor Unit Model 4 MACHRW 080ZB/PS(E)(01)
100ZB/PS(E)(01)
120ZB/PS(E)(01)
200ZB/PS(E)(01)
250ZB/PS(E)(01)
300ZB/PS(E)
Rated Output Water L/h 600 750 900 1500 1875 2250
Rated Cooling Capacity kW 20.0 25.0 30.0 50.0 62.5 75.0
Rated Input power(Cooling) kW 7.02 8.77 10.53 17.54 21.93 26.32
Rated Input Current(Cooling) A 13.3 16.7 20.0 33.4 41.7 50.0
Rated Heating Capacity ① KW 28.0 35.0 42.0 70.0 87.5 105.0
COP ① W/W 4.65 4.65 4.65 4.65 4.65 4.65
Rated Input power(Heating)① KW 6.
02 7.
53 9.
03 15.05 18.
8 22.
58
Rated Input Current(Heating)① A 11.4 14.
3 17.2 28.6 35.
8 42.
9
Rated Heating Capacity② KW 22.0 27.5 36.0 60.0 75.0 90.0
COP ② W/W 3.26 3.26 3.26 3.26 3.26 3.26
Rated Input power(Heating)② KW 6.75 8.44 11.04 18.40 23.01 27.61
Rated Input Current(Heating) ② A 12.8 16.0 21.0 35.0 43.7 52.
Rated Heating Capacity ③ KW 24.0 30.0 38.4 64.0 80.0 96.0
COP ③ W/W 4.12 4.12 4.12 4.12 4.12 4.12
Rated Input power(Heating) ③ KW 5.83 7.28 9.32 15.53 19.42 23.30
Rated Input Current(Heating)③ A 11.1 13.8 17.7 29.5 36.9 44.3
Power supply V/PH/Hz 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50
Max.current A 20.0 25.
0 30.0 50.
0 62.5 75.1
Noise dB(A) 58 59 60 65 66 68
Compressor Scroll Scroll Scroll Scroll Scroll Scroll
Water Outlet/Water Inlet inch 1-1/4″ 1-1/4″ 1-1/4″ 2″ 2″ 2-1/2″
Water Flow volume m3/h 4.82 6.02 7.22 12.04 .05
15 18.06
Refrigerant type R410A/R407C

2
3. Product appearance and installation dimension

A D

Units: mm Units: mm
MACHRW MACHRW 040ZA 045ZA
020ZA 030ZA 035ZA 035ZA/ S
Size Size 045ZA/ S

A 380 440 A 440 440


B 630 756 B 750 750
C 886 1115 C 1115 1115
D 550 700 D 935 935

D Units: mm
B
MARW 050ZA/S 060ZA/S
Size
A 440
A
B 750
C 1115
C D 1250

A
Units: mm
045ZB/S
MACW 025ZB 030ZB
050ZB/S
Size 035ZB 040ZB
060ZB/S
B D
A 450 450
B 756 860
C 676 780
C D 732 960

3
A

B D
C
Units: mm
MACW 100ZB/S 120ZB/S
080ZB/S
Size
A 708 708
B 750 750
C 1450 1450
D 1070 1270

Units: mm
MACW
150ZB/S
Size
A 2150
B 769
C 1150

G K
H
F
J
N D E M L
B Mode:MACHRW250ZB/S(01)
Sign Meaning Size(mm)
A High 2090
B Length 2006
C Wide 1003
C

D 1280
E 363
F Distance between 545
G 490
H 490
J 145
K Water outet 2"
L Water inlet 2"
M Electrical box
N Starting stents

4
II. Installation
1. Unit installation position
To avoid ventilation short, the r unit discharged air should not return when installation.
Please keep enough space around the unit for repair. Right and wrong means as below:
Wrong Right

! Notice:

1. To get enough air for ventilation of the unit, the installation position should be with good
ventilation.
2. The installation position can hold the outdoor unit without noise and shake.
3. No sunlight to the unit. Set an awning if necessary.
4. The water from rain and defrosting can be discharged in the installation position.
5. The unit will not be covered by snow in the installation position.
6. The discharged air will not face strong air in the installation position.
7. Assure the noise caused by the unit ventilation and operation will not affect the
neighbour.
8. The installation position will not be affected by garbage, oil and mist.
9. The unit will be damaged under the condition with oil(engine oil), salt(sea area)
and sulfide air(near thermal spring and refining factory).

5
2. Installation requirement
2.1. The unit can be installed in the balcony, roof, floor or any other convenient place and reliable
load-bearing.
2.2.Airiness place.
2.3.No heat radiation or other heat source place
2.4.Should be set up shed against the snow in winter.
2.5.Barrier-free at the air inlet or outlet place.
2.6.Outlet against strong winds blowing place.
2.7.There should be drainage channels around the machine in order to rule out the condensate.
2.8.Control Panel, do not install in the bathroom, so as not to affect the unit work by wet.
2.9. Should leave enough space around the machine. As shown below.
A、Side fan type installation space requirements:

≥600mm
≥500mm
≥300mm

≥1500mm
≥500mm

≥600mm

≥600mm Unit
≥200mm

≥200mm
Air outlet
Unit
Air intlet

Bolt Bolt
Unit fix fix

≥200mm

B、Top fan type installation space requirements:


≥2000mm

≥600mm ≥400mm
≥700mm

≥700mm
≥400mm

≥400mm

Bolt
fix

≥1000mm
≥1000mm

3.hot water tank(water tank)and buffer tank(water tank) install location select
3.1.The water tank can be installed in the outdoor with heat pump outdoor unit, such as balconies,
roofs, floors, also can be installed in the room.
3.2.Water tank must be standing install, the installation place is a solid foundation, must be bear
the weight of the tank when full of water.
3.3.Around the water tank , as well as water pipes and hot water pipes should install a valve.
3.4.Do not install the water tank, where exist pollute and corrosive gases.

4.The unit and water tank installation


4.1.Unit install base is concrete structures, also can be made of steel angle brackets, plus vibration
rubber pad placed on the ground or roof, to ensure the unit horizontally.
4.2.Installed base design should in accordance with units and water tanks installed size
And operational quality.
4.3.Directly use expansion bolts to fix unit and water tank to the concrete base.
4.4.Around the unit and tank should be drain or outlet.

6
5. Water system installation drawing
Hot water Water supply Unit electric box
tank temp. return temp. Water filling Water supply Water supply Hot water
valve return valve cycle pump cycle pump
High water High water power output power output power output power output
level level (220V1PH/50Hz) (220V1PH/50Hz)
R S T N
(220V1PH/50Hz) (220V1PH/50Hz)

L N 1 2 L N 1 2

QS
ROOM

1
A B C D 2 3 7
U V W N
Power input
M SET

Wire controller 5 (380VAC/3PH/50Hz)

5.1 Installation diagram of pressure-bearing type water tank


B
Cold water inlet

2 3
Air outlet
C

D
6
A
Unit
Cold water
5 inlet
7

1
4
1
Drain outlet

Note: 1 because the ground wire of water tank take participate in the control of water filling , so, please connect
water tank shell to the ground wire, and connect with the unit ground wire together, see the picture as below.

