Professional Documents
Culture Documents
Abstract—Accurate distribution secondary low-voltage cir- The on-going extensive roll-out of smart meters at utilities
cuit models are needed to enhance overall distribution system across the United States and the growing number of PV invert-
operations and planning, including effective monitoring and coor- ers and other modern distribution system sensors are rapidly in-
dination of distributed energy resources located in the secondary
circuits. We present a full-scale demonstration across three real creasing the available measurement data along distribution feed-
feeders of a computationally efficient approach for estimating ers. This new measurement data has sparked a growing interest in
the secondary circuit topologies and parameters using historical developing methods for distribution system topology and param-
voltage and power measurements provided by smart meters. The eter estimation. Distribution system parameter and topology es-
method is validated against several secondary configurations, and
timation methods have been proposed in various other works, in-
compares favorably to satellite imagery and the utility secondary
model. Feeder-wide results show how much parameters can vary cluding [6]–[11]. The methods, however, typically require volt-
from simple assumptions. Model sensitivities are tested, demon- age angle measurements and/or are not demonstrated/tested on
strating only modest amounts of data and resolutions of data mea- real utility feeders with field measurement data.
surements are needed for accurate parameter and topology results. Compared to these previous works, including our previous
Index Terms—Electrical engineering, energy management, work ( [12]–[14] ), this paper represents three major advances:
resistance. 1) The parameter and topology estimation results are vali-
dated using several real transformers under normal oper-
I. INTRODUCTION ating condition (Section V),
O MODEL, simulate, plan, and operate distribution sys- 2) We present a new method to resolve the parameters for
T tems with growing amounts of photovoltaics (PV) and
other distributed energy resources (DER), more accurate distri-
secondary systems with only a single customer by com-
paring them to other secondary systems (Section IV-B).
bution system models are required [1]. Secondary (low-voltage) 3) We expand on this new method by also applying it to
circuits, those which connect customers to service/distribution secondary systems with multiple customers, to detect
transformers, are becoming important to include in distribution additional resistances that might occur when there is a
grid models since that is where most DERs are connected and node between customers that is not at the transformer
since they have higher per unit impedances and hence a large (Section IV-C).
share of the feeder per unit voltage drop than primary circuits [2],
[3]. Inaccurate secondary circuit models can lead to, e.g., errors II. DISTRIBUTION SYSTEM SECONDARY CIRCUIT PARAMETERS
in hosting capacity estimates [4], [5] and ineffective choices of AND TOPOLOGY ESTIMATION CONCEPT
smart inverter volt/var or volt/watt settings. Currently, the ma-
jority of existing utility feeder models do not include secondary The overall objective of distribution system secondary circuit
circuits at all. When modeled, they are typically unverified and topology and parameter estimation (DSPE) is to determine the
represented with limited detail. topology, resistance (R), and reactance (X) parameters of a sec-
ondary circuit (shown in red in Fig. 1) by leveraging AMI mea-
surements of voltage (V ), real power (P ), and reactive power (Q)
Manuscript received July 24, 2018; revised December 2, 2018 and April 9,
2019; accepted May 12, 2019. Date of publication May 20, 2019; date of current (shown in blue in Fig. 1). This paper focuses on typical North
version June 20, 2019. This work was supported in part by the U.S. Department American split-phase secondary circuits that can be perfectly
of Energy’s Office of Energy Efficiency and Renewable Energy under Solar represented (under appropriate assumptions) with single-phase
Energy Technologies Office under Grant 34226 and in part by the Department
of Energy’s Grid Modernization Laboratory Consortium under Project 1.3.10 equivalent circuits. More details on split-phase secondary circuit
(Vermont Regional Partnership Enabling the Use of DER). Paper no. TSTE- modeling can be found in [4].
00736-2018. (Corresponding author: Matthew Lave.) We follow the linear regresstion parameter estimation (LRPE)
M. Lave and M. J. Reno are with the Sandia National Laboratories, Livermore,
CA 94551-0969 USA (e-mail: mlave@sandia.gov; mjreno@sandia.gov). method for secondary circuits described in [2] and [15]. The
J. Peppanen is with the Electric Power Research Institute, Palo Alto, CA LRPE method utilizes the linear approximation of voltage dif-
94304 USA (e-mail: jpeppanen@epri.com). ference between two customers connected in parallel:
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TSTE.2019.2917679 |V1 | − |V2 | ≈ IR2 R2 + IX2 X2 − IR1 R1 − IX1 X1 , (1)
1949-3029 © 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
1586 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 10, NO. 3, JULY 2019
Fig. 3. Timeseries showing measured voltage, real power, and reactive power Fig. 4. Relationship between measured V1 − V2 and predicted V1 − V2 based
for two customers on the same transformer. on R and X values found in linear regression (as listed in the bottom right
of plot).
customers with one another, using the virtual nodes found in the
first step, to determine if there is additional impedance between the highest R2 value was assigned as the actual topology, and
the final virtual nodes and the transformers. Combined, these a virtual node was created. This method was repeated until all
three steps derive the secondary circuit topology and parameters customers were included in the topology. We note that this linear
for all customers connected to the feeder. The three steps are regression is very fast, taking less than 0.1 s on a typical laptop
described in detail in the following sections. circa 2016. Because of the iterative nature, the number of linear
regressions that must be calculated increases with the number
A. Step 1: Transformers With Multiple Customers of customers. However, total runtime remains modest even for
transformers with many customers: the linear regressions for all
For transformers with multiple customers connected, all pos-
pairs of a 20 customer transformer, for example, can be run in
sible pairs of customers on the same transformer are evaluated.
about 2 minutes. Additionally, this process only needs to be run
For example, for transformers with 3 customers, all 3 possible
once: DSPE derived parameters will continue to be valid unless
combinations of customers pairs (1 and 2, 2 and 3, 3 and 1) are
there is a system configuration change.
evaluated. AMI data for voltage and real and reactive power, are
For most customers, the voltage fluctuations depended heavily
used to solve for R1 , X1 , R2 , and X2 using Eq. (2).
on the real current draw and only weakly on the reactive current.
To understand how well the linear regression fits the data,
That is, the reactive current was typically only responsible for
we computed the Pearson correlation coefficient (R2 ) of the fit.
explaining a small fraction of the variance in the voltage drop, in
This can be seen visually in Fig. 4, which shows the predicted
part because the real and reactive power draws were often well-
V1 − V2 using the right side of Eq. (2) with R1 , X1 , R2 , and X2
correlated. Therefore, we have more confidence in the derived
from linear regression on the x-axis plotted against the measured
resistance values than reactance values. In some cases, including
V1 − V2 on the y-axis.
when negative reactance is found, it may be best to use the found
Once R2 values were computed for all customer pairs, the pair
resistance and then assume a reasonable X/R ratio to determine
with the highest R2 value was assigned as the actual topology.
the reactance.