5.2 Installation diagram of pressure-bearing type water tank

Cold water
inlet

Air outlet

Unit A 6

8
1

B Drain outlet
Cold water 5
inlet
Legend:
Globe valves Shower head 7 Hot water cycle pump
Electric driven two-way valve 1 Unit 8 Pressure-bearing type
Check valve 2 Water filling valve water tank
Water pressure switch 3 Water supply return valve A Hot water tank temp.
Water temp. sensor 4 Open wide type hot water tank B Water supply return temp.
5
C High water level
Expansion Tank Water supply cycle pump
6 Bath room
D Low water level

7
6.Installation of terminal equipment
6.1.Indoor terminal equipment installation (such as: fan coil, radiator heater or floor heating), the
equipment should be installed in accordance with relevant regulatory requirements.
6.2.In accordance with the requirements of engineering design drawings, installation and
construction.
6.3.Use a soft connector to connect the unit and fan coil inlet and outlet pipes; install fan coil
condensate drain pipe, connect the condensate drain interface, and to ensure smooth drainage
of condensate water.
7.Pipe connection
7.1.Pipe material selection, can be stainless steel pipe, copper pipe, aluminum water pipe, hot
water PPR pipes and so on, according with national health and safety standards, heat-
resistant, rust-proof, no scaling pipe.
7.2.The choice of pipe sizes can be used the one which is matches the heat pump inlet and outlet
main pipe, and, respectively connect to heat pump inlet and outlet, and follow the proper
construction of plumbing standards.
7.3.Water tank outlet pipe and overflow pipe installed in the gutter or outlet position as far as
possible, where convenient to drainage.
7.4.The unit and the junction to the tank must be installed valve or demolition loose joint, for
maintenance use.
7.5.Water pipes are arranged reasonably to minimize bending and reduce the pressure loss of
water system
7.6.The unit air-conditioning side and the hot water side circle inlet must be installed a above 50
mesh water filter to reduce the water system resistance loss.
7.7.The unit air-conditioning side and the hot water side which connect to running water must be
installed a one-way valve, filter and pressure relief devices (pressure relief devices used on
the closed water tank, water tank accessories in general, the parameter value ≤ 0.7MPa), in
accordance with the flow and valve arrow direction, to avoid flow be obstructed.
7.8.The unit hot water side circle outlet connect to tank circle inlet, and the host hot water side
circle inlet connect to tank circle outlet,tank hot water supply connect to hot water pipe.
7.9.Air-conditioning side buffer tank in series installed on the outlet of the main pipe.
7.10. After hot water side and air-conditioning side water system pipes, circulated pipes, hot water
supply pipes connected, it must be pipe connection rigorous testing , plus 0.7Mpa pressure
testing 24 hours, system pipes connector no leakage and clean and sewage pipes, to ensure
that the system clean, no debris. No leakage after the test, then pack the pipe and valve with
insulation (including the replenishment pipes and valves).
7.11.In order to discharge the water system air clean, avoid air trapping in the pipeline, the water
supply return pipe highest point should be set up a automatically exhaust valve.
7.12.The water system expansion tank, automatic water valve and stop valve should be installed
indoors, to prevent water pipes and valves crack when not use in the winter.
7.13.The metal pipe must be used above 50mm thickness of glass fiber or high-density fire
retardant PE for thermal insulation and moisture, PPR water pipe can be used 30mm
thickness of glass fiber or high-density fire retardant PE for thermal insulation and moisture to
prevent cold, heat loss and condensation.

8
7.14.The unit water inlet and outlet must install a thermometer, water pressure gage, to facilitate
inspection when operate.
Note:
1) Tubing pipeline should be separate test pressure, must not test with hot water unit or tanks.
  2) The Water system allows working pressure range: 0.2-0.7 MPa.
  3) The Water system allows working temperature range: 5-75 ℃.
4) Water can drain from the pressure relief device drainage pipe, and the piope keep open to
atmosphere.
5) The pressure relief device regularly move to remove the calcium carbonate, and prove that
the device is not plugged.
6) Installation of one-way valves, filters and pressure relief device, valve body arrow as same
as flow direction .
7) The pressure relief device discharge pipe should be installed in the frost-free environment in
A continuous down way.
8.Installation of the temp detector

Tank Tank Tank Tank


Detector Detector Detector Detector
The head
The head of sensor
The head The head of sensor
of sensor of sensor
<Ф5 pin
<Ф5 pin
<Ф5 pin
The heat
conduction The heat
silica gel conduction
silica gel
The heat
conduction
silica gel

The first step The second step The third step The fourth step

8.1.The first step:Daub the heat conduction silica gel spreads in the front of sensor, and insert
into the detector.
8.2.The second step:use < Ф 5 pin to push the detector into the end of the detector against the
end of the sensor, and marks on level of the pin and the detector.
8.3.The third step:putout the pin,the position of mark to be at the same level with the inlet of
detector,check whether the sensor is inserted to the pipe terminal.
8.4.The fourth step:the inlet of the detector is sealed with the glass silica gel, and keep the inlet
of the detector upwards and uprightness about an hour。
9.Electrical wiring
9.1.The unit should use dedicated power supply, power supply voltage line corresponding
with rated voltage.
9.2.The unit power cable must use copper cable, the cable diameter must ensure that
the unit's maximum starting current requirements.
9.3.The unit power supply circuit must have a grounding wire, which should connect with
a reliable external ground wire, and the external ground wire is effective.