If this pair was found to be connected in parallel, then a new
virtual node, representing the point where these two parallel
lines connect, was created. The voltage at the virtual node was B. Step 2: Transformers With Only One Customer
found by adding the voltage drop to the measured voltage: On transformers with a single customer, Step 1 will not work:
we only have one voltage measurement (at the one customer),
Vvirtualnode = V1 + IR1 R1 + IX1 X1 . (3)
and so cannot solve for R and X between two voltage measure-
Based on the convention mentioned in Section II, mean(V1 ) ≥ ments using Eq. 2. Instead, we find a nearby transformer that also
mean(V2 ). Thus, equation 3 ensures that the voltage at the vir- has a single customer by finding the shortest latitude/longitude
tual node is, on average, higher than the voltage at each of the distance to another single-customer transformer on the same
customers. Real and reactive power consumption at the virtual phase. Because of the high voltage level on the primary system,
nodes were found by summing the real and reactive power of the per unit resistance on the primary voltage system between
the two customers. two nearby transformers is much smaller than the per unit re-
As a second iteration, all remaining customers (those not con- sistance on the low voltage secondary system from transformer
tributing to the virtual node) were again paired with one another to customer, as per unit resistance is inversely proportional to
and also were paired with the virtual node. Again, the pair with voltage squared. For example, on a 12-kV system, 900 feet of
1588 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 10, NO. 3, JULY 2019
Fig. 5. (a) DSPE results for a transformer with two customers on Feeder 1. (b) Satellite map showing utility secondary model for connections of customers to
this transformer. (c) Scatter plot of the DSPE resistances (y-axis) versus the utility secondary model distance (x-axis). Dashed lines show the resistance of different
wire types.
Fig. 6. (a) DSPE results for a transformer with five customers on Feeder 3. (b) Satellite map showing utility secondary model for connections of customers to
this transformer. (c) Scatter plot of the DSPE resistances (y-axis) versus the utility secondary model distance (x-axis). Dashed lines show the resistance of different
wire types.
Fig. 7. (a) DSPE results for two single-customer transformers Feeder 2. (b) Satellite map showing utility secondary model for these two customers. (c) Scatter
plot of the DSPE resistances (y-axis) versus the utility secondary model distance (x-axis). Dashed lines show the resistance of different wire types.
connected with #2 wire while customers 534, 579, and 630 may 1046 are connected through underground wiring, which is likely
be on lower resistance 2/0 wiring. This highlights the value of higher gauge. However, it is perhaps more likely that customer
DSPE: resistances from transformer to customer cannot be cal- 1046 is connected using 2/0 wiring and the secondary model
culated from secondary topology (or satellite imagery) alone; distance is inaccurate (i.e., actual distance is shorter).
accurate wiring type is also required. DSPE, resolves the topol-
ogy and parameters without need for the wire type as input.
C. Pair Multi-Customer Transformers With One Another
Fig. 8 shows the results of pairing two neighboring multi-
B. Transformers With Only One Customer customer transformers. In Fig. 8a, we see that for transformer
DSPE results are shown in Fig. 7. The resistances found 416, an extra 0.085 Ω of resistance were found between the
through DSPE are consistent with 2/0 and 4/0 wiring. These transformer and its final virtual node. This is consistent with
may be the actual wire types used as both customers 147 and the satellite imagery and the utility-provided secondary model
1590 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 10, NO. 3, JULY 2019
Fig. 8. (a) DSPE results for two transformers on Feeder 1, each with multiple customers. (b) Satellite map showing utility secondary model for these two
transformers. (c) Scatter plot of the DSPE resistances (y-axis) versus the utility secondary model distance (x-axis). Open circles show unadjusted parameters,
while filled in circles show parameters adjusted based on the additional resistance found between the final virtual node and the transformer. Dashed lines show the
resistance of different wire types.
Fig. 10. Measured voltage, and calculated voltage based on DPSE parameters
and a 100 ft of #2 wire assumption for customer 541 on feeder 1. The resistance
values for each method and the mean absolute errors (MAE) compared to the
measured voltage are shown in the text at the top.
Fig. 11. Same as Fig. 11, but for customer 1089 on feeder 3.
Fig. 12. Binned mean absolute errors (x-axis), measured versus modeled volt-
age, for all customers on two-customer transformers. The y-axis shows the num-
ber of customers in each bin. Modeled voltages are either from DSPE parameters
(solid lines) or based on the 100 ft assumption (dashed lines).
having reactive power measurements at all. As seen by the dots Energy’s National Nuclear Security Administration under con-
in the bottom plot of Fig. 14 when no reactive power measure- tract DE-NA0003525. This paper describes objective technical
ments are used, DSPE results are very similar (less than 3% results and analysis. Any subjective views or opinions that might
difference) to results when using full resolution reactive power be expressed in the paper do not necessarily represent the views
measurements. Similarly, over the 25 test feeders, the differ- of the U.S. Department of Energy or the United States Govern-
ence between using no reactive power measurements at all and ment. SAND2018-8168 J.
using full resolution reactive power measurements was always
less than 10%. The generally high correlation between real and
REFERENCES
reactive power means that measurement of reactive power is
not very important to DSPE accuracy and is an important result [1] B. Palmintier et al., “On the path to sunshot. Emerging issues and
challenges in integrating solar with the distribution system,” National
- reactive power collection may not be necessary for accurate Renewable Energy Laboratory, Golden, CO, USA, Tech. Rep. NREL/TP-
DSPE. 5D00-65331; SAND2016-2524 R, 2016.
Adding stochastic errors to the AMI measurements introduced [2] J. Peppanen, M. J. Reno, R. J. Broderick, and S. Grijalva, “Distribution sys-
tem secondary circuit parameter estimation for model calibration,” Sandia
stochastic differences in DSPE results. However, for added National Laboratories, Albuquerque, NM, USA, Tech. Rep. SAND2015-
stochastic measurement errors ranging from 0% to 10% of av- 7477, 2015.
erage measured voltage, real power, or reactive power, DSPE [3] J. Peppanen, C. Rocha, J. A. Taylor, and R. C. Dugan, “Secondary low-
voltage circuit models; how good is good enough?” in Proc. IEEE Rural
results were still within 5% of the results with no stochastic er- Elect. Power Conf., Apr. 2017, pp. 17–26.
rors added. Constant bias errors in measurements (i.e., if voltage [4] J. Peppanen, M. Bello, and M. Rylander, “Service entrance hosting ca-
measurements are 2 V too high over all timesteps) have no im- pacity,” in Proc. IEEE 7th World Conf. Photovolt. Energy Convers. (Joint
Conf. 45th IEEE PVSC, 28th PVSEC, 34th EU PVSEC), Waikoloa Village,
pact on DSPE results, as they simply change the value in Eqn. HI, USA, 2018, pp. 1451–1456. doi: 10.1109/PVSC.2018.8547340.
(2), but do not impact the resistance or reactance values. [5] S. Jothibasu and S. Santoso, “Sensitivity analysis of photovoltaic hosting
capacity of distribution circuits,” in Proc. IEEE Power Energy Soc. Gen.
Meeting, Jul. 2016, pp. 1–5.
VI. CONCLUSION [6] J. Yu, Y. Weng, and R. Rajagopal, “Patopa: A data-driven parameter and
topology joint estimation framework in distribution grids,” IEEE Trans.
Distribution system parameter estimation (DSPE) results Power Syst., vol. 33, no. 4, pp. 4335–4347, Jul. 2018.
agreed well with imagery and the utility secondary model for [7] Y. Weng, Y. Liao, and R. Rajagopal, “Distributed energy resources topol-
the customers examined. When applied over entire feeders, ogy identification via graphical modeling,” IEEE Trans. Power Syst.,
vol. 32, no. 4, pp. 2682–2694, Jul. 2017.
significant variations were seen from the simple assumption [8] A. M. Prostejovsky, O. Gehrke, A. M. Kosek, T. Strasser, and H. W. Bind-
that all customers have 100 ft of #2 wire, demonstrating the ner, “Distribution line parameter estimation under consideration of mea-
value of DSPE. Sensitivity analysis showed that the DSPE surement tolerances,” IEEE Trans. Ind. Inform., vol. 12, no. 2, pp. 726–735,
Apr. 2016.
method is robust: modest amounts of data (around 3 months [9] T. A. Short, “Advanced metering for phase identification, transformer iden-
of 15-minute resolution data) and measurement resolutions (1 tification, and secondary modeling,” IEEE Trans. Smart Grid, vol. 4, no. 2,
V, 0.5 kW) were sufficient to derive accurate parameters. For pp. 651–658, Jun. 2013.