9
9.4.Wiring construction must be installed by professional technicians refer to circuit diagram.
9.5.Power lines and signal line layout should be neat, rational, strong and weak lines separate
and can not interfere with each other, while not contacted with the connecting pipe and the
valve body.
9.6.When power lines and control lines parallel, the wires were placed in each tube, also
leave appropriate distance between the lines.
9.7.Unit electric wire connection: take the unit power line, remote control three core lines,
electric heater power line, solar circulated water pump control power line, water tank
temperature sensing line, solar collector temperature sensor line, terminal equipments
connect to unit lines, through the unit wiring hole set into the electrical box, connect to the
appropriate terminals according to wiring diagram, and fix it by the pressure line of board in the
electrical box.
9.8.Unit control panel Code Mk4088, Fuse specifications: 5A/250V

10. Electrical Wire Selection


10.1.Voltage drop occur may due to the large current draw during compressor starting, and may
be result in the compressor is difficult to stat. So we recommend selecting the wire
specification from the table below.
Unit
Power supply
1 2
PCB COM

Compressor
10.2.Size Table of Electrical Wire
The wiring specifications (mm2)
Starting current
(A) Mark②(Heat resistance
Mark①(Heat resistance temperature above 60℃) temperature above 120℃)
within 5m Within 10m Within 15m Within 20m Within 30m Within 50m Within 1m
Below 20 2.0 2.0 2.0 3.5 5.5 8.0 2.0
Below 30 ↑ ↑ 3.5 5.5 ↑ 14.0 ↑
Below 40 ↑ 3.5 5.5 ↑ 8.0 ↑ ↑
Below 50 ↑ ↑ ↑ 8.0 14.0 22.0 ↑
Below 60 ↑ 5.5 ↑ ↑ ↑ ↑ ↑
Below 70 3.5 ↑ 8.0 14.0 ↑ ↑ 3.5
Below 80 ↑ ↑ ↑ ↑ 22.0 30.0 ↑
Below 90 ↑ ↑ 14.0 ↑ ↑ ↑ ↑
Below 100 ↑ 8.0 ↑ ↑ ↑ 38.0 ↑
Below 110 ↑ ↑ ↑ ↑ ↑ ↑ ↑
Below 120 5.5 ↑ ↑ 22.0 30.0 ↑ ↑
Below 140 ↑ 14.0 ↑ ↑ ↑ 50.0 5.5
Below 160 ↑ ↑ 22.0 ↑ ↑ ↑ ↑
Below 180 ↑ ↑ ↑ ↑ 38.0 60.0 8.0
Below 200 8.0 ↑ ↑ 30.0 ↑ ↑ ↑
Below 220 ↑ ↑ ↑ ↑ 50.0 80.0 ↑
Below 240 ↑ ↑ ↑ ↑ ↑ ↑ 14.0

Power supply installation condition: The touching space of breaker should be more than 3mm,
use copper wire only.

10
10.3 Caution of Ground
The internal motor protector does not protect the compressor against all possible
conditions.Please be sure that the system utilizes the ground connection when installed in the
field.
10.4 Warning:
To avoid fire, electric shock and other accidents, keep in mind about these tips:
10.4.1.Only use power supply voltage indicated on the label, if you do not know the family of
voltage, contact the dealer or local power company.
10.4.2.When you use the unit by the maximum current please view the specifications, so make sure
your home's power supply (current, voltage and cable) to meet the machine's normal load
Requirements.
10.4.3.To protect the power lines. Power lines should be fixed, so that people will not be trip over or
the lines damaged by other things. Paying particular attention to plugs, which should be easily
plug into the socket, careful the plug position.
10.4.4.Do not overload wall plugs or extension the cable. Line overload can cause fire or electric
shock.
10.4.5.To ensure your safety, you must plug the power lines into the socket with a grounded
three-phase, and check to ensure your socket is accurate and reliable grounding.

10.5.Power wiring as follows (single unit):

L N R S T N
Phase line

Zero line

Ground line

Phase line 1

Phase line 2

Phase line 3

Zero line

Ground line

Max.line Tem. sensor Max.line


Mode Host Power Phase line Zero line Ground line Signal line
length (m) assistance line length (m)
2.5mm2 2.5mm2 2.5mm2
2 2
030ZA(B) 15 0.5mm 0.5mm 50
2 2 2 2 2
035ZA(B) 220V/1PH/50Hz 4.0mm 4.0mm 4.0mm 15 0.5mm 0.5mm 50
2 2 2 2 2
040ZA(B) 4.0mm 4.0mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
035ZA(B)/S 2.5mm 2.5mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
040ZA(B)/S 2.5mm 2.5mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
045ZA(B)/S 2.5mm 2.5mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
050ZA(B)/S 2.5mm 2.5mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
060ZA(B)/S 380V/3PH/50Hz 2.5mm 2.5mm 2.5mm 15 0.5mm 0.5mm 50
2 2 2 2 2
080ZB/S 4.0mm 4.0mm 4.0mm 15 0.5mm 0.5mm 50
2 2 2 2 2
100ZB/S 4.0mm 4.0mm 4.0mm 15 0.5mm 0.5mm 50
2 2 2 2 2
120ZB/S 4.0mm 4.0mm 4.0mm 15 0.5mm 0.5mm 50
150-200ZB/S 10.0mm
2
10.0mm
2
6.0mm
2
15 0.5mm
2
0.5mm
2
50
250ZB/S 16.0mm
2
16.0mm
2
10.0mm
2
15 0.5mm
2
0.5mm
2
50

Note:
1. used PVC insulated copper wire for above wiring
2. for installation requires, the line is longer than the maximum line length, please contact the
company

11
11.Trial operation(should be operated by professionals)
11.1 Check to confirm the correct installation of all the spare parts on the water piping
system of the hot water side and water supply side, and the connection of heat pump unit,
water tank, terminal equipments and piping. Check to confirm the proper water-supply of
the replenishing water pipe on the hot water side and water supply side, and the installation
of all the spare parts on the replenishing port such as pressure reducing valve, check valve
and filter.
11.2 Turn on the valve of the replenishing port on hot water side and water supply side, the
valve of circulating inlet and outlet, the valve of supply and return water for the mail pipes,
the valve of branch pipes for each floor, the valve of water inlet and outlet for the terminal
equipments. Fill the water tank on the hot water side, and the heat collecting system and
connecting pipes on the water supply side with water. Check to confirm all those valves that
should be opened, and all those should be closed. And check to confirm the completion of
the pipe insulation.
11.3 Turn on the vent valve and hot water valve. Turn off these two valves after the
confirmation of the discharge the air in the pipes.
10.4 Check to confirm that the power supply is the same as the one required on the nameplate.
11.5 Check to confirm the proper connection of all the power supply and control circuits
according the the wiring diagram. Check to confirm that all the cable terminals and ground
electrode are fixed. Check to confirm the proper connection of the high and low water level
of the water tank.
11.6 Independent functioning test of the circulating pump on the hot water side and water
supply side. First of all, switch on the power of heat pump unit, start the circulating pump
manually, turn on the vent valve again, discharge the residual air in the pipes, then observe
and listen quietly to the running of the water pump to see if the circulating water volume is
normal. Stop the circulating pump until the circulating system is working properly.
11.7 The operation of the remote controller. Select the running mode of the heat pump and
set the temperature, then return to the main page of remote controller, press button the
turn on the unit.
11.8 When the unit is working normally, judge by hearing to see if there's any abnormal
sound. If so, cut the power to check the unit. If there's no abnormal sound, then keep the
unit running while checking to see if the high and low pressure is normal.
11.9 Check again to see if the power input and running current is normal. If no, cut the power
to check it.
11.10 Looking through the running state of the remote controller, check and record the
output and input state to confirm the proper temperature indicating value of each point.
Notice: No 3-minute delay time protection for the first time of power-on, but for the other
times.

12
IV.USE
1. Single unit controller MK6024 interface displays.
22 2120 19 18 17 16
23

24
25 15
SET 14
26
27 MIN MIN 13
28 C C 12
29
12 11
30 34 10

M
1 2 3 4 5 6 78 9
No . Icon Instructions No . Icon Instructions
1 Keyboard lock icon 16 Energy-Saving mode icon
2 Breakdown maintenance icon 17 Defrost icon
3 Hour
ROOM 18 Hot water mode icon
4 Minutes 19 Cold mode icon
5 Water-supply pump timing ON 20 Heat mode icon
6 1 Unit timing ON/OFF for phase 1 21 SET Setting status icon
7 2 Unit timing ON/OFF for phase 2 22 AUTO mode icon
8 3 Water-return valve timing ON 23 Water cycle pump icon
9 4 Water recharge valve timing ON 24 Compressor icon
10 Timing OFF icon 25 Hot water electric heating icon
11 Timing ON icon 26 Water return valve icon
12 C Celsius icon 27 Water filling valve icon
13 MIN Minutes icon 28 Fan icon
14 Temp. icon 29 Supply pump icon
15 Temp. icon 30 Water level icon

Notice:some icon only with special mode


Timing button: Long press this button once to enter the timing setting interface,
adjust to modify the timing group 1, 2, 3, 4 by "Increasing" and "Decreasing" button
during the timing setting. Short press this button to enter the clock-modifying interface.

M Function button: short press this button once, enter to check the unit running status.
Long press this button to enter the users parameter-modifying interface.

Increasing button: short press this button once to increase the current setting value.
Long press this button to keep increasing the current setting value.

Decreasing button: short press this button once to decrease the current setting value.
Long press this button to keep decreasing the current setting value.

Unit ON/OFF button: normally, long press this button to turn on or off the unit. When
keyboard is locked, long press this button to unlock the keyboard.

13
2.How to use the controller
2.1 Keyboard lock/unlock
If there's no operation within 1 minute, the controller will switch to lock automatically.
Please long press for 3s to unlock.

OUT OUT

C C C C

M M
Keyboard unlocked Keyboard locked
2.2 Unit ON/OFF
Under the stand-by mode, long press to turn on the unit, the current mode would be shown on
the wire controller, the unit would run under such mode. Long press again to turn off the unit.

OUT OUT

C C C

M M
Unit OFF Unit ON

2.3 Set temperature adjustment


Under the hot water mode, press or to adjust the set temperature of hot water tank or
room temperature.

2.4 Time setting


Under the main interface, short press for 5s, the clock setting would flicker, then short press
once, the hour seting would flicker, press or to adjust hour. After that, short press once,
the minute setting would flicker, press or to adjust minute. Then short press once to
finish time setting.

2.5 Unit timing ON/OFF and timing water-return setting


Long press once, "1" on the controller would flicker, press or to select "1" or
"2". "1" is timing ON/OFF of phase 1, and "2" is timing ON/OFF of phase 2. "3" is timing
ON of water-return valve, and "4" is timing water-filling,and "5" is timing water-supply.
The flicker of icon refer to your selection. Then short press once, and hour will keep
flashing, press or to adjust hour of timing ON, then short press once, the minute
will keep flashing, press or to adjust minute of timing ON. And then short press
once, and hour will keep flashing, press or to adjust the hour of timing OFF, then
short press once, the minute will keep flashing, press or to adjust minute of
timing OFF. After all those settings above, short press once, the flashing of and
refer to the finish of one group of timing setting. Press or to continue setting other
timing groups. Press to quit timing setting if no need for other timing groups.

14
OUT OUT OUT OUT

C C C C C C C C
1 2 2 2

M M M M

OUT OUT OUT OUT

C C C C C C C C
2 2 2 2

M M M M

The above pictures show: Unit timing ON/OFF in Phase 2. Turn on unit on 1:30 and turn off on 23:50.
2.6 Cancel unit timing ON/OFF and timing water-return
When a certain group of timing set, if it needed to be canceled, both the timing ON and OFF
should be set back to 00:00. For example, if the timing water-return is needed to be canceled,
short press once, the "1" on the wired controller will flicker, press or to select "3"
(timing water-return), the flicker of the icon refer to the selection, then short press once,
at that time, and the hour will keep flashing, press or to set the hour of timing ON to
be 00, after that, short press once, the minute will keep flashing, press or to set that
00. Then press again, and hour will keep flashing, repeat the above steps to set both
hour and minute to 00. After finish that, short press once. Both and will be flashing,
then short press once to get back to the main interface, the number "3", and will
disappear which refer to the cancel of timing water-return.

OUT OUT OUT OUT

C C C C C C C C
1
3 3 3

M M M M

OUT OUT OUT OUT

C C C C C C C C

3 3 3

M M M M

15
2.7 Switch the current operating mode
Unit on. Main interface under long press the key can switch the currently running mode. The meaning of the main interface around the
two Numbers, On the basis of different patterns, Specific please see graphic below:

Setting Tank temp. Setting Inlet water temp.


SET Tank. temp SET IN Inlet water temp.
C C C C

M Hot water mode M Room heating mode


attention:Room automatic mode
Setting Inlet water temp. Setting Inlet water temp. is based on the measured water
SET IN Inlet water temp. SET IN Inlet water temp. temperature of the relation between
inflow set temperature in room room
C C C C
cooling and heating automatic s
witching.

M Room cold mode M Room AUTO mode

Setting Tank temp. Setting Inlet water temp.


SET Tank temp. SET IN Inlet water temp.
C C C C

M Hot water and Room cold mode M


Hot water and room heating mode

2.8 Open/close energy saving scheme


According to the and for 3 seconds at the same time, can open the energy saving plan.。Open the energy saving, will light up on
the main interface, this means you have open the energy saving mode.Each mode has its unique energy saving plan below, specific as
follows:

Living hot water model of energy saving scheme


The hot water tank is set according to the environment temperature, adjust automatically.
When the environment temperature 24 ℃ or less, according to the parameters of the L5 set of hot water tank
C C
temperature is carried out.
When the environment temperature is 26 ℃ ~ 28 ℃, set for 51 ℃ hot water tank temperature.
M When the ambient temperature of 30 ℃ ~ 32 ℃, set to 49 ℃ hot water tank temperature.
When the environment temperature 34 ℃ or higher, setting of 47 ℃ hot water tank temperature.
Room cooling mode of energy saving scheme
When the environment temperature 32 ℃ or higher, set the water temperature is 8 ℃.
C C When the environment temperature is 27 ℃ ~ 30 ℃, set the water temperature is 10 ℃.
When the ambient temperature of 25 ℃ or less, set the water temperature of 12 ℃.