[10] R. Singh, B. C. Pal, and R. A. Jabr, “Distribution system state estimation
this set of mostly residential customers, reactive power mea- through gaussian mixture model of the load as pseudo-measurement,” IET
surements were not found to be necessary, but this may change Gener., Transmiss. Distrib., vol. 4, no. 1, pp. 50–59, Jan. 2010.
for other customers with less correlated real and reactive power [11] S. Neshvad, H. Margossian, and J. Sachau, “Topology and parameter
estimation in power systems through inverter-based broadband stimula-
consumptions. tions,” IET Gener., Transmiss. Distribution, vol. 10, no. 7, pp. 1710–1719,
This paper supports the integration of the presented DSPE May 2016.
method into utility distribution grid management software solu- [12] J. Peppanen, S. Grijalva, M. J. Reno, and R. J. Broderick, “Distribution
system low-voltage circuit topology estimation using smart metering data,”
tions. The presented DSPE method can be leveraged to identify in Proc. IEEE/PES Transmiss. Distrib. Conf. Expo., 2016, pp. 1–5.
and fix errors in the utility geographic information system (GIS) [13] J. Peppanen, S. Grijalva, M. J. Reno, and R. J. Broderick, “Secondary
data. It can also be leveraged to automatically create accurate and circuit model generation using limited pv measurements and parameter
estimation,” in Proc. Power Energy Soc. Gen. Meeting, 2016, pp. 1–5.
detailed secondary system models based on AMI measurements [14] J. Peppanen, S. Grijalva, M. J. Reno, and R. J. Broderick, “Secondary
while minimizing the need for costly manual labor and field in- circuit model creation and validation with ami and transformer measure-
spections. As a result, the presented practical DSPE method can ments,” in Proc. North Amer. Power Symp., 2016, pp. 1–6.
[15] J. Peppanen, M. J. Reno, R. J. Broderick, and S. Grijalva, “Distribution
help utilities to greatly increase the accuracy and detail of their system model calibration with big data from ami and PV inverters,” IEEE
distribution grid models to enable high DER penetrations. Trans. Smart Grid, vol. 7, no. 5, pp. 2497–2506, Sep. 2016.
Future work building on the method presented here should [16] C. W. Brice, “Comparison of approximate and exact voltage drop calcula-
tions for distribution lines,” IEEE Trans. Power App. Syst., vol. PAS-101,
focus on validation of feeder-wide results (which was difficult no. 11, pp. 4428–4431, Nov. 1982.
with this data set due to the unvalidated utility model) and on [17] F. P. Villareal, “Nea specifications on distribution transformers,” NEA
integration into utility software for wide implementation. Report, Jun. 2015. [Online]. Available: https://www.google.com/url?sa=
t&rct=j&q=&esrc=s&source=web&cd=9&cad=rja&uact=8&ved=2
ahUKEwiqu-7Gus7iAhXvFzQIHVLpD9wQFjAIegQIBBAC&url=http
ACKNOWLEDGMENT %3A%2F%2Fnea.gov.ph%2Findex.php%3Foption%3Dcom_phocadown
load%26view%3Dcategory%26download%3D1231%3Adistribution-
Sandia National Laboratories is a multimission laboratory transformer-specifications%26id%3D103%3Aconsultative-session-with-
managed and operated by National Technology & Engineer- leadership-associations-of-ecs%26Itemid%3D143&usg=AOvVaw25k3
KK1JmUgDHE9PuwluWT
ing Solutions of Sandia, LLC, a wholly owned subsidiary of [18] W. Kersting, Distribution System Modeling and Analysis, 3rd ed. New
Honeywell International Inc., for the U.S. Department of York, NY, USA: Taylor & Francis, 2012.