Room heating mode of energy saving scheme.


There are two kinds of energy-saving solution of the model, the parameters according to user's specific L6 and
C C decide, when parameter L6 elected to 0, energy-saving solutions for curve heating energy saving solutions,
when the parameters of L6 elected 1, energy saving solutions to set period of time variable water temperature.
Set the water temp./℃

M
55

50

Curve heating energy saving scheme 45

The scheme according to the environment temperature 40

and the curve of the set, to set the water temperature


35
automatic adjustment.When leaving the factory, has set
30
t he curve as shown in the figure below (slope 40,
translation of 10), the user can set the water temperature 25

according to the picture to view the current unit.If the 20

user needs to adjust the curve, can adjust the curve of 15

the set in the appendix.


-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 Ambient temp./℃
(Pay attention to the factory Settings for: maximum set temperature limit is 55 ℃, the curve slope is 30, curvilinear translation amount of 10)

16
Period of time set temperature
In a period of time, heating demand less, some period of time, demand for heating and use of this
scheme is very suitable for large.Unit can be 1 day according to their demand is divided into four
different periods, and four times set water temperature can be set up.Parameters L9 to L12 for time
Settings,Parameters L13 for L9 time set the water temperature, parameter L14 for L10 time set
the water temperature, parameter L15 for L11 time set the water temperature and parameters
L16 for L12 time set the water temperature.
Factory has been set for the user as follows:
Parameters set to 23:00, L9 time L13 set water temperature of 35 ℃.
Parameters set to 6 PM, L10 time L14 inlet temperature of 42 ℃.
Parameters set to 9:00, L11 time L15 set water temperature 30 ℃.
Parameters set to 17:00, L12 time L14 set water temperature of 40 ℃.
So when the clock line drive controller in 23:00, unit set water temperature automatically to
35 ℃, the clock go to 6 PM, the unit set water
emperature automatically into 42 ℃, at the time clock to 9:00, unit set water temperature
automatically to 30 ℃, the clock went to 17:00, unit
set water temperature automatically to 40 ℃. Control result can be expressed in a graph:

Water inlet temp. Set/℃


50

40

30

20

10

13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00
Time

When models for hot water + cooling or hot water + heating mode, energy saving, open for making
living hot water and cooling/heating room two aspects, the energy-saving scheme will be
according to their control.

C C

M
Hot water + cooling mode opens the energy saving scheme

C C

M
Hot water + heating mode opens the energy saving scheme
Opens the energy-saving scheme, then according to the and for 3 seconds at the
same time, can cancel the energy saving plan, icon disappear at this time, cancel the energy
saving, the unit will according to the main interface of and regulating the temperature of
the execution.

17
3. Check the unit running state
Short press M once to enter the unit running state interface, press or to shift
among parameters of every running state. The specific meaning of each running state
parameters as follows:
Parameter Instructions Parameter Instructions
o1 Water tank temp. b4 System 2 compressor current
o2 Water inlet temp. b5 System 2 electronic expansion valve steps
o3 Water outlet temp. c1 System 3 discharge temp.
o4 Ambient temp. c2 System 3 coil temp.
o5 Water supply return temp. c3 System 3 suction temp.
o6 Auxiliary electronic expansion valve steps c4 System 3 compressor curret
a1 System 1 discharge temp. c5 System 3 electronic expansion valve steps
a2 System 1 coil temp. d1 System 4 discharge temp.
a3 System 1 suction temp. d2 System 4 coil temp.
a4 System 1 compressor curret d3 System 4 suction temp.
a5 System 1 electronic expansion valve steps d4 System 4 compressor curret
b1 System 2 discharge temp. d5 System 4 electronic expansion valve steps
b2 System 2 coil temp.
b3 System 2 suction temp.

4. Modify parameters of user level


Long press M for 3s to enter the user level's parameter interface, press or to
switch among each parameter. Short press M once to modify the selected parameter.
Press or to adjust the parameter, short press M again to confirm the adjustment.
The specific meaning of each user parameter as follows:
Parameter Instructions Range Default
L0 Room heating/cooling mode temperature difference between the unit stop and restart. 2℃~18℃ 3℃
L1 Set the temperature of the heating mode 20℃~55℃ 1 55℃
L2 Set the temperature of the cooling mode 8℃~30℃ 12℃
L3 Set the temperature of the AUTO mode 8℃~55℃ 1 40℃
Hot water tank mode, water tank temperature difference between
L4 the unit stop heating and restart heating 2℃~18℃ 5℃
L5 The water tank temperature setting of hot water tank mode 20℃~55℃ 1 55℃
0:Curve heating
L6 energy-saving scheme selection of heating mode 1:Period of time variable 0
water temperature

L7 Pan set of curve heating 0~30 10


L8 The slope of curve heating setting 24~50 30
L9 Set time period of variable water temperature of 1 0~23点 23点
L10 Set time period of variable water temperature of 2 0~23点 6点
L11 Set time period of variable water temperature of 3 0~23点 9点
L12 Set time period of variable water temperature of 4 0~23点 17点
L13 The water inlet temperature for set time period of variable water temperature of 1 20℃~55℃ 1 35℃
L14 The water inlet temperature for set time period of variable water temperature of 2 20℃~55℃ 1 42℃
18
Parameter Instructions Range Default
L15 The water inlet temperature for set time period of variable water temperature of 3 20℃~55℃ 1 30℃
L16 The water inlet temperature for set time period of variable water temperature of 4 20℃~55℃ 1 40℃
L17 Electric heating purposes 0~3 2
0
L18 Allow the environment temperature of electric heating open -30~35℃ 5℃
L19 Electric heating set time delay start 0~90min 30min
0(wet)/
L20 Region 1(dry)
1(dry)

L21 Ambient temp. setting of defrost cycle extension -30~2℃ -10℃


L22 Solar water pump start-up,temperature difference between the unit stop and restart. 3~15℃ 10℃
L23 The temperature setting of water supply 30~65℃ 40℃
Constant temperature water replenishing hot water tank temp.
L24
Setting value
20~60℃ 45℃
L25 Compressor over-current protection setting value 0~40A 3
30A
L26 The setting of the defrost cycle 20~90min 45min
L27 Into the coil temperature setting of defrosting -15~-1℃ -7℃
L28 The longest defrosting time setting 5~20min 8min
L29 Out of the coil temperature setting defrosting 1~40℃ 13℃
L30 Into the difference set of defrosting(Ambient temp.-coil temp.) 0~15℃ 5℃
0:OFF
L31 Electric heating starts, water cycle pump ON/OFF 1:ON 1
0:OFF
L32 Cooling/heating thermostatic downtime,water cycle pump ON/OFF 1:ON 1
0:independent
L33 The choice of more units to form, water flow switch 1:sharing 1
0:efficient
L34 When more units to form, central control scheme 1:Save 1
L35 About into a control scheme, the module adjustment cycle Settings 5~150(*6)S 20(*6)

L36 Water pump long open Press unit OFF manually and ambient temp.≤Para.L36 -30℃-5℃ -10℃
0:OFF
L37 Water cycle pump test 1:ON 0
0:OFF
L38 Water supply pump/Backwater valve/Solar water pump test 1:ON 0
0:OFF
L39 Three-way valve test 1:ON 0

19
attention 1 :Set different models, the highest temperature and the default setting temperature is
different, specific as follows:
★Taken the conventional air-cooled hot and cold water machine the highest set temperature
45 ℃, 40 ℃ by default.
★Taken the conventional single maximum set temperature of 55 ℃ hot water machine, the
default 55 ℃.
★Taken the conventional multi-function maximum set temperature of 55 ℃ hot water machine,
the default 55 ℃
★Taken the regular pool machine set the highest temperature of 40 ℃, the default 27 ℃
★Taken the part models have special requirements, not here.

attention 2 :Electric heating USES parameter tuning of 0: without electric heating; 1: electric
heating hot water; 2: air-conditioning electric heating; 3: two kinds of electric heating. According
to different customer requirements, electrical heating USES parameter a default value is
different, specific as follows:
★If not charged heating, the factory default is 0.
★If electric heating, and installed in the hot water tank/hot water outlet pipe, the factory
default is 1.。
★If electric heating unit, and in the buffer tank/air conditioning outlet pipe installation, is the
factory default is 2.
★If electric heating, and installed in the outlet pipe of heat exchanger units, is the factory
default is 3

attention 3 :Different number of units, mechanical and electrical flow pressure to protect the
default value is different, specific as follows:
★If a single compressor (normal) model of the horse for 5 P, the current protection value
defaults to 15 A.
★If a single compressor (conventional model) on the number of horse is 8 P, the current
protection value, the default is 25 A.
★If a single compressor (conventional model) on the number of horses to 10 P, the current
protection value defaults to 28 A.
★If a single compressor (normal) model number of the horse is 12 P, the current protection
by default is 30 A.
★Part using a special type of press machine, is not here.

20
IV.Maintenance and repair.
1.Malfunction indicating table
CODE Malfunction Reason Reasolution
The system 1 discharge
E 01 Failure of system 1 discharge sensor is open or short circuit Check or change the sensor
temperature sensor
The system 2 discharge
E 02 Failure of system 2 discharge sensor is open or short circuit Check or change the sensor
temperature sensor
The system 3 discharge
E 03 Failure of system 3 discharge sensor is open or short circuit Check or change the sensor
temperature sensor

E 04 Failure of system 4 discharge The system 4 discharge Check or change the sensor
temperature sensor sensor is open or short circuit
Failure of system 1 coil The system 1 coil
E 05 sensor is open or short circuit
Check or change the sensor
temperature sensor
Failure of system 2 coil The system 2 coil
E 06 sensor is open or short circuit
Check or change the sensor
temperature sensor
Failure of system 3 coil The system 3 coil
E 07 sensor is open or short circuit
Check or change the sensor
temperature sensor
Failure of system 4 coil The system 4 coil
E 08 sensor is open or short circuit
Check or change the sensor
temperature sensor

E 09 Failure of system 1 suction The system 1 suction Check or change the sensor
temperature sensor sensor is open or short circuit
Failure of system 2 suction The system 2 suction Check or change the sensor
E 10 temperature sensor sensor is open or short circuit
Failure of system 3 suction The system 3 suction
E 11 Check or change the sensor
temperature sensor sensor is open or short circuit
Failure of system 4 suction The system 4 suction
E 12 sensor is open or short circuit
Check or change the sensor
temperature sensor
Failureof solar/ return water The sensor is open or
E 17 Check or change the sensor
temperature sensor short circuit
Failure of water outlet The sensor is open or
E 18 temperature sensor
Check or change the sensor
short circuit
Failure of water inlet The sensor is open or Check or change the sensor
E 19 short circuit
temperature sensor
Failure of hot water tank The sensor is open or
E 20 temperature sensor
Check or change the sensor
short circuit
Connection failure between Check the communication cable between the
E 21 Communication failure
the controller and mainboard controller and mainboard.
Failure of ambient The sensor is open or
E 22 temperature sensor
Check or change the sensor
short circuit
Water level line got loose
E 25 Failure of Water Level Switch or misplace Check water level line normal or not

Water flow lackage or Check the water system, water pump and
P 01 Water flow protection
volume over-low water flow switch.

1. Check if the inlet water temp. is too high or if any


blocking
System 1 high System 1 high pressure 2. Checking if the ourdoor unit fan blade is so dirty that
P 02 it influences the efficiency of the heat exchanger.
pressure protection protection switch off
3. Check if too much refrigerant.
4. Check if the set water tank temp. is too high.

1. Check if the inlet water temp. is too high or if any


blocking
System 2 high System 2 high pressure 2. Checking if the ourdoor unit fan blade is so dirty that
P 03 it influences the efficiency of the heat exchanger.
pressure protection protection switch off
3. Check if too much refrigerant.
4. Check if the set water tank temp. is too high.

21
CODE Malfunction Reason Reasolution
1. Check if the inlet water temp. is too high or if any
blocking
System 3 high System 3 high pressure 2. Checking if the ourdoor unit fan blade is so dirty that
P 04 it influences the efficiency of the heat exchanger.
pressure protection protection switch off
3. Check if too much refrigerant.
4. Check if the set water tank temp. is too high.

1. Check if the inlet water temp. is too high or if any


blocking
System 4 high System 4 high pressure 2. Checking if the ourdoor unit fan blade is so dirty that
P 05 it influences the efficiency of the heat exchanger.
pressure protection protection switch off
3. Check if too much refrigerant.
4. Check if the set water tank temp. is too high.

1. Check if there is refrigerant leakage.


System 1 low System 1 low pressure 2. If refrigerant leakage is confirmed, repair it
P 06 and vacuumize it,
pressure protection switch off
then fill refrigerant according to the name plate.
1. Check if there is refrigerant leakage.
System 2 low System 2 low pressure 2. If refrigerant leakage is confirmed, repair it
P 07 and vacuumize it,
pressure protection switch off
then fill refrigerant according to the name plate.
1. Check if there is refrigerant leakage.
System 3 low System 3 low pressure 2. If refrigerant leakage is confirmed, repair it
P 08 and vacuumize it,
pressure protection switch off
then fill refrigerant according to the name plate.
1. Check if there is refrigerant leakage.
System 4 low System 4 low pressure 2. If refrigerant leakage is confirmed, repair it
P 09 and vacuumize it,
pressure protection switch off
then fill refrigerant according to the name plate.
Phase sequence error of Power phase sequence
P 10 Check the power supply of the unit.
power supply error
1. Check the water in system is clean or not,
System 1 compressor System 1 compressor ensure there is no corrosive liquid in pipeline.
2. Check machine leaked refrigerant or not.
P 11 discharge temperature discharge temp.
when machine leak refrigerant, repair it then
too high protection Higher than 105℃ vacuumize it, put the right refrigerant into
machine.
1. Check the water in system is clean or not,
System 2 compressor System 2 compressor ensure there is no corrosive liquid in pipeline.
2. Check machine leaked refrigerant or not.
P 12 discharge temperature discharge temp.
when machine leak refrigerant, repair it then
too high protection Higher than 105℃ vacuumize it, put the right refrigerant into
machine.
1. Check the water in system is clean or not,
System 3 compressor System 3 compressor ensure there is no corrosive liquid in pipeline.
2. Check machine leaked refrigerant or not.
P 13 discharge temperature discharge temp.
when machine leak refrigerant, repair it then
too high protection Higher than 105℃ vacuumize it, put the right refrigerant into
machine.
1. Check the water in system is clean or not,
System 4 compressor System 4 compressor ensure there is no corrosive liquid in pipeline.
2. Check machine leaked refrigerant or not.
P 14 discharge temperature discharge temp.
when machine leak refrigerant, repair it then
too high protection Higher than 105℃ vacuumize it, put the right refrigerant into
machine.
The temperature between 1.water system is normal or not.
Water flow and water pressure 2.machine is work or not, temp. of
P 15 water inlet and outlet is too
is too low. discharge and pressure of system
large protection
is normal or not
1.water system is normal or not.
Over cooling refrigeration The cooling mode work not
2.machine is work or not, temp. of
P 16 protection normal so that the temp of
discharge and pressure of system
outlet water was too low.
is normal or not

22
Freezing protection in Outdoor temperature Unit automatically start antifreezing protection.
P 17 Please leave it on standby without power cut-off.
winter under standby status lower than 0℃

1、Check the electric heating is normal or not


Electric heating overheating Electric heating overheating
P 18 2、Water flow is normal or not
protection protection switch off
3、Overheating switch is normal or not

System 1 compressor work situation of machine


Check the compressor cable is normal
P 19 current protection is so bad or compressor didn't work or not. Compressor working condition is
normal or not.

System 2 compressor work situation of machine


Check the compressor cable is normal
P 20 current protection is so bad or compressor didn't work or not. Compressor working condition is
normal or not.

System 3 compressor work situation of machine


Check the compressor cable is normal
P 21 current protection is so bad or compressor didn't work or not. Compressor working condition is
normal or not.

System 4 compressor work situation of machine


Check the compressor cable is normal
P 22 is so bad or compressor didn't work or not. Compressor working condition is
current protection
normal or not.
1.water system is normal or not.
Defrost Water outlet temp. The temp of outlet water is too low 2.machine is work or not, temp. of
P 23 Was too cold to protect at defrost discharge and pressure of system
is normal or not
1:Check whether the connection of the fan is
normal or not.
P 24 Protection of fan motor Fan can not to work 2:The unit input power supply is normal or not
3:The working conditions of unit is bad

Protection of ambient Ambient temperature is


P 25 temperature too low beyond machine work description.
Contact manufacturers immediately

23
2.Note
1.1 Check whether the exhaust equipment is normal. Avoid cutting of the water supply and or air entering
into the system, or it will influence the performance and reliability of the unit. The water filter should
be cleaned regularly. Keep the water clean in case of any damage to the unit due to filter's dirty and jam.
1.2 Keep the unit environment dry, clean and well ventilation. Clean the side air exchanger regularly(once
per1-2 months) in order to maintain high exchange efficiency and save energy.
1.3 Often check the performance of all the parts in the unit. Check whether the working pressure of the
refrigerant system is normal. Repair and change the parts timely if there's any abnormity.
1.4 Often check whether the wiring of the power and electric system is tightened and or electric parts
perform abnormally or smells. Repair and change the parts timely if there's any abnormity.
1.5 Care the unit if the unit stops for a long time. Discharge all the water in the pump and throughout the
pipe route in case breakdown to the water pump and pipe caused by frost and freeze. Discharge the
water from the water pump and tube exchange Button drain. Check the unit thoroughly and flood
water into the system before the unit power on again.
1.6 To check the operation of every process in the unit, the operation pressure of the refrigerant system.
You should maintain or change it in time.
1.7 To check the power supply and cable connection often, there is abnormal action or bad smell about
the electrical component. If there is, please maintain or change it in time.
3.Determine and solve malfunction by below table:

Malfunction Reason Solution


1.Power failures 1. Shut down and check the power
2. The unit wire loses 2.Check the reason and repair
The unit can't run 3. The unit power fuse burns out. 3.Check and change the power fuse

The water pump 1. The water system is lack of water 1.check the water supplement equipment and supply
can run but can't 2. There's air in the system. water into the system.
circulate and is 3. The water system valve doesn't open 2.Exhaust the air from the water system
noisy entirely 3.Clean the water filter or exhaust the air from system
4. The water filter is dirty and jam 4.Clean the water filter

The cooling 1. Refrigerant is insufficient 1.Check the leakage and add refrigerant
capacity is too low 2. Thermal insulation of the water system is 2.Enhance the thermal insulation of the pipe route
and the compressor poor 3.Clean the exchanger and improve the condensation
works continuously 3. Thermal discharge of the exchange is poor condition
without pause. 4. Water flow volume is insufficient 4. Clean the water filter

The compressor 1. Discharge surplus refrigerant


exhausted pressure 1.Too much refrigerant 2. Clean the exchanger and improve the condensation
is too high 2.Thermal discharge of the exchange is poor
condition

1. Refrigerant is insufficient 1.Check the leakage and add refrigerant


The compressor 2. The filter and or capillary tube jam 2.Change the capillary tube or filter
suction pressure is 3. Water flow volume is insufficient 3.Clean the exchanger and improve the condensation
too low 4. Capillary tube of expansion valve sensor condition
bulb breakdown 4.Change the expansion valve

1.Refrigerant enter into the compressor 1.Check the reason and solve the malfunction
Compressor noisy
2.Compressor damaged 2.Change the compressor

1. Power failure 1.Check the power and solve the malfunction


Compressor can't 2. Compressor Control damaged 2.Change Control
work 3. Wire loses 3.Check loose reason and repair
4. Compressor overload protection 4. Compressor overload protection
5. Return water temperature setting incorrect 5. Reset the return water temperature
6. Water flow volume is insufficient 6. Clean the water filer and exhaust the air from the
system

1 Fan relay damaged 1. Change the fan relay


Fan can't work 2. Change the fan motor
2.Motor is burnt out

24
1. Power failure 1.Check the power and solve the malfunction
Compressor can't 2. Compressor Control damaged 2.Change Control
work 3. Wire loses 3.Check loose reason and repair
4. Compressor overload protection 4. Compressor overload protection
5. Return water temperature setting incorrect 5. Reset the return water temperature
6. Water flow volume is insufficient 6. Clean the water filer and exhaust the air from the
system

1 Fan relay damaged 1. Change the fan relay


Fan can't work
2.Motor is burnt out 2. Change the fan motor

1. The refrigerant leak out 1.Check the leakage and add refrigerant
The compressor run 2. Plate exchanger freezes 2.Check the reason and change the plate exchanger
but no refrigeration 3. Compressor failure
3.Change the compressor
Low water 1.Clean the water filter and exhaust the air from the
temperature 1.Water flow volume is insufficient
2.Temperature Control setting is too low system
protection to the 2.Re-set
unit
Few water flow 1.Clean the water filter and exhaust the air from the
1.Water flow volume is insufficient system
volume protection
2.Flow switch 2.Change the flow switch
to the unit

25
V.Wiring diagram
1. MK6020PCB input and output port definition
AC-N

RY8

RY7

RY6

RY5

RY4

RY3

RY2

RY1
RY9
IN10
TRAN-IN
FUSE

IN9

IN8

IN7

IN6

IN5
R RY11 RY10

E-VALVE1

E-VALVE2

E-VALVE3
IN4
ON DP

S IN3

1 2 3 4 5 6 7 8
DEBUG IN2

T IN1

COM

TRAN-OUT W-H

W-M

CN4 W-L

CURRENT2 WATER-COM

RS485
CURRENT1 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11

Symbol Meaning Symbol Meaning


RY1 The crankshaft and tropical R Power input
RY2 Water filling valve signal output S Power input
RY3 Three-way vavle signal output T Power input
RY4 Soft start signal output AC-N Power input
RY5 EVI valve signal output TRAN-IN Transformer primary
RT6 Hot water electric heating signal output TRAN-OUT Transformer secondary
RY7 four way valve signal output E-VALVE1 System 1 electronic expansion valve
RY8 System 2 compressor signal output E-VALVE2 System 2 electronic expansion valve
RY9 System 1 compressor signal output E-VALVE3 Electronic expansion expansion board
RY10 Fan signal output RS485 Centralized control communication
RY11 Water cycle pump signal output CN4 Wire control interface
CURRENT1 System 1 compressor current detection IN10 Fan overload protection switch
CURRENT2 System 2 compressor current detection IN9 Overheating protection switch
T1 Hot water tank temperature IN8 Emergency switch
T2 Water outlet temperature IN7 Air conditioning on line switch
T3 System 1 coil temperature IN6 Reserve
T4 System 2 coil temperature IN5 System 2 low pressure switch
T5 System 1 discharge temperature IN4 System 1 low pressure switch
T6 System 2 discharge temperature IN3 System 2 high pressure switch
T7 System 1 suction temperature IN2 System 1 high pressure switch
T8 System 2 suction temperature IN1 Water flow switch
T9 Ambient temperature COM GND
T10 Water supply return temperature W-H Tank high water level
T11 Water inlet temperature W-M Reserve
DEBUG Programme writing port W-L Tank low water level
WATER-COM 12V

26
The purpose of code-dial switch
State :00000000 State:01100000

ON DP ON DP

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

Digits
1 2 3 4
State
ON:1 single phase Three system 00: return water valve 10:Soft start2
01: solar water cycle pump 11:The crankshaft and tropical
OFF:0 three phase Four system
Digits
5 6 7 8
State
ON:1 new transformer During the modular centralized control, the selection of address code of the unit
OFF:0 old transformer
The address setting of the last four digits of dial code switch.
Address Code Unit Number
000 NO.1
001 NO.2
010 NO.3
011 NO.4
100 NO.5
101 NO.6
110 NO.7
111 NO.8
Notice:
①Please set NO.1 as master unit and the others as slave units.
②There should not be modular units with the same address code, or the units with
the same address code could not start separately, and the status parameters shown on
the centralized wired controller are inaccurate.

27
3.Unit wiring diagram
3.1 Wiring diagram JXT-MK5064-EG-02 effective for the mode of : MACRW120ZB/PS

Wiring diagram

N
E-VALVE1 E-VALVE2

OUT1

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

OUT9
Fuse(220V/10A) S
R

Ry10

Ry11
TRAN-IN TRAN-OUT

P1
CURRENT1 P2
P3
CURRENT2
P4
T1

VA2

VA1
SW5 IN10 T2
T

transformer

White

White
Black

Black
SW4 IN9

Red

Red
T3
T

SW3 IN8
SW2 IN7 T4
KM2 KM1
T

Black Black
IN6 Red Red
LP2 IN5 T5 Capacitance Capacitance
T

KM2 KM1 MK4090 MK4090

LP1 Fan2 Fan1

Yellow/Green
IN4

Yellow/Green

Red

Black

White

Blue
T6
T

HP2 IN3 P3P4 P1P2


Orange Orange V V
HP1 IN2 White White W U W U
T7
T

SW1 IN1 compressor2 compressor1


COM T8
T

2
T9
T

W-H
W-M T10
W-L
WATER-COM T11
T

CN4 RS485

Concentrated
L N R S T N
Control A B
定时 功能

Water cycle pump Unit power input


Control power output (380V/3PH/50Hz)
(220V/1PH/50Hz)
Legend:
:A.C. Contactor/relay coil SW1 :Water flow switch T2 T :Water outlet temp. P1 :System 1 compressor current detection
:Electric driven valve coil SW2 :Air conditioning on line switch (closed) P2
T3 T :System 1 coil temp. P3 :System 2 compressor current detection
:Crankshaft electric heating SW3 :Emergency switch(closed) P4
T4 :System 2 coil temp.
KM1 :System 1 Compressor A.C. Contactor SW4 :Electric heating overheating protection switch(closed)
T

T5 :System 1 discharge temp.


KM2 :System 2 Compressor A.C. Contactor SW5 :Fan overload protection switch(closed)
T

VA1 :System 1 four way valve T6 T :System 2 discharge temp.


:System 1 high pressure protection switch
HP1
VA2 :System 2 four way valve T7 T :System 1 suction temp.
HP2
:System 2 high pressure protection switch
LP1 T8 T :System 2 suction temp.
:System 1 low pressure protection switch
LP2 T9 T :Ambient temp.
:System 2 low pressure protection switch
T11 T :Water inlet temp.
NOTE:1.For electrical box, on the left is system 1, on the right is system 2.
2.The parameters of the system 2 applies only to double system models.

30
MACON
AIR TO WATER HEAT PUMP